SPLIT TYPE ROOM AIR CONDITIONER
INSTALLATION MANUAL
(PART NO. 9312176021-02)
For authorized service personnel only.
WARNING
(1) For the room air conditioner to operate satisfactory, install it as outlined in this installation manual.
(2) Connect the indoor unit and outdoor unit with the air conditioner piping and cords available standards parts. This
installation manual describes the correct connections using the standard accessories and the parts specified in
this installation manual.
(3) Have installation work done by authorized service personnel only.
(4) Never cut the power cord, lengthen or shorten the cord, or change the plug.
(5) Also do not use an extension cord.
(6) Plug in the power cord plug firmly. If the receptacle is loose, repair it before using the room air conditioner.
(7) Do not turn on the power until all installation work is complete.
● Be careful not to scratch the air conditioner when handling it.
● After installation, explain correct operation to the customer, using the operating manual.
● Let the customer keep this installation manual because it is used when the air conditioner is serviced or
moved.
● The maximum length of the piping is 10 m. The maximum height difference of the piping is 5 m,
if the units are further apart than these, correct operation can not be guaranteed.
STANDARD ACCESSORIES
The following installation accessories are supplied.
Use them as required.
Name and Shape Q’ty Name and Shape Q’ty
Wall hook bracket
Drain pipe
(including drain packing)
(Reverse cycle type only)
1
Remote
control
unit
Cloth tape
1
Battery Tapping screw
28
1
1
One set of following parts are necessary in istallation of this product.
Name
Connection pipe assembly
Connection cord (3-conductor)
Connection cord (2-conductor) (Reverse cycle type only)
Wall pipe
Decorative tape
Vinyl tape
Wall cap
Saddle
Drain hose
Tapping screws
Sealant
ELECTRICAL REQUIREMENT
Always make the air conditioner power supply a special branch circuit
and provide a special switch and receptacle. Do not extend the power
cord.
INDOOR UNIT
CUTTING THE HOLE IN THE WALL FOR THE CONNECTING PIPING
(1) Cut a 65 mm diameter hole in the wall at the position shown in (Fig.
5).
(2) When cutting the wall hole at the inside of the installation frame, cut
the hole within the range of the left and right center marks 40 mm
below the installation frame.
When cutting the wall hole at the outside of the installation frame,
cut the hole at least 10 mm below less.
(3) Cut the hole so that the outside end is lower (5 to 10 mm) than the
inside end.
(4) Always align the center of the wall hole. If misaligned, water leakage
will occur.
(5) Cut the wall pipe to match the wall thickness, stick it into the acces-
sory wall cap, fasten the cap with vinyl tape, and stick the pipe through
the hole. (The connection pipe is supplied in the installation set.) (Fig.
5)
(6) For left piping and right piping, cut the hole a little lower so that drain
water will flow freely. (Fig. 5)
INSTALLING THE WALL HOOK BRACKET
(1) Install the wall hook bracket so that it is correctly positioned horizon-
tally and vertically. If the wall hook bracket is tiled, water will drip to
the floor.
(2) Install the wall hook bracket so that it is strong enough to withstand
the weight of an adult.
Before fastening the wall hook bracket to the wall with the screws,
level it by tapping the hook at the center of bracket to the wall with
the handle of a screwdriver.
● Fasten the wall hook bracket to the wall with 6 or more screws through
the holes near the outer edge of the bracket.
● Check that there is no rattle at the wall hook bracket.
WARNING
If the wall pipe is not used, the cord interconnecting
the indoor and outdoor units may touch metal and
cause electric leakage.
CAUTION
Install the wall hook bracket horizontally and perpendicularly.
FORMING THE DRAIN HOSE AND PIPE
[Rear piping, Right piping, Bottom piping]
● Install the indoor unit piping in the direction of the wall hole and bind
the drain hose and pipe together with vinyl tape. (Fig. 7)
● Install the piping so that the drain hose is at the bottom.
