General ASHA18LE, ASHA18LEC, AOHR18LEC Installation Manual

SPLIT TYPE ROOM AIR CONDITIONER
WALL MOUNTED
INVERTER
INSTRUCTION
Models Indoor unit Outdoor unit
AS*A18LEC
type
AO*R18LEC
R410A
1. SPECIFICATION
CONTENTS
AS*A18LEC.....................................................................................................................
2. DIMENSIONS
AS*A18LEC.....................................................................................................................
3. REFRIGERANT SYSTEM DIAGRAM
AS*A18LEC.....................................................................................................................
4. CIRCUIT DIAGRAM
AS*A18LEC.....................................................................................................................
5. DESCRIPTION OF EACH CONTROL OPERATION
1. COOLING OPERATION..............................................................................................
2. HEATING OPERATION..............................................................................................
01-01
02-01
03-01
04-01
05-01 05-02
3. DRY OPERATION......................................................................................................
4. AUTO CHANGEOVER OPERATION.........................................................................
5. INDOOR FAN CONTROL...........................................................................................
6. OUTDOOR FAN CONTROL.......................................................................................
7. LOUVER CONTROL...................................................................................................
8. COMPRESSOR CONTROL........................................................................................
9. TIMER OPERATION CONTROL................................................................................
10. ELECTRONIC EXPANSION VALVE CONTROL........................................................
11. TEST OPERATION CONTROL..................................................................................
12. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST )................................
13. FOUR-WAY VALVE EXTENSION SELECT...............................................................
14. AUTO RESTART........................................................................................................
15. MANUAL AUTO OPERATION ( Indoor unit body operation ).....................................
16. FORCED COOLING OPERATION............................................................................
17. COMPRESSOR PREHEATING..................................................................................
18. COIL DRY OPEARTION CONTROL..........................................................................
19. DEFROST OPERATION CONTROL..........................................................................
05-03 05-04 05-05 05-07 05-08 05-10 05-11 05-13 05-13 05-13 05-13 05-13 05-14 05-14
05-14 05-14
05-15
20. OFF DEFROST OPERATION CONTROL..................................................................
21. 10°C HEAT OPERATION...........................................................................................
22. VARIOUS PROTECTIONS......................................................................................... 05-18
05-17 05-17
6. REFRIGERANT CAUTION -R410A-
1. R410A TOOLS............................................................................................................
