Greenheck BCF Manual

0 (0)

Centrifugal Inline Fans

Models SQ and BSQ

Direct and Belt Drive

VARIGREEN

Motor

April

2010

Models SQ and BSQ

Centrifugal Square Inline Duct Fans

Greenheck Fan Corporation certifies the model SQ and BSQ fans shown herein are licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and Publication 311 and comply with the requirements of the AMCA Certified Ratings Program. The certified ratings for models SQ and BSQ are shown on pages 14 to 44.

*UL is optional and must be specified. SQ and BSQ models are listed for electrical (UL/cUL 705) File no. E40001

Table of Contents

 

Standard Construction Features . . . . . . .

. .4-5

Options and Accessories . . . . . . . . . . . . .

. . . 6

Vari-Green Motor . . . . . . . . . . . . . . . . . . . .

. . . 7

Discharge Configurations . . . . . . . . . . . . .

. .8-9

Mounting Options . . . . . . . . . . . . . . . . . . .

. . 10

Isolators . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . 11

Filter Options . . . . . . . . . . . . . . . . . . . . . . .

. . 12

Typical Installation . . . . . . . . . . . . . . . . . .

. . 13

Model Number Code . . . . . . . . . . . . . . . . .

. . 13

Direct Drive . . . . . . . . . . . . . . . . . . . . . . . .

14-22

Belt Drive . . . . . . . . . . . . . . . . . . . . . . . . . .

23-44

Specificatons . . . . . . . . . . . . . . . . . . . . . . .

45-46

Centrifugal Inline Guide . . . . . . . . . . . . . .

. . 47

Quick Delivery .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..

.. .. 48

Warranty . . . . . . . . . . . . . . . . . . . . . . . . . .

. . 48

Greenheck’s model SQ and BSQ centrifugal inline fans feature a unique combination of installation flexibility, rugged construction, ease of service, high efficiency and low sound levels.. These compact inline fans are the ideal selection for indoor clean air applications including intake, exhaust, return

or make-up air systems where space is a prime consideration.. The need for costly square to round transition pieces is eliminated reducing installation costs.. The square housing design, compact size and straight-thru airflow also give the system designer the flexibility to mount SQ and BSQ fans in any configuration - horizontal, vertical or at

any angle..

Broadest performance in the industry, up to 4 in.  wg (1,000 Pa) and 28,000 cfm (47,000 m3/hr).

Performance as cataloged is assured.. All fan sizes are tested in our AMCA Accredited

Laboratory, and all models are licensed to bear the AMCA sound and air performance seals..

UL Listed for electrical

These Greenheck products are subjected to extensive life testing to assure the fans will provide many years of reliable performance

Over the years Greenheck has listened to your needs and input to remain the industry leader..

Each fan is tested at the factory prior to shipping.. The test includes vibration check, adjusting RPM and maximum amp draw test..

Each fan displays a permanently stamped metal nameplate with complete model number, mark and unique serial number for future identification..

Packages are tested in accordance with ISTA (International Safe Transit Association) standards and procedures..

Turn to our inline fans to meet your requirements for applications in office buildings, schools and hospitals to name a few..

2

The Greenheck Standard

Leading

Edge

Technical

Support

When product and IOM (Installation, Operation and Maintenance Manual) information is needed, our products are supported by the industry’s best product literature, electronic media and Computer Aided Product Selection (CAPS) program.. You’ll also find this information on our

web site at www..greenheck..com

Our national and international representative organizations provide personal service and expertise.. To locate your nearest Greenheck representative, call 715-359-6171 or visit our web site at www..greenheck..com

Outstanding Customer Service

Your local Greenheck representative has a wealth of industry and product knowledge to answer your questions.. Our representatives receive the latest product information and can have orders processed directly to our factory.. With our direct order processing system, we can ship orders as fast as the next day.. With Greenheck’s experienced staff, we can answer questions

and provide solutions..

Greenheck’s Quick Delivery Program provides many options to help you meet your project’s schedule..

Stocking warehouses and distribution centers around the world ensure sameday pickup and same-day shipment for orders in by

2 p..m.. (CST).. Hundreds of custom products can be manufactured through Quick Build in just days..

Please refer to chart on back cover for model size and availability for QD and QB programs.. The Greenheck Stock & Quick Build Catalog is a great resource for specific options and accessories available with QD and QB fans..

