Haier AU242AGEAA, AU282AHEAA, AU362AIEAA, AU36NAIEAA, AU48NAIEAA User Manual

...
0 (0)

ROOM AIR CONDITIONER

OUTDOOR UNIT

INSTALLATION INSTRUCTIONS

 

CONTENTS

 

 

Name of Parts----------------------

1

AU182AEEAA

Safety Cautions------------------

2-3

 

Installation Procedure---------

4-13

AU242AGEAA

AU282AHEAA

AU28NAHEAA

AU36NAIEAA AU362AIEAA AU48NAIEAA AU60NAIEAA

No.0010577959

D

Before using the air conditioner,please read this manual carefully. Please keep this manual properly for future use.

Haier AU242AGEAA, AU282AHEAA, AU362AIEAA, AU36NAIEAA, AU48NAIEAA User Manual

Name of Parts

 

AU182AEEAA

AU242AGEAA

Air inlet

Air inlet

 

Air outlet

Air outlet

Compressor

Compressor

(Inside of unit)

(Inside of unit)

 

 

Air inlet

AU282AHEAA

Air outlet

AU28NAHEAA

 

 

Compressor

 

(Inside of unit)

 

Air inlet

AU36NAIEAA

 

AU362AIEAA

 

AU48NAIEAA

 

AU60NAIEAA

Air outlet

 

 

Compressor

 

(Inside of unit)

 

1

Safety Cautions

Carefully read the following information in order to operate the airconditioner correctly.

Below are listed three kinds of Safety Cautions and Suggestions.

WARNING! Incorrect operations may result in severe consequences of death or serious injuries. CAUTION! Incorrect operations may result in injuries or machine damages; in some cases may

cause serious consequences.

INSTRUCTIONS: These information can ensure the correct operation of the machine.

Be sure to conform with the following important Safety Cautions.

The Safety Cautions should be at hand so that they can be checked at any time when needed.

If the conditioner is transferred to the new user, this manual should be as well transferred to the new user.

WARNING!

If any abnormal phenomena is found (e. g.smell of firing), please cut off the power supply immediately, and contact the dealer to find out the handling method.

In such case, to continue using the conditioner will damage the conditioner, and may cause electrical shock or fire hazard.

switch off

After a long time use of air-conditioner the base should be checked for any damages.

If the damaged base is not repaired, the unit may fall down and cause accidents.

Don't dismantle the outlet of the outdoor unit.

The exposure of fan is very dangerous whichmay harm human beings.

When need maintenance and repairment, call dealer to handle it.

Incorrect maintenance and repairment may cause water leak, electrical shock and fire hazard.

2

Safety Cautions

WARNING!

Installed electrical-leaking circuit breaker.

It easily cause electrical shock without circuit breaker.

Air-conditioner can't be installed in the environment with inflammable gases because the inflammable gases near to air-conditioner may cause fire hazard.

Please let the dealer be responsible for installing the conditioner.

Incorrect installation may cause water leak, electrical shock and fire hazard.

Call the dealer to take measures to prevent the refrigerant from leaking.

If conditioner is installed in a small room be sure to take every measure in order to prevent suffocation accident even in case of refrigerant leakage.

When conditioner is deinstalled or reinstalleddealer should be respon-

sible for them.

Incorrect installation may cause water leaking, electrical shock and fire hazard.

Connect earthing wire.

Earthing wire should not be connected to the gas pipe, water pipe, lightning rod or phone line, incorrect earthing may cause shock.

Earthing

No goods or nobody is permitted to placed on or stand on outdoor unit.

The falling of goods and people may cause accidents.

Don't operate the air-conditioner with damp hands.

Otherwise will be shocked.

Only use correctly-typed fuse.

May not use wire or any other materials replacing fuse, other-wise may cause faults or fire accidents.

Use discharge pipe correctly to ensure efficient discharge.

Incorrect pipe use may cause water leaking.

3

Installation Procedure

Installation of outdoor unit

1. Accessories

Edging

"Edging" for protection of electric wires from an opening edge.

2. Selection of the place of installation

Select the place of installation satisfying the following conditions and, at the same time, obtain a consent from the client or user.

Place where air circulates.

Place free from heat radiation from other heat sources.

Place where drain water may be discharged.

Place where noise and hot air may not disturb the neighborhood.

Place where there is not heavy snowfall in the winter time.

Place where obstacles do not exist near the air inlet and air outlet .

Place where the air outlet may not be exposed to a strong wind.

Place surrounded at four sides are not suitable for installation. A 1m or more of overhead space is needed for the unit.

Mount guide-louvers to place where short-circuit is a possibility.

When installing several units, secure sufficient suction space to avoid short circuiting.

(1) Open space requirement around the unit

Air inlet

L3

L2

500

 

Air

(Servicing

inlet

space)

Air outlet

L1

Note :

(1). Fix the parts with screws

(2).Don't intake the strong wind directly to the outlet air-flow hole.

(3).A one meter distance should be kept from the unit top

(4).Don't block the surroundings of the unit with sundries

 

 

 

 

 

 

Unit: mm

Case

 

I

 

II

 

III

 

 

 

Distance

 

 

 

 

 

 

L1

 

open

 

open

 

500

 

 

 

 

 

 

 

L2

 

300

 

300

 

open

 

 

 

 

 

 

 

L3

 

150

 

300

 

150

 

 

 

 

 

 

 

NO

Wind direction

(2)Installation where the area with strong winds.

Install the unit so that the air outlet section of the unit must NOT be faced toward wind direction.

4