GE SG 10, SG 40, SG 30, SG 20 User Manual

4.5 (2)

g

GE

SGT5000_030-040_UPS_GE_01

SG Series 10, 20, 30 and 40 kVA

OPERATING MANUAL

UNINTERRUPTIBLE POWER SUPPLY

Digital Energy TM

SG Series

10 – 20 – 30 – 40 kVA Series 0

g

2500 Discovery Blvd.

Telephone:

(972)-290-7400

General Electric Company

Rockwall, TX 75032

Fax:

(972)-290-7500

 

 

 

SG Series UPS

Technology for the digital world

 

 

 

 

 

g

GE

Model:

SG Series 10, 20, 30 and 40 kVA / Series 0

Date of issue:

04/15/2003

File name:

OPM_SGS_USM_10K_40K_0US_V010

Revision:

1.0

Author:

Raimondo Bizzozero

Identification No.:

 

Up-dating

 

 

Revision

Concern

Date

COPYRIGHT © 2003 by GE

All rights reserved.

The information contained in this publication is intended solely for the purposes indicated.

The present publication and any other documentation supplied with the UPS system is not to be reproduced, either in part or in its entirety, without the prior written consent of GE.

The illustrations and plans describing the equipment are intended as general reference only and are not necessarily complete in every detail.

The content of this publication may be subject to modification without prior notice.

OPM_SGS_USM_10K_40K_0US_V010.doc

2/88

Operating Manual SG Series 10, 20, 30 & 40 kVA

g

GE

Dear Customer,

We thank you for selecting our products and are pleased to count you amongst our very valued customers at GE.

We trust that the use of the SG Series Uninterruptible Power Supply system, developed and produced to the highest standards of quality, will give you complete satisfaction.

Please carefully read the Installation Guide. It contains all the necessary information about the installation of the UPS.

Thank you for choosing GE !

START UP AND COMMISSIONING

A GE Global Services Field Engineer must perform start-up and commissioning of the UPS. Please Contact G.E. Global Services at least two weeks prior to schedule start-up and commissioning at 1-800-637-1738, or by E-mail at gedeservices@indsys.ge.com

Manufactured by:

Distributed in the USA by:

Your service contact:

g

GE

GE DIGITAL ENERGY SA

6595 Riazzino (Locarno)

Switzerland

OPM_SGS_USM_10K_40K_0US_V010.doc

3/88

Operating Manual SG Series 10, 20, 30 & 40 kVA

g

Preface

GE

Congratulations on your choice of a SG Series Uninterruptible Power Supply (UPS). It will help eliminate Load disturbances due to unexpected power problems.

This Manual describes the function of the UPS module, the purpose and location of the switches, the meaning of the system events related to the front panel indication, and provides procedures for starting and stopping the equipment.

Please refer to the accompanying Installations Guide, which describes how to prepare the installation site, and it provides weight, dimensions and procedures for moving, installing and connecting the UPS.

While every care has been taken to ensure the completeness and accuracy of this manual, GE assumes no responsibility or liability for any losses or damages resulting from the use of the information contained in this document.

WARNING!

SG Series 10, 20, 30 and 40 kVA, is a product that needs to be installed by a licensed and knowledgeable contractor.

We recommend that this manual be kept next to the UPS for future references.

If any problems are encountered with the procedures contained in this manual, please contact your Service Center before you proceed.

This document shall not be copied or reproduced without the permission of GE.

Some of the information contained in this manual may be changed without notice to reflect technical improvements.

Safety instructions

Read the safety instructions contained on the following pages carefully before the installation of the UPS, options and Battery System.

Pay attention to the rectangular boxes included in the text:

They contain important information and warning concerning electrical connections and personnel safety.

Parallel version secured with RPA

When included in the text, this symbol refers to operation needed only for parallel system.

OPM_SGS_USM_10K_40K_0US_V010.doc

4/88

Operating Manual SG Series 10, 20, 30 & 40 kVA

g

Table of contents

GE

Page

1

IMPORTANT SAFETY INSTRUCTIONS .................................................................

7

2

INTRODUCTION.....................................................................................................

10

3

DESCRIPTION........................................................................................................

11

 

3.1

BLOCK DIAGRAM AND MAIN ELEMENTS..................................................................

11

 

3.2

OPERATION MODES ...................................................................................................

12

 

3.2.1

Normal operation mode.................................................................................................

12

 

3.2.2

Utility failure operation...................................................................................................

12

 

3.2.3

Utility recovery operation...............................................................................................

13

 

3.2.4

Automatic Bypass..........................................................................................................

13

 

3.2.5

Manual Bypass..............................................................................................................

13

 

3.3

PARALLEL SYSTEM OPERATION ..............................................................................

14

 

3.3.1

Introduction to the parallel system.................................................................................

14

 

3.3.2

Features of RPA parallel system...................................................................................

15

 

3.3.3

System control...............................................................................................................

15

 

3.3.4

Synchronization.............................................................................................................

15

 

3.3.5

Load sharing..................................................................................................................

15

 

3.4

RECTIFIERS PARALLELED ON THE SAME BATTERY..............................................

16

 

3.5

RECYCLING AT THE END OF SERVICE LIFE............................................................

17

4

LAYOUT .................................................................................................................

18

 

4.1

LAYOUT SG SERIES 10 AND 20 KVA ..............................................................................

18

 

4.2

LAYOUT SG SERIES 30 AND 40 KVA ..............................................................................

19

5

CONTROL PANEL .................................................................................................

20

 

5.1

CONTROL PANEL ........................................................................................................

20

 

5.2

TABLE OF FUNCTIONS AND INDICATIONS ON CONTROL PANEL.........................

20

6

LCD SCREEN.........................................................................................................

22

 

6.1

METERING MODE........................................................................................................

23

 

6.2

ALARMS........................................................................................................................

