Fujitsu ASU9RLS2 Service instructions manual

5 (1)

SPLIT TYPE

ROOM AIR CONDITIONER

WALL MOUNTEDtype

INVERTER

SERVICE INSTRUCTION

Models Indoor unit

Outdoor unit

ASU9RLS2

AOU9RLS2

ASU12RLS2

AOU12RLS2

ASU15RLS2

AOU15RLS2

R410A

CONTENTS

1. DESCRIPTION OF EACH CONTROL OPERATION

1. COOLING OPERATION................................................................................................

01-01

2. HEATING OPERATION.................................................................................................

01-02

3. DRY OPERATION.........................................................................................................

01-02

4. AUTO CHANGEOVER OPERATION............................................................................

01-03

5. INDOOR FAN CONTROL..............................................................................................

01-04

6. OUTDOOR FAN CONTROL..........................................................................................

01-06

7. LOUVER CONTROL.....................................................................................................

01-07

8. COMPRESSOR CONTROL..........................................................................................

01-08

9. TIMER OPERATION CONTROL...................................................................................

01-09

10. ELECTRONIC EXPANSION VALVE CONTROL........................................................

01-12

11. TEST OPERATION CONTROL...................................................................................

01-12

12. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST ).................................

01-12

13. FOUR-WAY VALVE EXTENSION SELECT................................................................

01-12

14. AUTO RESTART.........................................................................................................

01-13

15. MANUAL AUTO OPERATION ( Indoor unit body operation ).....................................

01-13

16. FORCED COOLING OPERATION..............................................................................

01-13

17. COMPRESSOR PREHEATING...................................................................................

01-14

18. MIN.(MINIMUM) HEAT OPERATION..........................................................................

01-14

19. ECONOMY OPERATION............................................................................................

01-14

20. HUMAN SENSOR CONTROL.....................................................................................

01-14

21. OUTDOOR UNIT LOW NOISE OPERATION..............................................................

01-15

22. POWERFUL OPERATION...........................................................................................

01-15

23. BASE HEATER OPERATION......................................................................................

01-15

24. DEFROST OPERATION CONTROL...........................................................................

01-16

25. OFF DEFROST OPERATION CONTROL...................................................................

01-18

26. VARIOUS PROTECTIONS..........................................................................................

01-19

2. TROUBLE SHOOTING

2-1 ERROR DISPLAY.......................................................................................................

02-01

2-1-1 INDOOR UNIT AND WIRED REMOTE CONTROLLER DISPLAY.....................

02-01

2-1-2 WIRED REMOTE CONTROLLER DISPLAY (OPTION).....................................

02-02

2-2 TROUBLE SHOOTING WITH ERROR CODE............................................................

02-03

2-3 TROUBLE SHOOTING WITH NO ERROR CODE.....................................................

02-25

2-4 SERVICE PARTS INFORMATION..............................................................................

02-30

3. APPENDING DATA

3-1 FUNCTION SETTING.................................................................................................

03-01

3-1-1 INDOOR UNIT....................................................................................................

03-01

3-1-2 Procedures to change the Function Setting for wireless RC..............................

03-03

3-2 Thermistor Resistance Values.....................................................................................

03-05

3-2-1 INDOOR UNIT....................................................................................................

03-05

3-2-2 OUTDOOR UNIT................................................................................................

03-05

4. REPLACEMENT PARTS

4-1 ASU9/ 12/ 15RLS2.......................................................................................................

04-01

4-1-1 PARTS LAYOUT DRAWING...............................................................................

04-01

4-1-2 DISASSEMBLY PROCESS.................................................................................

04-02

R410A

WALL MOUNTED type

INVERTER

1 . DESCRIPTION OF EACH CONTROL OPERATION

1. COOLING OPERATION

A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor.

*If the room temperature is 4°F(2°C) higher than a set temperature, the compressor operation frequency will attain to maximum performance.

*If the room temperature is 5°F(2.5°C) lower than a set temperature, the compressor will be stopped.

*When the room temperature is between +4°F(+2°C) to -5°F(-2.5°C) of the setting temperature, the compressor frequency is controlled within the range shown in Table1.

However, the maximum frequency is limited in the range shown in Figure1 based on the fan speed mode and the outdoor temperature.

( Table 1 : Compressor frequency range )

 

Minimum

Maximum

Maximum

 

frequency

frequency

frequency

AOU9RLS2

10rps

76rps

57rps

AOU12RLS2

10rps

76rps

57rps

 

AOU15RLS2

12rps

91rps

59rps

When the compressor operates for 30 minutes continuously at over the maximum frequency, the maximum frequency is changed from Maximum Frequency to Maximum Frequency.