LEED

Greenheck is driving the fan industry in the Green Building and LEED charge.. As one of the first manufacturers in the air movement industry to join the United States Green Building Council in 2005, we have been actively researching how our products can be applied.. This commitment to the green movement continues with product development that qualifies within the LEED rating system—it’s prerequisites and credits..

The Vari-Green motor is

equipped to play a large role in the green building movement, specifically Prerequisite Two;

Minimum Energy Performance

and Credit One; Optimize Energy Performance..

See page 7 for more information..

World Class Manufacturing

Greenheck’s skilled production workers use cost-effective machines and unique dies, designed and built by our own engineers to add innovative features and greater strength to our centrifugal inline fans.. Our advanced manufacturing processes and quality control procedures always ensure the highest product quality.. And just to be sure you get the peace-of-mind you expect when you specify Greenheck, our assembly inspectors test run and monitor every fan before it leaves the factory.. Results of these tests are kept in permanent records for future reference..

Standard Construction Features

Model SQ Direct Drive

3

5

4

2

1

Model BSQ Belt Drive

5

2

9

7

4

3

6

8

1

4

Standard Construction Features

1 Cabinet Construction

The fan housing is constructed of rigid structural members and formed galvanized steel panels.. (Aluminum construction is optional in all SQ sizes 60 160 and in

BSQ sizes 70 300..)

2 Drive Frame

Constructed from heavy gauge steel..

3 Wheel

An aluminum, backward inclined, nonoverloading centrifugal wheel is utilized to deliver maximum efficiency.. Each wheel is statically and dynamically balanced..

4 Duct Collars

Inlet and discharge duct collars are provided for easy duct connection.. The square design provides a larger discharge area than tubular centrifugal, and vane axial fans; outlet velocities are reduced for quieter operation..

5 Motor

Permanently lubricated, sealed ball bearing motors are selected to provide years of trouble-free operation with minimal maintenance..

6 Bearings

100 percent factory tested bearings are designed specifically for air handling applications with a minimum L10 life in excess of 100,000 hours (L50 average life in excess of 500,000 hours)..

7Drive Assembly

Drives are sized for a minimum of 150 percent of driven horsepower.. Machined cast iron pulleys are factory set to the required RPM and adjustable for final system balancing.. Belts are static free and oil resistant.. Belt adjustment is accomplished by loosening fasteners, sliding the motor plate and retightening fasteners..

8Fan Shaft

Precisely sized, ground and polished so the first critical speed is at least 25 percent over the maximum operating speed.. Close tolerances where the shaft makes contact with bearings result in longer bearing life..

9 Disconnect Switch

NEMA-1 disconnect switch is factory mounted and wiring is provided from the motor as standard.. All wiring and electrical components comply with the National Electric Codes

and materials are UL Listed.. Other NEMA enclosure disconnect switches are optional..

Access Panels (not shown on images)

The cabinet construction features two side access panels.. These panels permit easy access to all internal components..

5

Options and Accessories

Aluminum Construction

Aluminum construction is available for all direct drive sizes 60-160 and belt drive sizes 70-300.. Some drive frame components may still be of galvanized construction to maintain

structural integrity..

Speed Controllers

Available for use with shaded pole and permanent split capacitor (PSC) motors on model SQ fans.. They provide an economical means of

system balancing with direct drive fans..

Inlet and Outlet Guards

Inlet and outlet guards provide protection for nonducted applications.. Guards are fabricated of welded wire on a galvanized steel frame.. They are easily removed for maintenance and inspection..

Belt Drive Motor Cover and Belt Guard

For belt driven fans, combination motor cover and belt guards constructed of galvanized steel are available for protection of motors, drives and personnel.. Standard on units specified with UL..

Direct Drive Motor Cover

Formed, galvanized steel motor covers are available to isolate direct drive motors from the airstream.. When motor covers are furnished, vents to the exterior of the fan are provided to ensure sufficient motor cooling..

Backdraft Dampers

Gravity or motorized parallel blade dampers (model WD-330) are available for duct mounting.. These dampers feature sturdy galvanized frames with prepunched mounting holes, aluminum blades

with felt edges, and a balanced design for minimal resistance to airflow..