● Wrap the pipes of the indoor unit that are visible from the outside
with decorative tape.
[For Left rear piping, Left piping]
Interchange the drain cap and the drain hose.
CAUTION
After removing the drain hose, do not forget to install
the drain cap.
Indoor unit
drain hose
Drain cap
Insert the drain cap and drain hose
until it butts against the drain port.
Fig. 5
Lower
10 mm
or over
Fasten with
vinyl tape
(Wall cap)
Fig. 6
Tapping screw (big)
Tapped
Hook
Fig. 7
Cut off the piping
outlet cutting groove
with a hacksaw, etc.
Decorative tape
Right piping
Notch the thin part
of under cover.
Under cover
65 mm dia. hole
(Wall pipe)
(Inside)
Wall hook
bracket
(Handle of
screwdriver)
Bottom piping
Indoor unit drain hose
Wall (Outside)
Center mark
5 to 10
mm low
Bind with
vinyl tape
Drain cap
10 mm
or over
65 mm dia. hole
(Right side hole only.
65 mm diameter hole
is also possible.)
Center notch
(String)
Pipe (top)
Rear piping
Indoor unit drain hose
(bottom)
For left outlet
piping, cut off the
piping outlet
cutting groove
with a hacksaw.
Remove the drain
cap by pulling at
the projection at
the end of the cap
with pliers, etc.
Lower
Hook
Wall hook
bracket
Counter
weight
● For left piping and left rear piping, align the marks on the wall hook
bracket and shape the connection pipe.
● Bend the connection piping at a bend radius of 70 mm or more and
install no more than 35 mm from the wall.
● After passing the indoor piping and drain hose through the wall hole,
hang the indoor unit on the hooks at the top and bottom of the wall
hook bracket.
[Installing the indoor unit]
● Hang the indoor unit from the hooks at the top of the wall hook bracket.
● Insert the spacer, etc. between the indoor unit and the wall hook
bracket and separate the bottom of the indoor unit from the wall.
Indoor unit
(Spacer)
Wall hook bracket
CONNECTING THE PIPING
CONNECTION
(1) Install the outdoor unit wall cap (supplied with the optional instal-
lation set or procured at the site) to the wall pipe.
(2) Connect the outdoor unit and indoor unit piping.
(3) After matching the center of the flare surface and tightening the
nut hand tight, tighten the nut to the specified tightening torque
with a torque wrench. (Tighten the flare nut of the outdoor unit 3-
way valve after air purging.)
FLARING
(1) Cut the connection pipe to the necessary length with a pipe cutter.
(2) Hold the pipe downward so that cuttings will not enter the pipe
and remove the burrs.
(3) Insert the flare nut onto the pipe and flare the pipe with a flaring
tool.
Check if [L] is flared uniformly and is not
cracked or scratched.
L dimension Thin pipe 1.4 to 1.7 mm
(6.35 mm dia.)
Thick pipe 1.8 to 2.0 mm
(9.52 mm dia.)
INDOOR UNIT WIRING
[Reverse cycle type]
(1) Remove the cord clamp.
(2) Bend the end of the connection cord as shown in the figure.
(3) Connect the end of the connection cord fully into the terminal block.
Fig. 10
Right bottom
of indoor unit
10 mm
4 mm
18 mm
2
, 2G × 1.5 mm
Under cover
Cord clamp
(There is a terminal
block inside.)
Earth screw
Pull
Connection cord
(Conform to Type245 IEC57)
3G × 1.5 mm
Fig. 8
Connection pipe
(6.35 mm dia.)
Bend (R70) with
a pipe bender
Indoor unit
After hooking the indoor unit to the top hook, hook the fittings of the indoor unit
to the two bottom hooks while lowering the unit and pushing it against the wall.
Fig. 9
Torque wrench
Indoor unit pipe
Connection pipe
(9.52 mm dia.)
(Fitting)
Tighten with two wrenches.