( Fig.1 : Outdoor temperature zone ) ( Table 2 : Limit of maximum speed based on outdoor temperature )

Outside air

Outside air

temperature

temperature

 

 

 

 

97°F

 

 

 

 

93°F

 

A zone

 

(36°C)

 

 

 

90°F

(34°C)

 

 

 

 

 

B zone

 

(32°C)

86°F

 

 

70°F

(30°C)

 

 

 

66°F

 

C zone

 

(21°C)

 

 

54°F

(19°C)

 

 

 

50°F

 

D zone

 

(12°C)

 

 

36°F

(10°C)

 

 

 

32°F

 

E zone

 

(2°C)

 

 

 

(0°C)

 

 

 

 

 

 

F zone

 

 

 

 

 

 

 

Outdoor

 

Indoor fan mode

 

 

temp. zone

Hi

Me

Lo

Quiet

AOU9RLS2

A zone

80rps

51rps

43rps

26rps

 

B zone

80rps

51rps

43rps

26rps

 

C zone

80rps

51rps

43rps

26rps

 

D zone

47rps

35rps

29rps

20rps

 

E zone

47rps

35rps

29rps

20rps

 

F zone

47rps

35rps

29rps

20rps

AOU12RLS2

A zone

76rps

45rps

37rps

29rps

 

B zone

76rps

45rps

37rps

29rps

 

C zone

76rps

45rps

37rps

26rps

 

D zone

43rps

35rps

26rps

20rps

 

E zone

51rps

37rps

31rps

22rps

 

F zone

51rps

37rps

31rps

22rps

AOU15RLS2

A zone

91rps

44rps

34rps

24rps

 

B zone

91rps

44rps

34rps

24rps

 

C zone

72rps

44rps

34rps

24rps

 

D zone

52rps

30rps

21rps

18rps

 

E zone

63rps

34rps

27rps

19rps

 

F zone

63rps

34rps

27rps

19rps

01-01

2. HEATING OPERATION

A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor.

*If the room temperature is lower by 6°F(3°C) than a set temperature, the compressor operation frequency will attain to maximum performance.

*If the room temperature is higher 5°F(2.5°C) than a set temperatire, the compressor will be stopped.

*When the room temperature is between +5°F(+2.5°C) to -6°F(-3°C) of the setting temperature, the compressor frequency is controlled within the range shown in Table3.

( Table 3 : Compressor frequency range )

 

Minimum

Maximum

 

frequency

frequency

AOU9RLS2

10rps

119rps

 

 

 

AOU12RLS2

10rps

119rps

 

 

 

AOU15RLS2

16rps

140rps

 

 

 

3. DRY OPERATION

The compressor frequency shall change according to the temperature, set temperature,

and room temperature variation which the room temperature sensor of the indoor unit body has detected as shown in the Table 4.

However, after the compressor is driven, the indoor unit shall run at operation frequency of 51rps (9RLS2), 51rps (12RLS2), 52rps (15RLS2) for 60 seconds.

( Table 4 : Compressor frequency in Dry mode)

 

 

Operating

 

 

 

Operating

 

 

 

Operating

 

 

frequency

 

 

 

frequency

 

 

 

frequency

 

 

 

 

 

 

 

 

 

 

 

AOU

X zone

26rps

 

AOU

X zone

26rps

 

AOU

X zone

24rps

9RLS2

J zone

18rps

 

12RLS2

J zone

18rps

 

15RLS2

J zone

16rps

 

Y zone

0rps

 

 

Y zone

0rps

 

 

Y zone

0rps

( Fig.2 : Compressor Control based on Room Temperature )

Room

 

 

Room

temperature

temperature

 

 

 

 

Ts+3°F

 

 

 

 

Ts+1°F

 

X zone

 

(Ts+1.5°C)

 

 

 

 

 

 

 

Ts-1°F

(Ts+0.5°C)

 

 

 

 

 

J zone

 

(Ts-0.5°C)

Ts-3°F

 

 

 

 

 

 

 

(Ts-1.5°C)

 

Y zone

 

 

 

 

 

 

 

 

 

 

 

01-02

4. AUTO CHANGEOVER OPERATION

When the air conditioner is set to the AUTO mode by remote control, operation starts in the optimum mode from among the HEATING, COOLING, DRY and MONITORING modes. During operation, the optimum mode is automatically switched in accordance with temperature changes. The temperature can be set between 64°F(18°C) and 88°F(30°C) in 2°F(1°C) steps.

(Fig3 : Operation flow chart)

START

Room temp.

 

YES

>Ts+4°F(2°C)?

 

 

 

NO

TS : Setting temperature

 

 

 

 

 

NO

Room temp.

 

<Ts- 4°F(2°C)?

 

 

YES

 

 

 

 

 

HEATING OPERATION

YES

Thermostat remains

 

 

in OFF state for 6 minutes or

 

 

 

 

longer?

 

 

 

NO

 

 

 

 

 

 

 

System stops

YES or operation command other than auto changeover operation?

NO

COOLING OPERATION

Thermostat remains

YES

in OFF state for 6 minutes or

 

 

 

 

 

 

longer?

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

System stops

 

YES

 

or operation command other than

 

 

auto changeover operation?

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

01-03

5. INDOOR FAN CONTROL

1. Fan speed

( Table 5 : Indoor fan speed )

Operation mode

Air flow mode

 

Speed (rpm)

 

ASU9RLS2

ASU12RLS2

ASU15RLS

 

 

 

 

 

 

 

Heating

Powerful

1470

1470

1620

 

Hi

1370

1370

1510

 

Me+

1260

1260

1440

 

Me

1180

1180

1220

 

Lo

960

960

1030

 

Quiet

650

650

790

 

Cool air prevention

610

610

610

 

S-Lo

570

570

570

Cooling/ Fan

Powerful

1470

1470

1550

 

Hi

1370

1370

1440

 

Me

1120

1120

1220

 

Lo

960

960

980

 

Quiet

650

650

740

Dry

 

X zone: 650

X zone: 650

X zone: 740

 

 

J zone: 610

J zone: 610

J zone: 710

2. FAN OPERATION

The airflow can be switched in 5 steps such as Auto, Quiet, Lo, Me, Hi, while the indoor fan only runs. When fan mode is set at [Auto], it operates on [Me] fan Speed.