26

 

6.3

PARAMETERS..............................................................................................................

27

 

6.4

EDIT MODE ..................................................................................................................

29

 

6.5

USER PARAMETERS...................................................................................................

32

 

6.6

EVENTS (ALARMS AND MESSAGES) ........................................................................

35

 

6.6.1

Alarms list......................................................................................................................

35

 

6.6.2

Messages list.................................................................................................................

39

 

6.6.3

Event report SG Series .....................................................................................................

41

7

OPERATION...........................................................................................................

42

 

7.1

PROCEDURES FOR SINGLE UPS..............................................................................

43

 

7.1.1

Start-up of the SG Series ..................................................................................................

43

 

7.1.2

Maintenance shutdown (Load on Q2) ...........................................................................

44

 

7.1.3

From Manual Bypass (Q2) to normal function On-line ..................................................

45

 

7.1.4

Complete UPS shutdown (No Load supply)..................................................................

46

 

7.1.5

Restore to normal operation after “total off”...................................................................

47

 

7.1.6

Restore to normal operation after EPO (Emergency Power Off)...................................

48

OPM_SGS_USM_10K_40K_0US_V010.doc

5/88

Operating Manual SG Series 10, 20, 30 & 40 kVA

g

GE

7.2

PROCEDURES FOR UPS FUNCTIONING AS FREQUENCY CONVERTER

.............49

 

7.2.1

Start-up of the SG Series as frequency converter ............................................................

49

 

7.2.2

Complete UPS shutdown (No Load supply)..................................................................

50

 

7.2.3

Restore to normal operation after “total off”...................................................................

51

 

7.2.4

Restore to normal operation after EPO (Emergency Power Off)...................................

52

7.3

PROCEDURES FOR PARALLEL SYSTEM..................................................................

53

 

7.3.1

Parallel System start-up ................................................................................................

53

 

7.3.2

Maintenance system shutdown (Load supplied from Q2 on all Units)...........................

55

 

7.3.3

From Manual Bypass (Q2) to normal function On-line ..................................................

56

 

7.3.4

Separate a Unit from the parallel system (System Redundancy)..................................

58

 

7.3.5

Reconnect a Unit to a parallel system...........................................................................

59

 

7.3.6

Parallel system shutdown (No Load supply) .................................................................

60

 

7.3.7

Restore to normal operation after “total off”...................................................................

62

 

7.3.8

Restore to normal operation after EPO (Emergency Power Off)...................................

64

7.4

PROCEDURES FOR PARALLEL SYSTEM WITH COMMON BATTERY ....................

66

 

7.4.1

Parallel System start-up ................................................................................................

66

 

7.4.2

Maintenance system shutdown (Load supplied from Q2 on all Units)...........................

68

 

7.4.3

From Manual Bypass (Q2) to normal function On-line ..................................................

69

 

7.4.4

Separate a Unit from the parallel system (System Redundancy)..................................

71

 

7.4.5

Reconnect a Unit to a parallel system...........................................................................

72

 

7.4.6

Parallel system shutdown (No Load supply) .................................................................

73

 

7.4.7

Restore to normal operation after “total off”...................................................................

75

 

7.4.8

Restore to normal operation after EPO (Emergency Power Off)...................................

77

8

CUSTOMER INTERFACE......................................................................................

79

8.1

CUSTOMER INTERFACE ............................................................................................

79

 

8.1.1

Serial Port J3.................................................................................................................

80

 

8.1.2

Output free potential contacts .......................................................................................

80

 

8.1.3

Programmable input free contacts ................................................................................

81

 

8.1.4

Gen Set Signaling (GEN ON)........................................................................................

81

 

8.1.5

AUX external Maintenance Bypass...............................................................................

81

 

8.1.6

Auxiliary Power Supply (APS) 24 VDC / 1A ..................................................................

81

 

8.1.7

EPO (Emergency Power Off) Input contact...................................................................

82

9

OPTIONS ................................................................................................................

83

9.1

BUILT IN UPS OPTIONS ..............................................................................................

83

9.2

COMMUNICATION OPTIONS ......................................................................................

83

9.3

OPTIONS IN UPS CABINET.........................................................................................

83

9.4

CONNECTION FOR OPTIONS.....................................................................................

84

 

9.4.1

Remote Signaling Box (RSB) ........................................................................................

84

10

MAINTENANCE......................................................................................................

85

10.1

MAINTENANCE ............................................................................................................

85

 

10.1.1

Service check ................................................................................................................

85

 

10.1.2

Fans and ventilation ......................................................................................................

85

 

10.1.3

Other components with limited lifetime..........................................................................

85

 

10.1.4

Battery ...........................................................................................................................

85

 

10.1.5

Long shut-down periods of the UPS-system .................................................................

86

 

10.1.6

UPS room conditions and temperature .........................................................................

86

 

10.1.7 Long shut-down periods of the UPS-system .................................................................

86

11

NOTES....................................................................................................................

87

11.1

NOTES FORM ..............................................................................................................

87

OPM_SGS_USM_10K_40K_0US_V010.doc

6/88

Operating Manual SG Series 10, 20, 30 & 40 kVA

g

GE

1 IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS

This manual contains important instructions for models SG Series 50 and 80 kVA that should be followed during installation and maintenance of the UPS and battery.

GENERAL

-Move the UPS in an upright position in its original package to the final destination room. To lift the cabinets, use a forklift or lifting belts with spreader bars.

-Check for sufficient floor and elevator loading capacity.

-Check the integrity of the UPS equipment carefully.

If you notice visible damage, do not install or start the UPS. Contact the nearest Service Center immediately.

-WARNING! RISK OF ELECTRICAL SHOCK: Do not remove covers; there are no user serviceable parts inside.

-All maintenance and service work should be performed by qualified service personnel. The UPS contains its own energy source (battery).

