Greenheck ECD-401 Installation Manual

5 (2)

ECD-401

Combination Louver/Damper

Drainable Blade

Application and Design

ECD-401 is a combination louver/damper designed to protect air intake and exhaust openings in building exterior walls that, at times, require tight air shut off. Design incorporates a drainable head member, drainable stationary blades and operable blades with exposed blade linkage. When the operable blades are open, airflow is permitted through the louver, when the blades are closed, a tight seal is created to prevent the passage of air. The ECD-401 is an extremely efficient louver with AMCA LICENSED PERFORMANCE DATA enabling designers to select and apply with confidence.

Standard Construction

Frame . . . . . . . .Heavy gauge extruded 6063-T5 aluminum, 4 in. x 0.081 in. nominal wall thickness

Blades . . . . . . . .Drainable design, heavy gauge extruded

6063-T5 aluminum, 0.081 in. nominal wall thickness, positioned at 37º and 45º angles on approximately 4 in. centers

Seals . . . . . . . . .Dual-durometer extruded vinyl blade and jamb seals

Temperature

Restrictions. . . .(-20º F) - (+180ºF)

Linkage . . . . . . .Exposed on-blade linkage

Bearings . . . . . .Synthetic sleeve type

Construction . . .Mechanically fastened

Birdscreen. . . . .3/4 in. x 0.051 in. fl attened expanded aluminum in removable frame, inside mount (rear)

Finish. . . . . . . . .Mill

Minimum Size . .12 in. W x 12 in. H

Maximum Single

Section Size . . . 120 in. W or 120 in. H (limited to 70 sq. ft.)

Options (at additional cost)

A variety of bird and insect screens

A variety of electric, pneumatic or manual actuators

Extended sill

Filter rack

Flanged frame

Glazing adaptor

Hinged frame

Security bars

0.125 in. nominal wall thickness

A variety of architectural finishes including:

Clear anodize

Integral color anodize

Baked enamel paint

Kynar paint

*Width and height dimensions furnished approximately ¼ inch under size.

Greenheck ECD-401 Installation  Manual

PERFORMANCE DATA

ECD-401

Free Area Chart (Sq. ft.)

Louver

 

 

 

 

Louver Width Inches

 

 

 

 

Height

 

 

 

 

 

 

 

 

 

 

 

 

 

Inches

12

 

24

36

48

60

 

72

84

96

108

120

 

 

 

 

 

 

 

 

 

 

 

 

 

12

0.29

 

0.68

1.06

1.44

1.82

 

2.20

2.59

2.97

3.35

3.73

 

 

 

 

 

 

 

 

 

 

 

 

 

24

0.67

 

1.54

2.41

3.28

4.15

 

5.03

5.90

6.77

7.64

8.51

 

 

 

 

 

 

 

 

 

 

 

 

 

36

1.08

 

2.49

3.90

5.30

6.71

 

8.12

9.52

10.93

12.33

13.74

 

 

 

 

 

 

 

 

 

 

 

 

 

48

1.55

 

3.57

5.58

7.60

9.62

 

11.63

13.65

15.66

17.68

19.69

 

 

 

 

 

 

 

 

 

 

 

 

 

60

1.93

 

4.44

6.94

9.44

11.95

 

14.45

16.96

19.46

21.97

24.47

 

 

 

 

 

 

 

 

 

 

 

 

 

72

2.34

 

5.38

8.42

11.46

14.50

 

17.54

20.58

23.62

26.66

29.70

 

 

 

 

 

 

 

 

 

 

 

 

 

84

2.81

 

6.46

10.11

13.76

17.41

 

21.06

24.71

28.36

32.01

35.66

 

 

 

 

 

 

 

 

 

 

 

 

 

96

3.19

 

7.33

11.47

15.60

19.74

 

23.88

28.02

32.16

36.30

40.43

 

 

 

 

 

 

 

 

 

 

 

 

 

108

3.60

 

8.28

12.95

17.62

22.30

 

26.97

31.64

36.32

40.99

45.67

 

 

 

 

 

 

 

 

 

 

 

 

 

120

4.07

 

9.36

14.64

19.92

25.20

 

30.49

35.77

41.05

46.34

51.62

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Greenheck Fan Corporation

certifies that the ECD-401

 

 

 

 

 

 

 

 

 

 

 

louvers shown herein are licensed to bear the AMCA Seal.

 

 

 

 

 

The ratings shown are based on tests and procedures

 

 

 

 

 

 

performed in accordance with AMCA Publication 511

 

 

 

 

 

 

and comply with the requirements of the AMCA Certified

 

 

 

 

 

 

Ratings Program. The AMCA Certified Ratings Seal applies

 

 

 

 

 

to air performance and water penetration ratings.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Airflow Resistance (Standard Air - .075 lb/ft3)

 

 

 

 

Combination Louver/Damper

Extruded Aluminum

Air Leakage (with damper section closed)

Test size 48 in. x 48 in.

 

kPa

 

in. wg

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.475

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.425

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.4

 

0.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.375

 

0.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.35

 

0.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pressure

 

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.325

 

0.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.3

 

0.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.275

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.25

 

0.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.225

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.09

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

cfm/ft 2

1

 

1.5

 

 

2

 

 

2.5

 

 

3

 

 

3.5

 

 

4

4.5

5

 

 

 

cmh/m 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

25

30

35

40

45

50

55

60

65

70

75 80 85 90

Leakage

Water Penetration (Standard Air - .075 lb/ft3)

Test size 48 in. x 48 in. Test duration of 15 min.

Static Pressure Drop

Pa

in. wg

 

1

 

0.9

2000.8

0.7

0.6

0.5

100

 

0.4

 

90

 

 

80

0.3

70

 

 

60

 

 

50

0.2

40

 

 

30

 

 

 

0.1

 

0.09

200.08

0.07

0.06

0.05

10

 

0.04

 

9

 

 

8

0.03

7

 

 

6

 

 

5

0.02

ft/min: 200

m/s:

Test Size 48 in. x 48 in.

3

Standard Air - .075 lb/ft

Intake

Exhaust

300 400 500 600 700 800 900 1000 2000 3000

2 3 4 5 6 7 8 9 10

Free Air Velocity

Model ECD-401 resistance to airflow (pressure drop) varies depending on louver application (air intake or air exhaust). Free area velocities (shown) are higher than average velocity through the overall louver size. See louver selection information.

The AMCA Water Penetration Test provides a method for comparing various louver models and designs as to their efficiency in resisting the penetration of rainfall under specific laboratory test conditions. The

beginning point of water penetration is defined as that velocity where the water penetration curve projects through .01 oz. of water (penetration) per sq. ft. of louver free area. *The beginning point of water penetration for Model ECD-401 is 1018 fpm free area velocity.

These performance ratings do not guarantee a louver to be weatherproof or stormproof and should be used in combination with other factors including good engineering judgement in selecting louvers.