Fujitsu ASU9RLQ Service Manual

5 (1)

SPLIT TYPE

ROOM AIR CONDITIONER

WALL MOUNTEDtype

INVERTER

SERVICE INSTRUCTION

Models Indoor unit

Outdoor unit

ASU9RLQ

AOU9RLQ

ASU12RLQ

AOU12RLQ

ASU18CL

AOU18CL

ASU18RL

AOU18RL

R410A

CONTENTS

1. SPECIFICATION

ASU9/12RLQ, AOU9/12RLQ, ASU18C/RL, AOU18C/RL...............................................

01-01

2. DIMENSIONS

ASU9/12RLQ, AOU9/12RLQ..........................................................................................

02-01

ASU18C/RL, AOU18C/RL...............................................................................................

02-02

3. REFRIGERANT SYSTEM DIAGRAM

ASU9/12RLQ, AOU9/12RLQ..........................................................................................

03-01

ASU18C/RL, AOU18C/RL...............................................................................................

03-02

4. CIRCUIT DIAGRAM

ASU9/12RLQ, AOU9/12RLQ...........................................................................................

04-01

ASU18C/RL, AOU18C/RL...............................................................................................

04-02

5. DESCRIPTION OF EACH CONTROL OPERATION

1. COOLING OPERATION..............................................................................................

05-01

2. HEATING OPERATION..............................................................................................

05-02

3. DRY OPERATION......................................................................................................

05-03

4. AUTO CHANGEOVER OPERATION.........................................................................

05-04

5. INDOOR FAN CONTROL...........................................................................................

05-05

6. OUTDOOR FAN CONTROL.......................................................................................

05-07

7. LOUVER CONTROL...................................................................................................

05-08

8. COMPRESSOR CONTROL........................................................................................

05-09

9. TIMER OPERATION CONTROL................................................................................

05-10

10. ELECTRONIC EXPANSION VALVE CONTROL........................................................

05-12

11. TEST OPERATION CONTROL..................................................................................

05-12

12. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST )................................

05-12

13. FOUR-WAY VALVE EXTENSION SELECT...............................................................

05-12

14. AUTO RESTART........................................................................................................

05-12

15. MANUAL AUTO OPERATION ( Indoor unit body operation ).....................................

05-13

16. FORCED COOLING OPERATION............................................................................

05-13

17. COMPRESSOR PREHEATING..................................................................................

05-13

18. COIL DRY OPEARTION CONTROL..........................................................................

05-13

19. DEFROST OPERATION CONTROL..........................................................................

05-14

20. OFF DEFROST OPERATION CONTROL..................................................................

05-16

21. VARIOUS PROTECTIONS.........................................................................................

05-17

6. REFRIGERANT CAUTION -R410A-

1. R410A TOOLS............................................................................................................

06-01

2. PRECAUTION FOR INSTALLATION.........................................................................

06-02

3. PRECAUTION FOR SERVICING...............................................................................

06-04

4. NEW REFRIGERANT R410A.....................................................................................

06-05

5. DEFFERENCE FROM CONVENTIONAL MODEL(R22) AND PRECAUTIONS........

06-08

7. TROUBLE SHOOTING

1. WHEN THE UNIT DOES NOT OPERATE AT ALL....................................................

07-01

2. SELF DIAGNOSIS FUNCTION..................................................................................

07-02

3. TROUBLE SHOOTING METHOD

 

4. SELF-DIAGNOSIS FUNCTION AND CHECKING POINTS.......................................

07-03

5. SERIAL SIGNAL DIAGNOSIS....................................................................................

07-07

6. IPM PROTECTION.....................................................................................................

07-08

7. TROUBLE SHOOTING OF REFRIGERANT CYCLE.................................................

07-09

8. APPENDING DATA

1. JUMPER SETTING OF INDOOR UNIT AND OUTDOOR UNIT................................

08-01

2. OUTDOOR UNIT PRESSURE VALUE AND TOTAL ELECTRIC

 

CURRENT CURVE...................................................................................................

08-02

3. THERMISTOR RESISTANCE VALUES.....................................................................

08-06

4. CAPACITY/INPUT DATA...........................................................................................

08-07

9. REPLACEMENT PARTS

1. EXPLODED VIEW......................................................................................................

09-01

2. INVERTER ASSEMBLY SPECIFICATION.................................................................

09-07

10. INSTALLATION MANUAL

R410A

WALL MOUNTED type

INVERTER

1 . SPECIFICATIONS

SPECIFICATIONS

 

MODEL NAME

 

 

ASU9RLQ

ASU12RLQ

ASU18CL

ASU18RL

 

 

 

AOU9RLQ

AOU12RLQ

AOU18CL

AOU18RL

 

 

 

 

 

 

 

 

 

PHASE

 

Ph

1

1

1

1

POWER SOURCE

 

FREQUENCY

 

Hz

60

60

60

60

 

 

 

VOLTAGE

 

V

208-230

208-230

208-230

208-230

 

 

 

 

 

kW

2.64

3.51

5.28

5.28

 

CAPACITY (230V)

 

 

(1.05~3.51)

(1.11~4.26)

(1.62~5.58)

(1.62~5.58)

 

 

 

 

 

 

 

Btu /h

9,000

12,000

18,000

18,000

 

 

 

 

 

 

 

 

 

 

(3,600~12,000)

(3,800~14,500)

(5,500~19,000)