Control Dampers

Square, opposed blade volume control dampers (model VCD) are available for duct mounting.. These dampers feature sturdy galvanized frames with prepunched mounting holes, steel blades with vinyl seals, and flexible metal jamb seals.. A balanced design results in minimal resistance to airflow..

Coatings

Wide variety of coatings and colors are available..

Decorative coatings are available in sixteen standard colors..

Protective coatings are available in a choice of five electrostatic applied powders providing an available selection for most environments..

All Greenheck coatings and resistance charts can be found in the performance coatings catalog..

Inlet Vane Dampers

Variable inlet vane dampers (model IVDE) are available for models SQ and BSQ sizes 140-420 and are factory assembled to the fan.. They can be specified for either manual or automatic operation (controls furnished by others).. These dampers

are constructed of heavy gauge steel and feature uniform blade movement for positive control.. Companion inlet rings for round duct connections are also available..

Insulated Housing

For noise reduction and condensation control, the interior of the fan housing can be lined with a 1-inch fiberglass duct liner.. The optional motor cover can also be insulated..

The table depicts the radiated sound reduction that can be obtained in each octave band for the

insulated housing and motor cover together..

Approximate Radiated Sound Attenuation (dB)

Octave Band

1

2

3

4

5

6

7

8

 

 

 

 

 

 

 

 

 

Sizes 60 - 130

-2

-7

-4

-4

-6

-13

-13

-9

 

 

 

 

 

 

 

 

 

Sizes 140 - 420

-3

-2

-5

-4

-5

-5

-7

-8

 

 

 

 

 

 

 

 

 

Wiring Pigtail

Allows direct hook-up to the power supply eliminating field wiring at the fan..

6

Vari-Green Motor

Electrically Commutated,

Controllable, Efficient

 

 

Start saving now—with

 

 

the new, low-cost, easy

 

 

to control, electronically-

 

 

commutated motor that

 

 

offers high reliability

 

 

and low maintenance..

VARI

GREEN The Greenheck Vari-

 

Motor

Green (VG) motor blends

 

 

technology, controllability and energy-efficiency into a low maintenance package that is changing the way the industry designs, specifies and operates air movement equipment..

Reliability

With industry leading technology comes a new standard in motor reliability

No shaft grounding required regardless of the turndown

Bearing life is greater since the motor runs cooler the further it is turned down

No voltage or current spikes as in VFD controlled motors

Electronic Commutation

Electronic commutation uses electronic circuitry to control the motor’s functions:

Solid state circuitry controls the output of power and the speed of rotation

Internal circuitry converts 115 volt single phase AC power to DC voltage for increased efficiencies and full controllability of speed

1

2

3

Speed Control Options

Motor is available with one of these control options:

1..Motor mounted dial

2..Control wire inputs (0-10V)

3..Remote dial (available with 0-10V motor)..

Motor and Fan Sizes

VG Motors come in three fractional horsepowers; 1/4, 1/2, 3/4 and are available in both 50 and

60 Hz power on models G, CUE, CW, and SQ.. Consult factory for other motor sizes available..

Better than a PSC

Potentiometer dial pre-mounted on motor for speed control

80% usable turndown vs.. 30% with PSC motor

No speed controller to wire

20%-70% energy savings

Full speed range for better adjustment

More Efficient than Belts

Potentiometer dial pre-mounted on motor for speed control

No belt and pulley losses

Higher efficiency motor

40% energy savings

Lower up-front cost

No maintenance required

Easier than

VFDs

0-10 volt control wires preinstalled in motor

No VFD to buy or install

30% energy savings

Lower up-front cost

Model SQ with Vari-Green motor

• Eliminates stray current and carrier frequencies

Specifications

Motor enclosures: Open type

Motor to be a DC electronic commutation type motor (ECM) specifically designed for fan applications.. AC induction type motors are not acceptable.. Examples of unacceptable motors are: Shaded Pole, Permanent Split Capacitor

(PSC), Split Phase, Capacitor Start and 3 phase induction type motors..

Motors are permanently lubricated, heavy duty ball bearing type to match with the fan load and pre-wired to the specific voltage and phase

Internal motor circuitry to convert AC power supplied to the fan to DC power to operate the motor..

