PRODUCT SPECIFICATIONS
PCK SERIES
10 SEER
Packaged
Air Conditioner
2 to 5 Ton
Cooling Capacity: 23,200 - 58,000 BTUH
C
The PCK packaged air conditioner allows for side-by-side ground-level or rooftop application and is approved for manufactured or modular homes.
Standard Features
•Hermetically sealed compressor with internal relief valve
•Two-speed evaporator blower motor; low-speed for normal or low-static application/high-speed for highstatic application in manufactured homes
•Totally enclosed, permanently lubricated condenser fan motor
•Copper tube/aluminum fin coil
•Fully charged R-22 system
•Liquid line filter drier
•Quiet-operating top grille condenser discharge
•Fully insulated air handling compartment
•Bottom pan rails elevate the unit above the slab
•Convenient access panels
Cabinet Construction
•Powder-paint finish with 500-hour salt spray approval
•Fully insulated air handling compartment
•Convenient access panels
•When properly anchored, meets the 2001 Florida Building Code unit integrity requirements for hurricane-type winds
Accessories
•Roof Curb
•Downflow Plenum (includes filter rack)
•Manual Fresh Air Damper (to be used with Downflow Plenum)
•Economizer (to be used with Downflow Plenum)
•Louvered Panel Kit (LPAK-00A, LPAK-01A, LPAK-02A)
•Square-to-Round Duct Converter for Round Duct applications (horizontal and downflow)
•Elbow and Flashing Downflow Kit
•Room Thermostat (CHT18-60)
•Outdoor Thermostat (OT18-60)
•Heat Kit from 5 to 20 kW with plug-in connection
Accessory Heat Kit Features
•Controlled by sequencers for better temperature control (single-phase units only)
•Control circuitry arranged to readily permit staging (HK10, 15, 20-1 only)
•Primary/secondary limit protection
•Rust-resistant nickel chromium heating elements
• Factory-installed circuit breakers on certain models (see Electrical Data)
SS-278D |
www.goodmanmfg.com |
1/05 |
Supercedes 8/04
PRODUCT SPECIFICATIONS
Nomenclature
PCK 024 -1 F
Revision
Electrical Designator
1 - 208/230 VAC, 1 Ph, 60 Hz
3 - 208/230 VAC, 3 Ph, 60 Hz
4 - 460 VAC, 3 Ph, 60 Hz
Nominal Capacity
024 - 24,000 BTUH
030 - 30,000 BTUH
036 - 36,000 BTUH
042 - 42,000 BTUH
048 - 48,000 BTUH
060 - 60,000 BTUH
Unit Type
Packaged Air Conditioner
(2nd Generation)
All Units Are Direct Drive
Specifications
|
PCK024-1F |
PCK030-1F |
PCK036-1F |
PCK036-3F |
PCK042-1F |
Total Cooling (BTUH) |
23,200 |
28,400 |
35,000 |
35,000 |
42,000 |
Sensible Cooling (BTUH) |
16,800 |
20,600 |
25,600 |
25,600 |
32,000 |
SEER1 |
10.0 |
10.0 |
10.0 |
10.0 |
10.0 |
EERa2 |
9.0 |
9.0 |
9.0 |
9.0 |
9.0 |
Sound Rating (bels) |
8.0 |
8.0 |
8.0 |
8.0 |
8.4 |
Indoor Blower |
|
|
|
|
|
Type |
DD |
DD |
DD |
DD |
DD |
Size (D” x W”) |
9 x 6 |
9 x 6 |
9 x 6 |
9 x 6 |
9 x 8 |
Motor Horsepower |
1/5 |
1/3 |
1/3 |
1/3 |
1/3 |