(5,500~19,000)

 

 

 

 

 

 

 

POWER CONSUMPTION (230V)

 

W

670

960

1,730

1,730

 

 

(200~1,200)

(200~1,500)

(250~2,000)

(250~2,000)

 

 

 

 

 

 

 

EER

 

 

W /W

3.93

3.66

3.05

3.05

 

 

 

Btu /(h.W)

13.4

12.5

10.4

10.4

 

 

 

 

 

COOLING

SEER

 

 

Btu /(h.W)

21.00

21.00

19.00

19.00

RUNNING CURRENT

 

 

A

3.2

4.5

7.7

7.7

PERFORMANCE

 

 

POWER FACTOR

 

 

%

90

93

98

98

 

 

 

 

MAXIMUM CURRENT

 

 

A

6.0

7.0

9.0

9.0

 

MOISTURE REMOVAL

 

 

L /hr

1.3

1.8

2.8

2.8

 

 

 

Pt /h

2.7

3.8

5.9

5.9

 

 

 

 

 

 

 

 

 

HI

dB

39

41

44

44

 

OPERATING NOISE

 

INDOOR UNIT

ME

dB

34

35

38

38

 

 

LO

dB

29

29

32

32

 

(SOUND PRESSURE)

 

 

 

 

 

QUIET

dB

20

20

25

25

 

 

 

 

 

 

 

OUTDOOR UNIT

 

dB

47

47

50

50

 

 

 

 

 

kW

3.51

4.68

-

6.30

 

CAPACITY

 

 

(0.87~5.28)

(0.90~6.18)

-

(1.32~8.52)

 

 

 

 

 

 

 

Btu /h

12,000

16,000

-

21,600

 

 

 

 

 

 

 

 

 

 

(3,000~18,000)

(3,000~21,000)

-

(4,600~29,000)

 

 

 

 

 

 

 

POWER CONSUMPTION

 

 

W

830

1,250

-

1,930

 

 

 

(200~1,800)

(200~2,140)

-

(250~2,930)

 

 

 

 

 

 

 

COP

 

 

W /W

4.25

3.75

-

3.28

HEATING

 

 

Btu /(h.W)

14.5

12.8

-

11.2

 

 

 

 

HSPF

 

 

Btu /(h.W)

11.00

10.55

-

10.00

PERFORMANCE

 

 

RUNNING CURRENT

 

 

A

3.9

5.7

-

8.6

 

 

 

 

POWER FACTOR

 

 

%

92

95

-

98

 

MAXIMUM CURRENT

 

 

A

8.5

10.0

-

13.5

 

 

 

 

HI

dB

40

41

-

42

 

OPERATING NOISE

 

INDOOR UNIT

ME

dB

35

35

-

37

 

 

LO

dB

28

28

-

32

 

(SOUND PRESSURE)

 

 

 

 

 

QUIET

dB

21

21

-

27

 

 

 

 

 

 

 

OUTDOOR UNIT

 

dB

47

48

-

50

 

COMPRESSOR

 

TYPE

 

-

Rotary

Rotary

Rotary

Rotary

 

 

OUTPUT

 

W

750

750

1,100

1,100

 

 

 

 

 

 

 

INDOOR UNIT

 

m3 /h

560

595

700

700

 

AIR CIRCULATION

 

 

cfm

329

374

412

412

 

 

 

 

 

(FAN MODE)

 

OUTDOOR UNIT

 

m3 /h

2,060

1,850

2,000

2,000

 

 

 

 

cfm

1,211

1,088

1,176

1,176

 

 

 

 

 

OTHER

STARTING CURRENT

 

 

A

3.9

5.7

7.7

8.6

MINIMUM CIRCUIT AMPACITY

 

A

10

12

16

16

INDICATION

 

MAXIMUM OVERCURRENT PROTECTION

 

A

20

20

20

20

 

 

 

DESIGN PRESSURE

 

HIGH SIDE

 

PSI(MPa)

450(3.10)

450(3.10)

450(3.10)

450(3.10)

 

 

LOW SIDE

 

PSI(MPa)

240(1.65)

240(1.65)

240(1.65)

240(1.65)

 

 

 

 

 

 

COOLING

 

°F

14~115

14~115

14~115

14~115

 

PERMISSIBLE OUTDOOR

 

°C

-10~46

-10~46

-10~46

-10~46

 

TEMPERATURE

 

HEATING

 

°F

5~75

5~75

-

5~75

 

 

 

 

°C

-15~24

-15~24

-

-15~24

 

 

 

 

 

01-01

SPECIFICATIONS

 

MODEL NAME

 

 

ASU9RLQ

ASU12RLQ

ASU18CL

ASU18RL

 

 

 

 

AOU9RLQ

AOU12RLQ

AOU18CL

AOU18RL

 

 

 

 

 

 

 

 

CONNECTING METHOD

 

-

Flare

Flare

Flare

Flare

 

 

 

LIQUID SIDE

 

mm

6.35

6.35

6.35

6.35

 

 

PIPE SIZE

 

in.

1/4

1/4

1/4

1/4

 

 

 

 

 

 

GAS SIDE

 

mm

9.52

9.52

12.7

12.7

 

 

 

 

 

 

 

 

in.

3/8"

3/8"

1/2"

1/2"

 

 

 

 

 

 

 

STANDARD PIPE LENGTH

 

m

7.5

7.5

7.5

7.5

 

 

 

ft.

