
Instruction Manual
March 2014
N600 Series Ball Valves
N600 Series
P1708
Figure 1. N600 Series Ball Valves
WARNING
!
Failure to follow these instructions or to
properly install and maintain this equipment
could result in an explosion and/or re causing
property damage and personal injury or death.
Fisher® equipment must be installed,
with federal, state and local codes and
manufacturer’s instructions. The installation
in most states must also comply with NFPA
No. 58 or ANSI K61.1 standards.
Only personnel trained in the proper
procedures, codes, standards and
regulations applicable industries should
install and service this equipment.
Introduction
Scope of the Manual
This Instruction Manual covers installation and maintenance
for Fisher N600 Series Ball valves used on LP-Gas and
anhydrous ammonia (NH3) service.
Description
WARNING
!
For “Hose End” service, use Fisher N480
Series hose end valves. Excessive cycling
of ball valves can cause stem thread failure
resulting in uncontrolled gas discharge and
personal injury.
www.fisherregulators.com
D450324T012

N600 Series
Specications
SERVICE INLET AND OUTLET CONNECTIONS
LP-Gas and NH
3
Maximum Operating Pressure: 1000 psig / 68.9 bar
Ball valves are used at bulk plants to control gas flow
in the piping system, at storage tanks, on trucks and at
pumps or compressors.
For LP-Gas service, a hydrostatic relief valve (Type H124)
or a vent valve be installed when liquid product can be
trapped in a hydrostatic state between to shutoff valves.
Type N610L – Steel or Stainless Steel valves for either
LP-Gas or NH
DN 50 to 80 only, each valve has PTFE packing for sealing
service. Ranging in size from NPS 2 to 3 /
3
against leakage.
N600L Series configurations are suitable for lowtemperature operating conditions.
Installation
TYPE NUMBER
N600L
2 FNPT N610L-16
3 FNPT N610L-24
Temperature Capabilities:
N600L Series: -60 to 450ºF / -51 to 232ºC
Use pipe compound on the threaded joints. Make sure the
compound or ‘pipe dope’ is suitable for the service conditions.
Pull the piping into the valve hand tight, and then wrench
tighten the piping for approximately two additional turns.
Do not install the piping with such extreme torque that the
piping can cut threads into the valve. This can cause valve
distortion and affect the internal working parts. Larger size
valves may require an additional amount of torque to obtain
a leak free connection.
After installation, test the inlet and outlet connections and around
the stem for leaks using an approved leak detector solution.
CAUTION
If the valve is to be used in service other than
LP-Gas or Anhydrous Ammonia, contact the
factory to determine if the valve materials are
suitable for the particular service.
LP-Gas Equipment
Emerson Process Management
Regulator Technologies, Inc.
USA - Headquarters
McKinney, Texas 75070 USA
Tel: +1 800 558 5853
Outside U.S. +1 972 548 3574
For further information visit www.fisherregulators.com
The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners. Fisher is a mark owned by Fisher Controls International LLC,
a business of Emerson Process Management.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or
guarantees, express or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specications of such
products at any time without notice.
Emerson Process Management Regulator Technologies, Inc. does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and
maintenance of any Emerson Process Management Regulator Technologies, Inc. product remains solely with the purchaser.
©Emerson Process Management Regulator Technologies, Inc., 2013, 2014; All Rights Reserved