2. PRECAUTION FOR INSTALLATION.........................................................................
3. PRECAUTION FOR SERVICING...............................................................................
4. NEW REFRIGERANT R410A.....................................................................................
5. DEFFERENCE FROM CONVENTIONAL MODEL(R22) AND PRECAUTIONS........
7. TROUBLE SHOOTING
1. WHEN THE UNIT DOES NOT OPERATE AT ALL....................................................
2. SELF DIAGNOSIS FUNCTION..................................................................................
3. TROUBLE SHOOTING METHOD
4. SELF-DIAGNOSIS FUNCTION AND CHECKING POINTS.......................................
5. SERIAL SIGNAL DIAGNOSIS....................................................................................
6. IPM PROTECTION.....................................................................................................
7. TROUBLE SHOOTING OF REFRIGERANT CYCLE.................................................
8. APPENDING DATA
06-01 06-02 06-04 06-05 06-08
07-01 07-02
07-03 07-07
07-08 07-09
1. Jumper & Function setting..........................................................................................
2. Thermistor Resistance Values....................................................................................
9. REPLACEMENT PARTS
10. INSTALLATION MANUAL
08-01 08-02
WALL MOUNTED type
R410A
INVERTER
1 . SPECIFICATIONS
SPECIFICATIONS
ELECTRICAL DATA
INDOOR UNIT
OUTDOOR UNIT
POWER SOURCE
FREQUENCY
COOLING CAPACITY
HEATING CAPACITY 6.30 kW
RUNNING CURRENT (Cool)
RUNNING CURRENT (Heat)
INPUT WATTS (Cooling)
INPUT WATTS (Heating)
E.E.R. (Cooling)
C.O.P. (Heating)
MAXIMUM CURRENT (Cool)
MAXIMUM CURRENT (Heat)
MOISTURE REMOVAL
AS*A18LEC
AO*R18LEC
230 V
50 Hz
5.20 kW
6.8 A
7.6 A
1.52 kW
1.71 kW
3.42 kW/kW
3.68 kW/kW
9.0 A
12.5 A
2.8 L/hr
COMPRESSOR AND REFRIGERANT
Hermetic type,
TYPE
DISCRIMINATION
WEIGHT (with oil)
REFRIGERANT TYPE
PRECHARGED REFRIGERANT
Pipe Length
FULL CHARGE
ADDITIONAL CHARGE
MAX HEIGHT
15 m
20 m
25 m
4 pole, Rotary,
DC inverter motor
808 903 80
9.0 kg
R410A
1,200 g
1,200 g
1,300 g
1,400 g
20 g/m
20 m
DIMENSIONS
INDOOR UNIT
OUTDOOR UNIT
H x W x D
H x W x D
320 x 998 x 228 mm
620 x 790 x 298 mm
AIR CIRCULATION HIGH
FAN MOTOR
POWER SOURCE
High speed
INDOOR UNIT
OUTDOOR UNIT
Middle
Low
Quiet
NOISE LEVEL
High
INDOOR UNIT (Cooling / Heating)
OUTDOOR UNIT (Cool / Heat)
Middle
Low
Quiet
900 m3/hr
230 V
1,220 r.p.m.
1,020 r.p.m.
900 r.p.m.
710 r.p.m.
1,050 r.p.m.
43 dB / 42 dB
37 dB / 37 dB
33 dB / 33 dB
26 dB / 25 dB
50 dB / 52 dB
WEIGHT
INDOOR UNIT
OUTDOOR UNIT
Gross / Net
Gross / Net
18 kg / 14 kg
45 kg / 40 kg
01-01
WALL MOUNTED type
R410A
INVERTER
2 . DIMENSIONS
INDOOR UNIT
DIMENSIONS
(unit : mm)
320
OUTDOOR UNIT
998
228
29867790
620
20
02-01
WALL MOUNTED type
R410A
INVERTER
3 . REFRIGERANT SYSTEM DIAGRAM
REFRIGERANT SYSTEM DIAGRAM
3-Way
valve
Muffler
Muffler
Compressor
4-Way valve
Sub-accumulator
Heat exchanger (Indoor unit)
2-Way
valve
Strainer
Expansion valve
Strainer Heat exchanger (Outdoor unit)
Refrigerant direction
Cooling Heating
Refrigerant pipe diameter Liquid : 1/4" (6.35 mm) Gas : 1/2" (12.7 mm)
03-01
WALL MOUNTED type
R410A
INVERTER
4 . CIRCUIT DIAGRAM
INDOOR UNIT
TERMINAL
THERMAL
FUSE 102
TO OUTDOOR UNIT
1 2 3
RED
CIRCUIT DIAGRAM
THERMISTOR ( ROOM TEMP. )
INDICATOR PCB ASSY
BLACK
WHITE
TM1
TM4
TM2
W5
GREEN
2
1
WHITE
RED
2
1
2
1
1 1
4
3
WHITE
WHITE
4
3
4
3
CN11
CN2
2
3
2
3
YELLOW
ORANGE
RED
CN201
5
6
7
WHITE
WHITE
WHITE
5
6
7
5
1
6
7
5
4
2
3 CN6
CN5
4
2
5
4
5
4
PINK
1
3