25

25

25

25

 

 

 

 

 

 

 

MAXIMUM PIPE LENGTH

 

m

20

20

20

20

 

INSTALLATION

 

ft.

66

66

66

66

 

 

 

 

 

CHARGE LESS PIPE LENGTH

 

m

15

15

15

15

 

 

 

 

 

 

ft.

49

49

49

49

 

 

 

 

 

 

 

AMOUNT OF ADDITIONAL CHARGE

 

g /m

20

20

20

20

 

 

 

oz. /ft.

3 /16

3 /16

3 /16

3 /16

 

 

 

 

 

 

 

MAXIMUM HEIGHT DIFFERENCE

 

m

15

15

15

15

 

 

 

ft.

49

49

49

49

 

 

 

 

 

 

 

NUMBER OF WIRE

 

-

4

4

4

4

 

 

DRAIN HOSE LENGTH

 

mm

580

580

580

580

 

 

 

in.

22-13/16"

22-13/16"

22-13/16"

22-13/16"

 

 

 

 

 

 

 

 

INDOOR UNIT

kg

9.5

9.5

9

9

 

 

NET

lbs.

21

21

20

20

 

 

 

 

 

 

OUTDOOR UNIT

kg

35

37

40

40

 

 

 

 

WEIGHT

 

lbs.

77

82

88

88

 

 

 

 

 

 

INDOOR UNIT

kg

12

12

12

12

 

 

 

 

 

GROSS

lbs.

26

26

26

26

 

 

 

 

 

 

(PACKAGING WEIGHT)

OUTDOOR UNIT

kg

39

41

44

44

 

 

 

lbs.

86

90

97

97

 

 

 

 

 

 

 

 

 

HEIGHT

mm

283

283

275

275

 

 

 

 

in.

11-1/8"

11-1/8"

10-13/16"

10-13/16"

 

 

 

 

 

 

 

 

INDOOR UNIT

WIDTH

mm

790

790

790

790

 

 

 

in.

31-1/8"

31-1/8"

31-1/8"

31-1/8"

 

 

 

 

 

 

 

 

 

DEPTH

mm

230

230

215

215

 

 

MAIN UNIT

 

in.

9-1/16"

9-1/16"

8-7/16"

8-7/16"

 

 

 

 

 

 

DIMENSIONS

 

HEIGHT

mm

540

540

578

578

 

 

 

 

in.

21-1/4"

21-1/4"

22-3/4"

22-3/4"

 

 

 

 

 

 

 

 

OUTDOOR UNIT

WIDTH

mm

790

790

790

790

 

 

 

in.

31-1/8"

31-1/8"

31-1/8"

31-1/8"

 

 

 

 

 

 

 

 

 

DEPTH

mm

290

290

300

300

 

OTHER

 

 

in.

11-7/16"

11-7/16"

11-13/16"

11-13/16"

 

 

 

 

 

INDICATION

 

 

HEIGHT

mm

316

316

290

290

 

 

 

 

in.

12-7/16"

12-7/16"

11-7/16"

11-7/16"

 

 

 

 

 

 

 

 

INDOOR UNIT

WIDTH

mm

835

835

835

835

 

 

 

in.

32-7/8"

32-7/8"

32-7/8"

32-7/8"

 

 

 

 

 

 

 

 

 

DEPTH

mm

360

360

345

345

 

 

PACKAGE

 

in.

14-3/16"

14-3/16"

13-9/16"

13-9/16"

 

 

 

 

 

 

DIMENSIONS

 

HEIGHT

mm

625

625

648

648

 

 

 

 

in.

24-5/8"

24-5/8"

25-1/2"

25-1/2"

 

 

 

 

 

 

 

 

OUTDOOR UNIT

WIDTH

mm

919

919

910

910

 

 

 

in.

36-3/16"

36-3/16"

35-13/16"

35-13/16"

 

 

 

 

 

 

 

 

 

DEPTH

mm

385

385

380

380

 

 

 

 

in.

15-3/16"

15-3/16"

14-15/16"

14-15/16"

 

 

 

 

 

 

 

KIND OF REFRIGERANT

 

 

-

R410A

R410A

R410A

R410A

 

Refrigerant

AMOUNT OF CHARGING

 

kg

0.95

1.05

1.15

1.15

 

 

 

lbs.

2-2/16

2-5/16

2-9/16

2-9/16

 

 

 

 

 

 

01-02

R410A

WALL MOUNTED type

INVERTER

2 . DIMENSIONS

D I M E N S I O N S

Models : ASU9RLQ / AOU9RLQ

(unit : mm)

ASU12RLQ / AOU12RLQ

 

INDOOR UNIT

 

 

790

 

 

 

 

 

230

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

283

OUTDOOR UNIT

 

 

 

 

790

 

290

17

56

 

 

288

 

 

 

540

356

02-01

Fujitsu ASU9RLQ Service Manual

D I M E N S I O N S

Models : ASU18CL / AOU18CL

(unit : mm)

 

ASU18RL / AOU18RL

 

790

215

275

 

508

48

20

347

320

540

125

790

66

300

578

 

 

10

 

 

02-02

 

 

R410A

WALL MOUNTED type

INVERTER

3 . REFRIGERANT SYSTEM DIAGRAM

REFRIGERANT SYSTEM DIAGRAM

Models : ASU9RLQ / AOU9RLQ

ASU12RLQ / AOU12RLQ

Muffler

Compressor

Heat exchanger 3-Way ( INDOOR ) valve

2-Way valve

Muffler

4-Way valve

Strainer

 