Wrench (fixed)
Flare nut
Connection pipe
Table 1 Flare nut tightening torque
Flare nut
6.35 mm dia.
9.52 mm dia.
Tightening torque
15.7 to 17.6 N•m
(160 to 180 kgf•cm)
29.4 to 47.1 N•m
(300 to 420 kgf•cm)
Align the marks.
Top hooks
Bottom hooks
To prevent gas leakage,
coat the flare surface with
refrigerator oil.
Tightening torque standard
(using a 20 cm wrench)
Wrist strength
Arm strength
Wall hook
bracket
CAUTION
(1) Fasten a flare nut with a torque wrench as instructed in this manual.
If fastened too tight, the flare nut may be broken after a long period
of time and cause a leakage of refrigerant.
(2) During installation, make sure that the refrigerant pipe is attached
firmly before you run the compressor. Do not operate the compressor under the condition of refrigerant piping not attached properly
with 2-way or 3-way valve open. This may cause abnormal pressure
in the refrigeration cycle that leads to breakage and even injury.
(4) Match the terminal block numbers and connection cord with those of
the outdoor unit.
(5) Fasten the connection cord with a cord clamp.
Be sure that the cord is
not applied inside the
hatched lines.
20 mm
20 mm
35 mm
110 mm
2
BAD
Fasten the outside
covering of the
connection cord
with cord clamp.
Connection
cord
Screw
Insert the tab into the square hole
of the indoor unit and fasten with
a screw.
Indoor unit
terminal
block
Cord clamp
(Tab)
[Cooling type]
(1) Remove the cord clamp.
(2) Bend the end of the connection cord as shown in the figure.
Fig. 11
Right bottom of
indoor unit
m
Be sure that the cord is
not applied inside the
10 m
hatched lines.
m
20 m
4 mm
110 mm
Under cover
Cord clamp
(There is a terminal
block inside.)
Pull
Earth screw
Connection cord
(Conform to Type245 IEC57)
3G × 1.5 mm
2
CAUTION
(1) Match the terminal block numbers and connection
cord colors with those of the outdoor unit.
Erroneous wiring may cause burning of the electric parts.
(2) Connect the connection cords firmly to the terminal
block. Imperfect installation may cause a fire.
FINISHING
(1) Insulate between pipes.
● For rear, right, and bottom piping, overlap the connection pipe
heat insulation and indoor unit pipe heat insulation and bind them
with vinyl tape so that there is no gap.
● For left and left rear piping, butt the connection pipe heat insula-
tion and indoor unit pipe heat insulation together and bind them
with and vinyl tape so that there is no gap.
● For left and left rear piping, wrap the area which accommodates
the rear piping housing section with cloth tape.
● For left and left rear piping, bind the connection cord to the top of
the pipe with vinyl tape.
● For left and left rear piping, bundle the piping and drain hose to-
gether by wrapping them with cloth tape over the range within
which they fit into the rear piping housing section.
(2) Temporarily fasten the connection cord along the connection pipe
with vinyl tape. (Wrap to about 1/3 the width of the tape from the
bottom of the pipe so that water does not enter.)
(3) Fasten the connection pipe to the outside wall with a saddle, etc.
(4) Fill the gap between the outside wall pipe hole and the pipe with
sealer so that rain water and wind cannot blow in.
(5) Fasten the drain hose to the outside wall, etc.
Fig. 13
(Outside wall cap)
(Saddle)
Wall
Pipe
(Sealer putty)
(Outdoors)
GOOD
(3) Connect the end of the connection cord fully into the terminal block.
(4) Fasten the connection cord with a cord clamp.
Indoor unit
terminal block
Cord clamp
(Tab)
20 mm
20 mm
35 mm
Fasten the outside
covering of the
connection cord
with cord clamp.
BAD
Connection cord
Screw
Insert the tab into the square hole
of the indoor unit and fasten with
a screw.