Motor shall be speed controllable down to 20% of full speed (80% turndown).. Speed shall be controlled by either a potentiometer dial mounted at the motor or by a 0-10 VDC signal

Motor shall be a minimum of 85% efficient at all speeds

7

Discharge Configurations

The side discharge option helps to reduce system effect.. It will increase performance and reduce installation labor.. The most notable is reducing system effects.. Note the figure 1 example, it shows the air being discharged into the corner.. It will take several duct lengths before the airflow becomes laminar or smooth again after making the turn..

In figure 2, the fan is placed in the corner using a side discharge.. In this configuration the air flow pattern at discharge is smooth and supports a more predictable system.. Remember the duct length

on the discharge side, should be approximately two to three wheel diameters to achieve catalog performance..

Discharge Configuration

Fan performance will change with different discharge positions.. Catalog data is based on an inline discharge.. Right side discharge will give you 108% of cataloged performance and left side will give you 109% of cataloged performance.. Use figure 3 to locate the orientation to fit your application.. Figures 4 and 5 on the facing page illustrate the proper side discharge definitions.. Refer to the CAPS program or consult factory for performance modifications..

Fan

Figure 1

Fan

Figure 2

Left Discharge

Left, Right & Inline Discharge

Right Discharge

Left & Right Discharge

Figure 3

8

Side Discharge

SQ Side Discharge

BSQ Side Discharge

Left Side

Access Door

Discharge

Inline

 

Discharge

Figure 4

 

Height

Inlet

 

Width

Right Side

 

Discharge

SQ Side Discharge Duct Openings

Unit Size

Width

Height

 

 

 

60-75

978 (251)

878 (225)

80-95

1278 (327)

1178 (302)

100

1378 (352)

1378 (352)

120

1578

(403)

1578

(403)

130

1778

(454)

1778

(454)

140

1978

(505)

1978

(505)

160

2278

(581)

2278

(581)

All dimensions in inches (millimeters).

Left Side

 

Discharge

Access Door

 

Inline

 

Discharge

Figure 5

 

Height

Inlet

 

Width

Right Side

 

Discharge

BSQ Side Discharge Duct Openings

Unit Size

Width

Height

 

 

 

70-80-90

1178 (302)

1178 (302)

100

1378 (352)

1378 (352)

120

1578 (403)

1578 (403)

130-130HP

1778 (454)

1778 (454)

140-140HP

1978 (505)

1978 (505)

160-160HP

2278 (581)

2278 (581)

180-180HP

2378 (606)

2378 (606)

200-200HP

2778 (708)

2778 (708)

240-240HP

2878

(733)

3478 (886)

300-300HP

3178

(810)

4178 (1064)

360-360HP

3278

(835)

3778 (962)

420

3478

(886)

4378 (1114)

All dimensions in inches (millimeters).

9

Greenheck BCF Manual

Horizontal and Vertical

Mounting Options

All SQ and BSQ fan models can be mounted horizontally, vertically or at an angle.. For ease of installation, knockouts are provided at each location where mounting brackets are shown in figures 6, 7 and 8.. Optional brackets are universally adjustable to mount in any of these locations..

 

NOTE: Hanging

 

 

G

A

rails by others

E

A

BG

B

 

 

 

 

F

 

 

 

 

 

 

B

 

A

A

 

 

F

E

 

B

 

Figure 6

Horizontal Hanging or Base Mount

With either a hanging or base mount the motor may be located on either side.. The base mount allows top access panels only..

 

 

E A

C

 

 

 

A

C

F

 

 

 

 

 

 

A

C

A

F E

 

 

 

 

C

Figure 7

Horizontal Hanging or Base Mount

With a hanging mount, the motor may be located on either top or bottom.. The base mount allows top motor location only.. Both options provide access panels on two sides..

 

 

D

 

NOTE: Hanging

B G

D

rails by others

 

B G

 

 

 

 

 

 

Figure 8

 

 

 

 

 

 

 

Vertical Hanging or Base Mount

 

 

 

 

 

 

 

Mounting brackets are turned

 

 

 

 

 

 

90° for vertical mounting.. Access

B

D

 

 

 

 

panels are located on the two sides

 

 

 

 

 

 

 

 

B

 

 

 

adjacent to the motor..