-The field-wiring terminals may be electrically live, even when the UPS is disconnected from the utility.

-Dangerous voltages may be present during battery operation.

The battery must be disconnected during maintenance or service work.

-This UPS contains potentially hazardous voltages.

-Be aware that the inverter can restart automatically after the utility voltage is restored.

INSTALLATION

-This UPS must be installed and connected only by trained personnel.

-Verify accurately during Commissioning and Maintenance of the UPS, for the following: Damaged components, squeezed wires and cables, or not correctly inserted plugs.

-After removing the sidewalls of the UPS, make sure that all earth connections when reassembling, are correctly reattached

-This UPS is intended for use in a controlled indoor environment free of conductive contaminants and protected against animals intrusion.

-HIGH GROUND LEAKAGE CURRENT: Ground connection is essential before connecting to AC input!

-Switching OFF the unit does not isolate the UPS from the utility.

-Do not install the UPS in an excessively humid environment or near water.

-Avoid spilling liquids on or dropping any foreign object into the UPS.

-The unit must be placed in a sufficiently ventilated area; the ambient temperature should not exceed 104°F (40°C).

-Optimal battery life is obtained if the ambient temperature does not exceed 77°F (25°C).

-It is important that air can move freely around and through the unit. Do not block the air vents.

-Avoid locations in direct sunlight or near heat sources.

STORAGE

-Store the UPS in a dry location; storage temperature must be within -13°F (-25°C) to 131°F (55°C).

-If the unit is stored for a period exceeding 3 months, the battery must be recharged periodically (time depending on storage temperature).

BATTERY

-The battery-voltage is dangerous for person’s safety.

-When replacing the battery, use the same number, voltage (V) and capacity (Ah).

-Proper disposal or recycling of the battery is required. Refer to your local codes for disposal requirements.

-Never dispose of battery in a fire: They may explode.

-Do not open or mutilate battery: Their contents (electrolyte) may be extremely toxic. If exposed to electrolyte, wash immediately with plenty of water.

-Avoid charging in a sealed container.

-Never short circuit battery.

When working with battery, remove watches, rings or other metal objects, and only use insulated tools.

OPM_SGS_USM_10K_40K_0US_V010.doc

7/88

Operating Manual SG Series 10, 20, 30 & 40 kVA

g

GE

Safety instructions when working with battery

EXTERNAL BATTERY MUST BE INSTALLED AND CONNECTED TO THE UPS BY QUALIFIED SERVICE PERSONNEL.

INSTALLATION PERSONNEL MUST READ THIS ENTIRE SECTION AND REFER TO THE BATTERY MANUFACTURERS INSTALLATION MANUAL BEFORE HANDLING THE UPS AND BATTERY.

UPS INTENDED TO BE USED WITH A REMOTE BATTERY SUPPLY – ALL MODELS: “PLEASE REFER TO THE BATTERY MANUFACTURER’S INSTALLATION MANUAL FOR BATTERY INSTALLATION AND MAINTENANCE INSTRUCTIONS”.

DANGER!

Full voltage and current are always present at the Battery Terminals.

The Battery used in this system can provide dangerous voltages, extremely high currents and a risk of electric shock.

They may cause severe injury if the terminals are shorted together or to ground.

You must be extremely careful to avoid electric shock and burns caused by contacting Battery Terminals or shorting terminals during battery installation.

Do not touch un-insulated Battery Terminals.

A qualified service person that is familiar with Battery systems and required precautions must install and service the Battery.

The installation must conform to national and local codes. Keep unauthorized personnel away from Battery.

The qualified service person must take these precautions:

1Wear protective clothing, such as rubber gloves and boots and protective eye wear. Batteries contain caustic acids and toxic materials and can rupture or leak if mistreated. Remove rings and metal wristwatches or other metal objects and jewelry.

Do not carry metal objects in your pockets where the objects can fall into the Battery Cabinet.

2Tools must have insulated handles and must be insulated so that they will not short Battery Terminals.

Do not allow a tool to short between individual or separate Battery Terminals or to the cabinet or rack.

Do not lay tools or metal parts on top of the Battery, and do not lay them where they could fall onto the Battery or into the cabinet.

3Install the Battery as shown on the drawing provided with the Battery.

When connecting cables, never allow a cable to short across a Battery’s Terminals, the string of batteries, or to the cabinet or rack.

4Align the cables on the Battery Terminals so that the cable lug will not contact any part of the cabinet or rack, even if the Battery is moved.

Keep the cable away from any sharp metal edges.

5Install the Battery Cables so the UPS or Battery Cabinet Doors cannot pinch them.

6Do not connect the Battery Terminal to Ground.

If any Battery Terminal is inadvertently grounded, remove the source of the ground. Contacting any part of a grounded Battery can cause a risk of electric shock.

7To reduce the risk of fire or electric shock, install the Battery in a temperature and humidity controlled indoor area, free of contaminants.

8Battery System Chassis Ground (earth) must be connected to the UPS chassis ground (earth).

If you use conduit, this ground conductor must be routed in the same conduit as the Battery Conductors.

9Where conductors may be exposed to physical damage, protect the conductors in accordance with all applicable codes.

10If you are replacing Battery or repairing Battery Connections, shut OFF the UPS and remove the

Battery Fuses or open the Battery System disconnect.

OPM_SGS_USM_10K_40K_0US_V010.doc

8/88

Operating Manual SG Series 10, 20, 30 & 40 kVA

g

GE

Safety symbols and warnings

Safety warnings

The text of this manual contains some warnings to avoid risk to the persons and to avoid damages to the UPS system and the supplied critical loads.

The non-observance of the warnings reminding hazardous situations could result in human injury and equipment damages.

Please pay attention to the meaning of the following warnings and symbols.

