Flowserve S25N User Manual

5 (1)
Flowserve S25N User Manual

Automax Valve Automation Systems

3-Position Control/Dribble Control

SR Limit Switch Method

Installation, Operation and Maintenance Instructions

Flowserve Corporation

1350 N. Mountain Springs Parkway

1978 Foreman Dr.

Flow Control Division

Springville, Utah 84663

Cookeville, TN 38501

www.flowserve.com

Phone: 801 489 8611

Phone: 931 432 4021

 

S25N NAMUR Directional Valve

 

The Automax NAMUR Directional valve mounts directly to SuperNova series actuators which eliminates the cost of tubing and fittings. The valves are available for double acting and spring return actuators with NEMA 4, 4X, 7 & 9, weatherproof intrinsically-safe, and low power solenoid operators.

These valves have been tested and proven reliable for over 1 million cycles.

Operation

Solenoid will not shift without backpressure on ports

2 and 4. Air supply lines to the valve must have I.D. at least as large as the NPT size of valve ports.

Temperature: NEMA 4X: -20° F to 150° F

NEMA 4X, 7 & 9: -20° F to 125° F

For temperatures below 40° F, air must be free of water vapor.

Pressure: Minimum: 35 psig Maximum: 150 psig

Media: Dry or lubricated non-corrosive gas compatible with nitrile seals.

CV = 1.8

Flow Schematics:

(Port 1 - air supply)

3-way Valve (Spring Return Actuators)

2 4

3 1 5

When operator is energized, the spool shifts allowing the air pressure to enter the actuator and compress the springs. When de-energized, the spool returns, exhausting the air.

4-way Valve (Double-acting Actuators)

2 4

3 1 5

When operator is energized, the spool shifts, driving the actuator CCW. When de-energized the spool returns, driving the actuator CW. For de-energized CCW, rotate directional valve 180° , so that operator points left.

Options:

Dual coil 2-position and 3-position valves are available. Consult factory.

Sandwich NAMUR mount accessories:

APS1 - Air purge system to purge spring chambers with solenoid valve exhaust.

FC1, FCSR and FCDA - Single port and dual port exhaust flow controls.

LV1 - Lockout and vent valve for lockout and manual override applications.

Automax sandwich NAMUR mount accessories provide compact, clean control packages for the SuperNova actuator.

Solenoid Information

NEMA 4X Weatherproof

Coil is U.L. and C.S.A. recognized

Standard 1/2" NPT connector meets NEMA 4X rating

Optional DIN connector for wiring with

3 lead, 18ga cord available. Eliminates junction boxes at solenoid. Simply plug in and tighten screw for easy installation and service

Standard with non-locking override

Continuous duty molded class H coil

24" electrical leads

External air pilot

NEMA 4X, 7 & 9 "Explosion-proof"

1/2" NPT conduit

24" electrical leads

Meets U.L., C.S.A. and NEMA requirements for Class I, Gr C & D Div. 1 & 2 Class II, Gr E, F & G Div. 1 & 2

Standard with non-locking override

Continuous duty molded Class B Coil

External air pilot

Solenoid Electrical Characteristics

Characteristics for standard coils are shown below. All common voltages and hertz are available.

 

 

AC VOLTAGE ± 10%

DC VOLTAGE

WEATHERPROOF

120 VAC

240 VAC

12 VDC

24 VDC

Inrush Amps

 

0.078

0.041

0.400

0.200

Holding Amps

 

0.058

0.030

0.400

0.200

Resistance ( Ω

)

840

3310

31.6

121

EXPLOSION-PROOF

 

 

 

 

Inrush Amps

 

0.127

0.063

0.632

0.320

 

 

 

 

 

 

Holding Amps

 

0.057

0.038

0.632

0.320

Resistance ( Ω

)

475

2000

19.0

75

Weatherproof intrinsically-safe/low power

A .67 watt coil is available with 1/2" NPT weatherproof housing. The operator has Factory Mutual Entity approval. See the separate I.S. operator I.O.M. for further information.

AXAIMO35-0

(AUTO-111)

07/03

Page 1 of 2

© 2003, Flowserve Corporation, Printed in USA