3. COOLING OPERATION

Switch the airflow [Auto], and the indoor fan motor will run according to a room temperature, as shown in Figure4.

On the other hand, if switched in [Hi][Quiet], the indoor motor will run at a constant airflow of [Cool] operation modes Quiet, Lo, Me, Hi, as shown in Table 5.

( Fig.4 : Airflow change - over ( Cooling : Auto ) )

TR-Ts > 4°F (2°C)

4°F > TR-Ts > 2°F (2°C) =(1°C)

2°F > TR-Ts (1°C)

HIGH mode

MED mode

LOW mode

When the room temperature drops

TR-Ts > 5°F =(2.5°C)

5°F > TR-Ts > 3°F (2.5°C) =(1.5°C)

3°F > TR-Ts (1.5°C)

When the room temperature rises

TR : Room temperature Ts : Setting temperature

4. DRY OPERATION

Refer to the Table 5.

During the dry mode operation, the fan speed setting can not be changed.

01-04

5. HEATING OPERATION

Switch the airflow [Auto], and the indoor fan motor will run according to a room temperature, as shown in Fig. 5

On the other hand, if switched in [Hi] [Quiet], the indoor motor will run at a constant airflow of [Heat] operation modes Quiet, Lo, Me, High, as shown in Table 6.

( Fig.5 : Airflow change - over ( Heating : Auto ) )

 

 

When the room

When the room

 

 

 

temperature rises

 

 

 

temperature drops

 

 

 

 

 

 

 

 

 

TR-Ts > -2°F

 

 

LOW mode

 

 

 

 

 

 

 

 

 

 

 

 

=

 

 

 

TR-Ts > -3°F

 

 

 

 

 

 

 

 

(-1°C)

 

 

 

 

 

 

=(-1.5°C)

-2°F > TR-Ts > -4°F

 

 

 

 

 

 

(-1°C)

=(-2°C)

 

 

MED mode

 

-3°F > TR-Ts > -5°F

 

-4°F > TR-Ts

 

 

 

 

 

(-1.5°C)

=(-2.5°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MED+ mode

 

-5°F > TR-Ts

TR : Room temperature

 

(-2°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

(-2.5°C)

Ts : Setting temperature

6. COOL AIR PREVENTION CONTROL (Heating mode)

The maximum value of the indoor fan speed is set as shown in Fig.6 based on the detected temperature by the indoor heat-exchanger sensor on heating mode.

( Fig.6 : Cool air prevension control )

 

 

 

 

<Powerful operation>

 

 

 

 

<Normal operation>

 

 

 

 

Indoor heat exchanger

 

 

 

 

 

 

 

Indoor heat exchanger

 

 

 

 

 

 

 

 

 

temperature rises

 

 

 

Indoor heat exchanger

temperature rises

 

 

 

 

Indoor heat exchanger

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

108°F

 

 

 

 

Hi

temperature drops

108°F

 

 

 

 

Powerful

 

temperature drops

 

 

 

 

 

 

 

 

(42°C)

 

 

 

 

Me+

 

 

 

99°F

(42°C)

 

 

 

 

Hi

 

 

 

 

 

99°F

102°F

 

 

 

 

 

 

 

(37°C)

102°F

 

 

 

 

 

 

 

 

 

(37°C)

(39°C)

 

 

Lo

 

 

 

 

93°F

(39°C)

 

 

Lo

 

 

 

 

 

 

96°F

99°F

 

 

 

 

 

 

 

 

 

99°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(34°C)

 

 

 

 

 

 

 

 

 

 

(34°C)

 

 

 

 

 

 

 

 

 

(37°C)

 

 

Cool air

 

 

 

 

90°F

(37°C)

 

 

Cool air

 

 

 

 

 

 

90°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

86°F

 

 

 

prevention

 

 

 

(32°C)

86°F

 

 

 

prevention

 

 

 

 

 

(32°C)

(30°C)

 

 

S-Lo

 

 

 

82°F

(30°C)

 

 

S-Lo

 

 

 

 

 

82°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(28°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

(28°C)

7. MOISTURE RETURN PREVENTION CONTROL (Cooling mode& Dry mode)

Switch the airflow [Auto] at cooling mode, and the indoor fan motor will run as shown in Fig.7. ( Fig.7 : Indoor fan control )

Compressor ON

OFF

Indoor fan

Setting air flow

Indoor fan

(as shown in Table 6)

S-Lo

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

10

30

60

 

180

60

180

60

10

30

( Table 6 : Indoor fan speed )

 

 

 

 

 

 

 

(sec)

 

 

 

 

 

 

 

 

 

 

Dry

 

 

Cooling

 

 

 

 

 

X zone

J zone

 

Y zone

 

 

 

 

 

 

 

 

 

 

 

ASU9 /12RLS2

650rpm

610rpm

0

570rpm

650rpm

 

 

 

 

ASU15RLS2

740rpm

710rpm

0

570rpm

740rpm

 

 

 

 

01-05

6. OUTDOOR FAN CONTROL

1. Outdoor Fan Motor

Following table shows the type of the outdoor fan motor. The control method is different between AC motor and DC motor.

