Goodman PCK024-1F, PCK030-1F, PCK036-1F, PCK036-3F, PCK042-1F REPAIR PARTS

...
5 (6)
Goodman PCK024-1F, PCK030-1F, PCK036-1F, PCK036-3F, PCK042-1F REPAIR PARTS

PRODUCT SPECIFICATIONS

PCK SERIES

10 SEER

Packaged

Air Conditioner

2 to 5 Ton

Cooling Capacity: 23,200 - 58,000 BTUH

C

The PCK packaged air conditioner allows for side-by-side ground-level or rooftop application and is approved for manufactured or modular homes.

Standard Features

Hermetically sealed compressor with internal relief valve

Two-speed evaporator blower motor; low-speed for normal or low-static application/high-speed for highstatic application in manufactured homes

Totally enclosed, permanently lubricated condenser fan motor

Copper tube/aluminum fin coil

Fully charged R-22 system

Liquid line filter drier

Quiet-operating top grille condenser discharge

Fully insulated air handling compartment

Bottom pan rails elevate the unit above the slab

Convenient access panels

Cabinet Construction

Powder-paint finish with 500-hour salt spray approval

Fully insulated air handling compartment

Convenient access panels

When properly anchored, meets the 2001 Florida Building Code unit integrity requirements for hurricane-type winds

Accessories

Roof Curb

Downflow Plenum (includes filter rack)

Manual Fresh Air Damper (to be used with Downflow Plenum)

Economizer (to be used with Downflow Plenum)

Louvered Panel Kit (LPAK-00A, LPAK-01A, LPAK-02A)

Square-to-Round Duct Converter for Round Duct applications (horizontal and downflow)

Elbow and Flashing Downflow Kit

Room Thermostat (CHT18-60)

Outdoor Thermostat (OT18-60)

Heat Kit from 5 to 20 kW with plug-in connection

Accessory Heat Kit Features

Controlled by sequencers for better temperature control (single-phase units only)

Control circuitry arranged to readily permit staging (HK10, 15, 20-1 only)

Primary/secondary limit protection

Rust-resistant nickel chromium heating elements

• Factory-installed circuit breakers on certain models (see Electrical Data)

SS-278D

www.goodmanmfg.com

1/05

Supercedes 8/04

PRODUCT SPECIFICATIONS

Nomenclature

PCK 024 -1 F

Revision

Electrical Designator

1 - 208/230 VAC, 1 Ph, 60 Hz

3 - 208/230 VAC, 3 Ph, 60 Hz

4 - 460 VAC, 3 Ph, 60 Hz

Nominal Capacity

024 - 24,000 BTUH

030 - 30,000 BTUH

036 - 36,000 BTUH

042 - 42,000 BTUH

048 - 48,000 BTUH

060 - 60,000 BTUH

Unit Type

Packaged Air Conditioner

(2nd Generation)

All Units Are Direct Drive

Specifications

 

PCK024-1F

PCK030-1F

PCK036-1F

PCK036-3F

PCK042-1F

Total Cooling (BTUH)

23,200

28,400

35,000

35,000

42,000

Sensible Cooling (BTUH)

16,800

20,600

25,600

25,600

32,000

SEER1

10.0

10.0

10.0

10.0

10.0

EERa2

9.0

9.0

9.0

9.0

9.0

Sound Rating (bels)

8.0

8.0

8.0

8.0

8.4

Indoor Blower

 

 

 

 

 

Type

DD

DD

DD

DD

DD

Size (D” x W”)

9 x 6

9 x 6

9 x 6

9 x 6

9 x 8

Motor Horsepower

1/5

1/3

1/3

1/3

1/3

Evaporator Coil

 

 

 

 

 

Face Area (ft2)

3.33

3.33

3.33

3.33

5.25

Fins per Inch

14

14

14

14

14

No. of Rows

2

2

3

3

3

Outdoor Fan

 

 

 

 

 

Fan Diameter

18”

18”

18”

18”

22”

Motor Horsepower

1/6

1/6

1/6

1/6

1/4

Condenser Coil

 

 

 

 

 

Face Area (ft2)

12.1

12.1

12.1

12.1

14.7

Fins per Inch

19

19

19

19

19

No. of Rows

1

1

1

1

1

Electrical

 

 

 

 

 

Ph

1

1

1

3

1

Volts

208/230

208/230

208/230

208/230

208/230

Compressor RLA

9.8

13.8

16.2

10.3

17.1

Compressor LRA

56.0

75.0

96.0

75.0

105.0

Indoor Blower FLA

1.7

2.6

2.6

2.6

2.6

Outdoor Blower FLA

1.0

1.0

1.0

1.0

1.6

Minimum Circuit Ampacity

15.0

20.9

23.9

16.5

25.6

Maximum Overcurrent Protection

20

30

40

20

40

Net Weight (pounds)

240

245

265

265

335

Shipping Weight (pounds)

255

260

280

280

350

(1)Certified per ARI 210

(2)BTU/Watt @ 80/67 °F inside - 95 °F outside air

Note - May use fuses or HACR type Circuit Breakers of the same size as noted.

2

PRODUCT SPECIFICATIONS

Specifications (cont.)

 

PCK048-1F

PCK048-3F

PCK060-1F

PCK060-3F

PCK060-4F

Total Cooling (BTUH)

46,000

46,000

58,000

58,000

58,000

Sensible Cooling (BTUH)

35,800

35,800

43,500

43,500

43,500

SEER1

10.0

10.0

10.0

10.0

10.0

EERa2

9.0

9.0

9.0

9.0

9.0

Sound Rating (bels)

8.4

8.4

8.4

8.4

8.4

Indoor Blower

 

 

 

 

 

Type

DD

DD

DD

DD

DD

Size (D” x W”)

10 x 8

10 x 8

10 x 8

10 x 8

10 x 8

Motor Horsepower

1/2

1/2

3/4

3/4

3/4

Evaporator Coil

 

 

 

 

 

Face Area (ft2)

5.75

5.75

6.22

6.22

6.22

Fins per Inch

14

14

14

14

14

No. of Rows

4

4

4

4

4

Outdoor Fan

 

 

 

 

 

Fan Diameter

22”

22”

22”

22”

22”

Motor Horsepower

1/4

1/4

1/3

1/3

1/3

Condenser Coil

 

 

 

 

 

Face Area (ft2)

14.7

14.7

16.2

16.2

16.2

Fins per Inch

19

19

19

19

19

No. of Rows

1

1

1

1

1

Electrical

 

 

 

 

 

Ph

1

3

1

3

3

Volts

208/230

208/230

208/230

208/230

460

Compressor RLA

18.3

12.6

25.0

15.5

7.5

Compressor LRA

102.0

91.0

170.0

124.0

59.6

Indoor Blower FLA

3.6

3.6

5.1

5.1

2.2

Outdoor Blower FLA

1.6

1.6

2.5

2.5

1.2

Minimum Circuit Ampacity

28.2

21.0

38.9

27.0

12.8

Maximum Overcurrent Protection

40

30

60

40

20

Net Weight (pounds)

340

340

350

350

350

Shipping Weight (pounds)

365

365

375

375

375

(1)Certified per ARI 210

(2)BTU/Watt @ 80/67 °F inside - 95 °F outside air

Note - May use fuses or HACR type Circuit Breakers of the same size as noted.

3

Loading...