 

 

 

D

 

 

 

 

 

 

Model

A

B

C

 

D

E

F

 

G

SQ 60-75

1058 (270)

17 (432)

1534 (400)

 

878 (225)

1934 (502)

7 (178)

 

 

SQ 80-95

1314 (337)

20 (508)

1834 (476)

1178 (302)

43 (1092)

2738 (695)

 

Hanging

BSQ 70-90

1858 (473)

2018 (511)

1834 (476)

1178 (302)

48516 (1227)

2738 (695)

 

 

rails not

SQ-BSQ 100

1858 (473)

2218 (562)

2034 (527)

1378 (352)

4478 (1140)

24 (610)

 

included.

SQ-BSQ 120

1858 (473)

24 (610)

2234 (578)

 

16 (406)

4938 (1254)

2818 (714)

 

Supplied by

SQ-BSQ 130

1858 (473)

2618 (664)

2434 (629)

1778 (454)

44 (1118)

23 (584)

 

others.

 

 

SQ-BSQ 140

1958 (498)

2818 (714)

2634 (679)

1978 (505)

50116 (1272)

28 (711)

 

 

SQ-BSQ 160

2312 (597)

31 (787)

2934 (756)

2278 (581)

4958 (1260)

2358 (600)

 

 

BSQ 180

2512 (648)

3312 (851)

29916 (751)

2234 (578)

52916 (1335)

2412 (622)

 

Hanging

BSQ 200

2918 (740)

37 (940)

3334 (857)

2634 (679)

64316 (1630)

3214 (819)

 

 

rails not

BSQ 240

3158 (803)

4414 (1124)

4034 (1035)

3378 (860)

6612 (1689)

3218 (816)

 

included.

BSQ 300

35 (889)

51 (1295)

4734 (1213)

4078 (1038)

6918 (1756)

3138 (797)

 

Supplied by

BSQ 360

3834 (974)

5714 (1454)

5312 (1359)

4634 (1187)

76 (1930)

341116 (881)

 

others.

 

 

BSQ 420

4718 (1197)

63 (1600)

5978 (1521)

5978 (1521)

9012 (2299)

4012 (1029)

 

 

All dimensions in inches (millimeters).

10

Base Mount or Hanging Isolators

j

Standing Neoprene Isolator

 

h

L

j

Standing Spring Isolator

 

 

58 inch (16 mm) nominal

h

i

Hanging Spring Isolator

K

h

j

Hanging Neoprene Isolator

h

j

Complete isolation kits are available with either neoprene or spring isolators and are sized to match the weight of the specified fan size.. The hanging isolator support brackets are designed to permit mounting of the fan with the motor located on top, bottom or side.. The base isolator support brackets are designed to permit mounting of the fan with the motor located on top or either side..

Note: Hanging rods to be supplied by others.

Model

H

I

J

K

L

SQ 60-75

 

 

 

 

 

SQ 80-95

 

 

 

 

 

 

 

 

 

 

 

BSQ 70-90

138

512

2

634

2516

SQ-BSQ 100

(35)

(140)

(51)

(171)

(59)

 

SQ-BSQ 120

 

 

 

 

 

SQ-BSQ 130

 

 

 

 

 

 

 

 

 

 

 

SQ-BSQ 140

 

 

 

 

 

SQ-BSQ 160

 

 

 

 

 

 

 

 

 

 

 

BSQ 180

 

 

 

 

 

BSQ 200

138

512

2

634

258

 

BSQ 240

(35)

(140)

(51)

(171)

(67)

BSQ 300

 

 

 

 

 

 

 

 

 

 

 

BSQ 360

 

 

 

 

 

BSQ 420

 

 

 

 

 

 

 

 

 

 

 

All dimensions in inches (millimeters).

11

Filter Options

The filter box is designed to provide a compact and convenient air solution.. Factory assembled as a single unit, this fan eliminates

costly process of designing, fabricating and installing special remote filter box assemblies.. Both the fan and filter section feature removable access panels on both sides to remove and replace filters, making fan maintenance simple and fast..

Model Selection Procedure

1..Calculate system pressure drop and cfm requirements (not including filters)..

2..Make a preliminary model size selection..

3..Calculate a filter pressure drop (P) for the preliminary

model size selected in step 2 using the equation: P = F x ( 10,000cfm )2

To determine the filter factor (F) refer to chart below..

4..Add the filter pressure drop (P) to the system pressure drop and make a revised model size selection..