4
2
1
3
YELLOW
ORANGE
BLUE
RED
THERMISTOR ( PIPE TEMP. )
BLACK
BLACK
2
3
1
2
3
BLACK
1
CN1
5
6
5
6
BLUE
PINK
1
BLACK
2
WHITE
RED
1
2
CN3
CN8
5
4
2
1
3
6
5
4
2
1
3
RED
ORANGE
6
BLUE
PINK
YELLOW
TEST
1
5
4
2
3
CONTROLLER PCB ASSY
( MAIN PCB )
CN13
CN10
1
2
3
4
5
6
5
6
RED
1
2
3
4
BLUE
YELLOW
WHITE
BLACK
OUTDOOR UNIT
REACTOR
WHITE
RED
THERMISTOR ( PIPE TEMP. )
THERMISTOR ( DISCHARGE TEMP. )
THERMISTOR ( OUTDOOR TEMP. )
WHITE
FUSE
250V 5A
BLACK
BLACK
REACTOR
or
BLACK
( RIGHT / LEFT )
WHITE
BLACK
BLACK BROWN BROWN
BLACK
BLACK
WHITE
FUSE
250V 20A
STEP MOTOR
RED
RED
BLACK
GREEN
STEP MOTOR
M
W10 W11
( UP / DOWN )
CONTROLLER PCB ASSY
1
1
2
2
CN71
3
3
4
4
1
1
CN70
2
2
3
3
W4
W2
W1
W3
M
CN800
CN40
CN30
W7 W8 W9
STEP MOTOR
( DIFFUSER )
M
RED
WHITE
BLACK
RED
1
1
2
2
3
3
BLACK
4
4
WHITE
5
5
YELLOW
6
6
BROWN
7
7
RED
1
1
BROWN
2
2
BLUE
3
3
ORANGE
4
4
YELLOW
5
5
WHITE
6
6
BLACK
1
1
2
2
BLACK
3
3
FAN MOTOR
FM
EXPANSION VALVE
PMV
4-WAY VALVE
4WV
F M
FAN MOTOR
COMPRESSOR
R
CM
S
C
TERMINAL
1
TO INDOOR UNIT
3 L
2
(N)
POWER SOURCE
N
04-01
WALL MOUNTED type
R410A
INVERTER
5 . DESCRIPTION OF EACH CONTROL OPERATION
1. COOLING OPERATION
1-1 COOLING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor. * If the room temperature is 2°C higher than a set temperature, the compressor operation frequency will attain to maximum performance.
* If the room temperature is 2.5°C lower than a set temperature, the compressor will be stopped.
* When the room temperature is between +2°C to -2.5°C of the setting temperature, the compressor frequency is controlled within the range shown in Table1. However, the maximum frequency is limited in the range shown in Figure 1 based on the fan speed mode and the outdoor temperature.
( Table 1 : Compressor Frequency Range )
minimum frequency
AS*A18LEC 18Hz 70Hz 95Hz
maximum frequency
maximum frequency
( Fig. 1 : Limit of Maximum Frequency based on Outdoor Temperature )
Outside air Outside air temperature temperature
A zone 95Hz 66Hz 54Hz 34Hz
B zone 95Hz 66Hz 54Hz 34Hz
C zone 95Hz 66Hz 54Hz 34Hz
D zone 58Hz 45Hz 30Hz 24Hz
E zone 58Hz 45Hz 30Hz 24Hz
F zone 58Hz 45Hz 30Hz 24Hz
34°C
30°C
19°C
10°C
0°C
A zone
B zone
C zone
D zone
E zone
36°C
32°C
21°C
12°C
2°C
18LEC
Hi Me Lo Quiet
F zone
When the compressor operates for 30 minutes continuously at over the maximum frequency , the maximum frequency is changed from Maximum Frequency to Maximum Frequency .
05-01
2. HEATING OPERATION
2-1 HEATING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor. * If the room temperature is lower by 3°C than a set temperature, the compressor operation frequency will attain to maximum performance.
* If the room temperature is higher 2.5°C than a set temperatire, the compressor will be stopped.
* When the room temperature is between +2.5°C to -3°C of the setting temperature, the compressor frequency is controlled within the range shown in Table2. However, the maximum frequency is limited in the range shown in Figure 2 based on the fan speed mode and the outdoor temperature.
( Table 2 : Compressor Frequency Range )
minimum frequency
AS*A18LEC 18Hz 130Hz
maximum frequency
( Fig.2 : Limit of Maximum Frequency based on Outdoor Temperature )
Outside air Outside air temperature temperature
17°C
12°C
C zone
B zone
A zone
19°C
14°C
18LEC
A zone
B zone
C zone
Hi Me+ Lo Quiet
130Hz 130Hz 75Hz 62Hz
130Hz 130Hz 75Hz 62Hz
130Hz 130Hz
Me
95Hz
95Hz
95Hz 75Hz 62Hz
* The room temperature is controlled 2°C higher than the setting temperature for 60 minutes after starting the operation. After 60 minutes, it is controlled based on the normal setting temperature.
