Generac Power Systems 6055 Owner's Manual

Page 1
Page 2
Use this page to record important information about your generator set.
Record the information found on your unit data label on this page for quick and easy reference. The label is affixed to the inside partition left of the control pad. For direc­tions on how to open the lid and remove the front panel, see Section 3 Operation. The Unit Identification label provides the following information:
 Model Number  Serial Number  Control Board Part Number  Voltage Rating of the unit  Maximum Current Rating of the unit (AMPS)
When contacting an independent always supply the complete model number and serial number of the unit.
Operation and Maintenance: Proper maintenance and care of the generator ensures a minimum number of problems and keeps operating expenses at a mini­mum. It is the operator’s responsibility to perform all safety checks, to make sure that all maintenance for safe operation is performed promptly, and to have the equipment checked periodically by an independent Authorized Service Dealer. Normal mainte­nance, service and replacement of parts are the responsibility of the owner/operator and, as such, are not considered defects in materials or workmanship within the terms of the warranty. Individual operating habits and usage may contribute to the need for additional maintenance or service.
When the generator requires servicing or repairs, contact an Service Dealer for assistance. Authorized service technicians are factory-trained and are capable of handling all service needs.
Authorized Service Dealer about parts and service,
independent Authorized
To find your Local Independent AUTHORIZED SERVICE DEALER
INDEPENDENT AUTHORIZED
SERVICE
DEALER LOCATION
To locate the nearest INDEPENDENT
AUTHORIZED SERVICE DEALER, please
call this number:
1-800-333-1322
or, visit the dealer locator at:
www.generac.com/Service/Dealer Locator/
WARNING
California Proposition 65. Engine exhaust and some of its constituents are known to the state of California to cause cancer, birth defects, and other reproductive harm.
(000004)
California Proposition 65. This product contains or emits chemicals known to the state of California to cause cancer, birth defects, and other reproductive harm.
ii Synergy Automatic Standby Generator Owner’s Manual
WARNING
(000005)
Page 3
Table of Contents
Table of Contents
Section 1 Safety
1.1 Introduction .......................................................................................................................... 1
1.2 General Safety ...................................................................................................................... 2
1.3 General Safety Hazards ....................................................................................................... 2
1.4 Exhaust Hazards .................................................................................................................. 3
1.5 Electrical Hazards ................................................................................................................ 3
1.6 Fire Hazards .......................................................................................................................... 3
1.7 Explosion Hazards ............................................................................................................... 4
Section 2 General Information
2.1 Synergy Operating Principle ............................................................................................... 5
2.1.1 Benefits .........................................................................................................................................5
2.1.2 Start Up ......................................................................................................................................... 5
2.1.3 Normal Running ............................................................................................................................5
2.1.4 Small Load Changes .................................................................................................................... 5
2.1.5 Large Load (Not Overload) ........................................................................................................... 5
2.1.6 Overload .......................................................................................................................................6
2.1.7 Low Speed Exercise .....................................................................................................................6
2.1.8 Normal Exercise ...........................................................................................................................6
2.1.9 Automatic Voltage Regulator (AVR) Cooling Fans .......................................................................6
2.2 The Generator ....................................................................................................................... 7
2.3 Protection Systems .............................................................................................................. 8
2.3.1 Alarms ........................................................................................................................................... 8
2.3.2 Warnings ....................................................................................................................................... 8
2.4 Emission Information .......................................................................................................... 8
2.5 Specifications ....................................................................................................................... 9
2.5.1 Generator ...................................................................................................................................... 9
2.5.2 Engine ........................................................................................................................................... 9
2.5.3 Fuel Requirements .....................................................................................................................10
2.5.4 Battery Requirements .................................................................................................................10
2.5.5 Battery Charger .......................................................................................................................... 10
2.5.6 Engine Oil Requirements ............................................................................................................10
2.6 Accessories ........................................................................................................................ 10
Section 3 Operation
3.1 Con trol Pad ......................................................................................................................... 13
3.2 Auto/Manual/Off ................................................................................................................. 14
3.3 Menu Navigation ................................................................................................................ 15
Synergy Automatic Standby Generator Owner’s Manual iii
Page 4
Table of Contents
3.4 Change Time and Date ....................................................................................................... 15
3.5 Programmable Timers ........................................................................................................ 15
3.5.1 Dealer Programmable ................................................................................................................15
3.5.1.1 High Run Speed Timer ....................................................................................................... 15
3.5.1.2 Start-Up Delay Timer .......................................................................................................... 15
3.5.2 User Programmable ................................................................................................................... 16
3.5.2.1 Exercise Time ..................................................................................................................... 16
3.6 USB Port for Firmware Updates ........................................................................................16
3.7 Transfer Switch Automatic Operation ..............................................................................18
3.7.1 Automatic Sequence of Operation ..............................................................................................18
3.7.1.1 Utility Failure ....................................................................................................................... 18
3.7.1.2 Cranking.............................................................................................................................. 18
3.7.1.3 Load Transfer...................................................................................................................... 18
3.7.2 Load Shed Functionality .............................................................................................................19
3.8 Transfer Switch Manual Operation ...................................................................................19
3.8.1 Transfer to Generator Power ......................................................................................................19
3.8.2 Transfer Back to Utility Power ....................................................................................................19
3.9 Removal From Service During Utility Outages ................................................................ 20
3.10 Side Door Compartment ..................................................................................................21
3.10.1 LED Indicators .......................................................................................................................... 21
3.10.2 120V GFCI Outlet/15 Amp Breaker .......................................................................................... 21
3.11 Battery Charger ................................................................................................................ 22
3.12 Setting the Exercise Timer ..............................................................................................22
Section 4 Maintenance
4.1 Maintenance ........................................................................................................................ 23
4.2 Maintenance Kits ................................................................................................................23
4.3 Service Maintenance Schedule .........................................................................................23
4.4 Remove From Service ........................................................................................................ 24
4.5 Daily Maintenance (If Running Continuously) ................................................................. 24
4.5.1 Check Enclosure Louvers ...........................................................................................................24
4.5.2 Check Lines and Connections ....................................................................................................25
4.5.3 Check Engine Oil Level .............................................................................................................. 25
4.5.3.1 Engine Oil Recommendations ............................................................................................ 25
iv Synergy Automatic Standby Generator Owner’s Manual
Page 5
Table of Contents
4.6 Schedule A Maintenance ................................................................................................... 26
4.6.1 Check Battery Condition/Fluid Level ...........................................................................................26
4.6.1.1 Check Condition and Clean ................................................................................................ 26
4.6.1.2 Check Fluid Level ............................................................................................................... 26
4.6.1.3 Check State of Charge........................................................................................................ 26
4.6.1.4 Battery Replacement .......................................................................................................... 26
4.6.2 Replace AVR Filter .....................................................................................................................27
4.6.3 Replace Engine Oil and Oil Filter ................................................................................................ 27
4.7 Schedule B Maintenance ................................................................................................... 29
4.7.1 Replace Engine Air Filter ............................................................................................................29
4.7.2 Clean/Gap/Replace Spark Plugs ................................................................................................29
4.7.3 Check/Adjust Valve Clearance ...................................................................................................30
4.7.3.1 Check Valve Clearance ...................................................................................................... 30
4.7.3.2 Adjust Valve Clearance....................................................................................................... 31
4.8 Return to Service ............................................................................................................... 32
4.9 Attention After Submersion .............................................................................................. 32
4.10 Corrosion Protection ....................................................................................................... 32
4.11 Out of Service Procedure ................................................................................................ 32
4.11.1 Remove For Storage ................................................................................................................32
4.11.2 Return To Service After Storage ............................................................................................... 33
Section 5 Troubleshooting
5.1 Engine Troubleshooting .................................................................................................... 35
5.2 Generator Troubleshooting ............................................................................................... 36
5.3 Synergy Troubleshooting .................................................................................................. 38
5.4 Load Shed Troubleshooting ............................................................................................. 40
Synergy Automatic Standby Generator Owner’s Manual v
Page 6
Table of Contents
This page intentionally left blank.
vi Synergy Automatic Standby Generator Owner’s Manual
Page 7
Sec t i o n 1
Safety
1.1 — Introduction
Thank you for purchasing this compact, high performance, variable speed, air-cooled, engine-driven stationary auto­matic standby generator set. Every effort was made to make sure that the information and instructions in this manual were both accurate and current at the time the manual was written. However, the manufacturer reserves the right to change, alter or otherwise improve this product or manual at any time without prior notice.
This generator is designed to automatically supply electrical power to operate critical loads during a utility power failure. This unit is factory installed in an all-weather metal enclosure and is intended exclus i v el y for outdoor instal lation. This generator will operate using either vapor withdrawn liquid propane (LP) or natural gas (NG).
NOTE: When properly sized, this generator is suitable for supplying typical residential loads such as Induction Motors (sump pumps, refrigerators, air conditioners, furnaces, etc.), Electronic Components (computer, monitor, TV, etc.), Lighting Loads and Microwaves.
READ THIS MANUAL THOROUGHLY: manufacturer strongly recommends that the operator read and thoroughly understand the instructions and contents of this owner’s manual before attempting to use the equipment. If any portion of this publication is not understood, contact the nearest Authorized Service Dealer for starting, operating and servicing procedures.
SAVE THESE INSTRUCTIONS: The manufacturer suggests that this manual and the rules for safe operation be cop­ied and posted near the unit’s installation site. Safety should be stressed to all operators and potential operators of this equipment.
SAFETY: Throughout this manual, and on tags and decals affixed to the unit, DANGER, WARNING, CAUTION and NOTE blocks are used to alert personnel to special instructions about a particular operation, function or service that may be hazardous if performed incorrectly or carelessly. Observe them carefully. Their definitions are as follows:
The operator is responsible for proper and safe use of this equipment. The
DANGER
Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
(000001)
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTE: Notes contain additional information important to an operation or procedure.
Synergy Automatic Standby Generator Owner’s Manual 1
(000002)
CAUTION
(000003)
Page 8
Safety
Four commonly used safety symbols accompany the DANGER, WARNING and CAUTION blocks. The type of informa­tion each indicates is as follows:
This symbol points out important Safety Information that, if not followed, could endanger personal safety and/or
*
property of others.
$
! +
These “Safety Alerts” cannot eliminate the hazards that they signal. Strict compliance with these special instructions, plus common sense are major accident prevention measures.
This symbol points out a potential Explosion Hazard.
This symbol points out a potential Fire Hazard.
This symbol points out a potential Electrical Shock Hazard.
1.2 — General Safety
Study these safety rules carefully before operating or servicing this equipment. Become familiar with this Owner’s Man­ual and with the unit. The generator can operate safely, efficiently and reliably only if it is properly installed, operated and maintained. Many accidents are caused by failing to follow simple and fundamental rules or precautions.
The manufacturer cannot anticipate every possible circumstance that might involve a hazard. The warnings in this manual, and on tags and decals affixed to the unit are, therefore, not all-inclusive. If using a procedure, work method or operating technique the manufacturer does not specifically recommend, ensure that it is safe for personnel. Also make sure the procedure, work method or operating technique utilized does not render the generator unsafe.
Despite the safe design of this generator, operating this equipment imprudently, neglecting its
*
maintenance or being careless can cause possible injury or death. Permi t only responsible and capable persons to install, operate and maintain this equipment.
Potentially lethal voltages are generated by these machines. Ensure steps are taken to make the machine safe before attempting to work on the generator.
+
Parts of the generator are rotating and/or hot during operation. Exercise care near a running
*
generator.
