Generac 9600-3 User Manual

0 (0)

Part No. 98772

OWNER’S

Manual

Series NP-66G

AIR-COOLED

RECREATIONAL VEHICLE

GENERATOR

Model No. 9600-3

C O R P O R A T I O N

Revision 0 (3/7/96)

Printed in U.S.A.

GENERAL SAFETY RULES

THE MANUFACTURER SUGGESTS THAT THESE “RULES” FOR SAFE OPERATION BE COPIED AND POSTED IN POTENTIAL HAZARD AREAS OF THE INDUSTRIAL VEHICLE. SAFETY SHOULD BE STRESSED TO ALL OPERATORS AND POTENTIAL OPERATORS OF THIS EQUIPMENT.

Study these SAFETY RULES carefully before operating or servicing applicable equipment. Become familiar with this Owner's Manual ana with your generator. Safe, efficient and reliable operation can only be achieved if enerator is properly installed, operated and main­ lined. Many accidents are caused by failing to follow simple and fundamental rules or precautions. The manufacturer suggests that these GENERAL SAFETY RULES be copied and posted in potential hazard areas of the industnal vehicle. Safety should be stressed to

all operators and potential operators of equipment.

The manufacturer cannot possibly anticipate every pos­ sible circumstance that might involve a hazaro. The warnings in this Manual ancfon tags and decals affixed to the unit are, therefore, not all-inclusive. If you use a procedure, work method or operating technique Generac does not specifically recommend, you must satisfy yourself that it is safe for you and others. You must also make sure the procedure, work method or operating technique that you chose does not render the generator to be unsafe.

• For fire safety, the industrial mobile generator must be properly installed and maintained. Installation must always remain in compliance with applicable codes ana standards. In addition, the generator must be installed in conformance to the manufac­ turer’s detailed installation instructions. Following installation, nothing must be done that might render the generator in noncompliance with such codes, standards and instructions.

• The RV generator produces extremely high and dangerous electrical voltages and can cause dan­ gerous, and possibly fatal, electrical shock. Avoid contact with bare wires, terminals, etc. while the unit is running. If you must work around an operat­ ing generator, stand on an insulated, dry surface to reduce shock hazard.

Never work on this equipment or handle any elec­ trical device while standing in water, while barefoot, or while hands or feet are wet. Dangerous electri­ cal shock will result.

Have the generator properly grounded (bonded) during installation onto the vehicle, either by solid

mounting to the vehicle frame or chassis or by means of an approved bonding conductor. DO NOT disconnect the bonding conductor, if so

equipped. DO NOT reconnect t^e bonding conduc­ tor to any generator part that might be removed or disassembled during routine maintenance. If the grounding conductor must be replaced, use only a flexible conductor that is of No. 8 AWG copper wire minimum.

Inspect the generator periodically. Repair or replace all damaged or defective parts immediately.

In case of accident caused by electric shock, shut down the source of electrical power down at once. If this cannot be done, free victim from live conduc­ tor. AVOID DIRECT CONTACT WITH THE VIC­ TIM. Use a dry board, dry rope, or other non-con­

ducting implement to free the victim from live con­ ductor. If victim is unconscious, apply CPR (cardio­ pulmonary resuscitation) and get m^ical help.

Inspect fuel system frequently for leaks or damage. Repair or replace any damaged or leaking compo­ nent immediately. Never attempt to change, alter or modi^ the generator fuel system in any way that might affect safety or compliance with applicable codes and standards.

The generator engine gives off DEADLY carbon monoxide gas through its exhaust system. This dangerous gas, if breathed in sufficient concentra­ tions, can cause unconsciousness or even death. This exhaust system must have been properly in­ stalled, in strict compliance with applicable codes and standards. Following installation, you must do nothing that might render the system unsafe or in non-compliance with such codes and standards. The generator compartment must be completely vapor sealed from vehicle interior. There must be no possibility of exhaust fumes entering the vehicle interior. Never operate this equipment with a leak­ ing or defective exhaust system.