05-02
3. DRY OPERATION
3-1 INDOOR UNIT CONTROL
The compressor rotation frequency shall change according to the temperature, set temperature, and room temperature variation which the room temperature sensor of the indoor unit body has detected as shown in the Table 3. However, after the compressor is driven, the indoor unit shall run at operation frequency of 40Hz, for a minute.
( Table 3 : Compressor frequency )
Operating frequency
18LEC
X zone
J zone
Y zone
( Fig.3 : Compressor Control based on Room Temperature )
Room Room temperature temperature
34Hz
20Hz
0Hz
Ts+0.5°C
Ts -1.5°C
( Fig.4 : Indoor Fan Control )
Compressor
ON
OFF
Indoor fan Setting air flow
Indoor fan (as shown in Table 4)
Quiet
Ts+1.5°C
X zone
Ts -0.5°C
J zone
Y zone
OFF
10 30 60 180 60 180 60 10 30
( Table 4 : Indoor fan speed )
X zone J, Y zone
AS*A18LEC 710rpm 660rpm
(SEC)
05-03
4. AUTO CHANGEOVER OPERATION
When the air conditioner is set to the AUTO mode by remote control, operation starts in the optimum mode from among the HEATING, COOLING, DRY and MONITORING modes. During operation, the optimum mode is automatically switched in accordance with temperature changes. The temperature can be set between 18°C and 30°C in 1°C steps.
When operation starts, only the indoor and outdoor fans are operated for 1 minute. After 1 minute,
1
the room temperature and outside air temperature are sensed and the operation mode is selected in accordance with the table below.
( Fig.5 : Outside air temperature zone selection )
C zone
32°C
B zone
-10°C A zone
( Table.5 Operation mode selection table)
Outside air temperature (TO)
Room temperature (TB)
TB > TS+2°C
TS+2°C TB TS - 2°C
<
TB TS- 2°C Heating Heating Monitoring
2
When COOING was selected at , the air conditioner operates as follow:
1
A zone B zone C zone
Monitoring
Monitoring Monitoring Monitoring
Cooling
(automatic dry)
Cooling
(automatic dry)
The same operation as COOLING OPERATION of item 1 above is performed.
When the room temperature has remained at (set temperature -1°C) for 8 minutes, operation is
automatically switched to DRY and the same operation as DRY OPERATION of item 3 above is performed.
If the room temperature reaches (set temperature +2°C during DRY operation, operation returns to COOLING operation.
3
When HEATING was selected at , the same operation as HEATING OPERATION of item 2
1
above is performed.
4
When the compressor was stopped for 6 consecutive minutes by the temperature control function after the COOLING or HEATING operation mode was selected at above, operation is switched
1
to MONITORING and the operation mode is selected again.
05-04
5. INDOOR FAN CONTROL
1. Fan speed
( Table 6 : Indoor Fan Speed )
AS*A18LEC
Operation mode Air flow mode Speed (rpm)
Heating
Cooling
Dry
2. FAN OPERATION
Hi Me+ Me Lo
Quiet
Cool air prevention
S-Lo Hi Me Lo
Quiet
1220 1120 1020
900 710 660
270 1220 1020
900
710
X zone: 710
J zone: 660
The airflow can be switched in 5 steps such as AUTO, QUIET, LOW, MED, HIGH, while the indoor fan only runs. When Fan mode is set at (Auto), it operates on (MED) Fan Speed.
3. COOLING OPERATION
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature, as shown in Figure 6. On the other hand, if switched in [HIGH] [QUIET], the indoor motor will run at a constant airflow of [COOL] operation modes QUIET, LOW, MED, HIGH,as shown in Table 6.
( Fig.6 : Airflow change - over ( Cooling : AUTO ) )
TR-Ts > 2.5 degC
=
2.5 degC > TR-Ts > 1.5 degC
1.5 degC > TR-Ts
=
TR-Ts > 2 degC
=
2 degC > TR-Ts > 1 degC
1 degC > TR-Ts
=
HIGH mode
MED mode
LOW mode
When the room temperature drops
When the room temperature rises
TR : Room temperature Ts : Setting temperature
05-05
4. DRY OPERATION
Refer to the Table 6. During the dry mode operation, the fan speed setting can not be changed.
5. HEATING OPERATION
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature, as shown in Figure 7.
