Heat Controller B-VMH09FC-1, B-VCH18FC-1, B-VMH18FC-1, A-VCH27TC-1, B-VMH12FC-1 User Manual

...
5 (2)

INSTALLATION

MANUAL

Indoor Models:

B-VCH12FC-1

B-VCH18FC-1

B-VMH09FC-1

B-VMH12FC-1

B-VMH18FC-1

Version C

InverterFlex

Ductless Mini-Split Heat Pumps

High Wall and Ceiling Cassettes

Outdoor Models:

A-VCH18DC-1

A-VCH27TC-1

A-VMH36QC-1

Heat Controller, Inc. • 1900 Wellworth Ave. • Jackson, MI 49203 • (517)787-2100 • www.heatcontroller.com

Installation Manual

VMH Series

Heat Controller, Inc.

 

 

 

 

CONTENTS

SAFETY PRECAUTIONS

 

Warning ...........................................................................................................................................

2

Caution ............................................................................................................................................

2

Nomenclature Combinations...............................................................

..............................................4

INSTALLATION INSTRUCTIONS

 

Selecting installation place...............................................................................................................

3

Wall-mounted type ...........................................................................................................................

3

Accessories .......................................

..................................................................4

Four-way cassette type ................................................................................................................

9

Duct & Ceiling type .......................................................................................................................

12

Outdoor unit installation ........................................

........................................................................23

REFRIGERANT PIPE CONNECTION

 

Refrigerant pipe connection ..........................................................................................................

24

ELECTRICAL WORK

 

Electrical work .................. ...........................................................................................................

25

AIR PURGING

 

Air purging with vacuum pump .....................................................................................................

27

Safety and leakage check ............................................................................................................

29

TEST RUNNING

 

Test running ..................................................................................................................................

30

Read This Manual

Inside you will find many helpful hints on how to install and test the air conditioner properly.

All the illustrations and specifications in the manual are subject to change without prior notice for product improvement. The actual shape should prevail.

CAUTION

Contact an authorised service technician for repair or maintenance of this unit.

Contact an authorised installer for installation of this unit.

The air conditioner is not intended for use by young children or infirmed persons without supervision.

Young children should be supervised to ensure that they do not play with the air conditioner.

If the power cord is to be replaced, replacement work shall be performed by authorised personnel only. Installation work must be performed in accordance with the national wiring Standards by authorised personnel only.

2

Heat Controller, Inc.

VMH Series

Installation Manual

 

 

 

SAFETY PRECAUTIONS

Read the follow SAFETY PRECAUTIONS carefully before installation.

Electrical work must be installed by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit for the model to be installed.

Incorrect installation due to ignoring of the instruction will cause harm or damage.

The seriousness is classified by the following indications.

WARNING

This symbol indicates the possibility of death or serious injury.

 

 

CAUTION

This symbol indicates the possibility of injury or damage to property.

 

 

The items to be followed are classified by the symbols:

Symbol with background white denotes item that is PROHIBITED from doing.

WARNING

1)Engage dealer or specialist for installation. If installation done by the user is defective, it will cause water leakage, electrical shock fire.

2)Install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electrical shock fire.

3)Use the attached accessories parts and specified parts for installation. otherwise, it will cause the set to fall, water leakage, electrical shock fire.

4)Install at a strong and firm location which is able to withstand the set,s weight. If the strength is not enough or installation is not properly done, the set will drop and cause injury.

5)For electrical work, follow the local national wiring standard, regulation and this installation instructions. An independent circuit and single outlet must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock fire.

6)Use the specified cable and connect tightly and clamp the cable so that no external force will be acted on the terminal. If connection or fixing is not perfect, it will cause heat-up or fire at the connection.

7)Wiring routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will cause heat-up at connection point of terminal, fire or electrical shock.

8)When carrying out piping connection, take care not to let air substances other than the specified

refrigerant go into refrigeration cycle. Otherwise, it will cause lower capacity, abnormal high pressure in the refrigeration cycle, explosion and injury.

9)Do not modify the length of the power supply cord or use of extension cord, and do not share the single outlet with other electrical appliances. Otherwise, it will cause fire or electrical shock.