Throughout this manual the following symbols are defined:

WARNING, if instruction is not followed injury or serious equipment damage may occur!

CAUTION, internal parts have dangerous voltage present.

Risk of electric shock!

PE (Earth) – GND (Ground) PROTECTIVE GROUNDING TERMINAL:

A terminal which must be connected to earth ground prior to making any other connection to the equipment.

A terminal to which or from which an alternating (sine wave) current or voltage may be applied or supplied.

A terminal to which or from which a direct current or voltage may be applied or supplied.

This symbol indicated the word “phase”.

This symbol indicates the principal on/off switch in the on position.

This symbol indicates the principal on/off switch in the off position.

OPM_SGS_USM_10K_40K_0US_V010.doc

9/88

Operating Manual SG Series 10, 20, 30 & 40 kVA

g

2 INTRODUCTION

GE

An Uninterruptible Power Supply (UPS) provides the power for critical loads that need a reliable, continuous, disturbance free supply.

In case the power provided by the Utility Fails, or exceeds the permitted tolerances, the power to supply the Load is provided by the Battery for the specified time at the rated Load (or longer at a reduced Load) or until the Utility power returns.

SG Series is a true double conversion On-line UPS system where the Load is continuously supplied by the Inverter through the Rectifier.

In case of trouble on the Inverter Output Voltage, or when overload or short-circuit on the output occur, the Load is instantly transferred to the Utility via the Automatic Bypass.

The UPS automatically returns to normal mode when the failure condition is restored.

Key features:

More Critical equipment supported

Rated at 0.8 Power Factor, SG Series delivers more real power than other UPS in the market.

With today’s trend toward power factor corrected loads, SG Series can support more total Load than any other UPS available, allowing you to support a greater number of today’s enterprise computing Power Factor Corrected (PFC) equipment.

No single point of failure

Redundant Parallel Architecture (RPA) is an exclusive GE technology.

With RPA, SG Series UPS are controlled in a true peer-to-peer configuration where all critical elements and functions (including Bypass) are redundant.

SG Series is designed to be the most reliable power protection system available on the market today.

High Efficiency

Using IGBT technology and Space Vector Modulation (SVM) strategy, SG Series offers low output voltage distortion and provides efficiencies up to 93%.

Fully digital

Digital Signal Processor (DSP), Flash memory and SVM strategy, are the technology corner stones of new age of power quality and power reliability.

Extremely flexible

Tailor made power protection to meet your individual installation requirements; SG Series offers various options like input harmonic filters and our comprehensive JUMP software suite for mission control and data protection to cover all your application needs.

OPM_SGS_USM_10K_40K_0US_V010.doc

10/88

Operating Manual SG Series 10, 20, 30 & 40 kVA

g

3 DESCRIPTION

GE

3.1BLOCK DIAGRAM AND MAIN ELEMENTS

 

Fig. 3.1-1 Block diagram

The SG Series system can be divided into the following main elements:

Control System

SG Series is designed with microprocessor-controlled signal

processing circuits. The interface between the operator and the unit is provided by the monitoring system on the front panel.

This monitoring system consists of an active mimic diagram, a keyboard and a backlit display.

Rectifier The standard Rectifier consists of a 6-pulse SCR-bridge, which converts the 3-phase Utility Voltage into a controlled and regulated DC-voltage.

This regulated DC-voltage is used to supply power to the Inverter, and to provide charging power to the Battery.

Inverter The Inverter converts the DC voltage into a three-phase ACvoltage with constant amplitude and frequency, which is completely independent and isolated from the AC-input voltage.

Automatic Bypass The Automatic Bypass consists of a static semiconductor-switch (SSM: Static Switch Module), used to provide an uninterrupted transfer of the Load from

Inverter to Utility.

Back-feed Protection All SG Series UPS's are equipped with an automatic system for the protection against voltage back feeding towards Utility, through the Bypass (Applied Standard IEC 62040-1).

This protection works automatically by opening contactor K6 and K8 (in series with the thyristors of the static switch) and eventually K7, and acts in case of internal defects of the system, or due to wrong manipulations on the Manual Bypass Q2.

Manual Bypass The Manual Bypass consists of a pair of manual switches (Q1 and Q2), which removes the UPS from the Load for maintenance, while still supplying the Load with power directly from the Utility.

Battery The Battery supplies the DC power to the Inverter when the Utility is out of accepted tolerances.

OPM_SGS_USM_10K_40K_0US_V010.doc

11/88

Operating Manual SG Series 10, 20, 30 & 40 kVA

g

GE

3.2OPERATION MODES

3.2.1 Normal operation mode

During normal operation, the Rectifier converts input AC power to DC.

The DC power provides input power for the Inverter and charging power for the Battery. The Inverter converts the DC power to continuous and regulated AC power, which supplies the critical load.

The control panel reports the Battery charge status and the expected backup time with the actual load.

3.2.2 Utility failure operation

When the Utility is no longer within acceptable tolerances, the Battery will provide the DC power to the Inverter.

The Inverter will maintain continuous AC power to the Load until the Battery Voltage reaches the lower limit of the Inverter operation capability.

During the discharge, the LCD screen displays the estimated time the Battery can support the critical load.

Prior to the Battery completely discharging, the "stop operation" alarm (shutdown imminent) warns the operator that the Battery is almost discharged and the UPS is about to shut down.

Fig. 3.2.1-1 Block diagram normal operation mode

Fig. 3.2.2-1 Block diagram Utility Failure operation

In case of parallel operation

With a parallel system for power capacity (see Section 3.3)

With the Bypass Utility power available, a low Battery warning on any unit will cause the Load to be transferred to Utility (after a selectable time delay).

With Bypass Utility power not available, a low Battery warning on any unit will start the “stop operation” timer (adjustable).

The Load will shut down at the end of the “stop operation” time period.