Never use the generator or any of its parts as a step. Stepping on the unit can stress and break parts and may result in dangerous operating conditions from leaking exhaust gases, fuel leakage, oil leakage, coolant leakage, etc.

Do not smoke around the generator. Wipe up any fuel, oil and coolant spills immediately. Never leave oily or fuel soaked rags in the generator compart­ ment or on the generator itself. Keep the area around the generator clean and free of debris.

Adequate ventilation is required to expel toxic fumes and gasoline vapors from the generator com­ partment. Do not alter the installation of this equip­ ment in any manner that might obstruct air and ventilation openings. Such openings must be kept clear and unobstructed.

Keep hands, feet, clothing, etc., away from drive belts, fans and other moving parts of this equip­ ment. Never remove any drive belt or fan guards while the unit is operating.

Some generators may use LP gas propane) as a fuel. LP gas is highly EXPLOSIVE. The gas is heavier than air and tends to settle in low areas where even the slightest spark can ignite the gas and cause an explosion.

Before performing any maintenance on the gener­ ator set, disconnect its battery cables to prevent accidental start up. Disconnect the cable from the battery post indicated by a NEGATIVE, NEG or (-) first. Reconnect that cable last.

WARNING:

The engine exhaust from this product contains chemicals known to the State of California to cause cancer, birth defects, or other reproductive harm.

Generac 9600-3 User Manual

 

 

IDENTIFICATION RECORD

Please record the following infonnation, from the generator DATA PLATE or infoimation decal:

1, Model Number__________________

2. Serial Number_________________________

3. kW Rating.

4.

Rated Voltage.

5. Phase_____

6.

Hertz________

 

 

 

N

»ODa.[

 

1 VOLISI J

 

sERxes[

 

1 AWSI 1

 

SERIAL f

1 WATTS 1 1

 

PHASE-l HERTZ-60 RPH-VARIABLE

CLASS F INSULATION AT 40*C CtMTlNUOUS OUTY

FOR SERVICE CENTER LOCATIONS

CALL 800-333-1322 24 HOURS A DAY

 

GENERAC CORPORATION

 

 

VAUKCSHA. VIS

 

 

MAOe IN U.S.A.

 

<

U.S. AND FOREKM PATENTS PENDING

4

 

I -

TABLE OF CONTENTS

GENERAL SAFETY RULES......................

inside cover

IDENTIRCATiON RECORD........................................

1

READ THIS MANUAL THOROUGHLY......................

3

Operation and Maintenance...........................................

3

How to Obtain Service...................................................

3

GENERATOR FEATURES..........................................

4

GENERATOR FAMIUARIZATION

 

Generator Applicabiiity...................................................

5

Installation......................................................................

5

Safety 5

 

Generator AC Connection System.................................

5

OPERATING INSTRUCTIONS

 

Generator Control Panel................................................

6

Automatic Choke............................................................

6

Before Starting the Engine.............................................

6

Starting...........................................................................

7

Stopping the Generator..................................................

7

Applying Loads to Generator.........................................

7

Operation in High Grass or Brush..................................

7

Don’t Overload the Generator........................................

8

Wattage Reference Guide.............................................

8

ENGINE PROTECTIVE DEVICES

 

Automatic Low Oil Pressure Shutdown..........................

9

High Temperature Shutdown.........................................

9

Overspeed......................................................................

9

Low Voltage...................................................................

9

SPECIHCATIONS

 

Fuel Requirements........................................................

10

Engine Oil Requirements..............................................

10

Generator Specifications...............................................

10

Engine Specifications...................................................

10

MAINTENANCE

 

Checking Engine Oil Level...........................................

11

Change Engine Oil.......................................................

11

Change Oil Filter...........................................................

11

Engine Air Cleaner........................................................

12

Spark Arrestor Muffler...................................................

12

Engine Spark Plugs......................................................