Expansion valve

Heat exchanger

Strainer

( OUTDOOR )

 

AOU9RLQ

 

(2Pass)

 

AOU12RLQ

(4Pass)

Cooling

Heating

03-01

REFRIGERANT SYSTEM DIAGRAM

Models : ASU18CL / AOU18CL

ASU18RL/ AOU18RL

3-Way valve

Muffler

Compressor

4-Way valve

 

Sub-accumulator

Heat exchanger ( INDOOR )

Sub-heat

2-Way

valve

exchanger

 

( INDOOR )

 

 

Strainer

 

Expansion valve

Heat exchanger

Strainer

( OUTDOOR )

 

Cooling

Heating

03-02

R410A

WALL MOUNTED type

INVERTER

4 . CIRCUIT DIAGRAM

CIRCUIT DIAGRAM

Models : ASU9RLQ / AOU9RLQ

ASU12RLQ AOU12RLQ

INDOOR UNIT

OUTDOOR UNIT

 

 

 

 

CONTROL BOARD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WHITE

1 1

WHITE

1

 

 

 

 

 

 

 

1

WHITE

 

 

 

2 2

YELLOW

2

CN201

RED

 

 

 

CN4

2

YELLOWRED

4

3

RED

3 3

RED

3

 

1

1 1

 

 

3

BLUE

2

1

 

4

4

BLUE

4

 

WHITE

 

 

4

 

 

 

5 5

5

DISPLAYBOARD

2

2 2

 

 

 

SWITCH

 

 

WHITE

CN3

CN10

1

 

 

 

 

 

8

WHITE

8

8

 

 

 

 

 

 

 

 

 

3

WHITE

3

3

 

 

 

 

 

 

 

 

 

 

 

4

4

4

 

 

2

 

 

 

 

 

 

 

 

 

5

WHITE

5

5

 

 

3

 

 

 

 

 

 

 

 

 

6

WHITE

6

6

 

 

4

 

 

 

 

 

 

 

 

 

 

7

WHITE

7

7

 

 

5

 

 

 

 

 

 

 

 

 

 

9

WHITE

9

9

 

 

1

1

RED

 

1 1

 

 

 

 

 

 

 

 

 

 

 

CN2

2

2

ORANGE

 

2 2

M

 

 

 

 

 

 

 

 

 

 

3 3

YELLOW

 

3 3

STEP MOTOR

 

 

 

 

 

 

 

 

4

4

PINK

 

4 4

 

 

 

 

 

 

 

BLUE

1 1

 

 

5

5

BLUE

 

5 5

 

 

 

 

 

 

 

YELLOW

2 2

 

 

1

BLACK

 

 

 

 

 

 

 

 

 

WHITE

3 3

CN1

CN6

 

 

 

 

 

 

 

F. M.

 

BLACK

4

4

2

BLACK

 

 

 

 

 

 

 

FAN MOTOR

RED

5

5

 

 

 

 

PIPE TEMPERATURE THERMISTOR

 

 

6

6

 

 

 

 

 

 

 

 

 

 

 

 

CN5

1

BLACK

 

 

 

 

 

SW

 

2

BLACK

 

 

 

 

 

 

 

 

ROOM TEMPERATURE THERMISTOR

 

 

POWER CIRCUIT

 

GRAY 3 3

CN7

 

BARISTOR

 

 

 

GRAY

2

2

 

 

 

 

1 1

 

 

 

 

 

 

 

 

 

 

 

 

 

FUSE

 

 

 

 

 

 

 

 

3.15A

 

 

 

 

 

 

W1

W2

W3

W4

 

 

 

 

 

 

WHITE

BLACK

RED

GREEN

 

YELLOW/

THERMAL FUSE 1

2

3

 

 

 

G

102

 

 

 

 

 

 

 

 

 

TERMINAL

 

 

 

 

 

 

GREEN

 

 

 

 

 

 

 

 

 

AIR CLEAN UNIT

04-01

CIRCUIT DIAGRAM

Models : ASU18CL / AOU18CL

ASU18RL / AOU18RL

INDOOR UNIT

 

G 3 2 1 FUSETHERMAL 102 TERMINAL

 

 

GRAY

GRAY

 

 

 

 

3 2 1

 

 

 

 

3 2 1

CIRCUIT POWER

UNITOUTDOOR TO

W1

 

CN7

 

 

 

 

WHITE

 

 

 

W2

 

 

 

BLACK

 

VARISTOR

 

RED W3

FUSE

 

15A3.

