Fisher Mounting Instructions for DVC6200/DVC2000 Digital Valve Controller on (Old NAMUR) Sliding Stem Actuator Manuals & Guides

www.Fisher.com
may or may not
include all components shown for kit installation.
Mounting Instructions
DVC6200/DVC2000
Valve Controller on
(Old Namur) Sliding Stem Actuator
D103997X012 May 2014
Digital
Use these instructions to mount a FIELDVUE DVC6200 or DVC2000.
Avoid personal injury or property damage from sudden release of process pressure or bursting of parts. Before performing any maintenance operations:
Always wear protective clothing,
gloves, and eyewear.
Do not remove the actuator from the valve while the valve is still pressurized.
Disconnect any operating lines providing air pressure, electric power, or a control signal to the actuator. Be sure the actuator cannot suddenly open or close the valve.
Use bypass valves or completely shut off the process to isolate the valve from process pressure. Relieve process pressure from both sides of the valve.
Vent the pneumatic actuator loading pressure and relieve any actuator spring precompression.
Use lock-out procedures to be sure that the above measures stay in effect while you work on the equipment.
Check with your process or safety engineer for any additional measures that must be taken to protect against process media.
Refer to the appropriate actuator instruction manual for actuator installation, operation, maintenance, and parts identification as this manual
1. Isolate the control valve from the process line
pressure and release pressure from both sides of the valve body. Shut off all pressure lines to the actuator, releasing all pressure from the actuator. Use lock-out procedures to be sure that the above measures stay in effect while you work on the equipment.
2. Install set screws into stem block.
3. Attach arm connector onto stem block set screws.
Two connecting arms are provided one suitable for use with large actuators and one for use with small actuators; select the appropriate one for the actuator being used.
DVC6200/DVC2000
Digital Valve Controller on
(Old Namur) Sliding Stem Actuator
4. Loosely (for later adjustment) attach washers and
nuts to set screws.
Mounting Instructions
D103997X012
May 2014
6. Connect array to extension arm with supplied
fasteners. Leave fasteners loose enough for fine adjustment.
7. Attach mounting bracket to actuator.
5. Attach extension arm to connector arm.
.
For Rib Actuator go to step 8a.
For Plane Actuator go to step 8b.
For Pillar Actuator go to step 8c.
DVC6200/DVC2000
(Old Namur) Sliding Stem Actuator
Mounting Instructions
D103997X012 May 2014
8a. Rib Actuator
Attach mounting bracket to actuator using supplied M8 hex head fastener.
Skip to step 9.
8b. Plane Actuator
Attach mounting bracket to actuator using supplied fasteners.
(4) M8X45 Hex Head Screws (4) External Tooth Lock Washer (4) M8 Hex Nuts
Digital Valve Controller on
8c. Pillar Actuator
Use hardware to attach mounting bracket to pillar. Ensure device mounting plane is perpendicular to array.
Hardware:
(2) M8 Round U Bolt
(4) External Tooth Lock Washer
(4) M8 Hex Nuts
Skip to Step 9
DVC6200/DVC2000
Digital Valve Controller on
(Old Namur) Sliding Stem Actuator
(Array Kit sold separately)
Ensure device mounting plane is perpendicular to array.
9. Attach alignment template to mounting bracket. Adjust array to line up with alignment template. If Actuator stroke is in the up position, use Step 10a. If Actuator stroke is in the down position, use Step 10b. Ensure that the index mark of the alignment tool will be in between the array index marks.
(Index Lines are shown below with arrows)
Mounting Instructions
D103997X012
May 2014
10a. Align array bottom index line with alignment template index line.
10b. Align array top index line with alignment template index line.
DVC6200/DVC2000
(Old Namur) Sliding Stem Actuator
Mounting Instructions
D103997X012 May 2014
11. Align array laterally with the alignment template.
12. Tighten all fasteners to lock array into position. Loctite® Thread Locker 242® is recommended but not supplied.
13. Remove alignment tool, and attach device to mounting bracket with supplied M8 fasteners.
Digital Valve Controller on
(Device Mounted to Bracket Isometric View)
14. Double check that Array will travel without obstruction in valley of device.
DVC6200/DVC2000
Digital Valve Controller on
(Old Namur) Sliding Stem Actuator
Bill of Materials
QTY
Description
4
2
2
4
3
2
1
2
2
2
1
1
1
1
2
4
1
Mounting Instructions
D103997X012
May 2014
Hex Head Cap Screw M8X1.25X45 External Tooth Lock Washer #8 Washer M4 Hex Nut M8X1.25 Hex Head Cap Screw M8X1.25X16 Hex Nut M6X1.0 Hex Head Cap Screw M8X1.25X25 Socket Head Cap Screw M4x12 Washer 6.4X12X1.6 Socket Head Cap Screw M6X1X20 Mounting Bracket Arm Connector (A) Arm Connector (B) Arm Extension U-Bolt M8X1.25X69 External Tooth Lock Washer M8 Array Kit (Sold Separately)
DVC6200/DVC2000
(Old Namur) Sliding Stem Actuator
Mounting Instructions
D103997X012 May 2014
Digital Valve Controller on
DVC6200/DVC2000
Digital Valve Controller on
(Old Namur) Sliding Stem Actuator
Mounting Instructions
D103997X012
May 2014
DVC6200/DVC2000
(Old Namur) Sliding Stem Actuator
Mounting Instructions
D103997X012 May 2014
Digital Valve Controller on
DVC6200/DVC2000
Digital Valve Controller on
(Old Namur) Sliding Stem Actuator
Air Filter Regulator
DVC6200
Mounting Instructions
D103997X012
May 2014
Common Mounting Bracket
Alignment Template
Connector Arm
DVC2000
Extension Arm
Shield
Linear Feedback Array
Spacer
Insert Assembly
U-Bracket
DVC6200/DVC2000
Digital Valve Controller on
(Old Namur) Sliding Stem Actuator
Neither Emerson, Emerson Process Management, Fisher, nor any of their affiliated entities assumes responsibility for the selection, use and maintenance of any product. Responsibility for the selection, use and maintenance of any product remains with the purchaser and end user.
Emerson Process Management
Mounting Instructions
D103997X012
May 2014
Fishe and FIELDVUE are marks owned by Fisher Controls International LLC, a member of the Emerson Process Management business unit of Emerson Electric Co. Emerson Process Management, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Marshalltown, Iowa 50158 USA Sorocaba, 18087 Brazil Chatham, Kent ME4 4QZ UK Dubai, United Arab Emirates Singapore 128461 Singapore
www.Fisher.com
______________________________________________________________________________________________________
© 2014 Fisher Controls International LLC. All right reserved.
Loading...