12

Fuel Filter......................................................................

12

MISCELLANEOUS MAINTENANCE

 

Cleaning the Generator.................................................

13

Battery 13

 

Service and Adjustments..............................................

13

Throttle Linkage Adjustment.........................................

13

Adjusting the Carburetor...............................................

14

Major Service Manual...................................................

14

Exercising the Generator..............................................

15

Out of Service Protection..............................................

15

Return the Unit to Service after Storage.......................

15

TROUBLESHOOTING.....................................................

16

ELECTRICAL DATA........................................................

17

REPAIR PARTS....................................................

18 to 25

WARRANTY......................................................

back page

-2-

READ THIS MANUAL THOROUGHLY

If you don’t understand any portion of this manual, contact Generac for a demonstration of actual starting, operating and servicing procedures.

Throughout

this

publication and on tags and decals

affixed to

the

generator, DANGER and CAUTION

blocks are used to alert you to special instructions about a particular operation that may be hazardous if per­ formed irKXjrrectly or carelessly. Observe them care­ fully.

These safety warnings cannot eliminate the hazards that they indicate. Strict compliance with the special instructions while performing the service plus “comnrton sense” are major measures to prevent accidents.

The following definitions apply to DANGER, CAUTION and NOTE blocks found throughout the manual.

DANGER: AFTER THIS HEADING YOU CAN A READ HANDLING, INSTALLING, OPERAT­ ING OR SERVICING INSTRUCTIONS THAT, IF NOT STRICTLY COMPLIED WITH, MAY RESULT IN PERSONAL INJURY.

CAUTION:

After this

heading you can read Instruc­

tions for

handling.

Installing, operating or

servicing

the generator that. If not strictly complied

with, may

result in damage to equipment and/or property.

 

NOTE: After this heading you can read explanatory statements that require special emphasis.

These symbols indicate the following:

A Points out important safety information and, if not followed, could endanger personal safety and/or property of yourself and others.

Potential explosion hazard

A Potential fire hazard

Potential electrical shock hazard

The operator (driver) is responsible for proper and safe use of the vehicle, equipment on the vehicle, and the safety of all vehicle occupants. We strongly recom­ mend that the operator read this Owner’s Manual and thoroughly understand all instructions before using this equipment. We also strongly recommend instructing other occupants in the vehicle to properly start and operate the generator. This prepares them if they need to operate the equipment in an emergency.

OPERATION AND MAINTENANCE

It is the operator’s responsibility to perform all safety checks; to make sure that all maintenance for safe operation is performed promptly; and to have the equip­ ment checked by an Authorized Dealer periodically. Normal maintenance service and replacement of parts are the responsibility of the. Owner/Operator and, as such, are not considered defects in materials or work­ manship within the terms of the warranty. Individual operating habits and usage contribute to the need for maintenance service.

Proper maintenance and care of your industrial mobile generator assures a minimum number of problems and keeps your operating expenses at a minimum. See your authorized Dealer/Distributor for service aids and accessories.

HOW TO OBTAIN SERVICE

When your industrial mobile generator set requires servicing or repairs, simply contact an Authorized Serv­ ice Station for assistance. Service technicians are fac­ tory-trained and are capable of handling all of your service needs.

When contacting an Authorized Service Facility or the factory about parts and service, always supply the com­ plete model number and serial number of your unit as given on its data plate.

The warranty on your generator is included in this Owner's Manual, as well as listings for repair parts.

- 3

GENERATOR FEATURES

REFERENCE NUMBER IDENTIFICATION

1.

Generator Air Intake Screen

8.

Starter Contactor

2.

Engine Start/Stop Switch

9.

Fuel Inlet

3.

15 amp Fuse

10.

Fuel Pump Primer Switch

4.

30 amp Circuit Breaker

1 1 .

Fuel Pump

5.

Optional Remote Panel Receptacle

12.

Oil Filter

6.

Generator AC Output Leads

13.

Oil Drain Plug

7.