( Table 7 : Type of Motor )

AC Motor

DC Motor

AOU9 / 12 / 15RLS2

2. Fan Speed

 

( Table 8 : Outdoor fan speed )

 

 

(rpm)

 

 

 

 

Zone

 

 

 

Cooling

 

Heating

Dry

 

 

 

 

Y

 

1050/ 870/ 720/ 590/ 530

 

 

 

AOU9RLS2

Z

 

870/530/300

 

 

 

1100/ 870/ 780/ 720/ 590/ 480

530

 

F

 

300/ 250

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

G

 

250/ 200

 

 

 

 

 

 

 

 

 

Y

 

1050/ 870/ 720/ 590/ 530

 

 

 

AOU12RLS2

Z

 

870/530/300

 

 

 

1100/ 870/ 780/ 720/ 590/ 480

530

 

F

 

300/ 250

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

G

 

250/ 200

 

 

 

 

 

 

 

 

 

Y

 

1050/ 870/ 720/ 530

 

 

 

AOU15RLS2

Z

 

870/ 530/ 300

 

1100/ 1000/ 780/ 720/ 590/ 480

530

 

F

 

300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

G

 

250/ 200

 

 

 

 

 

 

Refer to Fig.8

 

 

 

 

 

 

 

 

 

 

 

 

( Fig.8 : Outside air temperature zone selection )

 

 

 

 

Outside air

 

 

 

 

 

 

Outside air

 

 

temperature

 

 

D zone

temperature

 

 

70°F

 

 

 

 

 

 

 

 

(21°C)

 

 

 

F zone

 

 

 

 

66°F

 

 

 

 

 

 

 

 

 

 

 

 

 

54°F

 

 

 

 

 

 

(19°C)

 

 

(12°C)

 

 

 

G zone

 

 

 

 

 

50°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

36°F

 

 

 

 

 

 

 

(10°C)

 

 

(2°C)

 

 

 

H zone

 

 

 

 

 

32°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

( 0°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*The outdoor fan speed mentioned above depends on the compressor frequency.

(When the compressor frequency increases, the outdoor fan speed also changes to the higher speed. When the compressor frequency decreases, the outdoor fan speed also changes to the lower speed.)

*After the defrost control is operated on the heating mode, the fan speed keeps at the higher speed as table 9 without relating to the compressor frequency.

( Table 9 : Outdoor fan speed after the defrost )

AOU9RLS2

1100rpm

AOU12RLS2

1100rpm

AOU15RLS2

1100rpm

01-06

Fujitsu ASU9RLS2 Service instructions manual

7. LOUVER CONTROL

1. VERTICAL LOUVER CONTROL

(Function Range)

Each time the button is pressed, the air direction range will change as follow: Fig.9 : Air Direction Range

Types of Air flow Direction Setting:

,

,

 

: During Cooling/Dry modes

,

,

,

: During Heating

The Remote Controller's display does not change.

1

2

3

4

5

6

7

Use the air direction adjustments within the ranges shown above.

The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected. Cooling / Dry mode Horizontal flow

Heating mode

Downward flow

During AUTO mode operation, for the first a few minutes after beginning operation, air-flow will be horizontal 1; the air direction cannot be adjusted during this period.

The air flow direction setting will temporarily become 1 when the temperature of the air -flow is low at the start of the Heating mode.

2. ADJUST THE RIGHT-LEFT LOUVERS

Move the Right-Left louvers to adjust air flow in the direction you prefer.

Right-Left Louvers

Knob

Knob (2 places)

2. SWING OPERATION

To select Vertical Airflow Swing Operation

When the swing signal is received from the remote controller, the vertical louver starts to swing. (Table10 : Swinging Range)

Range

Cooling / Dry mode

Fan mode ( )

Heating mode

)

Fan mode (

The SWING operation may stop temporarily when the air conditioner’s fan is not operating, or when operating at very low speeds.

To select Horizontal Airflow Swing Operation

(No function)

01-07

8.COMPRESSOR CONTROL

1.OPEARTION FREQUENCY RANGE

The operation frequency of the compressor is different based on the operation mode as shown in the Table 11.

(Table 11 : Compressor frequency range)

 

Cooling / Dry

Heating

 

 

 

 

 

 

Minimum

Maximum

Minimum

Maximum

 

 

 

 

 

AOU9RLS2

10rps

76rps

10rps

119rps

AOU12RLS2

10rps

76rps

10rps

119rps

AOU15RLS2

12rps

91rps

16rps

140rps

2.OPEARTION FREQUENCY CONTROL AT NORMAL START UP

The compressor frequency soon after the start-up is controlled as shown in the Fig.10

(Fig.10 : Compressor control at start-up)

Frequency

 

 

 

 

 

 

Frequency

 

 

 

 

 

 

Frequency

 

 

 

 

 

 

Frequency

 

 

 

 

 

 

Frequency

 

 

 

 

 

 

Frequency

 

 

 

 

 

 

(Frequency)

Time

Time

Time

Time

Time

Time 6

 

 

 

 

 

 

Frequency Frequency Frequency Frequency Frequency Frequency

AOU9RLS2

40rps

57rps

72rps

80rps

101rps

110rps

AOU12RLS2

 

 

 

 

 

 

AOU15RLS2

40rps

59rps

72rps

80rps

101rps

110rps

(Time)

 

 

 

 

 

 

 

Time

Time

Time

Time

Time

Time 6

 

 

 

 

 

 

 

AOU9RLS2

 

 

 

 

 

 

AOU12RLS2

80sec

110sec

140sec

200sec

350sec

410sec

AOU15RLS2

 

 

 

 

 

 

3.LIMITATION OF COMPRESSOR FREQUENCY BY OUTDOOR TEMPERATURE

The minimum compressor frequency is limited by outdoor temperature as shown in the Table12.