The installation of this generator must always comply wi th appl icable codes, standards, laws
*
and regulations.
A running generator gives off DEADLY carbon monoxide, an odorless, colorl ess, poisonous gas. Breathing carbon monoxi de can cause dizziness, throbbing temples, nausea, muscular
*
twitching, headache, vomiting, weakness, sleepiness, inability to think clearly, fainting, uncon­sciousness or even death.
The control panel for this unit is intended to be operated by qualified service personnel only.
*
1.3 — General Safety Hazards
For safety reasons, this equipment should only be installed, serviced and repaired by a Service Dealer or other
competent, qualified electrician or installation technician who is familiar with applicable codes, standards, regula­tions and product Installation Manual guidelines. The operator also must comply with all such codes, standards, regulations and product Installation Manual guidelines.
2 Synergy Automatic Standby Generator Owner’s Manual
Page 9
The engine exhaust fumes contain carbon monoxide, which can be DEADLY. This dangerous gas, if breathed in
sufficient concentrations, can cause unconsciousness or even death. DO NOT alter or add to the exhaust system or do anything that might render the system unsafe or in noncompliance with applicable codes and standards.
Install a carbon monoxide alarm indoors, according to manufacturer’s instructions/recommendations.
Adequate, unobstructed flow of cooling and ventilating air is critical for correct generator operation. Do not alter the installation or permit even partial blockage of ventilation provisions, as this can seriously affect safe operation of the generator. The generator MUST b e ins talled and operated outd oo rs only.
Keep hands, feet, clothing, etc. away from drive belts, fans, and other moving or hot parts. Never remove any drive belt or fan guard while the unit is operating.
When working on this equipment, remain alert at all times. Never work on the equipment when physically or men­tally fatigued.
Inspect the generator regularly, and contact the nearest Dealer for parts needing repair or replacement.
Before performing any maintenance on the generator, remove the control panel fuse and disconnect the Nega-
tive (—) battery cable to prevent accidental startup. When disconnecting battery cables always remove the NEG­ATIVE (NEG or “—”) cable first, then remove the POSITVE (POS, or “+”) cable. When reconnecting the cables, connect the POSITIVE cable first, and the NEGATIVE cable last.
Never use the generator or any of its parts as a step. Stepping on the unit can stress and break parts, and may result in dangerous operating conditions from leaking exhaust gases, fuel leakage, oil leakage, etc.
1.4 — Exhaust Hazards
Safety
Generator engine exhaust contains DEADLY carbon monoxide, an odorless, colorless, poisonous gas. Breathing carbon monoxide can cause dizziness, throbbing temples, nausea, muscular twitching, headache, vomiting, weakness, sleepiness, inability to think clearly, fainting, unconsciousness or even death. If any carbon monoxide poisoning symptom is experienced, move into fresh air and immediately seek medical attention.
This generator is designed for OUTDOOR installation ONLY. Never operate the generator inside any garage or other enclosed space.
1.5 — Electrical Hazards
All generators covered by this manual produce dangerous electrical voltages that can cause fatal electrical
shock. Utility power delivers extremely high and dangerous voltages to the transfer switch, as does the standby generator when it is in operation. Avoid contact with bare wires, terminals, connections, etc. while the unit is run­ning. Ensure all appropriate covers, guards and barriers are in place, secured and/or locked before operating the generator. If work must be done around an operating unit, stand on an insulated, dry surface to reduce potential shock hazard.
Do not handle any kind of electrical device while standing in water, while barefoot, or while hands or feet are wet. DANGEROUS ELECTRICAL SHOCK MAY RESULT.
This is an Automatic Standby Generator, the generator may crank and start at any time when utility is lost. When this occurs, load circuits are transferred to the STANDBY (generator) power source. To prevent injury, before working on this generator (for inspection, service or maintenance), always put the generator into the OFF mode and remove the 7.5 Amp fuse from the generator control panel.
In case of accident caused by electric shock, immediately shut down the source of electrical power. If this is not
possible, attempt to free the victim from the live conductor. AVOID DIRECT CONTACT WITH THE VICTIM. Use a nonconducting implement, such as a dry rope or board, to free the victim from the live conductor. If the victim is unconscious, apply first aid and get immediate medical help.
Never wear jewelry when working on this equipment. Jewelry can conduct electricity resulting in electric shock, or may get caught in moving components resulting in injury.
1.6 — Fire Hazards
For fire safety, the generator must be installed and maintained properly. Installation MUST always comply with
applicable codes, standards, laws, regulations and product Installation Manual guidelines. Adhere strictly to local, state, and national electrical and building codes. Comply with regulations the Occupational Safety and
Synergy Automatic Standby Generator Owner’s Manual 3
Page 10
Safety
Health Administration (OSHA) has established. Also, ensure that the generator is installed in accordance with the manufacturer’s instructions and recommendations. Following proper installation, do nothing that might alter a safe installation and render the unit in noncompliance with the aforementioned codes, standards, laws and regu­lations.
Keep a fire extinguisher near the generator at all times. Extinguishers rated “ABC” by the National Fire Protection Association are appropriate for use on the standby generator. Keep the extinguisher properly charged and be familiar with its use. Consult the local fire department with any questions pertaining to fire extinguishers.
1.7 — Explosion Hazards
Do not smoke around the generator. Wipe up any fuel or oil spills immediately. Ensure that no combustible mate­rials are left in the generator compartment, or on or near the generator as FIRE or EXPLOSION may result. Keep the area surrounding the generator clean and free from debris.
Gaseous fluids such as natural gas and liquid propane (LP) gas are extremely EXPLOSIVE. Install the fuel sup-
ply system according to applicable fuel-gas codes. Before placing the home standby electric system into service, fuel system lines must be properly purged and leak tested according to applicable code. After installation, inspect the fuel system periodically for leaks. No leakage can be permitted.
If this generator is used to power electric al load circuits normally powered by a util ity power
+
source, it is required by code to install a transf er switch. The trans fer switch must effectively isolate the electrical system from the uti lity distribution system when the generator is operating (NEC 702). Failure to isolate an electrical system by such means will result in damage to the generator and also may result in injury or death to utility power workers due to backfeed of electrical energy.
4 Synergy Automatic Standby Generator Owner’s Manual
Page 11
Sec t i o n 2
General Information
2.1 — Synergy Operating Pri nciple
2.1.1— Benefits
The Synergy 20 kW generator brings exciting new technology to the Home Standby generator product. The generator is significantly more fuel efficient than constant speed generators at normal loads, provides premium power quality, and is significantly quieter while operating at exercise and normal loads.
Exceptionally quiet exercise at 57 dB
Quieter operation - 3 dB with improved tonal qualities at exercise and under normal loads
Cleanest Standby power available with 1.5 THD
Significant fuel savings: more fuel efficient under normal loads
Lower operating speed at 2700 rpm at low loads
Tuned Helmhortz resonator and muffler to further lower sound levels
Variable Speed / Constant Frequency operation
2.1.2— Start Up
When the generator starts up, the engine ramps up to 3600 RPM to produce maximum power. This ensures that there is sufficient power to carry the load when the transfer switch operates. The engine RPM then gradually ramps down to a speed appropriate for the attached load.
For example, if there is no load, the engine ramps down to approximately 2700 RPM. The time it takes to ramp down to 2700 RPM is approximately 4-5 minutes. Since the ramp rate is linear, less time would be required for it to ramp down to only 3400 RPM.
During startup, as the engine ramps up to 3600 RPM, the Automatic Voltage Regulator (AVR) electronics performs a self test (before transfer) involving an overall system check of the unit. If a fault is detected, the unit shuts down and displays an alarm.
2.1.3— Normal Running
The engine operates between 2700 RPM - 3600 RPM depending on the attached load. When the load increases or decreases, the speed increases or decreases accordingly.
2.1.4— Small Load Changes
The system is designed to maintain the current engine speed for small load changes. Larger load changes result in a change in engine speed to appropriately handle the load.
2.1.5— Large Load (Not Overload)
The engine always runs at a speed appropriate for the attached load. When a large load is applied, the fast Loadshed signal is activated. All loads attached to the Loadshed controller in the transfer switch are dropped and the engine speed immediately increases to 3600 RPM. Five seconds later, the Loadshed signal is deactivated and Loads 3 and 4 are sequenced back on, spaced 15 seconds apart. Loads 1 and 2, which are designed for air conditioners, are sequenced back on after 5 minutes.
The engine speed remains at 3600 RPM for a programmable time (20 minutes default) and then ramps down to the speed appropriate for the attached load. The programmable time can be changed by the dealer to prevent annoying ramps up and down in engine speed if large loads turn on and off frequently.
Synergy Automatic Standby Generator Owner’s Manual 5
Page 12
General Information
2.1.6— Overload
If a load is sensed that is too large for the engine, that load will be locked out for a period of 30 minutes. If the load is not connected through a fast Loadshed enabled controller and module, then the generator shuts down with an “Over­load” alarm.
2.1.7— Low Speed Exercise
Low speed exercise operates at 1950 RPM for five minutes. The output voltage and frequency will not be at the rated voltage and frequency during exercise.
2.1.8— Normal Exercise
Normal exercise is at 3600 RPM at normal voltage and frequency levels for 5 minutes.
2.1.9— Automatic Voltage Regulator (AVR) Cooling Fans
The system is equipped with two fans to cool the AVR electronics. The primary fan is powered by AC during operation. The secondary fan is powered by 12V DC through the controller. The fans are monitored during operation and if a fail­ure occurs, an alarm is displayed.
The secondary fan continues to operate for up to on e hour after the generator is shut down. Proper cooling must occur before removing battery connections for maintenance or other service activity.
If uti lity is pres en t , t h e sec o nd ar y 12V DC fan contin ues t o o p er at e fo r up to one hour after the genera-
*
NOTE: The AVR co o l in g air inlet inc l ud es a fi lter. Verify th e filter is instal led and pr operly seated at time the un it is instal l ed. Chec k the fil ter at r egular maintenance intervals to veri f y p roper airflow.
tor i s shut down (even if the 7.5 am p ATO f use i s r em oved). To avoi d hand i nj ury, always exercise cau­ti on when w orking near the AVR fan h ousing.
6 Synergy Automatic Standby Generator Owner’s Manual
Page 13
2.2 — The Generator
General Information
B
A
N
C
D E
F
G
H
I
L
M
Figure 2-1. Component Locations
A. Automatic Voltage Regulator (AVR) H. Circuit Breakers
B. Oil Dipstick I. Fuel Inlet (Back)
C. Oil Fill Cap J. Fuel Regulator
D. Engine Air Filter K. Battery Compartment
E. AVR Air Filter L. Oil Filter
F. Data Label M. Composite Base
G. Control Pad N. Exhaust Enclosure
J
K
Synergy Automatic Standby Generator Owner’s Manual 7
Page 14
General Information
2.3 — Protection Systems
The owner/operator is alerted to Alarm and/or Warning conditions via the control pad LCD screen. All Alarm conditions cause the generator to shut down. The Warning messages alert the operator to conditions that do not disable the unit, require immediate correction, or result in shut down.
Some of the possible Alarm/Warning messages are listed below.
NOTE: For Sy nergy spec ific alarms, see Su b section 5.3 — Synergy Troubleshoot i ng.
2.3.1— Alarms
High Temperature
Low Oil Pressure
Overcrank
Overspeed
Underspeed
RPM Sensor Loss
Wiring Error
Overvoltage
Undervoltage
Fuse Problem
Overload
Stepper Overcurrent
2.3.2— Warnings
Charger Warning
Charger Missing AC
Low Battery
The above list is not all inclusive. For more information about alarms, see Section 5 Troubleshooting.