30 amp Circuit Breaker

14.

Oil Dipstick and Filler Tube

■ 4 -

GENERATOR FAMILIARIZATION

GENERATOR APPLICABILITY

The NP-66G generator has been designed and manu­ factured for supplying electrical power for recreational vehicles. You should not modify the generator or use it for any application other than for what it was designed. If there are any questions pertaining to its application, write or call the factory. Do not use the unit until you have been advised by competent authority.

DANGER: FOR RRE SAFETY, THE GENER A ATOR MUST HAVE BEEN PROPERLY IN STALLED IN COMPUANCE WITH (1) ANS1119^ 1975/NFPA 5010-1974 “STANDARD FOR REC REATIONAL VEHICLES”, PART III, “INSTALLA TION OF ELECTRICAL SYSTEMS.” THE GENER ATOR ALSO MUST HAVE BEEN INSTALLED IN STRICT COMPLIANCE WITH THE MANUFAC­ TURER’S DETAILED INSTALLATION INSTRUC­ TIONS. AFTER INSTALLATION, DO NOTHING THAT MIGHT RENDER THE UNIT IN NON-COM­ PLIANCE WITH SUCH CODES, STANDARDS AND INSTRUCTIONS.

You can use your generator set to supply electrical power for operating 120 and/or 240 volts, single phase, 60 Hz electrical loads. These loads can require up to 6600 watts (6.6 kW) of power, but cannot exceed 55 AC amperes of current at 120 volts or exceed 27.5 AC amperes at 240 volts.

CAUTION: Do not overload the generator. Some installations may require that eiectrical ioads be aiternated to avoid overloading. Appiying exces­ sively high electrical loads may damage the gener­ ator and may shorten Its life. Add up the rated watts of all electrical lighting, appliance, tool and motor loads the generator will power at one time. This total should not be greater than the wattage capac­ ity of the generator. If an electrical device nameplate gives only volts and amps, multiply volts times amps to obtain watts (volts x amps = watts). Some electric motors require more watts of power (or amps of current) for starting than for continuous operation.

Owners/Operators have the responsibility to make sure that nothing is done that might render the installation unsafe or in non-compliance with applicable codes, standards and instructions.

SAFETY

Before using the generator set, carefully read GEN­ ERAL SAFETY RULES inside the cover. Comply with these RULES to prevent accidents and damage to equipment and/or property. Generac suggests copying and posting the GENERAL SAFETY RULES to potential operators of this equipment.

GENERATOR AC CONNECTION SYSTEM

These

air-cooled

NP Series

generator sets

are

equipped

with dual

stator AC

power windings.

These

two stator windings supply electrical power to customer electrical loads by means of a dual 2-wire connection system.

The generator may have been installed so that units only power 120 volts AC loads (Figure 1); or you can wire them to connect both 120 and/or 240 volts AC electrical loads. Be sure to remove the jumper between the circuit breakers when connecting for 120/240 volts.

GROUNDED

NEUTRAL

INSTALLATION

This Owner’s Manual has been prepared under the

Figure 1 Connection for 120 Volts Only

assumption that a competent, qualified technician

in­

stalled the generator into an industrial vehicle. We also

 

assume the installer complied with all applicable codes,

 

standards and regulations pertaining to installation.

 

 

An INSTALLATION MANUAL was shipped with the

 

generator. That Manual contains manufacturer’s

in­

 

structions and recommendations for installing the

unit

 

into an industrial vehicle. After installation, installers should forward the Installation Manual to Owners/Operators for their information.

-5-

OPERATING INSTRUCTIONS

GENERATOR CONTROL PANEL

Mounted on the generator control panel (Figure 2) are the following features:

Fuel Pump Primer: Before starting a cold engine

 

(it has not been started in more than two weeks),

 

you must press this switch to bring fuel from the tank

 

to the fuel pump. This rocker t^e switch

springs

 

back into its original position when you release it.