Model SQ Model

Model BSQ

Fan

Filter Box

 

Filter

 

Filter Factor (F)

 

Filter Size

1 inch (25)

2 inch (51)

Size

Weight

 

Quantity

 

 

 

 

 

Aluminum

Paper Filters

Aluminum

Paper Filters

 

 

 

 

60 - 75

40

10 x 12

1

186

318.06

251.1

303.18

(18)

(254 x 305)

 

 

 

 

 

 

80 - 95

74

14 x 25

1

21.8

37.28

29.43

35.53

(34)

(356 x 635)

 

 

 

 

 

 

100

88

16 x 20

2

8.72

14.91

11.77

14.21

(40)

(406 x 508)

 

 

 

 

 

 

120

114

16 x 25

2

5.58

9.54

7.53

9.10

(52)

(406 x 635)

 

 

 

 

 

 

130

120

20 x 20

2

5.58

9.54

7.53

9.10

(54)

(508 x 508)

 

 

 

 

 

 

140

174

20 x 25

2

3.57

6.11

4.82

5.82

(79)

(508 x 635)

 

 

 

 

 

 

160

246

20 x 20

4

2.09

3.57

2.82

3.41

(112)

(508 x 508)

 

 

 

 

 

 

70 - 80 - 90

117

14 x 25

1

21.8

37.28

29.43

35.53

(53)

(356 x 635)

 

 

 

 

 

 

100

120

16 x 20

2

8.72

14.91

11.77

14.21

(54)

(406 x 508)

 

 

 

 

 

 

120

144

16 x 25

2

5.58

9.54

7.53

9.10

(79)

(406 x 635)

 

 

 

 

 

 

130 - 130HP

140

20 x 20

2

5.58

9.54

7.53

9.10

(64)

(508 x 508)

 

 

 

 

 

 

140 - 140HP

181

20 x 25

2

3.57

6.11

4.82

5.82

(82)

(508 x 635)

 

 

 

 

 

 

160 - 160HP

294

20 x 20

4

2.09

3.57

2.82

3.41

(133)

(508 x 508)

 

 

 

 

 

 

180 - 180HP

344

20 x 25

4

1.34

2.29

1.81

2.18

(156)

(508 x 635)

 

 

 

 

 

 

 

 

12 x 25

3

 

 

 

 

200 - 200HP

441

(305 x 635)

0.77

1.32

1.04

1.26

 

(200)

16 x 25

3

 

 

 

 

 

 

 

(406 x 635)

 

 

 

 

 

 

 

 

 

 

 

 

 

20 x 25

4

 

 

 

 

240 - 240HP

573

(508 x 635)

0.41

0.70

0.55

0.67

 

(260)

16 x 25

4

 

 

 

 

 

 

 

(406 x 635)

 

 

 

 

 

 

 

 

 

 

 

300 - 300HP

759

20 x 25

8

0.33

0.56

0.45

0.54

(344)

(508 x 635)

 

 

 

 

 

 

 

 

16 x 25

10

 

 

 

 

360 - 360HP

957

(406 x 635)

0.15

0.26

0.20

0.25

 

(434)

20 x 25

5

 

 

 

 

 

 

 

(508 x 635)

 

 

 

 

 

 

 

 

 

 

 

 

 

16 x 25

5

 

 

 

 

420

1185

(406 x 635)

0.13

0.22

0.18

0.21

 

(538)

20 x 25

10

 

 

 

 

 

 

 

(508 x 635)

 

 

 

 

 

 

 

 

 

 

 

Note: 24-inch side clearance is recommended for accessing and removing filters. All dimensions in inches (millimeters) and weight in pounds (kilograms).

12

Typical Installation

Models SQ/BSQ ducted inline fans are designed for the exhaust, supply or recirculation of air in a building.. Typical installation requires ductwork on the inlet and outlet side of the fan.. A minimum of three duct diameters is required on the inlet and outlet of the fan to minimize system effect losses.. See the diagram below for a typical installation..

Installations can include flexible duct connections (by others) on either the inlet or outlet side of the fan

or both.. The motor is rigidly mounted and can be oriented in any direction (top, bottom, side)..

The model BSQ ducted inline fan must be installed with the motor accessible for maintenance and inspection..

External isolators are recommended, hanging (shown below) or base mounted..

Installation must meet all local governing codes and the NEC..