NOTE: A WARNING alerts the operator to a cond ition th at m ust be addressed, bu t does not s h ut down th e gen ­erator. An ALARM shuts d ow n the generato r to prot ect the un it from damage. In the event of an alarm, the owner m ay cl ear the alarm and restar t the g ener at or. If th e al arm o c c urs again, co ntact you r i ndepend ent s er­vi c i ng deal er.
Exercise Set Error
USB Warning
Download Failure
2.4 — Emission Information
The U.S. Environmental Protection Agency (EPA) requires that this generator comply with exhaust emission standards. This generator is certified to meet the applicable EPA emission levels, and is certified for use as a stationary engine for standby power generation. Any other use may be a violation of federal and/or local laws. To ensure that the engine complies with applicable emission standards for the duration of its service life, it is important to perform the mainte­nance tasks described in Subsection 4.3 — Service Maintenance Schedule. This generator is certified to operate on Liquid Propane Vapor fuel or pipeline Natural Gas.
The Emission Control System code is EM (Engine Modification). The Emission Control System on this generator may consist of the following components:
Air Induction System
– Intake Pipe / Manifold
– Air Cleaner
Fuel Metering System
– Carburetor / Mixer
Assembly
– Fuel Regulator
8 Synergy Automatic Standby Generator Owner’s Manual
Ignition System
– Spark Plug
– Ignition Module
Exhaust System
– Exhaust Manifold
– Muffler
Page 15
General Information
2.5 — Specifications
2.5.1— Generator
Model 20 kW Synergy
Rated Voltage 240
Rated Maximum Load Current (Amps) at 240 Volts (LP)*
Main Circuit Breaker 90 Amp
Phase 1
Rated AC Frequency 60 Hz
Battery Requirement Group 26R, 12 Volts and 525 CCA Minimum (Generac Part No. 0H3421S)
Unit Weight in Lbs. (kilos) 509 (231)
Enclosure Aluminum
Normal Operating Range This unit is tested in accordance to UL 2200 standards with an operating temperature of
-20º F (-29º C) to 122º F (50º C). For areas where temperatures fall below 32º F (0º C) a cold weather kit is required. When operated above 77º F (25º C) there may be a decrease in engine power. Please reference the engine specifications section.
These generators are rated in accordance with UL 2200, Safety Standard for Stationary Engine Generator Assemblies, and CSA­C22.2 No. 100-04 Standard for Motors and Generators.
* Natural Gas ratings will depend on specific fuel Btu/joules content. Typical derates are between 10-20% off the LP gas rating.
83.3
2.5.2— Engine
Model 20 kW Synergy
Type of Engine GT-999
Number of Cylinders 2
Displacement 999 cc
Cylinder Block Aluminum w/Cast Iron Sleeve
Recommended Spark Plug RC12YC
Spark Plug Gap 1.02 mm (0.040 in)
Starter 12 VDC
Oil Capacity Including Filter Approx. 1.9 Qt/1.8 L
Recommended Oil Filter Part #070185E
Recommended Air Filter Part #0J8478
Engine power is subject to and limited by such factors as fuel Btu/joules content, ambient temperature and altitude. Engine power decreases about 3.5 percent for each 1,000 feet (304.8 meters) above sea level, and also will decrease about 1 percent for each 6º C (10º F) above 15º C (60º F) ambient temperature.
The specification sheet for this generator was included in the documentation provided with the unit at the time of pur­chase. For additional copies, consult your local Authorized Independent Service Dealer.
Synergy Automatic Standby Generator Owner’s Manual 9
Page 16
General Information
$
2.5.3— Fuel Requirements
The engine has been fitted with a dual fuel carburetion system. The unit will run on natural gas or LP gas (vapor), but it has been factory set to run on natural gas. The fuel system is configured for the selected fuel source during installation.
Recommended fuels should have a btu content of at least 1,000 Btus per cubic foot (37.26 megajoules per cubic meter) for natural gas, or at least 2,500 Btus per cubic foot (93.15 megajoules per cubic meter) for LP gas (vapor). If converting to LP gas from natural gas, a minimum LP tank size of 250 gallons (946 liters) is recommended. See the Installation Manual for complete procedures and details.
Gaseous fuels suc h as n atu r al g as and li quid propane gas are highl y expl os iv e. A ny spark can ig ni t e su ch f uels and cause an exp lo sion. No leakag e of fuel is permitted. Natural gas, which is ligh ter th an air, tends to col lect in high areas. LP gas i s heav i er t han air and tends to settle in low areas.
2.5.4— Battery Requirements
Group 26R, 12V, minimum 525CCA (Generac Part No. 0H3421S).
For proper battery maintenance, see Subsection 4.6.1— Check Battery Condition/Fluid Level.
2.5.5— Battery Charger
The battery charger is integrated into the control system. It operates as a “Smart Charger,” which ensures output charging levels are safe and continuously optimized to promote maximum battery life.
2.5.6— Engine Oil Requirements
For correct engine oil type, see Subsection 4.5.3.1— Engine Oil Recommendations.
2.6 — Accessories
See Table 2-1. The following accessories are available.
Table 2-1. Accessories
Accesso ry Description
Cold Weather Kit Required in areas where temperatures fall below 32 º F (0 º C).
Scheduled Maintenance Kit
Auxiliary Transfer Switch Lockout
Fascia Skirt Wrap Standard on all 22 kW units. Available for all current production air-cooled units that don't
Mobile Link™ Provides a personalized web portal that displays the generator’s status, maintenance schedule,
Includes all pieces necessary to perform maintenance on the generator along with oil recom­mendations.
Enables any of the transfer switches to completely lock out one large electrical load by tying into its control system.
include it. It snaps together, around the base and mounting pad of the generator, to provide a smoothing, contoured look as well as rodent/insect protection. Requires use of the mounting pad shipped with the generator.
event history and much more. This portal is accessible via computer, tablet or smart phone. Sends emails and/or text notifications the moment there is any change in the generator’s sta­tus. Notification settings can be customized to what type of alert is sent and how often. For more information, visit www.standbystatus.com.
Wireless Local Monitor Completely wireless and battery powered, the Wireless Local Monitor provides you with instant
status without ever leaving the house. Status lights (red, yellow and green) alert owners when the generator needs attention. Magnetic backing permits refrigerator mounting and gives a 600 foot line of sight communication.
10 Synergy Automatic Standby Generator Owner’s Manual
Page 17
Table 2-1. Accessories (Continued)
Accesso r y Description
General Information
Power Management Mod­ule (PMM) Starter Kit
Power Management Mod­ule (PMM)
Touch-Up Paint Kit Very important to maintain the look and integrity of the generator enclosure. This kit includes
Extended Warranty Cov­erage
Includes one module with transformer. The transformer, which is mounted inside the ATS enclo­sure, interfaces with the OPCB to generate the 24 Vac signal needed for control of the contac­tor (Load 1 on the OPCB).
Includes one module only. To achieve full system functionality, a total of three kits are required to allow control of the three remaining contactors (Loads 2/3/4 on the OPCB).
touch-up paint and instructions.
Extend your generator’s warranty coverage by purchasing the 5 year extended warranty cover­age. Covers 5 years of both parts and labor. Extended coverage can be purchased within 12 months of the end-users purchase date. This extended coverage is applicable to registered units and end-user proof of purchase must be available upon request. Available for Generac ®, Guardian ® and Centurion ® products. Not available for Corepower™ and EcoGen products or all international purchases.
Contact an independent authorized Dealer for additional information on accessories.
Synergy Automatic Standby Generator Owner’s Manual 11
Page 18
General Information
This page intentionally left blank.
12 Synergy Automatic Standby Generator Owner’s Manual
Page 19
Sec t i o n 3
*
Operation
3.1 — Control Pad
The control pad is intended for use by q ual ified service personnel only.
See Figure 3-1. The control pad is located under the lid of the enclosure. The lid is secured by two locks, one on each side of the enclosure. For best results, press down on the lid directly above the side lock, and while holding the lid down, use key to unlock the latch. Repeat step on opposite side of enclosure. Always unlock both the left and right side locks before attempting to lift the lid.
NOTE: The lid may ap pear st u c k if pressure is not appli ed as des c r ib ed. A lw ay s verify that the side loc ks ar e un lo cked before pulling up on l i d.
To remove the front access panel, lift it straight up to disengage side hooks, and then outward away from unit.
When closing the unit, remember to lock both left and right side locks.
7.5 Amp Fu s e and USB Port
(Under Flap)
LCD Scr een
Con trol Pad
Generator Disc o nnect
Cir cuit B reaker
Sid e L ock
Side Door Com p artmen t
Figu re 3-1. Control Pad and Side Door Compartment
Synergy Automatic Standby Generator Owner’s Manual 13
Page 20
Operation
*
With th e c on t rol pad set to A UTO, the engine may crank and star t at an y time w i t hout warning. Such autom at i c starti n g o ccu rs during t he pr ogrammed exerc ise cycle or when utili ty power source voltage drops below the conf igu r ed l ev el . To preven t possibl e in jury that might occ ur d uring sudd en starts, always set the contro l pad to OFF and rem o ve the 7.5 amp fuse bef o re working on or around th e g ener ­ato r or transfer sw i t ch. For added security, place a DO NOT OPERATE tag or placard at both the co ntrol pad and transfer switch.
NOTE: Never r un the g enerator with any access panel remov ed.
LCD Scr een
UP ARROW
AUTO
MANUAL
Green
LED
OFF
Blu e LED
Figure 3-2. Control Pad and LCD Screen
3.2 — Auto/Manual/Off
Feature Descrip t ion
Press to activate fully automatic operation. Green LED illuminates to confirm that system is in AUTO mode.
AUTO
MANUAL
Transfer to standby power occurs if utility power fails. Exercise timer functionality is enabled, if set.
Press to crank and start engine. Blue LED illuminates to confirm that system is in MANUAL mode. Transfer to standby power occurs if utility power fails. Exercise timer functionality is disabled.
Red LED
ESCAPE
ENTER
DOWN ARROW
Press to shut down engine, if running. Red LED illuminates to confirm that system is in OFF mode.
OFF
14 Synergy Automatic Standby Generator Owner’s Manual
Transfer to standby power does not occur if utility power fails. Exercise timer functionality is disabled.
Page 21
3.3 — Menu Navigation
Feature Descrip t ion
Sys t em Men u s
The system returns to the Home screen if the control pad is not used for five minutes. The screen normally displays a Status message, such as Ready to Run (Auto mode) or Switched to OFF (Off mode), and the
HOME Screen
MAIN MENU
ESCAPE Used to abort a routine or back up to the preceding menu.
ENTER Used to make a selection or save an entry.
total Hours of Protection. If an active alarm/warning condition occurs, the associated Alarm/Warning mes­sage is displayed. To clear the Alarm/Warning message, press OFF on the control pad followed by ENTER. In the event of multiple Alarms/Warnings, the next message is then displayed. The highest priority alarm is always displayed first.
Enables the operator to navigate the software using UP ARROW, DOWN ARROW, ENTER and ESCAPE. The Main Menu can be accessed from any sub menu by consecutively pressing ESCAPE. Each time ESCAPE is pressed, the preceding menu is displayed. The Main Menu is reached when the System, Date/Time, Battery, and Sub Menus are displayed.
Navig ation
Operation
UP ARROW
DOWN ARROW
NOTE: Pressing the control pad illuminates the backlight for 30 seconds. The backlight also illuminates for 30 seconds when­ever an active Alarm/Warning message is displayed.