On the other hand, if switched in [HIGH] [QUIET], the indoor motor will run at a constant airflow of [HEAT] operation modes QUIET, LOW, MED, HIGH, as shown in Table 6.
( Fig.7 : Airflow change - over ( Heating : AUTO ) )
When the room temperature rises
TR-Ts > - 1 degC
=
- 1 degC > TR-Ts > - 2 degC
- 2 degC > TR-Ts
TR : Room temperature Ts : Setting temperature
=
LOW mode
MED mode
MED+ mode
When the room temperature drops
TR-Ts > - 1.5 degC
=
- 1.5 degC > TR-Ts > - 2.5 degC
- 2.5 degC > TR-Ts
=
6. COOL AIR PREVENTION CONTROL (Heating mode)
The maximum value of the indoor fan speed is set as shown in Figure 8, based on the detected temperature by the indoor heat exchanger sensor on heating mode.
(Fig.8 : Cool Air Prevention Control)
Indoor heat exchanger temperature
47°C
40°C
37°C
30°C
< [Hi] setting >
Hi
Me+
Lo
Cool air prevention
S-Lo
Indoor heat exchanger temperature
40°C
34°C
32°C
28°C
Indoor heat exchanger temperature
40°C
37°C
30°C
< The other of [Hi] setting >
Setting FAN mode
Lo (Qu)
Cool air prevention
S-Lo
Indoor heat exchanger temperature
34°C
32°C
28°C
05-06
6. OUTDOOR FAN CONTROL
1. Outdoor Fan Motor
Following table shows the type of the outdoor fan motor. The control method is different between AC motor and DC motor.
( Table 7 : Type of Motor )
AC Motor DC Motor
AS*A18LEC
2. Fan Speed
( Table 8 : Outdoor fan speed )
ZONE
AS*A18LEC 1050/ 870/ 720/ 530
Refer to Fig1.
It runs at 500(A-D ZONE)/200(E,F ZONE) rpm for 20 seconds after starting up the outdoor fan.
*
The outdoor fan speed mentioned avobe depends on the compressor frequency.
*
A - C
D
E
F
Cooling Dry Heating
870/ 530/ 300
300
250/ 200
530
870/ 780/ 720/ 590/ 480
300
250/ 200
(rpm)
(When the compressor frequency increases, the outdoor fan speed also changes to the higher speed. When the compressor frequescy decreases, the outdoor fan speed also changes to the lower speed.)
Outdoor temperature falls, and if it becomes E and F zone(Refer to Fig1), rotations of fan speed
*
will fall.
After the defrost control is operated on the heating mode, the fan speed keeps at the higher speed
*
as table 9 without relating to the compressor frequency.
( Table 9 : Outdoor fan speed after the defrost )
AS*A18LEC
Min
1100rpm
05-07
7. LOUVER CONTROL
1. LOUVER CONTROL
When the indoor control interface device receives a control signal light from the remote control, it will actuate, the step motor according to the control signal, and set the louver to each position. In addition, if the air conditioner is stopped, vertical louver will be closed automatically.
Vertical Air Direction Adjustment
(Function Range)
Each time the button is pressed, the air direction range will change as follow:
(Fig 9: Air Direction Range)
(Operation Range)
Cooling / Dry mode Heating mode Fan mode
Use the air direction adjustments within the ranges shown above.
Horizontal Air Direction Adjustment
(Function Range)
Each time the button is pressed, the air direction range will change as follow:
6
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
Cooling / Dry mode Horizontal flow Heating mode Downward flow
When the temperature of the air being blown out is low at the start of heating operation or during defrosting, the airflow direction temporarily becomes to prevent cold air being blown onto the body.
During use of the Cooling and Dry modes, do not set the Air Flow Direction Louver in the Heating
4
range ( ) for long period of time, since water vapor many condense near the outlet louvers and drop of water may drip from the air conditioner. During the Cooling and Dry modes, if the Air Flow Direction Louvers are left in the hating range for more than 20minutes, they will automatically return to position .
During Monitor operation in AUTO CHANGEOVER mode, the airflow direction automatically becomes , the horizontal airflow direction does not cahnge, and it cannot be adjusted.
6
1
6
6
05-08
Loading...
+ 45 hidden pages