CAUTION

1)This equipment must be earthed and installed with earth leakage current breaker. It may cause electrical shock if grounding is not perfect.

2)Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at surrounding of the unit, it may cause fire.

3)Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water

may enter the room and damage the furniture.

3

Installation Manual

VMH Series

Heat Controller, Inc.

 

 

 

Nomenclature

Outdoor Models:

A - vmh18dc - 1

Outdoor Inverter

Heat

Multi-Zone

Nominal Capacity

D=Dual Zone

 

Pump

Mini-Split

18=18kBtu/H

T-Tri-Zone

 

 

 

27=27kBtu/H

Q-Quad Zone

 

 

 

36=36kBtu/H

 

Indoor Models:

B - vmh09Fc - 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor Inverter M=Mini-Split

Heat

Capacity

 

 

Voltage Code

 

 

high wall

Pump

09=09kBtu/H*

 

 

1=208/230V-60hz-1PH

 

 

mount

 

 

12=12kBtu/H

 

 

 

 

 

 

 

 

 

 

 

 

C=Ceiling

 

 

18=18kBtu/H Design

Flexible

 

 

cassette

 

 

*not available in

Series

Matching

 

 

 

 

ceiling cassette

 

 

 

 

 

 

 

 

 

capabilities

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

Heat Controller, Inc.

VMH Series

Installation Manual

 

 

 

Unit combinations

NOTE: The total capacity of indoor air handlers can not exceed the nominal capacity of the outdoor unit. The minimum quantity of indoor air handlers is one on any outdoor unit, whether it is a dual, tri, or quad zone.

Indoor unit combinations for A-VMH18DC-1

Comb.

Combinations

Unit A

Unit B

 

Dual(1x1)

9k

12k

 

18k

Dual (1x2)

9k

9k

9k

12k

 

Indoor unit combinations for A-VMH27TC-1

Comb.

Combinations

Unit A

Unit B

Unit C

 

TRI (1x1)

9k

12k

 

18k

 

9k

9k

TRI (1x2)

9k

12k

9k

18k

 

 

12k

12k

TRI (1x3)

9k

9k

9k

Indoor unit combinations for A-VMH36QC-1

Comb.

 

Combinations

 

Unit A

Unit B

Unit C

Unit D

 

QUA (1x1)

9k

12k

 

18k

 

9k

9k

 

9k

12k

QUA (1x2)

9k

18k

12k

12k

 

 

12k

18k

 

18k

18k

 

9k

9k

9k

QUA (1x3)

9k

9k

12k

9k

9k

18k

 

9k

12k

12k

 

12k

12k

12k

QUA(1x4)

9k

9k

9k

9k

Available indoor models:

 

High Wall Mount

Ceiling Cassette

9k

B-VMH09FC-1

N/A

12k

B-VMH12FC-1

B-VCH12FC-1

18k

B-VMH18FC-1

B-VCH18FC-1

5

Heat Controller B-VMH09FC-1, B-VCH18FC-1, B-VMH18FC-1, A-VCH27TC-1, B-VMH12FC-1 User Manual

Installation Manual

VMH Series

Heat Controller, Inc.

 

 

 

INSTALLATION INSTRUCTIONS

NOTE: Indoor units shown can be replaced with ceiling cassettes.

 

 

 

Mo

 

 

 

2

More than 15cm

 

 

 

 

 

 

 

1

 

 

 

ret

han

 

 

 

 

 

 

 

12cm

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ter

 

 

 

 

r

 

filter

 

Airfil

 

 

 

 

 

 

 

 

 

 

te

Air

 

 

 

Air

fil

 

 

 

 

ter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Airfil

 

 

 

 

 

 

5

Remote

4

 

 

 

 

Remote

 

Remote

 

controller

 

controller

 

 

controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote

 

 

 

 

 

 

 

 

controller

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

Air out

 

 

 

 

er

 

 

 

 

 

Air

filt

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

One-Two

 

Loop a

 

 

 

 

 

 

 

connective

 

 

 

 

 

 

One-Three

 

cable

 

 

 

 

 

 

 

 

 

Remote

 

One-Four

 

 

 

controller

 

One-Five

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CAUTIONS

This illustration is for explanation purposes only. The actual shape of your air condtioner may be slightly different.