Used to move forward or backward from menu to menu or to scroll forward or backward (increment or dec­rement) through available selections.
3.4 — Change Time and Date
To change the time and date after activation, see the Navigation Menu in Figure 3-3. If power is lost (battery is discon­nected/reconnected, 7.5 amp control pad fuse is removed/installed, etc.), the display automatically prompts the user for the Time and Date. All other information is retained in memory.
3.5 — Programmable Timers
3.5.1— Dealer Programmable
NOTE: A dealer pass code is required .
3.5.1.1—High Run Speed Timer
A programmable high run speed timer is provided. The timer controls the length of time the generator runs at maximum speed after application of a large load (such as an air conditioner). The time can be increased to prevent the potential cycling of engine RPM as loads turn on and off. For example, if the timer is currently set to ten minutes, and the normal AC cycling time is 15 minutes, increasing the timer to 20 minutes would prevent the engine speed from ramping up and down every ten minutes between AC cycles (even though fuel consumption would increase).
3.5.1.2—Star t-Up Delay Timer
A programmable line interrupt delay (or Start-Up Delay) timer is provided. When utility voltage fails (falls below 65% of nominal), the start-up delay timer is started. If the voltage rises above the Utility Volts Low threshold, the timer is reset. If the utility voltage remains below the threshold during the duration of the timer, the unit cranks and starts.
NOTE: The fac tory default setting is five seco nds, but is adjus table from 2 to 1500 second s.
Synergy Automatic Standby Generator Owner’s Manual 15
Page 22
Operation
3.5.2— User Programmable
3.5.2.1—Ex ercis e Ti me
A programmable exercise time is provided. In the AUTO mode, the engine starts and runs at the programmed interval, either weekly, bi-weekly (the default), or monthly, at the time and day specified. During the exercise cycle, the unit runs approximately fi v e minutes and then shuts down. Transfer of loads to the generator does not occur unless utility power fails. For more information, see Subsection 3.12 —Setting the Exercise Timer.
3.6 — USB Port for Firmware Updates
A USB port is located beneath the rubber flap adjacent to the control pad, and is provided for firmware updates. Firm­ware updates must be performed by an Independent Authorized Service Dealer.
NOTE: The USB por t is i nten ded for use with a USB t hu mb drive only. The USB p o rt is not intend ed for ch arg i ng devices such as phones or lapt ops. Do not connect any consu m er electron ics to the USB port.
16 Synergy Automatic Standby Generator Owner’s Manual
Page 23
Operation
+
UP ARROW =
02/14/13 07:40
Current Date/Time
-
DOWN ARROW =
0.0
Run Hours (H)
ENTER
ESC
Run Hrs
ESC ENTER
ESC
Scheduled
ESCENTER
Maint. Log
MAINT:
ENTER
ESC
Access Requires Passwor d
MAINT
DEALER
and
EXAMPLE:
Inspect Battery 200 R nHr or 12/27/1 3
Next Maintenance 200 R nHr or 12/27/ 13
ESCENTER
- 1 thru 50 + "Inspect Battery"
"Battery Maintained"
"Maintenance Reset"
"Service Schedule A"
"Schedule A Serviced"
"Service Schedule B"
"Schedule B Serviced"
+
Language
+ Portuguese -
-
+
ENTER
ENTER
- 13 +
Select Year (0-99)
ESC
ENTER
- 13 +
Select Date (1-31)
ESC
ENTER
ESC ESC ESC
- 2 +
Select Month (1-12)
ESC
ENTER
Select “Yes” then Press “Enter” to continue or Press
“ESCAPE” to escape o ut of updating.
During update process the Blue “Manual” light
flashes, then the Green “Auto” light flashes.
Sequence does this t wice. When update is complete
the unit returns to Insta ll Wizard menu.
When the controller po wers up the very first screen
displays the version nu mber for a few seconds.
When update is comple te remove Thumb Drive,
then follow the Install W izard Menu.
Select Day
- Wednesday +
ENTER
"- Yes or No +"
"Are You Sure?"
- 0 +
Select Min (0-59)
ENTERENTERENTER
- 14 +
Select Hour (0-23)
ESC
ENTER
"Current:V XXXX "
"USB: V XXX X"
DATE/TIME
ESC
0 (H)
Switched to “OFF”
Hours of Protection
Running Manual
Running-Utility Lost
SUB MENUS
ENTER
HISTORY
EDIT
SYSTEM
BATTERY
ESC
ENTER
ENTER
Battery Condition
“Good” “Inspect Battery” or “Check Battery”
Switched Off
Stopped - Auto
Stopped - Alarm
Running - Exercise
Running-2 Wire Start
Running-Remote St art
ESC
ENTER
ENTER
“Run Log”
“Alarm Log”
ESC
ENTER
ENTER
- Run Log +
- Alarm Log +
ESC
ENTER
ENTER
- 1 thru 50 +
- 1 thru 50 +
Language
Language
Language
ENTER
Language English
+ Francais -
-
+
+ Espanol -
ESC
-
+
+ English -
ESC
ESC
- 0 +
Select Min (0-59)
ESCESC
ENTERENTER
ESC
- 14 +
Select Hour (0-23)
+ NG or LP -
Fuel Selection
ENTER
NG or LP
Fuel Selection
ESC
2/12/13 12:22
Current Date/Time
ESC
- YES or NO +
Quiet Test Mode ?
Quiet Test Mode only
Weekly
Monthly
Bi-Weekly
ENTER
Exercise Time
14:00 Wed Weekly
ESC
Invalid File
Corrupted File
File Not Found
Unsupported Device
Possible Message(s)
on certain models
Insert USB
Firmware Update
ESC
ENTER
Press Enter
Firmware Update
ESC
SYNERGY HSB MENU MAP
Synergy Automatic Standby Generator Owner’s Manual 17
"Low Battery"
"Fuel Pressure"
"Battery Problem"
"Charger Warning"
"Exercise Set Error"
Warning Message(s)
"FIRMWARE ERROR-9"
"USB Warning"
Alarm Message(s)
"Download Failure"
"Overload Warning"
"SEEPROM ABUSE"
"Overload Cooldown"
"Charger Missing AC"
"High Engine Temp."
Figu re 3-3. Navigation Menu
"Overcrank"
"Overspeed"
"Underspeed"
"Internal Fault"
"Low Oil Pressure"
"RPM Sense Loss"
"Over Voltage"
"WIRING ERROR"
"FIRMWARE ERROR-7"
"Fuse Problem"
"Under Voltage"
"Stepper Over Current"
"Overload Remove Load "
"Low Volts Remove Load"
For com p lete listing o f alarm s and w arnings,
see Sec tio n 5 Tro ubl esho o tin g.
Page 24
Operation
3.7 — Transfer Switch Automatic Operation
In AUTO, the generator starts automatically when utility source voltage drops below the preset level. Once the unit starts, loads are transferred to the standby power source.
To select automatic operation:
Verify that the transfer switch main contacts are set to the UTILITY position (loads connected to the utility power
1.
source).
Verify that normal UTILITY power source voltage is available to transfer switch terminal lugs N1 and N2.
2.
Move the Generator Disconnect Circuit Breaker switch under the side door to the ON (Closed) position.
3.
Press AUTO on the control pad. A green LED illuminates to confirm that the system is in the AUTO mode.
4.
3.7.1— Automatic Sequence of Operation
3.7.1.1—Utili ty Failure
If the control pad is set to AUTO when the utility power fails (falls below 65% of nominal, dealer programmable), a fiv e second Start-Up Delay timer is started (dealer programmable). If utility power is still absent when the time expires, the engine cranks and starts.
Once started, a five second engine Warm-Up Delay timer starts. When the time has elapsed, the load is transferred to the generator. If utility power is restored (above 80% of nominal, dealer programmable) between the time the engine is first started and expiration of the warm-up time, the system completes the start cycle and then runs through its normal cool-down cycle while the load remains on the utility source.
3.7.1.2—Crankin g
The cyclic cranking is controlled as follows:
Sixteen (16) seconds crank, seven (7) seconds rest, sixteen (16) seconds crank, seven (7) seconds rest; this sequence is repeated for a total of five (5) crank cycles.
3.7.1.3—Load Transfer
With the generator running, the transfer of load is dependent upon the operating mode as follows:
Starts and runs if utility power fails (falls below 65% of nominal) for five consecutive sec­onds (adjustable).
Starts a five second engine warm-up timer.
Does not execute transfer if utility power returns before expiration of warm-up timer (but finishes the warm-up and cool-down cycles).
Transfers back to utility once utility power returns (above 80% of nominal) for fifteen
consecutive seconds.
AUTO
Only shuts down if OFF is pressed on the control pad or an alarm shutdown occurs.
Once utility power returns, starts a one minute cool-down cycle before it shuts down.
EXERCISE
Only works in the AUTO mode when the generator is NOT running.
Does not exercise if generator is already running in AUTO or MANUAL modes.
During exercise cycle, transfers only if utility power fails for ten consecutive seconds.
Engine cranks and runs even if utility power is present, but does not transfer to generator.
Transfers to generator if utility fails (falls below 65% of nominal) for ten consecutive sec-
MANUAL
18 Synergy Automatic Standby Generator Owner’s Manual
onds.
Transfers back to utility when utility returns for fifteen consecutive seconds. The engine
continues to run until AUTO or OFF is pressed.
Page 25
Operation
3.7.2— Load Shed Functionality
The Synergy product Transfer Switch includes an Overload Prevention Control Board (OPCB) to shed critical loads.
The OPCB, commonly referred to as the Load Shed Board, has “Fast Load Shed” capability, which effectively prevents large loads from stalling the engine. ALL LOADS GREATER THAN 10 kW OR 2 HP (MOTORS) MUST BE CON­NECTED TO THE OPCB. If natural gas is th e selected fu el typ e, t h en all l oad s g r eat er t han 9kW must be con ­nec ted to th e OPCB. Examples of a large load are a 3T air conditioner, 3 HP well pump, 3 HP sump pump, etc.
When the generator senses the application of a large load (greater than 10 kW or 2HP) while the engine is at low speed, the load is instantly shed (within milliseconds) and the engine is instructed to run at 3600 RPM. This action pre­vents stalling of the engine. The loads are then reapplied when the engine is back up to speed. Normal loads take about six seconds. Large loads, such as an air conditioner, have specially designated connections on the OPCB, and are only reapplied after fiv e minutes (to protect the air conditioner motor).
See the Transfer Switch Owner’s Manual for a complete description.
3.8 — Transfer Switch Manual Operation
DO NOT attempt to activate the tran s fer switch manuall y unti l all power vo ltage supplies to the sw it ch hav e been completely tu r ned off. Failu re to turn off all pow er vol tage supp li es may result in extremely hazardou s and p o ssibly fatal elect rical shock.
Prior to automatic operation, manually exercise the transfer switch to verify that there is no binding or interference with proper operation of the mechanism. Manual operation of the transfer switch is required if automatic operation fails.
IMPORTANT NOTE: Al ways u se the ap plicable transfer switch ow ner 's manual for actual manual transfer sw it ch operation instructions. The i nform ation pres en t ed h ere descr i b es a t y pical V-sty l e tr ansfer switch, wh i ch is n ot used for three phase application s .
3.8.1— Transf er to Generator Power
When utility power fails, manually transfer to standby power and start the generator as follows:
Press OFF on the control pad.
1.
Move the Generator Disconnect Circuit Breaker switch to the OFF (Open) position.
2.
3.
Turn off the utility power supply to the transfer switch using the means provided (such as a utility main line circuit breaker).