(3) Always fasten the outside covering of the connec-
tion cord with the cord clamp. (If the insulator is
chafed, electric leakage may occur.)
(4) Securely earth the power cord plug.
(5) Do not use the earth screw for an external connec-
tor. Only use for interconnection between two units.
Fig. 12
Connection pipe
(heat insulation)
Bind the pipes together
to that there is no gap.
Pipe
Drain hose
[Reverse cycle type] [Cooling type]
Connection cord
Pipe
Drain hose
For connection from the left rear
[Reverse cycle type] [Cooling type]
Connection cord
Drain hose
(View from indoors)
Check the following:
Drain hose
Saddle
Lifted up
Overlap the insulation
Left piping
Wall pipe
Connection
pipe
BAD
Indoor unit pipe
(heat insulation)
Vinyl tape
Wrap with cloth tape
Cloth tape
Connection cord
Pipe
Drain hose
Connection cord
Connection pipe
Drain hose
BAD
Wave End in water
BAD
SELECTING THE MOUNTING
POSITION
Decide the mounting position with the customer as follows:
1. INDOOR UNIT
(1) Install the indoor unit level on a strong wall which is not subject to
vibration.
(2) The inlet and outlet ports should not be obstructed : the air should
be able to blow all over the room.
(3) Install the unit near an electric outlet or special branch circuit.
(4) Do not install the unit where it will be exposed to direct sunlight.
(5) Install the unit where connection to the outdoor unit is easy.
(6) Install the unit where the drain pipe can be easily installed.
(7) Take servicing, etc. into consideration and leave the spaces shown
in (Fig. 2). Also install the unit where the filter can be removed.
2. OUTDOOR UNIT
(1) If possible, do not install the unit where it will be exposed to direct
sunlight. (If necessary, install a blind that does not interfere with
the air flow.)
(2) Do not install the unit where a strong wind blows or where it is very
dusty.
(3) Do not install the unit where people pass.
(4) Take you neighbors into consideration so that they are not disturbed
by air blowing into their windows or by noise.
(5) Provide the space shown in Fig. 2 so that the air flow is not blocked.
Also for efficient operation, leave open three of the four directions
front, rear, and both sides.
[Reverse cycle type only]
(6) Since the drain water flows from the outdoor unit during heating
operation, when it is installed at a high place, install the drain pipe
as shown in (Fig. 4) and connect it to a 16 mm (inside diameter)
hose available anywhere. (Fig. 4)
WARNING
Install at a place that can withstand the weight of the
indoor and outdoor units and install positively so that
the units will not topple or fall.
CAUTION
(1) Do not install where there is the danger of com-
bustible gas leakage.
(2) Do not install near heat sources.
(3) If children under 10 years old may approach the
unit, take preventive measures so that they can-
not reach the unit.
(4) Install the indoor unit on the wall where the height
from the floors more than 230 cm.
[Indoor unit piping direction]
The piping can be connected in the five directions indicated by 1,
2, 3, 4, and 5 in (Fig. 1). When the piping is connected in
direction 2 or 5, cut along the piping groove in the side of the
front cover with a hacksaw.
When connecting the piping in direction 3, cut a notch in the thin
wall at the front bottom of the front cover.
Fig. 1
(Rear)
4 Left rear
2 Right
outlet
1 Rear outlet
3 Bottom outlet
outlet
5 Left
outlet
INSTALLATION DIAGRAM OF
INDOOR AND OUTDOOR UNITS
Fig. 2
[INDOOR UNIT]
Wall hook
5 cm or over
150 cm or over
230 cm or over
Remote
control unit
Connection Cord
Conform to Type245 IEC57
[OUTDOOR UNIT]
10 cm or over
60 cm or over
Mounting Support
(Prepared On-site)
Fig. 3
6 cm or over
60 cm or over
5 cm
or over
50 cm
Fig. 4
[Reverse cycle type only]
Drain hose
(commercial hose,
inside diameter 16 mm)
Bottom of outdoor unit
Drain pipe
NOTE:
Do not install the drain pipe and drain hose in areas where the
outside temperature drops to 0°C or below.