(Table12 : Limitation of Compressor Frequency)

[ Cooling/ Dry ]

 

 

10°C

 

14°C

 

40°C

 

 

 

 

 

Under

 

Over

Under

Over

Under

Over

 

 

 

AOU9RLS2

35rps

 

18rps

 

10rps

 

15rps

 

 

 

AOU12RLS2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[ Heating ]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- 5°C

 

3°C

 

7°C

 

18°C

 

 

Under

 

Over

Under

Over

Under

Over

Under

Over

AOU9RLS2

35rps

 

29rps

 

18rps

 

10rps

 

16rps

AOU12RLS2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[ Cooling/ Dry ]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0°C

 

 

10°C

 

40°C

 

 

 

 

 

Under

 

Over

Under

Over

Under

Over

 

 

 

AOU15RLS2

24rps

 

18rps

 

12rps

 

16rps

 

 

 

[ Heating ]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7°C

 

 

14°C

 

 

 

 

 

 

 

 

Under

 

Over

Under

Over

 

 

 

 

 

 

AOU15RLS2

24rps

 

18rps

 

16rps

 

 

 

 

 

 

01-08

9. TIMER OPEARTION CONTROL

9-1 WIRELESS REMOTE CONTROLLER

The Table 13 shows the available timer setting based on the product model. ( Table 13 : Timer Setting )

ON TIMER / OFF TIMER PROGRAM TIMER

SLEEP TIMER WEEKLY TIMER

ASU9/ 12/ 15RLS2

1. OPEARTION FREQUENCY RANGE

OFF timer : When the clock reaches the set time, the air conditioner will be turned off.

Operation mode

Stop mode

Set time of timer

ON timer : When the clock reaches the set time, the air conditioner will be turned on.

Operation mode

Stop mode

Set time of timer

2. PROGRAM TIMER

The program timer allows the OFF timer and ON timer to be used in combination one time.

Operation mode

Operation mode

Operation mode

 

Stop mode

Stop mode

 

Stop mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set time

Set time

Set time

Set time

Operation will start from the timer setting (either OFF timer or ON timer) whichever is closest to the clock's current timer setting.

The order of operations is indicated by the arrow in the remote control unit's display. SLEEP timer operation cannot be combined with ON timer operation.

01-09

3. SLEEP TIMER

If the sleep is set, the room temperature is monitored and the operation is stopped automatically. If the operation mode or the set temperature is change after the sleep timer is set, the operation is continued according to the changed setting of the sleep timer from that time ON.

In the cooling operation mode

When the sleep timer is set, the setting temperature is increased 2°F(1°C). It increases the setting temperature another 2°F(1°C) after 1 hour.

After that, the setting temperature is not changed and the operation is stopped at the time of timer setting.

Set temperature rises ( Ts : Set temperature )

+4°F (2°C)

 

 

 

 

 

+2°F (1°C)

 

 

 

Stop of operation

Ts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set

60min

In the heating operation mode

 

 

 

When the sleep timer is set, the setting temperature is decreased 2°F(1°C). It decreases the setting temperature another 2°F(1°C) every 30 minutes.

Upon lowering 8°F(4°C) the setting temperature is not changed and the operation stops at the time of timer setting.

Set temperature lowers ( Ts : Set temperature )

Ts

-2°F (-1°C)

-4°F (-2°C)

-6°F (-3°C)

-8°F (-4°C)

Stop of operation

Set 30min 30min 30min

4. WEEKLY TIMER

This timer function can set operation times of the each day of the week.

All days can be set together,the weekly timer can be used to repeat the timer setting for all of the days.

 

ON

 

OFF

ON

OFF

ON

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting day

 

 

 

 

Setting day

 

 

 

Setting day

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set time

 

Set time

 

 

 

 

 

 

 

 

 

 

 

 

01-10

9-2 WIRED REMOTE CONTROLLER (OPTION)

The Table14 shows the available timer setting based on the product model. ( Table14 : Timer Setting )

ON TIMER / OFF TIMER WEEKLY TIMER TEMPERATURE SET BACK TIMER

ASU9/ 12/ 15RLS2

1. ON TIMER / OFF TIMER

Same to 9-1 1.ON TIMER / OFF TIMER and shown in those.

2. WEEKLY TIMER

This timer function can set operation times of the each day of the week.

All days can be set together,the weekly timer can be used to repeat the timer setting for all of the days.

 

ON

 

OFF

ON

OFF

ON

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting day

 

 

 

 

Setting day

 

 

 

Setting day

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set time

 

Set time

 

 

 

 

 

 

 

 

 

 

 

 

3. TEMPERATURE SET BACK TIMER

This timer function can change setting temperature of setting operation times of the each day of the week. This can be together with other timer setting.

 

 

 

ON

 

OFF

 

Set back tmp.