Use the manual transfer handle inside the transfer switch to move the main contacts to the STANDBY position
4.
(loads connected to the standby power source).
Press MANUAL on the control pad. The engine cranks and starts.
5.
Allow the engine to run for 20 seconds to bring it up to normal operating speed.
6.
7.
Move the Generator Disconnect Circuit Breaker switch to the ON (Closed) position.
3.8.2— Transfer Back to Utility Power
When utility power is restored, manually transfer back to utility power and shut down the generator as follows:
NOTE: Verify that utility voltage has returned and is at the proper value.
Move the Generator Disconnect Circuit Breaker switch to the OFF (Open) position.
1.
2.
Allow the engine to run for on e minute at no-load to cool down the unit.
Press OFF on the control pad to shut down the engine.
3.
Verify that utility power supply to the transfer switch is turned off.
4.
5.
Use the manual transfer handle inside the transfer switch to move the main contacts to the UTILITY position (loads connected to the utility power source).
Synergy Automatic Standby Generator Owner’s Manual 19
Page 26
Operation
Manual Trans fer
Handl e
Load Connected t o Ut ili ty
Lo ad Connected t o Stand by
Transf er Switch
Operating Lev er
Figure 3-4. Manual Transfer Switch Operation (Typical)
6.
Turn on the utility power supply to the transfer switch using the means provided.
Press AUTO on the control pad. A green LED illuminates to confirm that the system is in the AUTO mode.
7.
3.9 — Removal From Service During Utility Outages
If, during prolonged utility outages, the user wishes to remove the unit from service to conserve fuel, reduce run hours, or to perform maintenance tasks, then complete the steps listed below.
IMPORTANT NOTE: Failu r e to abi de by th is procedure can result in equ ip m ent dam ag e.
To remove the generator from service while running in AUTO and online, proceed as follows:
1.
Turn the main utility disconnect to OFF (Open).
2.
Move the Generator Disconnect Circuit Breaker switch to the OFF (Open) position.
3.
Allow unit to cool for one minute.
Press OFF on the control pad to shut down the engine.
4.
NOTE: If the generator is to remain off fo r m o re than an hou r w ith utilit y p o wer NOT PRESENT, wait one h our for t he internal fans to cool it dow n.
5.
Pull up rubber flap covering fuse holder and remove 7.5 amp fuse to prevent discharge of the starting battery.
To return the generator to service, proceed as follows:
Pull up rubber flap covering fuse holder and install 7.5 amp fuse.
1.
2.
Follow Install Wizard and enter information as required.
3.
Press AUTO on the control pad. A green LED illuminates to confirm that the system is in the AUTO mode. Allow the generator to start and run for 20 seconds.
Move the Generator Disconnect Circuit Breaker switch to the ON (Closed) position.
4.
Turn the main utility disconnect to ON (Closed).
5.
20 Synergy Automatic Standby Generator Owner’s Manual
Page 27
Operation
3.10 — Side Door Compartment
Check local codes for side door locking requirements. A hasp is provided, so that the side door can be secured with a customer supplied padlock if necessary.
120 GFCI Outlet
LED Ind i cators
15 Amp Ou tlet Br eak er
GFCI BREA KER
ON OFF
ON
ON
ON
ON
GENERATOR DISCONNECT
OFF
OFF
Generator Disc o nnect
Circuit Br eaker
OFF
OFF
Figu re 3-5. Open Side Door Compartment
3.10.1— LED Indicators
Green Ready LED: Illuminates when utility power is present and the control pad is set to AUTO. Also indicates when the generator is running.
Red Alarm LED: Illuminates when the control pad is set to OFF or a fault is detected. Contact your authorized
servicing dealer if necessary.
Yellow Maintenance LED: Indicates that maintenance is required.
3.10.2— 120V GFCI Outlet/15 Amp Breaker
Some units are equipped with an external 15 amp, 120 volt GFCI convenience outlet located in the side door compart­ment.
When the generator is running, in the absence of utility power, this outlet may also be used to power items outside the home such as lights or power tools. This outlet may also be used when utility power is present by running the generator in manual mode.
This outlet does not provide power if the generator is not running. DO NOT USE THIS OUTL ET WHEN THE GENER­ATOR IS IN EXERCISE MODE. This outlet is protected by a 15 Amp circuit breaker located in the side door compart­ment.
Synergy Automatic Standby Generator Owner’s Manual 21
Page 28
Operation
3.11 — Battery Charger
NOTE: The battery charger is int eg r ated i nto the control mod ul e.
The battery charger operates as a “Smart Charger” that ensures:
Output is continually optimized to promote maximum battery life.
Charging levels are safe.
NOTE: A warni n g i s d i sp layed on the LCD screen when th e battery need s serv i ce.
3.12 — Setting the Exercise Timer
This generator is equipped with a configurable exercise timer. The first of two settings specifies the Day/Time of the exercise. Once set, the generator will start and exercise on the day of the week and at the time of day specified. During the exercise period, the unit runs for approximately fiv e minutes, and then shuts down. The second setting establishes exercise frequency, and can be set to WEEKLY, BIWEEKLY (the default), or MONTHLY. If monthly is selected, the date of the month must be entered. Transfer of loads to the generator does not occur during the exercise cycle unless utility power is lost.
IF THE INSTALLER TESTS THE GENERATOR PRIOR TO INSTALLATION, PRESS ENTER ON THE CONTROL PAD TO SKIP EXERCISE TIMER SETUP.
The exercise information and programming options is shown in Table 3-1.
Figure 3-6 illustrates the engine speed profile during a typical low speed exercise cycle. While providing the necessary periodic exercise, the lower RPM reduces fuel consumption, engine wear, and noise.
NOTE: The exer cise f eat ur e o per ates o nly when t he gen erator is in the AUTO mo de an d th e Ex erci s e Tim er is proper ly set. The cur rent date/time must be reset every time the T1 c ircuit is sh ut do w n , th e 12 vo lt batter y is di sco nnected, the 7.5 amp fuse is rem o ved, and/or th e b att er y c har ger i s disconnected (cont r o l pad has no po wer an d LCD screen is bl ank).
Table 3-1. Generator Exercise Character istic s
Mod el 20 kW Synerg y
Low Speed Exerc ise 1950 rpm
Exerc i se Frequency Optio n s Weekly/Bi-WeeklyMonthly
Exer c ise Tim e L ength 5 minutes
3800
3600
3400
3200
3000
2800
2600
2400
Exerci se Speed (RPM)
2200
2000
1800
0 sec 5 s 10 s 15 s 20 s 25 s 30 s 35 s 40 s 45 s 1 min 5 min
Figure 3-6. Low Speed Exercise Profile - 20 kW Synergy
22 Synergy Automatic Standby Generator Owner’s Manual
Exercise Time
Page 29
Sec t i o n 4
*
+
Maintenance
4.1 — Maintenance
NOTE: Proper maintenance is necessary for s af e op er at i on an d is crucial to th e l i fe o f the generator. Genui ne Generac par ts MUST be used to ensure warranty co ver ag e
NOTE: Since most maintenance alerts occur at t h e sam e time (two or fo u r year intervals), only one w i ll appear at any on e ti m e. Clearing one will cau se th e next active aler t t o b e d i sp layed.
4.2 — Maintenance Kits
To maintain the warranty, genuine Generac replacement parts MUST be used, including Generac oil kits (which include both an oil filter and an air filter). Generac oil kits can be obtained through an Authorized Dealer or purchased on-line. To purchase on-line, access the maintenance kits page through www.g en er ac .c o m . Follow the prompts to enter deliv­ery information and complete the purchase.
All Generac oil kits meet minimum American Petroleum Institute (API) Service Class SJ, SL, or better. Use no special additives. Select the appropriate viscosity oil grade according to the expected operating temperature. Synthetic oil also can be used in the appropriate weight as standard.
4.3 — Service Maintenance Schedule
NOTE: Use only Genuine Gener ac parts to ens u r e w ar r an ty coverag e.
All generator serv ice mu s t be p erformed by a qualified servi ce person onl y.
It is important to perform all maintenance at the interval specified in the Service Maintenance Schedule. This ensures safe and proper operation, as well as compliance with applicable emissions standards. Critical emissions maintenance must be performed for the Emissions Warranty to remain valid. Service and repairs may be performed by any qualified service technician or repair shop.
The LCD sc reen prompts the us er when it is tim e to perfor m the Schedule A or Schedule B m ai nten ance task s. When perform i n g Sc hed ul e B m aint en anc e, firs t perform all tas k s l isted under Sched ule A mai ntenance.
Observe the maintenance tasks and intervals shown in Table 4-1.
IMPORTANT NOTE: The secondary 12V DC fan conti nu es to oper at e for up to one hou r aft er the generato r is shu t d own. Proper cooling must occ ur b ef ore remo vi ng battery connecti ons for maintenance or other ser ­vi c e activity.
If util i ty is present, the secondary 12V DC fan co n tinues to operate for up to on e hou r after the gen­erato r is sh ut down (even if th e 7.5 amp ATO fuse is removed). To avo id hand injury, always exer cise cau tio n wh en working near the AVR fan housing.
Synergy Automatic Standby Generator Owner’s Manual 23
Page 30
Maintenance
Table 4-1. Service Maintenance Schedule
Daily If Ru nning
Servi c e
Check Enclosure Louvers for Dirt and Debris
Check Lines and Connections for Fuel or Oil Leaks
Check Engine Oil Level
Check Battery Condition, Electrolyte Level, and State of Charge
Replace AVR Filter *
Replace Engine Oil and Oil Filter **
Replace Engine Air Filter
Replace/Gap Spark Plugs
Inspect/Adjust Valve Clearance ***
Con tact t he near est ind ependent Au t ho rized Servi ce Deal er f o r assistance if n ece ss ary.
* Replace AVR filter more frequently if operating in dusty conditions.
** Change engine oil and filter after the first 25 hours of operation. In cold weather conditions (ambient below 40 or if unit is operated continuously in hot weather conditions (ambient above 85
every year or 100 hours of operation. *** Check/adjust valve clearance after the first 25 hours of operation.
Con t inuou s ly
or
Before Eac h Use
Every
Year
º
F / 29.4º C), change engine oil and filter
Sch ed ule A
Every
Two Years
or 200 Ho urs
F/ 4.4º C),
º
Sched ule B
Every
Fou r Years
or 400 Ho urs
4.4 — Remove From Service
To ensure safety, follow the steps below prior to inspection, maintenance or service.
Unlock left and right side locks. Open lid.
1.
NOTE: For best results, p ress d own on lid directl y abo v e each si d e lock, and wh i le hol ding the lid down , us e key to u n lock latches.
Press OFF on the control pad. A red LED illuminates to confirm that the system is in the OFF mode.
2.
Move the Generator Disconnect Circuit Breaker switch to the OFF (Open) position.
3.
If the generator has been running, allow one hour to elapse for unit to cool down and fans to stop running.
4.
Pull up rubber flap covering fuse holder and remove 7.5 amp fuse.
5.
Remove T1 fuse from transfer switch.
6.
4.5 — Daily Maintenance (If Running Continuously)
4.5.1— Check Enclosure Louvers
Verify that intake and exhaust louvers and openings are clean and unobstructed.
1.
Wipe exterior surfaces clean using a damp cloth.
2.
Loosen dirt, oil, etc. with a soft bristle brush.
3.
Remove loose dirt and debris using a vacuum cleaner, or low pressure compressed air (not exceeding 25 psi).
4.