Install where drain can be taken directly from the drain hole at
the bottom of the outdoor unit.
● If the drain pipe and drain hose are installed, water in the
pipe and hose may freeze and obstruct drainage and cause
outdoor unit trouble.
bracket
5 cm or over
Wall cap
5 cm or over
25 cm or
over
26.5 cm
OUTDOOR UNIT
OUTDOOR UNIT INSTALLATION
● Set the unit on a strong stand, such as one made of concrete blocks
to minimize shock and vibration.
● Do not set the unit directly on the ground because it will cause trou-
ble.
Connector cover removal
● Remove the two mounting screws.
● Put your hand on the back side ( mark) and take out the connector
cover forwards.
Installing the connector cover
(1) After inserting the three front hooks, then insert the rear hook.
(2) Tighten the two mounting screws.
AIR PURGE
Close the high pressure side valve of the gauge manifold fully and do
not operate it during the following work.
1. Check if the piping connections are secure.
2. Check that the stems of 2-way valve and 3-way valve are closed
fully.
3. Connect the gauge manifold service hose to the charging port
of the 3-way valve (side with the projection for pushing in the
valve core).
4. Open the low pressure side valve of the gauge manifold fully.
5. Operate the vacuum pump and start pump down.
6. Slowly loosen the flare nut of the 3-way valve and check if air
enters, then retighten the flare nut.
(When the flare nut is loosened the operating sound of the
vacuum pump changes and the reading of the compound
pressure gauge goes from minus to zero.)
7. Pump down the system for at least 15 minutes, then check if the
compound pressure gauge reads -100 kPa (-76 cmHg, -1 bar).
8. At the end of pump down, close the low pressure side gauge of
the gauge manifold fully and stop the vacuum pump.
9. Slowly loosen the valve stem of the 3-way valve. When the
compound pressure gauge reading reaches 1-2 kg/cm
retighten the valve stem and disconnect the service hose
from the 3-way valve charging port.
(If the stem of the 3-way valve is opened fully before the
service hose is disconnected, it may be difficult to disconnect
the service hose.)
2
,
WARNING
(1) Install the unit where it will not be tilted by more
than 5°.
(2) When installing the outdoor unit where it may ex-
posed to strong wind, fasten it securely.
Fig. 14
ø5 mm
tapping screw (special)
(Rear hook)
Connector cover
ø4 mm
skirted screw
Always use the screws as shown above.
Do not select the top and bottom screws incorrectly.
10. Fully open the valve stems of the 2-way valve and 3-way valve
using a hexagon wrench. (After the valve stem begins to turn,
turn the it with a torque of less than 2.9 N•m (30 kgf•cm) until it
stops turning.)
11. Firmly tighten the 2-way valve and 3-way valve blank cap and
the charging port cap.
Fig. 15
2-way valve
Valve
stem
Charging
port cap
Outdoor unit
Table 2
Blank cap 19.6 to 24.5 N•m (200 to 250 kgf•cm)
Charging port cap 6.9 to 8.8 N•m (70 to 90 kgf•cm)
Front hook
Flare nut
Compound pressure gauge
-100 kPa
(-76 cmHg
Blank
-1 bar)
cap
3-way valve
Charging port
Service hose
(For a description of how to use the
gauge manifold, refer to the gauge
manifold operation manual.)
Low pressure
side valve
Tightening torque
Gauge manifold
Pressure gauge
High
pressure
side valve
(closed)
Service
hose
Vacuum pump
CAUTION
During installation, make sure that the refrigerant
pipe is attached firmly before you run the compressor. Do not operate the compressor under the condition of refrigerant piping not attached properly with
2-way or 3-way valve open. This may cause abnormal pressure in the refrigeration cycle that leads to
breakage and even injury.