 

 

GREEN /

 

 

 

 

 

 

YELLOW

 

 

 

 

 

 

 

 

 

 

RTHERMISTO

TEMPERATURE ROOM

 

OUTDOOR UNIT

 

 

 

MOTOR FAN

 

 

 

 

 

 

 

 

INDICATOR PCB ASSY

 

 

 

FM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CN201

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

6

5

4

3

2

1

 

 

RED

BLUE YELLOW WHITE BLACK

 

 

WHITE

WHITE

WHITE

WHITE

WHITE

WHITE

RED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

5

4

1 2 3

 

 

7

6

5

4

 

3

2

1

 

 

SW

6

5

4

3

2

1

 

 

7

6

5

4

 

3

2

1

 

 

 

 

 

CN1

 

 

 

 

 

 

CN3

 

 

 

 

 

 

 

 

 

 

 

 

CONTROLLER PCB ASSY

CN5

CN6

1 2

1 2

BLACK BLACK

BLACK BLACK

 

TEMPERATURE PIPE THERMISTOR

CN2

CN10

1 2 3 4 5

1 2 3 4 5

1 2 3 4 5

 

RED ORANGE YELLOW PINK BLUE

 

1 2 3 4 5

 

1 2 3 4 5

 

M

 

MOTOR STEP

 

REACTOR

YELLOW

YELLOW

 

 

 

2

1

 

W7

RED

2

1

 

WHITE

 

W8

 

WHITE

W10

BLACK

 

W9

 

RED

 

 

W11

 

 

 

 

 

PIPE TEMP. THERMISTOR

 

 

 

 

1

1

RED

 

 

 

BLACK

1

1

 

 

2

2

BLACK

 

 

 

 

CN801

3

3

 

 

 

BLACK

2

2

CN71

4

4

WHITE

 

 

 

BROWN

3

3

 

5

5

YELLOW

 

 

 

BROWN

4

4

 

 

6

6

BLUE

DISCHARGE PIPE TEMP. THERMISTOR

 

 

 

 

 

 

 

 

 

 

 

 

CONTROLLER PCB ASSY

 

 

 

OUTDOOR TEMP. THERMISTOR

 

 

 

 

 

 

 

 

 

 

BLACK

1

1

 

 

 

 

RED

 

 

 

 

 

 

1

1

 

 

 

BLACK

2

2

CN70

 

 

 

 

3

3

 

 

2

2

BROWN

 

 

 

 

 

 

 

CN40

3

3

BLUE

 

WHITE

 

 

 

 

 

4

4

ORANGE

 

 

 

 

 

 

 

 

 

 

RED

 

W4

 

5

5

YELLOW

 

 

 

WHITE

 

 

6

6

WHITE

FUSE

 

 

 

W2

 

 

 

 

 

 

 

 

 

 

 

 

5A-250V

 

 

BLACK

W1

 

 

 

 

 

 

BLACK

 

 

 

 

 

 

BLACK

BLACK

FUSE 20A-250V

W3

CN30

1

1

BLACK

GREEN

 

2

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLACK

 

 

 

 

 

 

 

 

3

3

 

 

RED

 

 

1

1

 

R(R)

WHITE

 

C M COMPRESSOR

2

2

 

S(S)

3

3

C(T)

 

 

BLACK

 

F M FAN MOTOR

E V EXPANSION VALVE

4WV 4-WAY VALVE

TERMINAL 1 2 3 4 5

(L) (N) G

TO INDOOR UNIT POWER SUPPLY

04-02

R410A

WALL MOUNTED type

INVERTER

5 . DESCRIPTION OF EACH CONTROL OPERATION

1. COOLING OPERATION

1-1 COOLING CAPACITY CONTROL

A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor.

*If the room temperature is°F(2°C)4 higher than a set temperature, the compressor operation frequency will attain to maximum performance.

*If the room temperature is°F(25.5°C)lower than a set temperature, the compressor will be stopped.

*When the room temperature is between °F(+2°C)+4 to -5°F(-2.5°C)of the setting temperature, the compressor frequency is controlled within the range shown in Table1.

However, the maximum frequency is limited in the range shown in Figure 1 based on the fan speed mode and the outdoor temperature.

( Table 1 : Compressor Frequency Range )

 

minimum

maximum

maximum

 

frequency

frequency

frequency

ASU9RLQ

18Hz

61Hz

80Hz

ASU12RLQ

18Hz

80Hz

96Hz

ASU18CL

18Hz

70Hz

90Hz

ASU18RL

18Hz

70Hz

90Hz

( Fig. 1 : Limit of Maximum Frequency based on Outdoor Temperature )

Outside air

Outside air

 

 

Hi

Me

Lo

Quiet

temperature

temperature

9RLQ

A zone

80Hz

61Hz

51Hz

33Hz

 

 

97°F(36°C)

 

B zone

80Hz

61Hz

51Hz

33Hz

 

 

 

 

 

 

C zone

80Hz

61Hz

51Hz

33Hz

 

 

 

 

93°F(34°C)

A zone

 

 

D zone

51Hz

42Hz

36Hz

27Hz

 

90°F(32°C)

 

E zone

51Hz

42Hz

36Hz

27Hz

 

 

 

 

 

 

F zone

51Hz

42Hz

36Hz

27Hz

 

B zone

 

 

86°F(30°C)

 

12RLQ

A zone

96Hz

61Hz

51Hz

33Hz

 

70°F(21°C)

 

B zone

96Hz

61Hz

51Hz

33Hz

 

 

 

 

C zone

 

 

C zone

96Hz

61Hz

51Hz

33Hz

66°F(19°C)

 

 

D zone

57Hz

42Hz

36Hz

27Hz

 

54°F(12°C)

 

 

 

 

E zone

57Hz

42Hz

36Hz

27Hz

50°F(10°C)

D zone

 

 

F zone

57Hz

42Hz

36Hz

27Hz

 

18CL

A zone

90Hz

45Hz

42Hz

30Hz

 

36°F(2°C)

 

 

 

B zone

90Hz

45Hz

42Hz

30Hz

32°F(0°C)

E zone

 