NOTE: Peri o dically wash and wax enclosur e usi ng au t o m o tive type products. Fr equent washing is recom ­mend ed in salt water/c o astal areas.
24 Synergy Automatic Standby Generator Owner’s Manual
Page 31
4.5.2— Check Lines and Connections
*
Perform a general inspection as follows:
Maintenance
Check Fuel Lines and Connections for Leaks
4.5.3— Check Engine Oil Level
1.
Remove dipstick and wipe with a clean cloth. See A of Figure 4-1.
Completely insert the dipstick and then remove it.
2.
A B
Figure 4-1. Check Engine Oil Level
Check Oil Lines and Connections for Leaks
SAE 30
10W-30
Synthetic 5W-30
-20 -10 0 10 20 4032 60 80 100
-30°F-20 -10 0 10 20 30 40
°C
Temperature Range of Exp ected Use
Engine Oil Recommendati ons
Verify that the oil level is at or near the FULL mark.
3.
If necessary, remove the oil fill cap and slowly add the recommended type of oil until the level is at the FULL
4.
mark. DO NOT OVERFILL . See B of Figure 4-1.
Install dipstick and oil fill cap.
5.
Never operate the engine with the oil level below the ADD mark on th e dipstic k . Doing so co uld damage th e engi n e.
*
Hot oil may caus e bu rns . Avoid pro lo nged or repeated skin exposure with used oil . Thor ou ghly wash
*
exposed areas with so ap.
Any attempt to c rank or star t the en gi ne b ef o r e it has b een pr o p erly serviced with the recommended oil may result in an engi n e fail ure.
4.5.3.1— En gine Oil Reco mmendations
All oil should meet minimum American Petroleum Institute (API) Service Class SJ, SL or better. Use no special addi­tives.
See B of Figure 4-1. Select the oil viscosity grade according to the expected operating temperature.
Above 32° F (0° C), use SAE 30
Between 40° F and -10° F (4° C and -23° C), use 10W-30
For all temperature ranges, use Synthetic 5W-30
Synergy Automatic Standby Generator Owner’s Manual 25
Page 32
Maintenance
$
$
4.6 — Schedule A Maintenance
NOTE: Perfo rm Schedul e A m ai ntenance ev er y tw o year s o r after 200 hours of servic e, which ever co mes fi rst.
4.6.1— Check Battery Condition/Fluid Level
4.6.1.1— Check Condition and Cl ean
Remove front access panel.
1.
2.
Verify that top of battery is clean and dry. Dirt and electrolyte on top of the battery can cause battery to self-dis­charge. Clean battery top with a solution of baking soda (sodium bicarbonate) and water (5 teaspoons baking soda per quart or liter of water). When solution stops bubbling, rinse off the battery with clean water.
Clean cable clamps and battery terminals using a wire brush or sandpaper to remove any oxidation.
3.
Inspect battery screws, clamps and cables for breakage, loose connections and corrosion. Tighten and clean as
4.
necessary.
5.
Check the battery posts for melting or damage caused by over tightening.
Inspect battery for discoloration, raised top or a warped or distorted case, which might indicate that the battery
6.
has been frozen, overheated or overcharged.
7.
Inspect the battery case for cracks or leaks.
Check the battery fluid level of unsealed batteries. See Subsection 4.6.1.2—Check Fluid Level.
8.
9.
Check the battery state of charge. See Subsection 4.6.1.3—Check State of Charge.
Replace battery if damaged or unable to hold a charge. See Subsection 4.6.1.4—Battery Replacement.
10.
4.6.1.2— Check Flui d L evel
Check the fluid level of unsealed batteries. If necessary, fill with distilled water only. DO NOT use tap water.
4.6.1.3— Check State of Charge
Check the state of charge using a Digital Multimeter. Recharge and retest if state of charge is below manufacturer's recommendations. Replace battery if necessary.
4.6.1.4— Battery Rep l acement
Removal
Al w ay s disconnect the negative batt ery cab le first. If the positive cable shou ld contac t ground w ith the negativ e cable installed, the resulting sparks may cause a b at tery ex plosion whi c h co uld result in seri­ous in j ury.
Remove battery negative cable (black) from battery negative (-) terminal.
1.
Remove battery positive cable (red) from battery positive (+) terminal.
2.
Remove battery from battery tray.
3.
Ins tallation
Install battery onto battery tray.
1.
Al w ay s c onn ect the positive battery cab le fir s t . If t he positive cable should co ntact ground wi th the negativ e cable installed, the resulting sparks may cause a b at tery ex plosion whi c h co uld result in seri­ous in j ury.
Install battery positive cable (red) to battery positive (+) terminal.
2.
Install battery negative cable (black) to battery negative (-) terminal.
3.
26 Synergy Automatic Standby Generator Owner’s Manual
Page 33
4.6.2— Replace AVR Filter
+
If uti l ity is present, th e secondar y 12V DC fan c on tinues to operate for up to o n e ho u r after the genera-
+
tor i s shut down (even if the 7.5 amp ATO fu se is r em o v ed). To avoid hand inj ury, always exerc ise c au­ti on when working near the AVR fan h ousing.
The AVR remains charged for up to thr ee min ut es after power down. To avoid pot en tial electri c al sho c k, allow five minutes to elapse bef o re r emo vin g AVR f ilter housing .
Remove screw to release AVR filter housing from back panel. See A of Figure 4-2.
1.
Remove AVR filter housing.
2.
Grasp rubber lifting strap and remove filter from filter housing. Discard filter. See B of Figure 4-2.
3.
4.
Install new filter, so that edge is positioned inboard of two tabs on filter housing.
5.
Install AVR filter housing so the bottom drops into the slots, ensuring that the rubber boot is completely around the fan opening. Install screw to fasten AVR filter housing to back panel and torque to 50-96 in-lbs (6-11 Nm).
A B
Maintenance
4.6.3— Replace Engine Oil and Oil Filter
Remove oil drain hose from holding clamp.
1.
Remove drain plug from oil drain hose. See A of Figure 4-3.
2.
Drain oil into a suitable container.
3.
Install drain plug onto end of oil drain hose.
4.
Install oil drain hose into holding clamp.
5.
Rotate oil filter counterclockwise to remove from oil filter adapter. See B of Figure 4-3.
6.
Apply a light coat of clean engine oil to gasket of new oil filter.
7.
Install oil filter by hand until gasket just contacts oil filter adapter. Tighten oil filter an additional 3/4 to one full turn.
8.
Remove oil fill cap and fill engine with the recommended oil. See Figure 4-1.
9.
Install oil fill cap.
10.
Return unit to service. See Subsection 4.8 —Return to Service.
11.
Synergy Automatic Standby Generator Owner’s Manual 27
Figu re 4-2. Replace AVR Filter
Page 34
Maintenance
12.
Press MANUAL on the control pad to start the engine. A blue LED illuminates to confirm that the system is in the MANUAL mode.
Allow the engine to run for a few minutes. Check for leaks while the engine is running.
13.
Press OFF on the control pad to shut the engine down. A red LED illuminates to confirm that the system is in the
14.
OFF mode.
Remove dipstick and wipe with a clean cloth.
15.
Completely insert the dipstick and then remove it.
16.
Verify that the oil level is at or near the FULL mark.
17.
If necessary, remove the oil fill cap and slowly add oil until the level is at the FULL mark.
18.
DO NOT OVERFILL .
Install dipstick and oil fill cap.
19.
NOTE: Disp os e of us ed engin e oil and o il filter at a proper co ll ect i on center.
A B
Figu re 4-3. Oil Drain and Filter Location
28 Synergy Automatic Standby Generator Owner’s Manual
Page 35
Maintenance
+
4.7 — Schedule B Maintenance
NOTE: Perform Sched ul e B maintenance every fou r years or after 400 hou rs of servi c e, whichever com es first. Bef o re pr o c eedin g bel ow, fi r st perform all tas ks li s ted under Schedule A Mai nten ance.
4.7.1— Replace Engine Air Filter
Remove unit from service. See Subsection 4.4 —Remove From Service.
1.
Disengage cover clip and remove air cleaner cover. See A of Figure 4-4.
2.
Remove air filter and discard.
3.
Thoroughly clean the air cleaner cover and housing of dust and dirt.
4.
5.
Install new air filter. See B of Figure 4-4.
6.
Install air cleaner cover and engage cover clip.
A B
Figu re 4-4. Replace Engine Air Filter
4.7.2— Clean/Gap/Replace Spark Plugs
Clean, gap or replace spark plugs as follows:
Never dis con n ect a s park plug wit h th e en gi ne r u nning. Doing so will res ul t in an electr ic shock th at
+
+
Synergy Automatic Standby Generator Owner’s Manual 29
cou l d resu lt in death or seri ou s in jury.
If util i ty is present, the secondary 12V DC fan co n tinues to operate for up to on e hou r after the genera­to r i s s hut down (even i f the 7.5 amp ATO fu se is r em o v ed). To avoid hand inj ury, always exerc ise cau­ti on when working near the AVR fan h ousing.
The AVR rem ains charged for up to thr ee minutes after power down. To avoid potent i al electri cal sh o c k, allo w f ive minutes to elapse b efore remo vin g AVR f i lter housing.
Remove screw to release AVR filter housing from back panel. Remove AVR filter housing.
1.
Remove spark plug cables from spark plug terminals.
2.
Page 36
Maintenance
+
NOTE: Wh en disconnectin g spark plug cable from spar k plug terminal, always grasp and pu ll on th e boot at the t erm i nal en d o f the cab l e. Pul lin g on cable p ortion can resul t i n parts d am ag e.
3.
Thoroughly clean area around spark plugs.
4.
Remove spark plugs from cylinder head using a 5/8 inch spark plug socket.
Figure 4-5. Adjust Spark Plug Gap
Check condition of threads in cylinder head and on spark plugs. If necessary, soften deposits with penetrating oil
5.
and clean out with a thread chaser.
Clean spark plugs using a wire brush and commercial solvent. Do not blast spark plugs. Use new spark plugs if
6.
necessary.
7.
See Figure 4-5. Check spark plug gap using a wire feeler gauge. Adjust gap by carefully bending ground elec­trode to the dimensions in Section 2.5.2 - ENGINE.
Finger tighten spark plugs into cylinder head, and then using a spark plug socket, tighten to 15-18 ft-lbs (20-25
8.
Nm).
9.
Install spark plug cables onto spark plug terminals.
Install AVR filter housing. Install screw to fasten AVR filter housing to back panel and torque to 50-96 in-lbs (6-11
10.
Nm).
4.7.3— Check/Adjust Valve Clearance
IMPORTANT: If uncomfortable performing thi s p rocedure or the proper tool s ar e not availab le, co n tact the nearest in dep en d ent A uth orized Service Dealer for as sistan ce. This pro cedu r e is a very impo rtant to ensu re maxi mum eng i ne ser v ice life.
4.7.3.1— Check Valve Clearance
Verify that engine is at ambient air temperature.
1.
The AVR remains ch arg ed fo r up to thr ee min ut es after po w er do w n . To avoid po t en t ial electric sh oc k , allow f ive m i nutes to elaps e befor e rem o vi n g AVR fi l t er housing.
Remove screw to release AVR filter housing from back panel. Remove AVR filter housing. See A of Figure 4-2.
2.
Depress external latch to disconnect 4-pin connector from AVR.
3.
Remove three screws to release AVR fan from AVR. See Figure 4-6.
4.
Remove spark plug cables from spark plug terminals.
5.
NOTE: Wh en disconnectin g spark plug cable from spar k plug terminal, always grasp and pu ll on th e boot at the t erm i nal en d o f the cab l e. Pul lin g on cable p ortion can resul t i n parts d am ag e.