ADDITIONAL CHARGE
Refrigerant suitable for a piping length of 7.5 m is charged in the outdoor
unit at the factory.
When the piping is longer than 7.5 m, additional charging is necessary.
For the additional amount, see the table below.
Table 3
Pipe length
Additional
refrigerant
Between 7.5 m and 10 m, when using a connection pipe other than that
in the table, charge additional refrigerant with 16g/1 m as the criteria.
7.5 m
None
10 m
40 g
OUTDOOR UNIT WIRING
(1) Remove the outdoor unit connector cover.
(2) Remove the control box cover-B.
(3) Bend the end of the cord as shown in the figure.
(4) Connect the end of the connection cord fully into the terminal block.
[Reverse cycle type]
Fig. 16
Terminal block
(Sheath)
Earth
screw
Indoor unit
terminal block
Connection cord wiring
Run the connection cord to the rear of the outdoor unit within the range of
the arrows shown in the figure.
(The connector cover becomes difficult to install.)
(1) Match the terminal block numbers and connection
cord colors with those of the indoor unit.
Erroneous wiring may cause burning of the electric
parts.
(2) Connect the connection cords firmly to the terminal
block. Imperfect installation may cause a fire.
Earth
screw
Cord clamp
After installed the
control box cover-B
Connection cord
Connection cord
12 mm
23 mm
(Insulator)
Outdoor unit
terminal block
Control box
cover-B
Earth
screw
Sheath
Cord
clamp
Earth
screw
CAUTION
CAUTION
(1) When moving and installing the air conditioner, do
not mix gas other than the specified refrigerant
(R22) inside the refrigerant cycle.
(2) When adding refrigerant, add the refrigerant from
the charging port at the completion of work.
(3) The maximum length of the piping is 10 m. If the
units are further apart than this, correct operation
can not be guaranteed.
(4) After connecting the piping, check the joints for
gas leakage with gas leak detector.
(5) Fasten the sheath with a cord clamp.
(6) Install the control box cover-B.
(7) Install the connector cover.
[Cooling type]
Fig. 17
Fig. 18
(3) Always fasten the outside covering of the connec-
(4) Securely earth the power cord plug.
(5) Do not use the earth screw for an external connector.
Terminal block
(Sheath)
Earth
screw
Indoor unit
terminal block
Outdoor unit
Earth screw
Cord clamp
After installed the
control box cover-B
Connection cord
Connection cord
Sheath
Cord clamp
12 mm
23 mm
(Insulator)
Connection cord
Control box cover-B
Earth screw
Outdoor unit
terminal block
Earth
screw
tion cord with the cord clamp. (If the insulator is
chafed, electric leakage may occur.)
Only use for interconnection between two units.
FRONT PANEL REMOVAL AND INSTALLATION
THE INTAKE GRILLE REMOVAL
(1) Open the intake grille.
(2) Pull down the knob.
(3) Open the intake grille , and lift the intake grille upward ,until the axle at the top of the intake
grille is removed.
THE INTAKE GRILLE INSTALLATION
(1) The fixing axle of the intake grille is installed on the front panel.
(2) Push the knob up to the position.
(3) Lay down the intake grille.
Intake grille
THE FRONT PANEL REMOVAL
(1) Turn the wind guide and remove two screws at two sides of air outlet.
(2) Take out the air outlet part of the front panel, then lift the whole front panel up to remove
it.
THE FRONT PANEL INSTALLATION
(1) Firstly fit the lower part of the front panel to the air outlet part and insert its lower edge into
the slot of the lower cover.
(2) Insert three hooks on the upper side of the front panel into the slot of bracket.
(3) Turn the wind guide, tighten the screws, and then turn the wind guide back to its origial
position.
Intake grille
Fixing axle
Fixing screw (2 position)
Lift up
Top hook
Mounting shaft
Knob
Font panel
Top hole
Front cover
THE LOWER COVER REMOVAL AND INSTALATION
The lower cover removal should be done after the panel has been removed beforehand, or the parts may be
damaged.
