Grieve Corporation 1996-20 Installation Manual

Series 1996 Gas Pressure Switches are
reliable and convenient switches for gas-fired furnaces and equipment using natural, manufactured or LP gas. Both models (Model 1996-5, with a pressure range of 1.4 to 5.5″ w.c.; Model 1996-20, with a pressure range of 4 to 20″ w.c.) feature visible set point and on-off indicators.
OPERATION
Pressure acting on the power diaphragm rotates the amplifying lever, which in turn extends the range spring and rotates the snap switch input lever. When the set point is reached, the snap switch is actuated and the electrical contacts make or break. Decreasing pressure after the switch has been actuated reverses the action, de-actuating the switch and returning the contacts to their normal position.
INSTALLATION
1. Select a location free from excessive vibration and corrosive atmosphere. These switches may be used in ambient temperatures as low as - 30°F ( - 34°C) and as high as 110°F (43°C).
2. Mount switch with diaphragm in a horizontal position and gas pressure connection at bottom. Connect the switch to the source of gas pressure using either the NPT (F)8or NPT (M) 4thread. Gas pressure connec­tion should always be to bottom connection of switch— see diagram above—which is equipped with a restrictor orifice. Be sure to hold or turn switch with a wrench on the hex portion of the bottom connection. This will pre­vent applying excessive torque to the bottom fitting, which could damage the switch.
The port identified with the letters LO-PR is used as a vent in fuel gas switches and should be vented to outside atmosphere or the combustion chamber in accordance with the furnace manufacturer’s instructions. The port identified by the letters HI-PR is
not used in fuel gas switches and is neither tapped nor connected to the diaphragm chamber.
Series 1996 – Natural and L.P. Gas Pressure Switches
Specifications - Installation and Operating Instructions
Bulletin E-58
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000 www.dwyer-inst.com
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.com
Lit-By Fax: 888/891-4963
Series 1996 Gas Pressure Switches
are designed for use with natural, man­ufactured or LP gas or air.
Note set point adjustment indicator win­dow. For quick adjustment of set point before/after installation, turn adjustment screw until red bar is at desired set point. To adjust for low gas pressure interlock service, refer to chart (other side).
Connections, dimensions and visible on-off indicator: Model 1996-20 and
Model 1996-5 Gas Pressure Switches.
PHYSICAL DATA
Temperature limits: 32°F/0°C (- 30°F/- 34.4°C for dry gas or
air) to 110°F/ 43.3°C
Pressure connection:
8NPT (F) or 4NPT (M)
Vent connection:
8NPT
Electrical rating: 15 amps, 120-480 volts, 60 Hz. A.C. Resistive
8H. P. @ 125 volts, 4H. P. @ 250 volts, 60 Hz.
A.C.
Wiring connections: 3-screw type, Common, Normally Open and Normally Closed
Set point adjustment: Screw type with visible indicator, inside cabinet enclosure
On-off indicator: In window, on exterior of conduit enclosure. Shows at a glance whether pressure is above or below set and reset points.
Housing: Aluminum die casting and steel stamping, zinc-plated for 200 hour salt spray resistance
Diaphragm: Molded Buna-N
Calibration spring: Stainless Steel
Weight: 1 lb, 2 oz
U.L. and C.S.A. listed, F.M. approved
WARNING:
Do not connect fuel gas to LO-PR port.
REMOVABLE CONDUIT ENCLOSURE COVER
7/8 [22.23] OPENING FOR 1/2 [12.7] CONDUIT CONNECTION
3-1/8
[79.38]
3-1/2
[88.90]
WINDOW AND VISIBLE ON-OFF INDICATOR
VENT CONNECTION ON OPPOSITE SIDE
1/4 NPT EXTERNAL THREAD (ALTERNATE GAS CONNECTION)
1/8 (F) GAS PRESSURE CONNECTION
3. Remove the snap-on cover from the conduit enclosure by loosening its retaining screw and pulling firmly on its set screw held end. Electrical terminals for all switches are marked Common, Normally Open, and Normally Closed. The switch is not actuated until pressure is applied. On rising pressure, the switch actu­ates and Normally Open contacts close. Should gas pressure fail, the switch (when set for low gas pressure) will de-actuate and the Normally Open contacts re-open. When set for high gas pressure (regulator failure) the switch will actuate (and Normally Closed contacts will open) when overpressure occurs. Wire switch accord­ingly: make sure load doesn't exceed electrical ratings. Use flexible or rigid conduit to enclose wires to switch.
4. Adjust the set point following instructions under adjustment.
5. Check carefully for leaks. Be sure that switch set point and installation complies with the furnace/burner manufacturer’s instructions. Watch the On-Off indicator in window to observe proper operation.
ADJUSTMENT
1. To change the set point, remove the cover from the conduit enclosure. Turn the slotted Adjustment Screw at the end of the range spring housing clockwise to raise the set point pressure and counter-clockwise to lower the set point. The visible set point indicator shows the set point from 4 (min) to 20 (max) inches w.c. for Model 1996-20 and 1.5 (min) to 5 (max) inches w.c. for Model 1996-5.
2. (a) For high gas pressure applications, to actuate on regulator failure, adjust the set point so that desired set­ting (normally 1or 12above operating pressure) shows in the window. (b) For low gas pressure applications, to actuate on gas
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000 www.dwyer-inst.com
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.com
Lit-By Fax: 888/891-4963
Series 1996 – Natural and L.P. Gas Pressure Switches
Specifications - Installation and Operating Instructions
Bulletin E-58
Page 2
©Copyright 2000 Dwyer Instruments, Inc. Printed in U.S.A. 6/00 FR # 26-440252-00 Rev. 1
Visible on-off pointer indi­cates actuation or de-actuation of switch. This permits instant trouble-shoot­ing of electrical circuit or gas supply.
Motorized
Gas Valves
Typical Piping Diagram for Gas-Fired Furnaces
(Pilots Not Shown)
Low Pressure
Gas Switch
Vent outside
separately or to
combustion chamer
per manufacturer's
instructions.
Gas
Supply
Main Gas
Shut-Off Valve
Gas Pressure
Regulator
Solenoid
Vent Valve
(Normally Open)
Test
Cock
High Pressure
Gas Switch
Checking
Gas Cock
To Main
Burner
Inches in Water Column
Set Point Approximate Dead Band Reset Point
Model 1996-5
1.5 0.10 1.30
20.12 1.88
30.14 2.86 4 0.17 3.83
50.19 4.81
Model 1996-20
40.15 3.85
50.15 4.85 10 0.24 9.76 15 0.33 14.67 20 0.41 19.59
pressure failure, adjust the set point slightly below (usually 2or 1w.c.) the normal gas pressure. De-actuation will occur at set point pressure minus the dead band. See chart below.
MAINTENANCE
The moving parts of these switches are sealed in and are permanently tamper-proof. The single adjustment is that of the set point. Care should be taken to keep the switch reasonably dry and free from dust or dirt. No lubrication or unusual precautions are required for normal use.
Loading...