6.
Thoroughly clean area around spark plugs.
7.
Remove spark plugs from cylinder head using a 5/8 inch spark plug socket.
Remove four screws to release valve cover.
8.
30 Synergy Automatic Standby Generator Owner’s Manual
Page 37
9.
Move piston to Top Dead Center (TDC) of compression stroke (both valves closed). Proceed as follows:
a. Remove intake screen at front of engine to gain access to flywheel nut.
b. Place large socket and socket wrench on flywheel nut and rotate engine in a clockwise direction while watch-
ing piston through spark plug hole.
NOTE: Pis ton is at TDC when it is at the h i ghes t point of travel.
Left Righ t
4-Pin
Connecto r
Maintenance
Figure 4-6. Remove AVR Fan Connector and Screws
Insert a 0.002 - 0.004 inch (0.05 - 0.1mm) feeler gauge between rocker arm and valve stem. Clearance is correct
10.
when a slight drag is felt while sliding feeler gauge back and forth. Verify that clearances are within the following specification:
Intake and Exhaust: 0.002 - 0.004 inch (0.05 - 0.1mm)
Proceed as follows:
11.
a. If valve clearance adjustment is required, see Subsection 4.7.3.2— Adjust Valve Clearance.
b. If valve clearance is within specification, see steps 5-12 under Subsection 4.7.3.2— Adjust Valve Clearance.
4.7.3.2— A d just Valve Clearan ce
1.
Loosen rocker arm jam nut. Use an Allen wrench to turn the pivot ball stud, while also checking clearance between rocker arm and valve stem with the feeler gauge.
NOTE: Hold the rocker arm jam nut in place as the pivot ball s t ud is turned.
When the correct valve clearance is obtained, hold the pivot ball stud in place with the Allen wrench and tighten
2.
rocker arm jam nut until snug.
3.
Using a torque wrench, tighten jam nut to 174 i n-lbs (20 N-m).
4.
Recheck valve clearance to verify that it did not change during tightening of the jam nut.
Install new valve cover gasket.
5.
Start four screws to install valve cover.
6.
Verify that valve cover gasket is properly positioned, and then alternately tighten screws to 6-9 ft-lbs (8-12 Nm)
7.
using a crosswise pattern
8.
Finger tighten spark plugs into cylinder head, and then using a spark plug socket, tighten to 15-18 ft-lbs (20-25 Nm).
9.
Install spark plug cables onto spark plug terminals.
Synergy Automatic Standby Generator Owner’s Manual 31
Page 38
Maintenance
10.
Install the AVR fan.
Piv ot Ball
Stu d
Roc ker
Ar m
Jam Nut
Valve
Stem
Figure 4-7. Check/Adjust Valve Clearance
11.
Connect 4-pin connector to AVR. Press pin and socket halves together until external latch engages.
Install AVR filter housing so the bottom drops into the slots and ensuring that the rubber boot is completely around
12.
in-lb s
the fan opening. Install screw to fasten AVR filter housing to back panel and torque to 50-96
(6-11 Nm).
4.8 — Return to Service
Install front access panel.
1.
2.
Install T1 fuse in transfer switch.
3.
Pull up rubber flap covering fuse holder and install 7.5 amp fuse.
Follow Install Wizard instructions using LCD screen and control pad.
4.
Move the Generator Disconnect Circuit Breaker switch to the ON (Closed) position.
5.
Press AUTO on the control pad. A green LED illuminates to confirm that the system is in the AUTO mode.
6.
7.
Close lid. Lock left and right side locks.
4.9 — Attention After Submersion
If the generator has been submerged in water, it MUST NOT be started and operated. Following any submersion in water, have a Dealer thoroughly clean, dry, and inspect the generator. If the structure (home) has been flooded, it should be inspected by a certified electrician to ensure there won’t be any electrical problems during generator opera­tion or when utility power is returned.
4.10 — Corrosion Pro tection
Periodically wash and wax the enclosure using automotive type products. Frequent washing is recommended in salt water/coastal areas. Spray engine linkages with a light oil such as WD-40.
4.11 — Out of Service Procedure
If the generator cannot be exercised every seven days and will be out of service longer than 90 days, prepare the gen­erator for storage.
4.11.1— Remove For Storage
1.
Press MANUAL on the control pad to start the engine. A blue LED illuminates to confirm that the system is in the MANUAL mode.
32 Synergy Automatic Standby Generator Owner’s Manual
Page 39
Maintenance
$
$
2.
Allow the unit to warm up for a few minutes.
Press OFF on the control pad to stop the engine. A red LED illuminates to confirm that the system is in the OFF
3.
mode.
While the engine is still warm, completely drain engine oil and refill the crankcase with oil. See Subsection
4.
4.6.3—Replace Engine Oil and Oil Filter.
Press MANUAL on the control pad to start the engine. A blue LED illuminates to confirm that the system is in the
5.
MANUAL mode.
6.
Close the fuel shutoff valve in the fuel supply line and allow the unit to shut down.
7.
Verify that engine oil level is at or near the FULL mark. Remove the oil fill cap and slowly add the recommended type of oil, if necessary. DO NOT OVERFILL.
Set the Generator Disconnect Circuit Breaker switch to the OFF (Open) position.
8.
Turn off the utility power to the transfer switch.
9.
Pull up rubber flap covering fuse holder and remove 7.5 amp fuse.
10.
Al w ay s disconnect the negative batt ery cab le first . If the po sitive cable shou ld contac t ground w ith the negativ e cabl e in s talled, the resulti n g sparks may cause a bat tery ex plosion whi c h co uld result in seri­ous in j ury.
11.
Remove battery negative cable (black) from battery negative (-) terminal.
12.
Remove battery positive cable (red) from battery positive (+) terminal.
Remove battery charger AC input T1/Neutral cable (with white sleeve).
13.
Attach tag to engine indicating the viscosity and classification of the oil added to the crankcase.
14.
Remove spark plugs. Spray a fogging agent into the spark plug holes. Reinstall spark plugs. For more informa-
15.
tion, see Subsection 4.7.2—Clean/Gap/Replace Spark Plugs.
Remove battery and store in a cool, dry room on a wooden board. Never store the battery on a concrete or
16.
earthen floor.
Clean and wipe down the entire generator. See Subsection 4.5.1—Check Enclosure Louvers.
17.
4.11.2— Return To Service After Storage
To return the unit to service after storage:
1.
Verify that utility power is turned off.
2.
Check tag on engine indicating the viscosity and classification of the oil added to the crankcase. If necessary, drain and refill crankcase with the proper oil. See Subsection 4.6.3—Replace Engine Oil and Oil Filter.
Check the fluid level of unsealed batteries. If necessary, fill with distilled water only. DO NOT use tap water.
3.
Check the state of charge using a Digital Multimeter. Recharge and retest if state of charge is below manufac­turer's recommendations. Replace battery if necessary.
Clean and wipe down the entire generator. See Subsection 4.5.1—Check Enclosure Louvers.
4.
5.
Pull up rubber flap covering fuse holder and remove 7.5 amp fuse.
Install battery onto battery tray.
6.
Al w ay s c onn ect the positive battery cab le fir s t . If t he positive cable should co ntact ground wi th the negativ e cabl e in s talled, the resulti n g sparks may cause a bat tery ex plosion whi c h co uld result in seri­ous in j ury.
Install battery positive cable (red) to battery positive (+) terminal.
7.
Install battery negative cable (black) to battery negative (-) terminal.
8.
9.
Reconnect the battery charger AC input T1/Neutral cable (with white sleeve).
Open the fuel shutoff valve.
10.
Synergy Automatic Standby Generator Owner’s Manual 33
Page 40
Maintenance
11.
Pull up rubber flap covering fuse holder and install 7.5 amp fuse.
Follow Install Wizard instructions using LCD screen and control pad.
12.
Press MANUAL on the control pad to start the engine. A blue LED illuminates to confirm that the system is in the
13.
MANUAL mode.
14.
Allow the unit to warm up for a few minutes.
15.
Press OFF on the control pad to stop the engine. A red LED illuminates to confirm that the system is in the OFF mode.
Turn on the utility power to the transfer switch.
16.
Move the Generator Disconnect Circuit Breaker switch to the ON (Closed) position.
17.
Press AUTO on the control pad to stop the engine. A green LED illuminates to confirm that the system is in the
18.
AUTO mode.
The generator is ready for service.
NOTE: When a battery is dead or has been disconnected, the exercise timer and current date and time must be reset.
34 Synergy Automatic Standby Generator Owner’s Manual
Page 41
Sec t i o n 5
Troubleshooting
5.1 — Engine Troubleshooting
Table 5-1. Eng ine Diagnostics
Prob lem Cause Correcti on
Engine will not crank. 1) Fuse blown.
2) Loose, corroded or defective battery cables.
3) Defective starter contact.
4) Defective starter motor.
5) Dead Battery.
Engine cranks but will not start.
Engine starts hard and runs rough.
Generator is set to OFF, but the engine continues to run.
No AC output from genera­tor.
1) Out of fuel.
2) Defective fuel solenoid (FS).
3) Defective spark plug(s).
4) Valve clearance needs adjustment.
1) Air cleaner plugged or damaged.
2) Defective spark plug(s).
3) Fuel regulator not set.
4) Fuel pressure incorrect.
5) Fuel selector in wrong position.
1) Control board wired incorrectly.
2) Defective control board.
1) Main line circuit breaker is in the OFF
(or OPEN) position.
2) Generator internal failure.
1) Correct short circuit condition by replacing 7.5 Amp fuse.
2) Tighten, clean or replace as necessary.*
3) Tighten, clean or replace as necessary.*
4) Tighten, clean or replace as necessary.*
5) Charge or replace battery.
1) Replenish fuel / Turn on fuel valve.
2) *
3) Clean, re-gap or replace plug(s).
4) Adjust valve clearance.
1) Check / replace air cleaner.
2) Clean, re-gap or replace plug(s).
3) Set fuel regulator.
4) Confirm fuel pressure to regulator is 10-
12” water column (19-22mm mercury) for LP, and 3.5 - 7” water column (9­13mm mercury) for natural gas.
5) Move selector to correct position.
1) Repair wiring or replace control board.*
2) Replace control board.
1) Reset circuit breaker to ON (or CLOSED).
2) *
No transfer to standby after utility source failure.
Unit consumes large amounts of oil.
* Contact an Authorized Independent Service Dealer for assistance.
Synergy Automatic Standby Generator Owner’s Manual 35
1) Defective transfer switch coil.
2) Defective transfer relay.
3) Transfer relay circuit open.
4) Defective control logic board.
1) Engine over filled with oil.
2) Engine breather defective.
3) Improper type or viscosity of oil.
4) Damaged gasket, seal or hose.
1) *
2) *
3) *
4) *
1) Adjust oil to proper level.
2) *
3) See “Engine Oil Recommendations.”
4) Check for oil leaks.
Page 42
Troubleshooting
5.2 — Generator Troubleshooting
Table 5-2. Generator Diagnostics
Ac ti ve A lar m LED Problem
NONE GREEN Unit running in AUTO but no
power in house.
HIGH TEMPERATURE
OVERLOAD REMOVE LOAD
RPM SENSE LOSS
NOT ACTIVATED
None GREEN Unit will not start in AUTO with
LOW OIL PRESSURE
RPM SENSE LOSS
OVERCRANK RED Unit will not start in AUTO with
LOW VOLTS REMOVE LOAD
FUSE PROB­LEM
OVERSPEED RED Unit will not start in AUTO with
UNDER VOLTAGE
UNDERSPEED RED Unit will not start in AUTO with
RED Unit shuts down during operation. Check the
RED Unit shuts down during operation. Check the
RED Unit was running and shuts down,
attempts to restart.