 

 

 

 

 

 

 

 

 

 

 

Normal tmp.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set time

 

Set time

 

01-11

10. ELECTRONIC EXPANSION VALVE CONTROL

The most proper opening of the electronic expansion valve is calculated and controlled under the present operating condition based on the Table15.

The compressor frequency, the detected temperature by the discharge temperature sensor,

the indoor heat exchanger sensor, the outdoor heat exchanger sensor, and the outdoor temperature sensor. ( Table15 : The pulse range of the electronic expansion valve control )

 

Operation mode

Pulse range

AOU9RLS2

Cooling / Dry mode

Between 60 to 480 pulses.

 

 

AOU12RLS2

Heating mode

Between 45 to 480 pulses.

 

 

 

 

AOU15RLS2

Cooling / Dry mode

Between 60 to 480 pulses.

Heating mode

 

 

The expansion valve is set at 480 pulses 110seconds after the compressor had stopped.

Initialization will start after 24 hours pass from the last initialization, and the compressor stops

At the time of supplying the power to the outdoor unit, the initialization of the electronic expansion valve is operated (528 pulses are input to the closing direction).

11. TEST OPERATION CONTROL

[ Operation method ]

The outdoor unit, may not operate, depending on the room temperature.

In this case, keep on pressing the MANUAL AUTO button of the indoor unit for more than 10 seconds. The Operation lamp and Timer lamp will begin to flash simultaneously during cooling test run.

Then, heating test run will begin in about 3 minutes when HEAT is selected by the remote control operation. (When the air conditioner is running by pressing the test run button, the Operation lamp and Timer lamp will simultaneously flash slowly.)

[ Release ]

Perform the test operation for 60 minutes.

Pressing the MANUAL AUTO button of the indoor unit for more than 3 seconds.

[ Using the Wired remote control (Option) ]

If the Operation lamp is on, press the START/STOP button to turn it off.

Press the MODE and the FAN buttons at the same time for more than two seconds to start the test operation.

The operation lamp will light up and "o1" will be displayed on the set temperature display.

[ Release ]

Perform the test operation for 60 minutes.

Pressing the START/STOP button will stop the test operation.

12. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST )

The compressor won't enter operation status for 2 minutes and 20 seconds after the compressor is stopped, even if any operation is given.

13. FOUR-WAY VALVE EXTENSION SELECT

At the time when the air conditioner is switched from the cooling mode to heating mode, the compressor is stopped, and the four-way valve is switched in 2 minutes and 20 seconds later after the compressor stopped.

01-12

14. AUTO RESTART

When the power was interrupted by a power failure, etc. during operation, the operation contents at that time are memorized and when power is recovered, operation is automatically started with the memorized operation contents.

When the power is interrupted and recovered during timer operation, since the timer operation time is shifted by the time the power was interrupted, an alarm is given by blinking (7 sec ON/2 sec OFF) the indoor unit body timer lamp.

[ Operation contents memorized when the power is interrupted ]

Operation mode

Set temperature

Set air flow

Timer mode and set time (set by wireless remote controller)

Set air flow Direction

Swing

ECONOMY operation

10°C HEAT operationOutdoor low noise operation Human sensor

15. MANUAL AUTO OPERATION (Indoor unit body operation)

When the remote control is lost or battery power dissipated, this function will work without the remote control. When MANUAL AUTO button is set more than 3seconds and less than 10seconds, MANUAL AUTO OPERATION will be started as shown in Table16.To stop operation, press the MANUAL AUTO button for 3seconds.

(Table16 : MANUAL AUTO OPERATION)

 

Manual auto operation

OPERATION MODE

Auto changeover

FAN CONT. MODE

Auto

TIMER MODE

Continuous (No timer setting available)

SETTING TEMP.

75°F(24°C)

SETTING LOUVER

Standard

SWING

OFF

ECONOMY

OFF

 

AUTO

MANUAL AUTO

Press and hold MANUAL

button for 3 ~ 10seconds

button

16. FORCED COOLING OPERATION (TEST OPERATION)

When FORCED COOLING OPERATION is set, the operation is controlled as shown in Table17. ( Table17 : FORCED COOLING OPERATION )

 

Forced cooling operation

OPERATION MODE

Cooling

FAN CONT. MODE

Hi

TIMER MODE

-

SETTING TEMP.

Room Temp is not controlled

SETTING LOUVER

Horizontal

 

(It is changed follow as setting of remote controller)

SWING

OFF

ECONOMY

-

Forced cooling operation is started when press MANUAL AUTO button for 10 seconds or more.

During the forced cooling operation, it operates regardless of room temperature sensor.

Operation LED and timer LED blink at the same time during the forced cooling operation.

They blink for 1 second ON and 1 second OFF on both operation LED and timer LED (same as test operation).

Forced cooling operation is released after 60 minutes of starting operation or pressing MANUAL AUTO button for 3 seconds.

01-13

17. COMPRESSOR PREHEATING

When the outdoor heat exchanger temperature is lower than 41°F(5°C) and the all operation has been stopped for 30 minutes, power is applied to the compressor and the compressor is heated. (By heating the compressor, warm air is quickly discharged when operation is started.)

When operation was started, and when the outdoor heat exchanger temperature rises to 44.6°F(7°C) or greater, preheating is ended.

18. MIN. (MINIMUM) HEAT OPERATION

MIN. HEAT OPERATION performs as below when pressing MIN. HEAT button or Weekly timer setting on the remote controller.