 

C zone

90Hz

45Hz

42Hz

30Hz

 

 

 

D zone

58Hz

38Hz

34Hz

24Hz

 

 

 

 

 

F zone

 

 

E zone

58Hz

38Hz

34Hz

24Hz

 

 

 

F zone

58Hz

38Hz

34Hz

24Hz

 

 

 

18RL

A zone

90Hz

45Hz

42Hz

30Hz

 

 

 

 

B zone

90Hz

45Hz

42Hz

30Hz

 

 

 

 

C zone

90Hz

45Hz

42Hz

30Hz

 

 

 

 

D zone

58Hz

38Hz

34Hz

24Hz

 

 

 

 

E zone

58Hz

38Hz

34Hz

24Hz

 

 

 

 

F zone

58Hz

38Hz

34Hz

24Hz

When the compressor operates for 30 minutes continuously at over the maximum frequency, the maximum frequency is changed from Maximum Frequency to Maximum Frequency. The room temperature is controlled°F(1°C)2 lower than the setting temperature for 40 minutes after starting the operation.

After 40 minutes, it is controlled based on the normal setting temperature.

05-01

2. HEATING OPERATION

2-1 HEATING CAPACITY CONTROL

A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor.

*If the room temperature is lower by°F(3°C)6 than a set temperature, the compressor operation frequency will attain to maximum performance.

*If the room temperature is higher°F(25 .5°C)than a set temperatire, the compressor will be stopped.

*When the room temperature is between °F(+2°C)+4 to -6°F(-3°C)of the setting temperature, the compressor frequency is controlled within the range shown in Table2.

However, the maximum frequency is limited in the range shown in Figure 2 based on the fan speed mode and the outdoor temperature.

( Table 2 : Compressor Frequency Range )

 

minimum

maximum

 

frequency

frequency

ASU9RLQ

18Hz

130Hz

ASU12RLQ

18Hz

130Hz

ASU18CL

-

-

ASU18RL

18Hz

119Hz

( Fig.2 : Limit of Maximum Frequency based on Outdoor Temperature )

Outside air

 

 

 

Outside air

 

 

Hi

Me

Lo

Quiet

temperature

 

 

temperature

 

 

 

 

9RLQ

A zone

130Hz

96Hz

80Hz

68Hz

 

 

 

 

 

 

 

 

 

66°F(19°C)

 

 

 

 

 

 

 

B zone

130Hz

96Hz

80Hz

54Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C zone

 

 

 

 

C zone

130Hz

96Hz

80Hz

45Hz

 

 

 

 

 

 

 

 

63°F(17°C)

12RLQ

A zone

130Hz

96Hz

80Hz

68Hz

 

 

 

 

 

 

 

 

57°F(14°C)

 

 

 

 

 

 

 

 

B zone

130Hz

96Hz

80Hz

54Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

B zone

 

 

 

 

C zone

130Hz

96Hz

80Hz

45Hz

 

 

 

 

 

 

 

 

54°F(12°C)

18CL

A zone

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B zone

-

-

-

-

 

 

 

 

 

A zone

 

 

 

 

C zone

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18RL

A zone

119Hz

90Hz

70Hz

58Hz

 

 

 

 

 

 

 

 

 

 

B zone

119Hz

90Hz

70Hz

58Hz

 

 

 

 

 

 

 

 

 

 

C zone

119Hz

90Hz

70Hz

58Hz

* The room temperature is controlled°F(2°C)4 higher than the setting temperature for 60 minutes after starting the operation.

After 60 minutes, it is controlled based on the normal setting temperature.

05-02

3. DRY OPERATION

3-1 INDOOR UNIT CONTROL

The compressor rotation frequency shall change according to the temperature, set temperature, and room temperature variation which the room temperature sensor of the indoor unit body has detected as shown in the Table 3. However, after the compressor is driven, the indoor unit shall run at operation frequency of 58Hz, for a minute.

( Table 3 : Compressor frequency )

 

Operating

 

frequency

ASU9RLQ

33Hz

ASU12RLQ

33Hz

ASU18CL

24Hz

ASU18RL

24Hz

( Fig.3 : Compressor Control based on Room Temperature )

room

room

temperature

temperature

Ts+1°F(0.5°C)

 

compressor ON

 

 

Ts+3°F(1.5°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

compressor OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

( Fig.4 : Indoor Fan Control )

Compressor

ON

OFF

Indoor fan

Dry air flow

S-Lo

OFF

 

 

 

 

 

 

 

 

 

10

30

60

180

60

180

60

10

30

(SEC)

 

 

 

 

 

 

 

 

 

When an IAQ works in 9/12LA models, it operate with S-LO without stopping.

05-03

4. AUTO CHANGEOVER OPERATION

When the air conditioner is set to the AUTO mode by remote cintrol, operation starts in the optimum mode from amoung the HEATING, COOLING, DRY and MONITORING modes. During operation, the optimum mode is automatically swiched in accordance with temperature changes. The temperature can be set between 64°F(18°C)and 88°F(30°C)in 2°F(1°C)steps.

1 .When operation starts, only the indoor and outdoor fans are operated for 1 minute. After 1 minute, the room temperature and outside air temperature are sensed and the operation mode is selected in accordance with the table below.