With a parallel system for redundancy (see Section 3.3)

When a Battery low warning occurs on a unit not necessary to support the present load, this unit will shut down after a timeout period (selectable).

The Load is shared between the other units

As the warning occurs on one unit necessary to support the present load, the system starts the "stop operation" timeout (selectable).

The Load will shut down at the end of the “stop operation” time period.

OPM_SGS_USM_10K_40K_0US_V010.doc

12/88

Operating Manual SG Series 10, 20, 30 & 40 kVA

g

GE

3.2.3Utility recovery operation

As soon as the AC input power recovers, the

Rectifier will start automatically, supplying DC power to the Inverter and recharging the Battery.

If the Inverter was previously shut down due to low Battery, the Load will be initially powered by Utility through the Automatic Bypass.

When the Battery is recharged enough to ensure a minimum time of operation with the present load, the Inverter will start automatically and the Load will be transferred back to the Inverter.

Fig. 3.2.3-1 Block diagram Utility recovery operation

In case of parallel operation

When the AC input power recovers, the Rectifiers will start up sequentially, according to their number in the parallel system. This minimizes the initial inrush current.

The Inverters will start up automatically, but only when the Battery has recharged enough for a minimum runtime with the present load.

When enough Inverters to supply the Load have been restarted, the Load will be transferred from the Automatic Bypass back to the Inverter output.

3.2.4 Automatic Bypass

In normal operation, the Load is supplied by the

Inverter.

When the control system detects a fault in the Inverter, an overload condition or a short-circuit condition, the Automatic Bypass will transfer the critical Load to the Utility without interruption.

When the Inverter recovers, or the overload or short-circuit condition is corrected, the Load will be automatically transferred back to the Inverter.

If the UPS is unable to return to normal mode following an automatic transfer to Bypass mode, an alarm condition will be initiated.

A Manual Bypass (operator initiated) will not be considered as an alarm condition.

FIG. 3.2.4-1 BLOCK DIAGRAM AUTOMATIC

BYPASS

In case of parallel operation

Each unit has it’s own internal Bypass. These units are continuously exchanging information, enabling all of the internal Bypass circuits in a parallel system to operate simultaneously.

If the Inverter of a unit fails, it’s Bypass circuit remains available to the parallel system.

It is excluded only if the unit is separated from the common bus by opening it’s output switch Q1.

3.2.5Manual Bypass

The Manual Bypass circuit consists of Q1 and Q2 manual switches, which permits transfer of the Load directly to the unconditioned AC power without interruption, leaving the UPS available for maintenance.

Fig. 3.2.5-1 Block diagram Manual Bypass

OPM_SGS_USM_10K_40K_0US_V010.doc

13/88

Operating Manual SG Series 10, 20, 30 & 40 kVA

g

GE

3.3PARALLEL SYSTEM OPERATION

3.3.1 Introduction to the parallel system

Two or more equal power units can be paralleled to increase the output power (paralleling for capacity) or to improve the overall reliability of an UPS system (paralleling for redundancy). The outputs of parallel units are connected to a common power bus, and in normal operation the units connected on the parallel bus share the Load equally.

The modular concept of SG Series allows parallel operation of up to 8 units, without using paralleling switchgear, external bypass circuits or common control circuitry (see Fig. 3.3.1-1).

Parallel units for power capacity

Several units can be paralleled in order to achieve output power greater than the maximum power of a single unit.

The maximum total power shared between the paralleled units is equal to the total installed nominal power.

In the event of a failure of one unit, the power supplied by the UPS system becomes insufficient and the Load will be transferred to the Utility Bypass source.

Parallel units for redundancy

The nominal power rating of the n+1 out of n redundant paralleled modules must be equal to or greater than the required Load power.

The Load will be equally shared by the n units connected on the output bus.

Should one of the n paralleled units trip Off-line, the remaining (n+1) modules will supply the load, maintaining conditioned power to the critical load.

From this results higher reliability and security for the Load plus a higher MTBF (Mean Time Between Failures).

Fig. 3.3.1-1 Block diagram parallel system operation

OPM_SGS_USM_10K_40K_0US_V010.doc

14/88

Operating Manual SG Series 10, 20, 30 & 40 kVA

g

GE

3.3.2 Features of RPA parallel system

The SG Series parallel system is designed to provide a complete Redundant Parallel Architecture, and is free from common equipment.

Not only the Inverters are redundant, but also the Bypass functions are designed with redundant modular concept.

When one UPS needs maintenance or service, the Load is powered by the other units supplying the Load bus.

The redundant communication bus to which all units are connected keeps each unit informed about the status of all the other units.

The control panel located on each unit allows controlling and monitoring the status of this unit.

3.3.3 System control

A high-speed redundant, serial communication bus guarantees the exchange of data and thus the communication between the CPU's of each unit.

Each module controls it's own function and operational status and communicates with all other modules, in order to act or react if necessary, adapting it to the new conditions.

3.3.4 Synchronization

All units are identical, but one unit is arbitrarily selected as the reference and all the other units synchronize to this unit, which in turn, synchronizes to the Utility Bypass voltage, as long as the later is within tolerances.

In case of reference failure, another unit in the parallel system is automatically chosen to take over the reference role.

The Bypass Input for all the units of the parallel system must be supplied from the same AC source (no phase shift allowed between them).

3.3.5 Load sharing

On each unit of the parallel system, Inverter Output Voltage and Current are measured and applied to a Load sharing bus.

An eventual difference between the units is therefore automatically equalized.

It is strongly recommended that no transformers, automatic circuit breakers or fuses should be inserted between the unit’s output and the Load common bus bars.

However, it is recommended that a disconnect or isolation switch be inserted.