( Table 18 : MIN. HEAT OPERATION )

Mode

Heating

Setting temperature

50°F(10°C)

Fan mode

Auto

 

LED display

Economy

Defrost operation

Operate as normal

 

 

 

19. ECONOMY OPERATION

The ECONOMY operation functions by pressing ECONOMY button on the remote controller.

At the maximum output, ECONOMY Operation is approximately 70% of normal air conditioner operation for cooling and heating.

The ECONOMY operation is almost the same operation as below settings. ( Table 19 )

Mode

Cooling/ Dry

Heating

 

 

 

Target temperature

Setting temp.+2°F(+1°C)

Setting temp.-2°F(-1°C)

 

 

 

20 . HUMAN SENSOR CONTROL

The HUMAN SENSOR functions by pressing SENSOR button on the remote controller. When the sensor detects that there is no one in the room for 20 minutes or more,

it automatically changes the operation as below settings.

When someone comes back into the room, the human sensor will detect this, and automatically revert to the original settings.

( Table 20 )

Mode

Cooling/ Dry

Heating

 

 

 

Target temperature

Setting temp.+4°F(+2°C)

Setting temp.-8°F(-4°C)

 

 

 

( Application range )

Vertical angle 90°(Side view)

6 m

90°

Horizontal angle 100°(Top view)

 

6 m

50°

50°

The sensor unit should detect when the human body (estimate: 100cmX30cm) or the object which has more than 39°F(4°C) temp, difference from the background and are crossed with 1.0m/s speed in front of the sensor unit.

01-14

21. OUTDOOR UNIT LOW NOISE OPERATION

The OUTDOOR UNIT LOW NOISE Operation functions by pressing OUTDOOR UNIT LOW NOISE button on the remote controller.

This operation stops the PFC control, and changes the Current release operation/release value.

OUTDOOR UNIT LOW NOISE Operation mode can be used during cooling, heating and automatic operation. It can not be used in Fan and Dry mode

( Table 21 )

 

Control / Release

 

 

Current release

3.5A / 3.0A

operation/release value

 

22. POWERFUL OPERATION

The POWERFUL OPERATION functions by pressing POWERFUL button on the remote controller. The indoor unit & outdoor unit will operate at maximum power as shown in Table22.

(Table22)

 

Powerful operation

COMPRESSOR FREQUENCY

Maximum

FAN CONT. MODE

Powerful

 

 

SETTING LOUVER

Cooling/ Dry : 3, Heating : 5

Release Condition is as follows. [Cooling / Dry]

- Room tenperature < Setting temperature -3°F(- 1.5°C) or Operation time has passed 20 minutes.

=

[Heating]

- Room tenperature > Setting temperature +3.5°F(+1.5°C) or Operation time has passed 20 minutes.

=

23. BASE HEATER OPERATION

The base heater is operated as shown in Figure 11.

( Fig.11 : Base heater control )

When outdoor

 

 

When outdoor

temperature drops

 

 

temperature rises

 

 

 

OFF

 

 

41°F

 

 

 

 

 

 

 

 

 

 

 

35.6°F

 

 

 

 

(5°C)

 

 

 

 

 

(2°C)

 

 

ON

 

 

 

 

 

 

 

 

 

When the compressor stops, Base heater is OFF.

When the outdoor fan motor stops, Base heater is OFF.

In the cooling mode, Base heater is OFF.

In the defrost operation, Base heater maintains the same status as before the compressor stops.

01-15

24. DEFROST OPERATION CONTROL

1.CONDITION OF STARTING THE DEFROST OPERATION

The defrost operation starts as shown in the following Table 23.

(Table 23 : Condition of starting Defrost Operation)

Normal defrost

Compressor integrating operation time

 

 

 

 

 

Less than 25 minutes (9/12RLS2)

More than 25 minutes (9/12RLS2)

 

 

Less than 40 minutes (15RLS2)

More than 40 minutes (15RLS2)

 

 

 

 

 

 

 

Does not operate

Outdoor heat exchanger temp. < 1.4°F(-17°C)

 

 

=

 

 

 

 

(at outside air temp. > 14°F(-10°C)

 

 

 

=

 

 

 

 

Outdoor heat exchanger temp. < Outside air temp.- 44.6°F(7°C)

 

 

 

=

 

 

 

 

or Outdoor heat exchanger temp. < -13°F(- 25°C)

 

 

 

=

 

 

 

 

(at outside air temp. < 14°F(-10°C)

 

 

 

 

 

 

 

 

 

 

Integrating defrost

Compressor integrating operation time

 

 

 

 

 

 

More than 210 minutes

Less than 10 minutes

 

 

 

(For continuous operation)

( For intermittent operation )

 

 

 

Outdoor heat exchanger

OFF count of the compressor

 

 

 

temperature below 26.6°F(-3°C)

40 times

 

 

 

 

 

 

If the compressor continuous operation time is less than 10 minutes, the OFF number of the compressor is counted.

If any defrost operated, the compressor OFF count is cleared.

2. CONDITION OF THE DEFROST OPERATION COMPLETION

Defrost operation is released when the conditions become as shown in Table 24. (Table 24 : Defrost Release Condition)

Release Condition

Outdoor heat exchanger temperature sensor value is higher than 60.8°F(16°C) or

Compressor operation time has passed 15 minutes.