Flexible duct (by others)

3 Wheel

Diameters

3 Wheel

Diameters

Model Number Code

The model number system is designed to completely identify the fan.. The correct code letters must be specified to designate belt or direct drive.. The remainder of the model number is determined by the size and performance selected from the following pages..

BSQ - 300 HP - 75

Model Configuration

Bsq - Belt Drive Inline Exhaust

SQ - Direct Drive Inline Exhaust

Fan Size

60 through 420

Pressure Level (Belt Drive Only)

HP - High Pressure Wheel

Motor­

HP (Belt Drive only)

6 = 1/6

 

7

= 3/4

30 = 3

4 = 1/4

 

10

= 1

50 = 5

3 = 1/3

 

15

= 112

75 = 712

5 = 1/2

 

20

= 2

100 = 10

Motor RPM (Direct Drive only)

A = 1725

D = 1550

B = 1140

E = 1050

C = 860

 

G = 1300

13

SQ 60-65 - Direct Drive

1

(25)

878

(225)

12

(305)

12 13

(305)

(330)

Damper size = 9 x 9 (229 x 229) Unit weight** = 26 (12) Housing thickness = 20 ga Outlet velocity = 1.828 x cfm

Dimensions shown in inches (millimeters) and weight is shown in pounds (kilograms).

**Weight shown is largest cataloged Open Drip Proof motor.

Static Pressure Pa

110

100

90

80

70

60

50

40

30

20

10

0

 

0.45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RPM

 

 

0.40

 

 

 

 

 

 

 

 

Density 0.075 lb/ft3

 

0.35

 

 

 

SQ-

 

 

 

 

 

 

wg

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.30

 

 

 

 

65

D

 

 

 

 

in.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SQ

 

 

 

 

Pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-

 

 

 

 

 

0.25

 

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

60

 

 

 

 

 

 

 

 

 

 

 

 

-

 

 

 

 

 

 

 

 

 

SQ-

 

D

 

 

 

 

 

0.20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

G

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Static

 

 

 

 

SQ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.15

 

 

 

 

-

 

 

 

 

 

 

 

 

 

60

 

 

 

 

 

 

 

 

 

 

 

 

-

 

 

 

 

 

 

 

SQ-

 

SQ

 

G

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.10

 

 

60-

 

 

 

 

 

 

 

 

 

 

 

E

 

 

65-

 

 

 

 

 

 

 

 

 

 

 

 

E

 

 

 

 

 

0.05

 

 

 

 

 

 

 

 

 

 

 

 

0.000

 

50

 

 

100

150

 

200

250

 

 

 

 

 

 

 

 

cfm

 

 

 

 

 

0

50

100

 

150

 

200

250

300

350

400

 

 

 

 

 

 

 

 

m3/hr

 

 

 

 

Model Number

Motor

Fan

 

 

 

 

CFM / Static Pressure in Inches wg

 

 

 

HP

RPM

 

0..000

0..050

0..100

 

0..125

0..150

0..200

0..250

 

0..300

0..350

0..375

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

126

101

78

 

63

42

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SQ-60-E

1/140

1050

BHP

0.005

0.006

0.007

 

0.007

0.006

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sones

1.7

1.7

1.8

 

1.8

1.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

156

135

117

 

109

99

72

37

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SQ-60-G

1/80

1300

BHP

0.01

0.011

0.012

 

0.012

0.013

0.013

0.012

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sones

2.5

2.5

2.5

 

2.5

2.5

2.5

2.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

186

168

153

 

145

138

122

105

 

78

47

31

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SQ-60-D

1/40

1550

BHP

0.017

0.018

0.019

 

0.02

0.020

0.022

0.022

 

0.021

0.020

0.019

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sones

4.0

4.0

4.0

 

4.0

4.0

4.0

4.0

 

4.1

4.1

4.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

154

129

98

 

79

56

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SQ-65-E

1/100

1050

BHP

0.007

0.008

0.009

 

0.009

0.008

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sones

2.1

2.0

2.0

 

1.9

1.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

191

171

149

 

137

123

92

52

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SQ-65-G

1/50

1300

BHP

0.013

0.014

0.016

 

0.016

0.017

0.016

0.015

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sones

2.9

2.9

2.9

 

2.9

2.9

2.8

2.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

228

213

194

 

184

175

153

128

 

101

66

46

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SQ-65-D

1/30

1550

BHP

0.022

0.023

0.026

 

0.026

0.027

0.028

0.028

 

0.027

0.025

0.023

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sones

4.2

4.1

4.1

 

4.0

4.0

3.9

3.8

 

3.7

3.6

3.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).