OPM_SGS_USM_10K_40K_0US_V010.doc

15/88

Operating Manual SG Series 10, 20, 30 & 40 kVA

g

GE

3.4RECTIFIERS PARALLELED ON THE SAME BATTERY

A parallel system with a Common Battery for two or more Rectifiers, requires a particular installation and adequate setting of some parameters, (accessible only through password), and can therefore only be done by a qualified engineer from GE.

Usually each Rectifier-Inverter Unit runs with its own Battery.

In case of parallel units are running with a Common Battery (max. 4 UPS - see Fig 4.12-1), the sharing circuit between individual Rectifier is integrated in the communication bus of the system in order to assure an equal sharing of the Rectifiers output currents.

1 – Rectifier

2 – Inverter

3 – Automatic Bypass

4 – Manual Bypass

5 – Mains Power

6 – Load Bus Bar

7 – External Battery Fuse

8 – Battery

Fig. 3.4-1 Diagram RPA system with Rectifiers on Common Battery

Pay attention to the following recommendations:

The units delivered for this functioning mode needs a special parameters setting, so they must be prepared in advance before the installation.

The installation must be performed only with the UPS system must be completely shut down.

The AC Rectifiers input power (5) must be the same, with clockwise phase rotation for each unit.

Each Rectifier must be set for the same floating DC voltage and the same Battery current limitation.

It is recommended to install the fuses / MCB (7) on each line connecting the Rectifiers to the common Battery for maintenance / safety reasons.

In case one must be powered down for maintenance, switch-OFF the concerned unit before open the DC fuses / MCB on the Battery line (7).

It is recommended to connect an external NO free contact “Battery Fuses” to the UPS and to enable the function by setting the parameter (see Section 7.1).

If an emergency generator set supply the UPS, and the free contact “Generator ON” is connected to the Customer interface, connect a separate NO free contact on each parallel unit.

The parameters enabling the Battery test, both manual and automatic, must be set in the same mode on all the units having the Rectifiers on Common Battery.

Do not connect the temperature sensor for automatic battery floating voltage compensation.

Do not enable the function Boost charge (parameter 87).

OPM_SGS_USM_10K_40K_0US_V010.doc

16/88

Operating Manual SG Series 10, 20, 30 & 40 kVA

g

GE

3.5RECYCLING AT THE END OF SERVICE LIFE

NOTE!

This product has been designed to respect the environment, using materials and components respecting eco-design rules.

It does not contain CFCs (Carbon Fluor Clorid) or HCFCs (Halogen Carbon Fluor Clorid).

Packing material recycling

GE, in compliance with environment protection, uses only environmentally friendly material.

UPS packing materials must be recycled in compliance with all applicable regulations.

WARNING!

Leads contained in the batteries is a dangerous substance for the environment, therefore it must be correctly recycled by specialized companies!

OPM_SGS_USM_10K_40K_0US_V010.doc

17/88

Operating Manual SG Series 10, 20, 30 & 40 kVA

g

GE

4LAYOUT

4.1LAYOUT SG Series 10 AND 20 KVA

SGT5000 030-040 UPS GE 02

SGT5000 010-020 UPS GE 03

FIG. 4.1-1 SG SERIES GENERAL VIEW

Fig. 4.1-2 SG Series general view with open doors

Fig. 4.1-4 Control Panel

Fig. 4.1-3 Manual operated switches

 

 

interface 03

 

 

100-150 Customer

 

1

SGT5000_

 

 

 

2

 

 

3

XA

P4

4

 

 

 

SNMP

1

XB

 

2

 

 

3

 

 

4

 

Fig. 4.1-5 Connectivity Rack

P4 Customer Interface Board

Q1 UPS output switch

Q2 Manual Bypass switch

SNMP SNMP Card (option)

XA Terminals for 24VDC Auxiliary Power Supply connection

XB Terminals for EPO (Emergency Power Off) connection

OPM_SGS_USM_10K_40K_0US_V010.doc

18/88

Operating Manual SG Series 10, 20, 30 & 40 kVA

GE SG 10, SG 40, SG 30, SG 20 User Manual

g

GE

4.2LAYOUT SG Series 30 AND 40 KVA

SGT5000 030-040 UPS GE 02

SGT5000 030-040 UPS GE 03

Q1 Q2

FIG. 4.2-1 SG SERIES GENERAL VIEW

Fig. 4.2-2 SG Series general view with open doors

Fig. 4.2-4 Control Panel

Fig. 4.2-3 Manual operated switches

 

1

 

2

 

3

P4

4

 

SGT5000_100-150_Customer interface_03

 

P4

Customer Interface Board

XA

Q1

UPS output switch

 

 

 

Q2

Manual Bypass switch

SNMP

1

XB

SNMP

SNMP Card (option)

 

 

2

 

 

 

 

3

 

XA

Terminals for 24VDC Auxiliary Power Supply connection

 

4

 

 

 

 

 

 

Fig. 4.2-5 Connectivity Rack

 

XB

Terminals for EPO (Emergency Power Off) connection

 

 

 

 

OPM_SGS_USM_10K_40K_0US_V010.doc

19/88

Operating Manual SG Series 10, 20, 30 & 40 kVA

g

5 CONTROL PANEL

GE

5.1CONTROL PANEL

Fig. 5.1-1 Control Panel

5.2TABLE OF FUNCTIONS AND INDICATIONS ON CONTROL PANEL

inverter on/off

Key to switch the Inverter ON.

(This key is also used to reset total offif pressed simultaneously with total off push button).

inverter on/off

Key for Inverter shutdown.

Press key to transfers the Load to Utility.

Keep pressed for 5 seconds to shutdown the Inverter.

This key is also used as the EPO (Emergency Power Off) reset.

mute

Key to reset general alarm and buzzer.

test

Key to test the control panel LED’s and buzzer.

 

(Pressing this key causes all the LED’s to light and the buzzer to

 

sound 3 times).

The push-button total offis protected by a red cover.