StarVStop Switch: To crank and start the engine,

 

hold this switch at its START position. Release the

 

switch when the engine starts. To stop an operating

 

engine, place the switch in its STOP position. The

 

switch center position is the RUN position.

 

15 amp Fuse: Protects the engine DC control

 

circuit against electrical overload. If the fuse ele­

 

ment has melted open due to overloading, the en­

 

gine cannot be cranked. If you must replace it, use

 

only an identical IS.amp replacement njse.

 

«

Line Breakers; Protects generator’s AC

output

 

circuit against overload, i.e., prevents unit from

 

exceeding wattage/amperage capacity.

NP-66G

 

has one 20-amp and one 30-amp breaker.

 

NOTE: If the SeriesQ-66G has been reconnected for dual voltage AC output (120/240 volts), you can install line breakers having an amperage rating that is different than stated above. The replacement line breakers con­ sist of two separate breakers with a connecting piece between the breaker handles (so that both breakers will operate at the same time). If the unit is reconnected for dual voltage, it is no longer RVIA listed.

Figure 2 Typical Control Panel

OPTIONAL REMOTE START/STOP PANEL

Optional remote mounted panels are available which permit you to crank and start the generator from any convenient location in the recreational vehicle. Figure 3 shows the Model 9042 remote panel which includes (a) start/stop switch and (b) a generator run lamp.

You can also order Model 9043, a remote panel which includes the (a) start/stop switch, (b) the generator run lamp and (c) an hourmeter. The hourmeter provides a continuous indication of engine-generator operating time. Use the hourmeter for checking off periodic main­ tenance requirements on the unit.

Figure 1 — Optional Remote Panel (Model 9042)

AUTOMATIC CHOKE

The engine is equipped with an automatic choke that consists of two main components—choke solenoid and prechoke.

Choke Solenoid: During engine cranking (start/stop

switch at START), a solid

state choke

module

signals

the choke

solenoid to

actuate

and

cycle

(choke

on/choke off)

until engine

starts.

The

choke

solenoid

thus opens and closes the carburetor choke valve only when the engine is cranking. When the engine starts, the choke cycling stops.

Prechoke: The choke system also has a temperature sensitive metal strip that adjusts the choke valve angle according to ambient temperatures (i.e. in cold ambient temperatures the choke valve closes more). Once the engine starts, an element heats the temperature-sensi­ tive strip to a normal operating condition, opening the choke valve. This may take about 3 minutes in cooler weather.

BEFORE STARTING THE ENGINE

IMPORTANT: INSTRUCTIONS AND

INFORMATION

IN THIS MANUAL ASSUME THE GENERATOR HAS

BEEN PROPERLY INSTALLED,

CONNECTED,

SERVICED, TESTED AND ADJUSTED BY A QUALI­ FIED INSTALLATION TECHNICIAN OR INSTALLA­ TION CONTRACTOR.

• Installation: Generator installation must have been properly completed so it complies with all applicable codes, standards and regulations and with the manufacturer’s recommendations.

• Engine Lubrication:

Have engine crankcase

properly serviced with

recommended oil before

starting. Refer to “Maintenance" and “Specifica­ tions" sections for oil servicing procedures and rec­ ommendations.

CAUTION: Any attempt to crank or start the engine before you have properly serviced it with the recom­ mended oil will result in an engine failure.

- 6 -

TTietoig^ must have adequstia supply of proper fuel to Operate. Before starting, check that sunicientfuel is available.

NOTE: On some installations, the generator

en­

gine may "share” the vehicle’s gasoline fuel

tank

with vehicle engine. Sonte installations may

pro­

vide separate fuel tanks for generator and vehicle engine.

Cooling and Ventilating Air: Air inlet and Outlet openings in the generator compartment must be c^n and unobstructed for continued proper opera­ tion. Without sufficient cooling and ventilating air flow, the engine-oenerator quickly overheats which causes it to quickly shutdown. Overheating could also damage the unit or your vehicle.