01-16

3. Defrost Flow Chart

The defrosting shall proceed by the integrating operation time, outdoor temperature and outdoor heat exchanger temperature as follows.

 

 

 

 

 

Heating operation start : Compressor ON

 

 

 

 

 

 

 

 

 

 

 

 

 

(Not defrosted for 10 minutes)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal

defrost

 

 

Integrating

 

defrost

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outside air temp. > 14°F

Outside air

temp. < 14°F

Intermittent

operation

 

Continuous

operation

 

 

= (-10°C)

 

 

(-10°C)

 

 

 

 

 

 

 

 

 

Outdoor HEX temp.

 

 

Outdoor HEX temp.

 

 

Compressor

 

 

Compressor

 

 

 

Below 1.4°F(-17°C)

 

 

< Outside air temp.

 

 

OFF count :

 

 

integrating

 

 

 

 

 

=

 

 

 

40 times

 

 

operation:

 

 

 

 

 

 

 

-44.6°F(7°C)

 

 

 

 

 

 

 

 

 

 

 

or

 

 

(Less than 10min.)

 

 

Over 210

min.

 

 

 

 

 

 

Outdoor HEX temp.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Below - 25°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

heat exchanger

 

 

 

 

 

 

 

 

 

 

 

 

 

 

temperature:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Below 26.6°F(-3°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Defrost start

Defrost Indicator: [Operation lamp]

7 sec ON / 2 sec OFF

Outdoor fan : OFF Compressor speed : 0 rps EEV : 480pulse

4-way valve : OFF

Compressor speed : 70rps (9/12RLS2) 80rps (15RLS2)

Outdoor HEX temp.: Over 60.8°F(16°C) or

Compressor ON time: Maximum 15 minutes

Defrost end

01-17

25. OFF DEFROST OPEARTION CONTROL

When operation stops in the [Heating operation] mode, if frost is adhered to the outdoor unit heat exchanger, the defrost operation will proceed automatically. In this time, if indoor unit operation lamp flashes slowly (7 sec ON / 2 sec OFF), the outdoor unit will allow the heat exchanger to defrost, and then stop.

1. OFF DEFROST OPERATION CONDITION

In heating operation, the outdoor heat exchanger temperature is less than 24.8°F(- 4°C), compressor continuous operation more than 10 minutes, and

compressor operation integrating time lasts for more than 30 minutes.

2. OFF DEFROST END CONDITION

Release Condition

Outdoor heat exchanger temperature sensor value is higher than 60.8°F(16°C) or Compressor operation time has passed 15 minutes.

OFF Defrost Flow Chart

Heating operation stop

Outdoor heat exchanger temperature :

Below 24.8°F(- 4°C)

Compressor continuous operation :

Over 10 minutes

Compressor integrating operation :

Over 30 minutes

Defrost start

Defrost Indicater: [Operation lamp]

7 sec ON / 2 sec OFF

Outdoor heat exchanger temperature:

Over 60.8°F(16°C) or

Compressor ON time: Over 15 minutes

Defrost end

01-18

26. VARIOUS PROTECTIONS

1.DISCHARGE GAS TEMPERATURE OVERRISE PREVENSION CONTROL

The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas temperature.

When the discharge temperature becomes higher than Temperature , the compressor frequency is decreased 20rps, and it continues to decrease the frequency for 20rps every 120 seconds until the temperature becomes lower than Temperature .

When the discharge temperature becomes lower than Temperature, the protection control of the compressor frequency will be released.

When the discharge temperature becomes higher than Temperature, the compressor is stopped and the indoor unit LED starts blinking.

( Table 25 : Discharge temperature over rise prevension control / Release temperature )

Temperature

Temperature

Temperature

219.2°F

213.8°F

230°F

(104°C)

(101°C)

(110°C)

 

 

 

2.CURRENT RELEASE CONTROL

The compressor frequency is controlled so that the outdoor unit input current does not exceed the current limit value that was set up with the outdoor temperature.

The compressor frequency returns to the designated frequency of the indoor unit at the time when the frequency becomes lower than the release value.

( Table 26 : Current release operation value / Release value )

[ Heating ]

AOU9 / 12RLS2

OT (Control / Release)

62.6°F

7.0A / 6.5A

 

(17°C)

9.0A / 8.5A

53.6°F

 

(12°C)

10.0A / 9.5A

41°F

 

(5°C)

10.0A / 9.5A

OT : Outdoor Temperature

[ Heating ]

AOU15RLS2

OT (Control / Release)

62.6°F

7.0A / 6.5A

 

(17°C)

9.0A / 8.5A

53.6°F

 

(12°C)

11.0A / 10.5A

41°F

 

(5°C)

13.0A / 12.5A

OT : Outdoor Temperature

[ Cooling ]

AOU9 / 12RLS2

OT (Control / Release)

114.8°F

4.5A / 4.0A

(46°C)

 

6.0A / 5.5A

104°F

 

 

 

(40°C)

8.5A / 8.0A

OT : Outdoor Temperature

[ Cooling ]

AOU15RLS2

OT (Control / Release)

114.8°F 4.5A / 4.0A

(46°C)

6.0A / 5.5A

104°F

 

(40°C)

9.0A / 8.5A

 

OT : Outdoor Temperature

01-19

Loading...
+ 52 hidden pages