By pressing it, you immediately separate the UPS from utility and the Load.

Attention: total offcannot disconnect the UPS from the Load with Q2 closed.

To reset total off: push and hold the total offpush-button and the Ikey (inverter on) simultaneously for some seconds.

For parallel system, pressing “total off” on one unit connected on parallel bus (switch Q1 closed), all the units are separated from the load.

The “total offreset must be done only on one unit connected on the parallel bus (switch Q1 closed).

Special care must be taken in using this command, in order to avoid accidental Load disconnection.

OPM_SGS_USM_10K_40K_0US_V010.doc

20/88

Operating Manual SG Series 10, 20, 30 & 40 kVA

g

GE

alarm

service check

General alarm condition.

It blinks when one or more alarm is activated. The internal buzzer is ON. The LED remains lighted (with alarm condition still present) and the buzzer stops as the key “mute” has been pressed.

LED ON indicates that a regular maintenance service is needed. May be reset by a service technician only.

(See chapter 10 – Maintenance)

THE LED IS ON ALSO WHEN THE OUTPUT SWITCH Q1 IS OPEN, INDICATING THAT THE INVERTER IS IN SERVICE MODE, NOT SUPPLYING THE LOAD.

a) LED ON indicates that the Battery reserve lasts for only 3 more minutes (selectable).

b)LED ON in case of over temperature or overload >125% together with missing Utility.

After the timeout the Inverter will shut down.

All LED’s ON indicate that the Battery is fully charged.

LED a

Yellow

 

(Fixed: indicating last 25 % of Battery backup)

 

(Blinking: indicating Battery backup 5%)

LED b, c, d

Green

 

(EACH ONE INDICATING 25 % OF BATTERY BACKUP)

LED’s ON indicate the Load status of the UPS.

LED d

red

LED c

yellow

LED b

green

LED a

green

Fig. 5.2.1-1 LED’s on synoptic diagram

Fig. 5.2.1-2 LCD screen

(100 % load) (100% load) (66% load) (33% load)

Definition of the LED’s on mimic diagram

LED 1

= Input Utility Rectifier (green)

LED 2

= Input Utility Bypass (green)

LED 3

=

Rectifier ON (green)

LED 4a

=

Discharging (yellow)

LED 4b

=

Charging (green)

LED 5

=

Inverter ON (green)

LED 6

= Load on Inverter (green)

LED 7

= Load on Utility (green)

LED 8

= Output Load Voltage (green)

LED 9

=

Manual Bypass (Q2) ON (yellow)

User LCD Interface

Consist of a LCD screen, 4 lines with 20 characters each and six keys. It offers:

UPS operating, AC and DC metering information.

History of alarms and events.

Functionality can be programmed to meet customer needs by changing parameters.

OPM_SGS_USM_10K_40K_0US_V010.doc

21/88

Operating Manual SG Series 10, 20, 30 & 40 kVA

g

6 LCD SCREEN

GE

The user interface consists of a back lit LCD screen having:

4 lines with 20 characters (standard version for Latin characters). And

6 keys (the function is described for each operating mode).

The operation is extremely simple and is structured on three important main menus related to the UPS operation, as follows:

metering A UPS must offer some metering information for the user to be able to examine the operating status at any time.

alarms In the event of Utility failures or abnormal functioning, the UPS must keep a history of what has happened as a series of events.

parameters The user must be able to program certain functions of the UPS (user parameters, accessible without password) to his needs.

LCD screen standard version

metering

LCD screen

+

alarms

4 rows x

parameters

20 characters

ok

 

 

 

 

The 3 buttons existing on the left side of the screen are used to activate the operating modes, while the buttons on the right side are used to carry out functions inside these operating modes.

OPM_SGS_USM_10K_40K_0US_V010.doc

22/88

Operating Manual SG Series 10, 20, 30 & 40 kVA

g

GE

6.1METERING MODE

The metering mode is entered any time the metering button is pressed.

While in this mode the LCD will display a series of screens containing metering information. In this mode the buttons perform the following functions:

metering

Scrolls forward to the next screen.

alarms

Abandons the metering mode and enters the alarms mode.

parameters

Abandons the metering mode and enters the parameters mode.

+

Scrolls forward to the next screen.

Scrolls backward to the previous screen.

ok

Displays the main screen for this mode.

Main screen

This screen displays the current status of the UPS in a condensed form.

The information offered by this screen consists of:

The type of the machine: Family name, series number (P + unit number for parallel version from 1 to 8) and power range.

The status of the load.

The Load amount as a percentage of the nominal Load (referred to the most loaded phase).

The estimated Battery backup time in minutes with the present load.

metering

SG Series S0 30kVA

+

alarms

LOAD ON INVERTER

LOAD = 84%

parameters

Autonomie = 12min

ok

 

Battery data screen

This screen displays:

The Battery voltage.

The Battery Current (negative values correspond to the discharge of the Battery).

The temperature of the Battery (XXX indicates sensor disabled).

The current charge level.

The estimated backup time with the present load.

metering

Ub=540V

Ib=

+ 15A

+

alarms

Battery

Temp=

+ 20°C

Charge

Level=

87%

parameters

Autonomy

=

12min

ok

 

 

 

 

 

 

 

 

 

 

Bypass Utility data screen

This screen refers to the AC source supplying the Bypass. This screen displays:

The frequency.

The voltage levels of the three phase voltages.

m etering

UTILITY

+

alarm s

f = 60.0Hz

U1=276V U2=275V

param eters

U3=277V

ok

 

OPM_SGS_USM_10K_40K_0US_V010.doc

23/88

Operating Manual SG Series 10, 20, 30 & 40 kVA

g

GE

Rectifier Utility data screen

This screen refers to the AC source supplying the Rectifier.

This screen displays:

Iout1 = output current Rectifier Bridge.