Engine Exhaust Gases: Before starting the gen­ erator engine, you should be sure there is no way for exhaust gases to enter the vehicle interior and endangering people or animals. Close windows, doors and other openings in the vehicle that, if open, might permit exhaust gases to enter the vehicle.

DANGER: THE GENERATOR ENGINE A GIVES OFF DEADLY CARBON MONOXIDE GAS THROUGH ITS EXHAUST SYSTEM. THIS DANGEROUS GAS, IF BREATHED IN SUFFI­ CIENT CONCENTRATIONS, CAN CAUSE UN­ CONSCIOUSNESS OR EVEN DEATH. DO NOT OPERATE THE GENERATOR IF ITS EXHAUST SYSTEM IS LEAKING OR HAS BEEN DAMAGED. SYMPTOMS OF CARBON MONOXIDE POISON­ ING ARE (A) INABILITY TO THINK COHERENTLY,

(B) VOMITTING, (C) TWITCHING MUSCLES, (D) THROBBING TEMPLES, (E) DIZZINESS, (F) HEADACHE, (G) WEAKNESS AND SLEEPINESS. IF YOU FEEL ANY OF THESE SYMPTOMS, MOVE INTO FRESH AIR IMMEDIATELY. IF SYMPTOMS PERSIST, GET MEDICAL HELP. _________________

STARTING

IMPORTANT: Read the vehicle manufacturer’s instruc­ tions. The owner/operator should become familiar with the vehicle in which this generator is installed. Differ­ ences exist between vehicles. For example, some ve­ hicles may use a transfer switch to isolate dockside power from the generator, while other vehicles may use an isolating receptacle. Some vehicles may be equipped with a DC converter which allows the gener­ ator to power certain DC lighting and other DC loads.

To crank and start the generator engine, proceed as follows:

1. Turn OFF electrical loads, using whatever means provided in your vehicle (such as a main line circuit breaker or transfer switch.

NOTE: If you start the engine with start/stop switch on the generator control panel, turn OFF loads by setting the panel’s main breakers to their “OFF” or “OPEN” positions. Electrical load circuits will be turned ON after the generator has started, stabilized and warmed up.

Z If you have rrotslarted the engine in more than twct weeks, presstheFuel Pump PriniierswitchandhokK^ it for about 30 seconds to activate the automatic shut-off function. However, if the engine Is warm, skip Step 2.

3. To crank and start the engine, hold the start/stop switch at START. Release the switch whertthe.^ engine starts.

CAUTION: If the engine does not start after It has been cranking for 15 seconds, release the start/stop switch and try again. Holding the switch for longer than 15 seconds can damage the starter motor.

4.Let the engine run at no-load for a few minutes to stabilize and warm up the engine.

5.Turn ON electrical loads, using whatever meem provided (such as a main circuit breaker or transfer switch).

NOTE: If you start a warm generator engine, yoirmay only press the start switch slightly to engage thaignitioR system. However, you should press and hold the starter switch for a minimum of two seconds to energize the field boost system. If you start the engine without energizing the field boost system, the generator pro­ duces no AC output.

STOPPING THE GENERATOR

1. Turn OFF all electrical loads, using whatever means provided (such a main circuit breaker or transfer switch).

2.

Let

the

generator run

at no-load for a few minutes,

 

to

stabilize

internal

engine-generator tempera­

 

tures.

 

 

 

3.

Press

STOP

on the

start/stop switch. The engine

 

will come to complete stop.

APPLYING LOADS TO GENERATOR

When applying electrical loads to the generator, ob­ serve these guidelines:

Before applying electrical loads, let the generator stabilize and warm up for a minute or two.

DO NOT overload the generator.

Letting Engine Stabilize: The generator supplies cor­ rect rated frequency and voltage only at the proper governed speed, ^me electrical appliances may be extremely sensitive to voltage and frequency. Incorrect frequencies and/or voltages can damage those appli­ ances.