Copper lines must be insulated independently

CAUTION

NOTE: Ceiling cassettes come with an optional wall mounted wireless thermostat that can take the place of the wireless remote controller.

6

Heat Controller, Inc.

VMH Series

Installation Manual

 

 

 

Pipe length and elevation

 

Pipe size

Standard

 

 

Max.

 

Max.

 

Additional

Unit

 

 

 

length

 

Elevation

 

Length

 

refrigerant

Gas inch

Liquid inch

 

(mm)

(mm)

 

 

(m)

 

B (m)

 

A (m)

 

(g/m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9K

3/8’’ (Ф9.52)

1/4’’ (Ф6.35)

(5)

 

(10)

 

 

(15)

 

 

(20)

 

 

 

 

 

 

16.5ft

 

 

33ft

 

50ft

 

0.2 oz/ft

12K/18K

1/2’’ (Ф12.7)

1/4’’ (Ф6.35)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max. Total length for all rooms

Dual-zone(m)

 

 

Tri-zone(m)

 

Quad-zone(m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(30)100ft

 

 

(45)150ft

 

 

(60)200ft

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2XWGRRU XQLW

 

 

 

 

 

 

 

 

 

 

 

 

 

$

 

 

 

 

 

 

 

 

 

 

 

 

2LO WUDS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

,QGRRU XQLW

%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTES:

Do not exceed 50 ft. (15m) per each indoor unit.

Minimum pipe lenght of 10ft (3m) is required for each indoor unit.

Oil trap should be installed per (3-5 meters) 10-15 ft., where outdoor unit is located above indoor unit.

Outdoor connections are 1/4” (f6.35 mm) liquid and 3/8” (f9.52 mm) gas, therefore a flare nut adapter is provided with all 12/18k indoor sections.

7

Installation Manual

VMH Series

Heat Controller, Inc.

 

 

 

INSTALLATION INSTRUCTIONS

1. Selecting Installation Place

Read completely, then follow step by step.

More than 6in.(15cm)

Indoor unit

More than 5in.(12cm)

More than 5in.(12cm)

Do not expose the indoor unit to heat or steam.

 

Select a place where there are no obstacles

 

in front or around the unit.

 

Make sure that condensation drainage can

More than 6.5 ft.(2.0m)

 

be conveniently routed away.

Fig.1

Do not install near a doorway.

 

Ensure that the proper clearance is maintained per Fig.1.

 

Use a stud finder to locate studs to prevent unnecessary damage to the wall. Variations in pipe length may require adjustment to refrigerant charge.

There should not be any direct sunlight. Otherwise, the sun will fade the plastic cabinet and affect its appearance. If unavoidable, sunlight prevention should be taken into consideration.

Outdoor unit

If an awning is built over the outdoor unit to

 

More than 1ft.(30cm)

 

 

 

prevent direct sunlight or rain exposure,

More than 1 ft.(30cm)

 

 

make sure that heat radiation from the

 

 

 

condenser is not restricted.

 

 

 

Ensure that the clearance is maintained

 

 

 

per Fig 2.

 

 

More than 2ft.(60cm)

Do not place animals and plants in the path

 

 

 

of the air inlet or outlet.

More than 6.5 ft.(200cm)

 

 

Take the air conditioner weight into account

 

 

 

Fig.2

 

and select a place where noise and vibration

 

 

will not be an issue.

Clearance

Select a place so that the warm air and noise from

 

11” (280mm)

the air conditioner do not disturb neighbors.

 

 

 

 

 

A

 

Outlet

Inlet

Outlet

 

7.5ft (>2300)

 

Ground

 

 

Fig.13

 

 

(>1000)

 

3.5ft (>1000)

 

3.5ft

 

 

 

 

 

3.5ft (>1000)

 

5.3

 

 

 

(>1000) ft

 

 

Fig.14

 

 

8

 

 