The sound ratings shown are loudness values in fan sones at 1.5 m (5 feet) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type B: free inlet hemispherical fan sone levels.

14

SQ 70-75 - Direct Drive

1

(25)

878

(225)

12

(305)

12

13

(305) (330)

Damper size = 9 x 9 (229 x 229) Unit weight** = 26 (12) Housing thickness = 20 ga Outlet velocity = 1.828 x cfm

Dimensions shown in inches (millimeters) and weight is shown in pounds (kilograms).

**Weight shown is largest cataloged Open Drip Proof motor.

Static Pressure Pa

110

100

90

80

70

60

50

40

30

20

10

0

 

0.45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RPM

 

 

 

0.40

 

 

 

 

 

 

 

 

Density 0.075 lb/ft3

 

 

0.35

 

 

 

 

 

 

SQ

 

 

 

 

wg

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75

 

 

 

 

 

0.30

 

 

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

in.

 

 

 

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

SQ

 

 

 

 

Pressure

 

 

 

 

 

 

 

 

 

 

0.25

 

 

SQ

 

-

 

 

 

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

70

 

 

 

 

 

 

 

 

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

 

SQ

 

 

 

 

 

0.20

 

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

75

 

 

 

 

 

 

 

 

 

-

 

G

 

 

 

 

Static

 

 

 

 

70

 

 

 

 

 

0.15

 

 

 

75

-

 

 

 

 

 

 

 

SQ

 

 

G

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

SQ

-

 

 

 

 

 

 

 

0.10

 

 

 

E

 

 

 

 

 

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

70

 

 

 

 

 

 

 

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

E

 

 

 

 

 

 

 

0.05

 

 

 

 

 

 

 

 

 

 

 

 

0.000

50

100

 

150

 

200

250

300

350

400

 

 

 

 

 

 

 

 

cfm

 

 

 

 

 

0

100

200

 

 

 

300

400

500

600

 

 

 

 

 

 

 

 

 

m3/hr

 

 

 

 

Model Number

Motor

Fan

 

 

 

 

CFM / Static Pressure in Inches wg

 

 

 

HP

RPM

 

0..000

0..100

0..125

 

0..150

0..200

0..250

0..300

 

0..350

0..375

0..400

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

212

140

118

 

86

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SQ-70-E

1/100

1050

BHP

0.008

0.009

0.009

 

0.009

 

 

 

 

 

 

 

 

 

 

Sones

2.7

1.7

1.5

 

1.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

262

204

190

 

176

139

77

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SQ-70-G

1/50

1300

BHP

0.015

0.018

0.018

 

0.018

0.017

0.015

 

 

 

 

 

 

 

 

Sones

4.1

3.4

3.3

 

3.1

2.9

2.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

313

265

252

 

240

216

189

155

 

99

67

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SQ-70-D

1/30

1550

BHP

0.026

0.029

0.030

 

0.030

0.030

0.030

0.029

 

0.026

0.025

 

 

 

 

Sones

5.6

5.2

5.1

 

5.1

4.9

4.7

4.5

 

4.2

4.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

241

167

146

 

123

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SQ-75-E

1/100

1050

BHP

0.010

0.011

0.011

 

0.010

 

 

 

 

 

 

 

 

 

 

Sones

3.6

2.9

2.8

 

2.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

298

239

224

 

209

176

133

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SQ-75-G

1/50

1300

BHP

0.019

0.021

0.021

 

0.021

0.020

0.019

 

 

 

 

 

 

 

 

Sones

4.1

3.7

3.7

 

3.7

3.6

3.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

356

306

294

 

281

256

229

201

 

164

137

99

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SQ-75-D

1/30

1550

BHP

0.032

0.034

0.035

 

0.035

0.035

0.035

0.034

 

0.033

0.032

0.029

 

 

 

Sones

6.1

5.5

5.4

 

5.3

5.1

4.9

4.9

 

4.8

4.8

4.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).

The sound ratings shown are loudness values in fan sones at 1.5 m (5 feet) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type B: free inlet hemispherical fan sone levels.

15

Loading...