NONE Unit will not start in AUTO with
utility loss.
utility loss.
RED Unit will not start in AUTO with
utility loss.
RED Unit will not start in AUTO with
utility loss.
utility loss.
RED Unit will not start in AUTO with
utility loss.
RED Unit will not start in AUTO with
utility loss.
utility loss.
RED Unit will not start in AUTO with
utility loss.
utility loss.
Thin g s to
Check
Check Gener­ator Discon­nect circuit breaker.
LEDs/Screen for alarms.
LEDs/Screen for alarms.
Check the LEDs/Screen for alarms.
See if screen says unit not activated.
Check screen for start delay countdown.
Check the LEDs/Screen for alarms.
Check the LEDs/Screen for alarms.
Check the LEDs/Screen for alarms.
Check the LEDs/Screen for alarms.
Check the LEDs/Screen for alarms.
Check the LEDs/Screen for alarms.
Check the LEDs/Screen for alarms.
Check the LEDs/Screen for alarms.
Solutio n
Contact servicing dealer if Generator Disconnect circuit breaker is in the ON position.
Check ventilation around the intake, exhaust and rear of generator. Contact serving dealer if no obstruction is found.
Clear alarm and remove household loads from the generator. Put back in AUTO and restart.
Clear alarm and remove household loads from the generator. Put back in AUTO and restart. If problem returns, contact servicing dealer to investigate possible fuel issue.
Refer to activation section in Owner’s Manual.
If the start up delay is greater than expected, contact servicing dealer to adjust from 2 to 1500 seconds.
Check oil level. Add oil per Owner’s Manual. Contact servicing dealer if oil level is correct.
Clear alarm. Navigate to the BATTERY MENU on the control pad LCD. Contact servicing dealer if battery is GOOD. Replace battery If CHECK BATTERY is displayed.
Check fuel line shutoff valve is in the ON position. Clear alarm. Attempt to start the unit in MANUAL. If it does not start or starts and runs rough, contact servic­ing dealer.
Clear alarm and remove household loads from the generator. Set back to AUTO and restart.
Check ATO 7.5 Amp fuse. Replace with same type fuse if bad. Contact servicing dealer if fuse is good.
Contact servicing dealer.
Contact servicing dealer.
Contact servicing dealer.
36 Synergy Automatic Standby Generator Owner’s Manual
Page 43
Table 5-2. Generator Diagnostics (Continued)
Troubleshooting
Ac ti ve A lar m LED Problem
STEPPER OVERCUR­RENT
MISWIRE RED Unit will not start in AUTO with
OVERVOLTAGE RED Unit will not start in AUTO with
LOW BATTERY YELLOW Yellow LED illuminated in any
BATTERY PROBLEM
CHARGER WARNING
SERVICE A YELLOW Yellow LED illuminated in any
SERVICE B YELLOW Yellow LED illuminated in any
Inspect Battery YELLOW Yellow LED illuminated in any
RED Unit will not start in AUTO with
utility loss.
utility loss.
utility loss.
state.
YELLOW Yellow LED illuminated in any
state.
YELLOW Yellow LED illuminated in any
state.
state.
state.
state.
Thin g s to
Check
Check the LEDs/Screen for alarms.
Check the LEDs/Screen for alarms.
Check the LEDs/Screen for alarms.
Check screen for additional information.
Check screen for additional information.
Check screen for additional information.
Check screen for additional information.
Check screen for additional information.
Check screen for additional information.
Sol u t ion
Contact servicing dealer.
Contact servicing dealer.
Contact servicing dealer.
Clear alarm. Navigate to the BATTERY MENU on the control pad LCD. Contact servicing dealer if battery is GOOD. Replace battery If CHECK BATTERY is displayed.
Contact servicing dealer.
Contact servicing dealer
Perform SCHEDULE A maintenance. Press ENTER to clear.
Perform SCHEDULE B maintenance. Press ENTER to clear.
Inspect battery. Press ENTER to clear.
Synergy Automatic Standby Generator Owner’s Manual 37
Page 44
Troubleshooting
5.3 — Synergy Troubleshooting
Table 5-3. Synergy Diagnostics
Ecode/Activ e
Alarm
1048 VSCF Overload RED Unit shuts down
1049 VSCF Overload RED Unit shuts down
1051 VSCF High Battery
1052 VSCF DC Overvoltage
1053 VSCF Gate Fault
1054 VSCF IGBT Overtemp.
1055 VSCF Phase Error
1056 VSCF Undervoltage
LED Problem
during operation.
during operation.
YELLOW Yellow LED illumi-
nated in any state.
RED Unit shuts down
during operation.
RED Unit shuts down
during operation or starting.
RED Unit shuts down
during operation or starting.
RED Unit shuts down
during starting.
RED Unit shuts down
during operation or starting.
Thing s to
Check
Check the LEDs/Screen for alarms.
Check the LEDs/Screen for alarms.
Check the LEDs/Screen for alarms.
Check the LEDs/Screen for alarms.
Check the LEDs/Screen for alarms.
Check the LEDs/Screen for alarms.
Check the LEDs/Screen for alarms.
Check the LEDs/Screen for alarms.
Pos s i ble Caus es/Sol u tion
Alternator, AVR or wiring is damaged. Contact servicing dealer.
Generator output is shorted or severely overloaded. Iden­tify and clear the overload, and then restart.
Voltage supply to the AVR is high. If an external battery charger is in use, contact installing dealer to correct instal­lation. If an external battery charger is NOT in use, contact servicing dealer.
Probable causes are:
1) The generator was temporarily overloaded.
2) The output was temporarily shorted. Try to restart the unit.
AVR is damaged. Contact servicing dealer.
Probable causes are:
1) Replace AVR filter. Inspect fan.
2) Intake or exhaust air path is blocked. Check intake and exhaust.
3) The BIG fan is not running (only runs when the engine is running). KEEP FINGERS AWAY FROM FAN HOUS­ING- PERSONAL INJURY CAN OCCUR IF FAN IS RUN­NING. Contact servicing dealer.
4) Air leak in AVR enclosure. Contact servicing dealer.
5) Engine running too hot. Inspect air intake and exhaust.
6) Ambient temperature has risen above 60º F. Derate the generator output per specifications.
An incorrect voltage and frequency has been detected during starting. Probable causes are:
1) Alternator damage. Contact servicing dealer.
2) Generator has started into a severe load. Manually operate transfer switch back to utility position and try to restart unit. If problem persists, remove load and attempt to restart unit again.
3) The engine may not be reaching its prescribed speed. Proceed as follows:
Verify stepper motor is moving and linkage is free.
Verify stepper motor is plugged in.
Verify gas pressure is within specified limits.
The generator output voltage is too low. Probable causes are:
1) The load is too large. Remove load and attempt to restart unit.
2) Alternator or AVR damage. Contact servicing dealer.
38 Synergy Automatic Standby Generator Owner’s Manual
Page 45
Table 5-3. Synergy Diagnostics (Continued)
Troubleshooting
Ecod e/Active
Alar m
1057 VSCF Overvoltage
1058 VSCF DC Undervoltage
1059 VSCF Field Loss
1061 VSCF Field Loss
1060 Big Fan Failure RED Unit shuts down
1065 Overfrequency RED Unit shuts down
1066 VSCF Speed mismatch
1070 Small fan failure
LED Problem
RED Unit shuts down
during operation or starting.
RED Unit shuts down
during operation or starting.
RED Unit shuts down
during starting.
RED Unit shuts down
during operation.
during operation.
during operation.
RED Unit shuts down
during Operation or starting.
YELLOW “Small fan failure”
is displayed. If
unit was running
in AUTO and utility returns, it will continue to
run for one hour to
cool electronics
without fan.
Thing s to
Check
Check the LEDs/Screen for alarms.
Check the LEDs/Screen for alarms.
Check the LEDs/Screen for alarms.
Check the LEDs/Screen for alarms.
Check the LEDs/Screen for alarms.
Check the LEDs/Screen for alarms.
Check the LEDs/Screen for alarms.
Check the LEDs/Screen for alarms.
Pos s i ble Caus es/Sol u tion
Probable causes are:
1) The generator has been overloaded. Remove load and attempt to restart unit.
2) Generator has started into a severe load. Manually operate transfer switch back to utility position and try to restart unit. If problem persists, remove load and attempt to restart unit again.
The DPE winding supplies this voltage.
1) Alternator damage. Contact servicing dealer.
Unit detects no output voltage while starting.
1) Alternator damage. Contact servicing dealer.
Unit detects loss of output voltage while running.
1) Alternator damage. Contact servicing dealer.
This alarm occurs when the AVR electronics temperature exceeds 70 C. Possible causes are:
1) AVR filter faulty. Replace AVR filter.
2) Intake or exhaust air path is blocked. Check intake and exhaust.
3) The BIG fan is not running (only runs when the engine is running). KEEP FINGERS AWAY FROM FAN HOUS­ING- PERSONA L INJURY CA N OCCUR IF FAN IS RUN­NING. Contact servicing dealer.
4) Air leak in AVR enclosure. Contact servicing dealer.
5) Engine running too hot. Inspect air intake and exhaust.
6) Ambient temperature has risen above 60º F. Derate the generator output per specifications.
If message is displayed when generator is stopped, also check SMALL fan. Small fan RUNS for 60 minutes after generator is stopped and keeps electronics cool during heat soak.
Probable causes are:
1) Overload. Remove load and attempt to restart unit.
2) RPM sensor has failed. Contact servicing dealer.
3) Stepper motor problem. Contact servicing dealer.
1) Fuel problem (pressure loss). Check fuel supply and attempt to restart unit.
2) A large load is not wired through the Loadshed module. Contact installing dealer to correct installation.
3) Large overload. Remove load and attempt to restart unit.
4) Throttle or engine problem. Contact servicing dealer.
Small fan current incorrect. Probable causes are:
1) Fan wiring or mechanical problem. Contact servicing dealer.
2) Air path is blocked. Check AVR filter.
KEEP FINGERS AWAY FROM FAN HOUSING- PER­SONAL INJ URY CA N OCCUR IF FAN IS RUNNING.
Synergy Automatic Standby Generator Owner’s Manual 39
Page 46
Troubleshooting
5.4 — Load Shed Troubleshooting
Table 5-4. Load Shed Diagnostics
Sympto m Pos s ib le Cau ses
Generator stalls when large load is supplied.
Large loads keep getting shed and locked out (load LED goes out for 30 minutes).
Output voltage is low/high. Voltage calibration incorrect. Contact servicing dealer.
Generator does not pull full power. Current calibration incorrect. Contact servicing dealer.
1) Total load is too big for the generator and fuel type. Contact installing dealer to correct installation.
2) A large load is not wired through the Loadshed module. Contact installing dealer to correct installation.
Total load is too big for generator. Contact installing dealer to correct installa­tion.
40 Synergy Automatic Standby Generator Owner’s Manual
Page 47
Page 48
Part No. 0K2502 Rev. C 01/20/2015 Printed in USA © Generac Power Systems, Inc. All rights reserved Specifications are subject to change without notice. No reproduction allowed in any form without prior written consent from Generac Power Systems, Inc.
Generac Power Systems, Inc.
S45 W29290 Hwy. 59 Waukesha, WI 53189
1-888-GENERAC (1-888-436-3722)
generac.com
Loading...