( Fig.5 : Outside air temperature zone selection )

C zone

90°F(32°C)

B zone

14°F(-10°C)

A zone

( Table.4 Operation mode selection table)

Outside air temperature

(TO)

B zone

C zone

Room temperature(TB)

A zone

 

 

 

TB > TS+4°F(2°C)

Monitoring

Cooling

Cooling

(automatic dry)

(automatic dry)

 

 

TS+4°F(2°C) TB TS - 4°F(2°C)

Monitoring

Monitoring

Monitoring

TB<TS- 4°F(2°C)

*Heating

*Heating

Monitoring

 

 

*18CL is Monitoring

2 .When COOING was selected at 1 , the air conditioner operates as follow:

The same operation as COOLING OPERATION of item 1 above is performed.

When the room temperature has remained at (set tempareure -2°F(1°C)) for 8 minutes, operation is automatically switched to DRY and the same operation as DRY OPERATION of item 3 above

is performed.

If the room temperature reaches (set temperature+4°F(2°C) during DRY operation, operation returns to COOLING operation.

3.When HEATING was selected at 1 , the same operation as HEATING OPERATION of item 2 above is performed.

4 When the compressor was stopped for 6 consecutive minutes by the temperature control function after the COOLING or HEATING operation mode was selected at 1 above, operation is switched to MONITORING and the operation mode is selected again.

05-04

5. INDOOR FAN CONTROL

(1).Fan speed

( Table 5 : Indoor Fan Speed )

 

ASU9RLQ

 

Operat ion mode

Air flow mode

Speed (rpm)

Heating

Hi

1390

 

Me+

1350

 

Me

1200

 

Lo

1000

 

Quiet

760

 

Cool air

760

 

prevention

 

 

 

S-Lo

480

Cooling

Hi

1300

Fan

Me

1120

 

Lo

950

 

Quiet

700

Dry

 

700

 

ASU18CL

 

Operation mode

Air flow mode

Speed (rpm)

Heating

Hi

-

 

Me+

-

 

Me

-

 

Lo

-

 

Quiet

-

 

Cool air

-

 

prevention

 

 

 

S-Lo

480

Cooling

Hi

1480

Fan

Me

1260

 

Lo

1040

 

Quiet

850

Dry

 

850

 

ASU12RLQ

 

Operation mode

Air flow mode

Speed (rpm)

Heating

Hi

1440

 

Me+

1350

 

Me

1200

 

Lo

1000

 

Quiet

760

 

Cool air

760

 

prevention

 

 

 

S-Lo

480

Cooling

Hi

1370

Fan

Me

1150

 

Lo

950

 

Quiet

700

Dry

 

700

 

ASU18RL

 

Operation mode

Air flow mode

Speed (rpm)

Heating

Hi

1480

 

Me+

1420

 

Me

1300

 

Lo

1110

 

Quiet

950

 

Cool air

850

 

prevention

 

 

 

S-Lo

480

Cooling

Hi

1480

Fan

Me

1260

 

Lo

1040

 

Quiet

850

Dry

 

850

(2).FAN OPERATION

The airflow can be switched in 5 steps such as AUTO, QUIET, LOW, MED, HIGH, while the indoor fan only runs.

When Fan mode is set at (Auto), it operates on (MED) Fan Speed.

05-05

(3).COOLING OPERATION

Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature, as shown in Figure 6.

On the other hand, if switched in [HIGH] [QUIET], the indoor motor will run at a constant airflow of [COOL] operation modes QUIET, LOW, MED, HIGH, as shown in Table 5.

+4°F(+2°C)

+2°F(+1°C)

(4).DRY OPERATION

Refer to the table 4.

Durring the dry mode operation, the fan speed setting can not be changed.

(Fig.6)

airflow change - over ( Cooling:AUTO )

When the room temperature rises

HIGH mode

+5°F(+2.5°C)

 

MED mode

+3°F(+1.5°C)

LOW mode

When the room temperature lowers

(Room temperature) D (Setting temperature)

(5).HEATING OPERATION

Switch the airflow [AUTO], and the

 

 

 

(Fig.7)

indoor fan motor will run according

 

 

 

 

 

airflow change - over ( Heating:AUTO)

to a room temperature, as shown in

 

 

 

When the room

Figure 7.

 

 

 

 

 

temperature rises

On the other hand, if switched

 

 

 

 

 

 

LOW mode

 

 

 

 

 

 

 

 

 

 

 

[HIGH] [QUIET], the indoor motor

-2°F

(-1°C)

 

 

 

 

 

 

 

 

 

-3°F(-1.5°C)

 

 

 

will run at a constant airflow of [HEAT]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

operation modes QUIET, LOW, MED,

 

 

 

 

 

 

MED mode

 

 

 

 

HIGH, as shown in Table 5.

-4°F(-2°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-5°F(-2.5°C)

 

 

 

 

 

 

 

MED + mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When the room

 

 

 

 

 

 

 

 

 

 

temperature lowers

 

 

 

 

 

 

 

(Room temperature) D (Setting temperature)

 

 

 

 

 

 

 

 

 

 

(6).COOL AIR PREVENTION CONTROL (Heating mode)

The maximum value of the indoor fan speed is set as shown in Figure 8, based on the detected temperature by the indoor heat exchanger sensor on heating mode.