The lower cover should be installed before the fixing of the panel, or it may result in poor installation.
THE LOWER COVER REMOVAL
(1) While pressing the joint part between the right part of the lower cover and the bracket, pull it out of the slot.
(2) Hold two sides of the lower cover and slide it to the left. Make sure its lower part getting out of the slot.
(3) Turn the right part of the lower cover lower-left to separate the left slot of the lower cover from the bracket.
THE LOWER COVER INSTALLATION
(1) Hold two sides of the lower cover and align it to the side of the bracket.Firstly match the left slot on the lower
cover to the bracket.
(2) Make five slots on the lower cover fit into the fixing plate of the body, then slide it to the right until the left
side of the lower cover align to the bracket.
(3) Push the right part of the lower cover inward to make the slot and bracket engaged with each other completely.
CAUTION
Install the front panel and intake grille
securely. If installation is imperfect, the
front panel or intake grille may fall off
and cause injury.
Be sure that the top hole of the front panel
is hooked securely to the hook of the base.
TEST RUNNING
● Perform test operation and check items 1 and 2 below.
● For the test operation method, refer to the operating manual.
● The outdoor unit, may not operate, depending on the room temperature. In this case, press the
test run button on the remote control unit while the air conditioner is running, (Point the transmitter section of the remote control unit toward the air conditioner and press the test run
button with the tip of a ball-point pen, etc.)
● To end test operation, press the remote control unit START/STOP button.
(When the air conditioner is run by pressing the test run button, the OPERATION indicator
lamp and TIMER indicator lamp will simultaneously flash slowly.)
CUSTOMER GUIDANCE
Explain the following to the customer in
accordance with the operating manual:
(1) Starting and stopping method,
operation switching, temperature
adjustment, timer, air flow switching,
and other remote control unit operations.
(2) Air filter removal and cleaning, and
how to use the air louvers.
(3) Give the operating and installation
manuals to the customer.
1. INDOOR UNIT
(1) Is operation of each button on the remote control unit normal?
(2) Does each lamp light normally?
(3) Do the air flow-direction louver operate normally?
(4) Is the drain normal?
2. OUTDOOR UNIT
(1) Is there any abnormal noise and vibration during operation?
(2) Will noise, wind, or drain water from the unit disturb the
neighbors?
(3) Is there any gas leakage?
POWER
WARNING
(1) The rated voltage of this product is 230 V AC 50 Hz.
(2) Before turning on the power, check if the voltage is within
the 220 V -10 % to 240 V +10 % range.
(3) Always use a special branch circuit and install a special
receptacle to supply power to the room air conditioner.
(4) Use a circuit breaker and receptacle matched to the
capacity of the air conditioner.
(5) Do not extend the power cord.
(6) Perform wiring work in accordance with standards so
that the air conditioner can be operated safely and
positively.
(7) Install a leakage circuit breaker in accordance with the
related laws and regulations and electric company
standards.
(1) The power source capacity must be the sum of the air conditioner
current and the current of other electrical appliances. When the
current contracted capacity is insufficient, change the contracted
capacity.
(2) When the voltage is low and the air conditioner is difficult to
start, contact the power company the voltage raised.
NOTE: These equipment shall be connected to a suitable mains network
with a main impedance less than the following: 0. 424Ω
The product is intended for use only in premises having a service
current capacity 100A per phase,supplied from a distribution
network having a nominal voltage of 230 V, and instruct the user
to determine in consulation with the supply authority, if necessary,
that the service current capacity at the interface point is sufficient
for the equipment.
CAUTION
Grill
Fixing axle
Bracket
Transmitter
section
Test run
button
Grill
Fixing axle
Knob
Knob
Turning direction
Before turning After turning
Turning wind guide
Fig. 19
Fig. 20
Fig. 21