Evaporator Coil |
|
|
|
|
|
Face Area (ft2) |
3.33 |
3.33 |
3.33 |
3.33 |
5.25 |
Fins per Inch |
14 |
14 |
14 |
14 |
14 |
No. of Rows |
2 |
2 |
3 |
3 |
3 |
Outdoor Fan |
|
|
|
|
|
Fan Diameter |
18” |
18” |
18” |
18” |
22” |
Motor Horsepower |
1/6 |
1/6 |
1/6 |
1/6 |
1/4 |
Condenser Coil |
|
|
|
|
|
Face Area (ft2) |
12.1 |
12.1 |
12.1 |
12.1 |
14.7 |
Fins per Inch |
19 |
19 |
19 |
19 |
19 |
No. of Rows |
1 |
1 |
1 |
1 |
1 |
Electrical |
|
|
|
|
|
Ph |
1 |
1 |
1 |
3 |
1 |
Volts |
208/230 |
208/230 |
208/230 |
208/230 |
208/230 |
Compressor RLA |
9.8 |
13.8 |
16.2 |
10.3 |
17.1 |
Compressor LRA |
56.0 |
75.0 |
96.0 |
75.0 |
105.0 |
Indoor Blower FLA |
1.7 |
2.6 |
2.6 |
2.6 |
2.6 |
Outdoor Blower FLA |
1.0 |
1.0 |
1.0 |
1.0 |
1.6 |
Minimum Circuit Ampacity |
15.0 |
20.9 |
23.9 |
16.5 |
25.6 |
Maximum Overcurrent Protection |
20 |
30 |
40 |
20 |
40 |
Net Weight (pounds) |
240 |
245 |
265 |
265 |
335 |
Shipping Weight (pounds) |
255 |
260 |
280 |
280 |
350 |
(1)Certified per ARI 210
(2)BTU/Watt @ 80/67 °F inside - 95 °F outside air
Note - May use fuses or HACR type Circuit Breakers of the same size as noted.
2
PRODUCT SPECIFICATIONS
Specifications (cont.)
|
PCK048-1F |
PCK048-3F |
PCK060-1F |
PCK060-3F |
PCK060-4F |
Total Cooling (BTUH) |
46,000 |
46,000 |
58,000 |
58,000 |
58,000 |
Sensible Cooling (BTUH) |
35,800 |
35,800 |
43,500 |
43,500 |
43,500 |
SEER1 |
10.0 |
10.0 |
10.0 |
10.0 |
10.0 |
EERa2 |
9.0 |
9.0 |
9.0 |
9.0 |
9.0 |
Sound Rating (bels) |
8.4 |
8.4 |
8.4 |
8.4 |
8.4 |
Indoor Blower |
|
|
|
|
|
Type |
DD |
DD |
DD |
DD |
DD |
Size (D” x W”) |
10 x 8 |
10 x 8 |
10 x 8 |
10 x 8 |
10 x 8 |
Motor Horsepower |
1/2 |
1/2 |
3/4 |
3/4 |
3/4 |
Evaporator Coil |
|
|
|
|
|
Face Area (ft2) |
5.75 |
5.75 |
6.22 |
6.22 |
6.22 |
Fins per Inch |
14 |
14 |
14 |
14 |
14 |
No. of Rows |
4 |
4 |
4 |
4 |
4 |
Outdoor Fan |
|
|
|
|
|
Fan Diameter |
22” |
22” |
22” |
22” |
22” |
Motor Horsepower |
1/4 |
1/4 |
1/3 |
1/3 |
1/3 |
Condenser Coil |
|
|
|
|
|
Face Area (ft2) |
14.7 |
14.7 |
16.2 |
16.2 |
16.2 |
Fins per Inch |
19 |
19 |
19 |
19 |
19 |
No. of Rows |
1 |
1 |
1 |
1 |
1 |
Electrical |
|
|
|
|
|
Ph |
1 |
3 |
1 |
3 |
3 |
Volts |
208/230 |
208/230 |
208/230 |
208/230 |
460 |
Compressor RLA |
18.3 |
12.6 |
25.0 |
15.5 |
7.5 |
Compressor LRA |
102.0 |
91.0 |
170.0 |
124.0 |
59.6 |
Indoor Blower FLA |
3.6 |
3.6 |
5.1 |
5.1 |
2.2 |
Outdoor Blower FLA |
1.6 |
1.6 |
2.5 |
2.5 |
1.2 |
Minimum Circuit Ampacity |
28.2 |
21.0 |
38.9 |
27.0 |
12.8 |
Maximum Overcurrent Protection |
40 |
30 |
60 |
40 |
20 |
Net Weight (pounds) |
340 |
340 |
350 |
350 |
350 |
Shipping Weight (pounds) |
365 |
365 |
375 |
375 |
375 |
(1)Certified per ARI 210
(2)BTU/Watt @ 80/67 °F inside - 95 °F outside air
Note - May use fuses or HACR type Circuit Breakers of the same size as noted.