(Fig.8 : Cool Air Prevention Control)

Indoor heat exchanger

 

 

 

Indoor heatxchanger

temperature

 

 

 

temperature

117°F(47°C)

 

Hi

 

 

 

104°F(40°C)

 

 

 

Me+

 

 

104°F(40°C)

 

 

 

 

 

 

 

 

 

 

 

99°F(37°C)

 

Lo

 

 

 

93°F(34°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

86°F(30°C)

 

Cool air prevention

 

 

90°F(32°C)

 

 

 

 

 

 

82°F(28°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S-Lo

05-06

6. OUTDOOR FAN CONTROL

(1). Fan Speed

( Table 6 : Outdoor fan speed )

 

 

(rpm)

 

 

ZONE

 

Cooling

Dry

Heating

ASU9RLQ

 

A-D

 

800/760/470

500

 

 

 

E

 

400/280

400/280

760/680/470

 

 

F

 

200

200

 

ASU12RLQ

 

A-D

 

800/760/470

500

 

 

 

E

 

400/280

400/280

760/680/470

 

 

F

 

250/200

250/200

 

ASU18CL

 

A-D

 

860/820/670/500

500

 

 

 

E

 

400/340/280

400/340/280

-

 

 

F

 

280/250/230

280/250/230

 

 

 

 

 

 

 

 

ASU18RL

 

A-D

 

860/820/670/500

500

 

 

 

E

 

400/340/280

400/340/280

820/750/670/450

 

 

F

 

280/250/230

280/250/230

 

Refer to Fig1.

 

 

 

 

 

(1). Fan Speed

*It runs at 500(A-D ZONE)/200(E,F ZONE) rpm for 20 seconds after starting up the outdoor fan.

*The outdoor fan speed mentioned avobe depends on the compressor frequency.

(When the compressor frequency increases, the outdoor fan speed also changes to the higher speed. When the compressor frequescy decreases, the outdoor fan speed also changes to the lower speed.)

*Outdoor temperature falls, and if it becomes E and F zone(Refer to Fig1), rotations of fan speed will fall.

*After the defrost control is operated on the heating mode, the fan speed keeps at the higher speed as table 7 without relating to the compressor frequency.

( Table 7 : Outdoor fan speed after the defrost )

 

Min

ASU9RLQ

800rpm

ASU12RLQ

900rpm

ASU18CL

-

ASU18RL

950rpm

05-07

7. LOUVER CONTROL

(1). VERTICAL LOUVER CONTROL

(Function Range)

Each time the button is pressed, the air direction range will change as follow:

(Fig 9: Air Direction Range)

(Operation Range)

Cooling / Dry mode Heating mode Fan mode

Use the air direction adjustments within the ranges shown above.

The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.

Cooling / Dry mode

Horizontal flow

Heating mode

Downward flow

When the temperature of the air being blown out is low at the start of heating operation or during defrosting, the airflow direction temporarily becomes to prevent cold air being blown onto the body.

During use of the Cooling and Dry modes, do not set the Air Flow Direction Louver in the Heating range () for long period of time, since water vapor many condense near the outlet louvers and drop of water may drip from the air conditioner. During the Cooling and Dry modes, if the Air Flow Direction Louvers are left in the hating range for more than 30minutes, they will automatically

return to position .

During Monitor operation in AUTO CHANGEOVER mode, the airflow direction automatically becomes , and it cannot be adjusted.

(2). SWING OPERATION

When the swing signal is received from the remote controller, the vertical louver starts to swing.

(Swinging Range)

Cooling mode / Dry mode / Fan mode() Heating mode / Fan mode()

When the indoor fan is either at S-lo or Stop mode, the swinging operation is interrrupted and the louver stops at the memorized position.

05-08

8. COMPRESSOR CONTROL

(1). OPEARTION FREQUENCY RANGE

The operation frequency of the compressor is different based on the operation mode as shown in the table 8.

(Table 8 : Compressor Operation Frequency Range)

 

Cooling

 

Heating

Dry

 

Min

Max

Min

Max

 

 

ASU9RLQ

18Hz

80Hz

18Hz

130Hz

33Hz

ASU12RLQ

18Hz

96Hz

18Hz

130Hz

33Hz

ASU18CL

18Hz

90Hz

-

-

24Hz

ASU18RL

18Hz

90Hz

18Hz

119Hz

24Hz

(2). OPEARTION FREQUENCY CONTROL AT START UP

The compressor frequency soon after the start-up is controlled as shown in the figure 10. (Fig.10 : Compressor Control at Start-up)

Frequency

Frequency

Frequency

Frequency

Frequency

Frequency

Time

Time

Time

Time

Time

Time

 

(Frequency)

 

 

 

 

 

 

 

Frequency

Frequency

Frequency

Frequency

Frequency

Frequency

ASU9RLQ

56Hz

74Hz

87Hz

97Hz

108Hz

119Hz

ASU12RLQ

56Hz

74Hz

87Hz

97Hz

108Hz

119Hz

ASU18CL

40Hz

59Hz

72Hz

80Hz

101Hz

110Hz

ASU18RL

40Hz

59Hz

72Hz

80Hz

101Hz

110Hz

(Time)

 

 

 

 

 

 

 

Time

Time

Time

Time

Time

Time

ASU9RLQ

80sec

60sec

60sec

180sec

60sec

60sec

ASU12RLQ

80sec

60sec

60sec

180sec

60sec

60sec

ASU18CL

60sec

40sec

40sec

60sec

150sec

60sec

ASU18RL

60sec

40sec

40sec

60sec

150sec

60sec

05-09

Loading...
+ 56 hidden pages