If electrical loads are applied at reduced operating speeds, such loads imposed on the engine when suffi­

cient

power

is

not available may shorten engine life.

Never

turn

ON

electrical loads until after the generator

engine has started and stabilized ON-speed.

- 7-

Do Not Overload the Generator: You can read the rated wattage/amperage capacity of your generator on the generator data plate (see “Identification Record” on Page 1).

Applying electrical loads in excess of the unit’s rated capacity can bum out the unit and any^ing connected to it. Also, overloading trips main circuit breakers.

To avoid overloading, add up the wattage of all con­ nected electrical lighting, appliance, tool and motor loads. This total should not be greater than the gener­ ator’s rated wattage capacity.

• Most lighting, appliance, tool and motor loads indi­ cate their required watts on their nameplate or data plate. For light bulbs, simply note the wattage rating of the bulb.

If a load does not show its rated wattage, multiply that load’s rated VOLTS times AMPS to obtain WATTS.

Induction type motors (such as those that run the

vehicle’s furnace

fan,

refrigerator,

air

conditioner,

etc.)

need

about

2^^¡2 times more watts of power

for

starting

than

for

running (for

a

few seconds

during motor starting). I Be sure to allow for this when connecting electrical loads to the generator. First, figure the watts needed to start electric motors in the system. To that figure, add the running wattages of other items that will be operated by the generator.

Do not apply heavy electrical loads for the first two or three nours of operation.

WATTAGE REFERENCE GUIDE

 

RUNNING

 

WATTS

‘Air Conditioner (12,000 Btu).......................................

1700

Battery Charger (20 amp).............................................

500

Belt Sander (3")...........................................................

1000

Chain Saw...................................................................

1200

Circular Saw (6-12/").........................................

800 to 1000

Coffee Maker...............................................................

1000

‘Compressor (1 HP).....................................................

2000

‘Compressor (3/4 HP)..................................................

1800

‘Compressor (1/2 HP)..................................................

1400

Curling Iron....................................................................

700

‘Deep Freeze.................................................................

500

Disc Sander (9“)...........................................................

1200

Edge Trimmer................................................................

500

Electric Nail Gun..........................................................

1200

Electric Range (one element)......................................

1500

Electric Skillet..............................................................

1250

‘Furnace Fan (1/3 HP).................................................

1200

Hair Dryer....................................................................

1200

Hand Drill (Г)................................................................

1100

Hand Drill (1/2")...............................................

750 to 1000

Hand Drill (3/8“).............................................................

500

Hand Drill (1/4”).............................................................

250

Hedge T rimmer.............................................................

450

Impact Wrench...............................................................

500

‘Jet Pump.......................................................................

800

 

 

RUNNING

 

 

WATTS

Lawn Mower..........................

.......................................

1200

Light Bulb..............................

:.......................................

100

Microwave Oven............................................................

 

700

‘Milk Cooler...........................

;.......................................

1100

Oil Burner on Furnace...........

........................................

300

Oil Fired Space Heater (140,000 Btu)............................

400

Oil Fired Space Heater (85,000 Btu)..............................

225

Oil Rred Space Heater (30,000 Btu)..............................

150

‘Paint Sprayer, Airless (1/3 HP).....................................

600

Paint Sprayer, Airless (handheld)..................................

150

Radio..................................................................

 

50 to 200

‘Refrigerator...........................

'.......................................

600

Slow Cooker...................................................................

 

200

‘Submersible Pump (1-1/2 HP)....................................

2800

‘Submersible Pump (1 HP)..........................................

 

2000

‘Submersible Pump (1/2 HP)........................................

 

1500

Sump Pump...................................................................

 

600

‘Table Saw (10”)...................

........................

1750 to 2000

Television...........................................................

 

200 to 500

Weed Trimmer...............................................................

 

500

‘ Allow 2-1/2 times the listed watts for starting these devices^

- 8 -

Loading...
+ 22 hidden pages