Iout2 = output current 2nd Rectifier Bridge (optional 12 pulse Rectifiers only).

The voltage levels between the three phases (line-to-line).

The input frequency of the Rectifier.

metering

RECTIFIER

+

alarms

U12=481V

Iout1 =107A

U23=480V

Iout2 = 0A

parameters

U31=482V

f=60.0Hz

ok

 

 

 

 

 

 

Inverter data screen

This screen displays:

The voltage level of the three phase voltages (line-to-neutral).

The output frequency of the Inverter.

The synchronization status of the Inverter with respect to Utility.

metering

INVERTER:

U1=277V

+

alarms

U2= 277V

U3=277V

Frequency = 60.0Hz

parameters

Synchronized

ok

 

 

 

 

 

 

Status Load screen

This screen displays:

The Load level in kVA (for RPA: only this unit).

The Load level as a percentage of the nominal rated Load (for RPA: only this unit).

The source of the power supplied to the Load.

metering

 

LOAD ON UPS

+

alarms

Load

=

25.20kVA

Percentage =

84%

parameters

LOAD ON INVERTER

ok

 

 

 

Load on phases screen 1

This screen displays for each phase:

The output phase voltage and current as RMS values (for RPA: total value of Parallel System).

The output Load as percent (for RPA: respect to the rated power of Parallel System).

metering

alarms parameters

LOAD ON PHASES U1=277V I=30A 84% U2=277V I=26A 73% U3=277V I=27A 76%

+

ok

OPM_SGS_USM_10K_40K_0US_V010.doc

24/88

Operating Manual SG Series 10, 20, 30 & 40 kVA

g

GE

Load on phases screen 2

This screen displays for each phase:

The Load active power (kW) (for RPA: total value of Parallel System).

The Load apparent power (kVA) (for RPA: total value of Parallel System).

metering

LOAD ON PHASES

alarms

L1= 6.72kW

8.40kVA

L2= 5.84kW

7.30kVA

 

parameters

L3= 6.08kW

7.60kVA

 

 

Miscellaneous screen

This screen displays:

The temperature of the Inverter Bridge.

The total operating time for the UPS (in hours).

The total operating time for the Inverter (in hours).

+

ok

metering

MISCELLANEOUS

+

alarms

InvHeatsink =

45°C

UpsOperTime=

3125h

parameters

InvOperTime =

2135h

ok

 

 

 

 

 

 

Utility Faults Statistics screen

This screen displays:

The total number of minor Utility faults (Bypass Utility out of tolerance faults).

The total number of major Utility faults (Rectifier Utility out of tolerance faults).

The total number of detected output overloads.

metering

UTILITY FAULTS STAT.

+

alarms

Minor

=

43210

Major

=

11267

parameters

Overloads=

654

ok

 

 

 

 

 

 

 

 

UPS identification screen

This screen displays:

The UPS family and the power range.

The software version.

The serial number.

metering

UPS IDENTIFICATION

+

alarms

SG Series S0 30kVA

SW Version: x.xx

parameters

S/N: P0030-2003-0001

ok

 

 

 

 

OPM_SGS_USM_10K_40K_0US_V010.doc

25/88

Operating Manual SG Series 10, 20, 30 & 40 kVA

g

GE

6.2ALARMS

The alarms mode is entered any time the alarms button is pressed.

The LCD will display a series of screens corresponding to the last 256 events, one event per screen.

The buttons perform the following functions:

metering

Abandons alarms mode and enters metering mode.

alarms

Next screen.

parameters

Abandons the alarms mode and enters the parameters mode.

+

Scrolls forward to the next screen.

Scrolls backward to the previous screen.

ok

Display the main screen for this mode.

The events displayed are the standard GE events as described in the Section 6.7 - EVENTS (Alarms and Messages).

The information displayed includes:

The exact date and time when the event occurred.

The number of the event, 255 being the most recent event, and 0 the oldest.

The standard GE code for the event and the machine status word.

An explicit text description of the event.

metering

01.10.2002 22:11:51

+

alarms

NR=255 Status=4A61

4115:LOW BATTERY

parameters

VOLTAGE

ok

 

The initial screen of this mode is the one showing the most recent event.

OPM_SGS_USM_10K_40K_0US_V010.doc

26/88

Operating Manual SG Series 10, 20, 30 & 40 kVA

g

GE

6.3PARAMETERS

The parameters mode is entered any time the parameters button is pressed.

The LCD will display a series of screens containing the user parameters, accessible without password protection.

The buttons perform the following functions:

metering

Abandon parameters mode and enter metering mode.

alarms

Abandon parameters mode and enter alarms mode.

parameters

Scroll forward to the next screen.

+

Scroll forward to the next screen.

Select from the current screen the parameter to edit.

ok

Start the editing for the currently selected parameter.

During parameters mode there is no means to perform scroll back on the display.

Example of operation within parameters mode:

Purpose: to correct a wrong telephone number previously stored in Tel2.

1 – entering parameters mode (parameters). The first screen is displayed.

2 – scroll to the next screen (+). The second screen is displayed.

3 – scroll to the next screen (+). The third screen is displayed.

4 – move the selection (underscore cursor) to the next parameter in this page (-).

5 – move the selection to the next parameter in page (-).

6 – enter Edit mode for the currently selected parameter (ok).

1

2

 

metering

DATE AND TIME

+

 

 

alarms

 

D M Y

 

Date:

01.10.2002

 

parameters

Time:

12:45:07

ok

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

metering

PROTOCOL SETUP

+

alarms

Modem enabled=N

Init=BEQV1X3&D0S0=2

parameters

Alarm= N

Delay=22s

ok

 

 

 

 

 

 

OPM_SGS_USM_10K_40K_0US_V010.doc

27/88

Operating Manual SG Series 10, 20, 30 & 40 kVA