Installation Instructions
June 2007
Mounting a DVC6020/DVC6020f Digital
R
Valve Controller on Fisher
Type 585 and
585R Size 50 Actuators with 2 Inch Travel
Use these instructions to mount a FIELDVUE
DVC6020 or DVC6020f digital valve controller on
R
Fisher
inch travel.
Type 585 and 585R size 50 actuators with 2
R
WARNING
Avoid personal injury or property
damage from sudden release of process
pressure or bursting of parts. Before
performing any installation operations:
D Always wear protective clothing,
gloves, and eyewear.
D Disconnect any operating lines
providing air pressure, electric power, or
a control signal to the actuator. Be sure
the actuator cannot suddenly open or
close the control valve.
D Use bypass valves or completely
shut off the process to isolate the
control valve from process pressure.
Relieve process pressure from both
sides of the control valve.
D Vent the pneumatic actuator
loading pressure and relieve any
actuator spring precompression.
D Use lock-out procedures to be sure
that the above measures stay in effect
while you work on the equipment.
D Check with your process or safety
engineer for any additional measures
that must be taken to protect against
process media.
Refer to figure 1 and the parts list for mounting parts
identification. Refer to the FIELDVUE
Series Digital Valve Controller Instruction Manual,
Form 5647, or the FIELDVUE
Digital Valve Controller Instruction Manual, Form 5774
for digital valve controller parts identification. Refer to
the appropriate actuator instruction manual for actuator
installation, operation, maintenance, and parts
identification.
1. Isolate the control valve from the process line
pressure and release pressure from both sides of the
valve body. Shut off all pressure lines to the actuator,
releasing all pressure from the actuator. Use lock-out
procedures to be sure that the above measures stay in
effect while you work on the equipment.
R
R
DVC6000
DVC6000f Series
WARNING
To avoid personal injury due to the
sudden, uncontrolled movement of
parts, do not loosen the stem connector
cap screws when the stem connector
has spring force applied to it.
2. Remove the cover plate screws and cover plate
from the actuator, if present.
3. During the attachment of the cam (key 1) to the
valve stem connector it will be necessary to loosen the
stem connector cap screws. Consult the appropriate
actuator instruction manual for proper actuator
disassembly and reassembly.
4. Attach the cam to the stem block using hex head
cap screws (key 2). Ensure that the cam is oriented as
shown in figure 1.
5. Attach the mounting adapter (key 7) to the yoke
using the four spacers (key 9) and the four cap screws
(key 6).
6. Remove the roller from the digital valve controller by
removing the screw, lockwasher and nut (key 87, 89,
and 90; refer to the appropriate digital valve controller
instruction manual for parts identification, if necessary).
Retain the screw, lockwasher, and nut.
7. In place of the roller, install the follower arm
extension (key 12) on the digital valve controller, using
two machine screws (key 3), lockwashers (key 4), and
machine screw hex nut (key 5), as shown in figure 2.
8. Install the roller (key 13) on the follower arm
extension (key 12) as shown in figure 2, using the
retained screw, lockwasher and nut (key 87, 89,
and 90)
9. Install the vent adapter (key 10) and vent (key 11)
on the digital valve controller pressure outlet.
10. Mount the digital valve controller on the mounting
adapter (key 7) using four hex socket cap screws
(key 8).
11. Ensure that the roller is centered and resting on
the cam surface.
12. Make pneumatic and electrical connections to the
digital valve controller as described in the digital valve
controller instruction manual.
13. Setup and calibrate the digital valve controller as
described in the digital valve controller instruction
manual or quick start guide.
14. Re-attach actuator cover plate, if necessary.
www.Fisher.com
D103281X012

Mounting a DVC6020/DVC6020f Digital
R
Valve Controller on Fisher
Type 585 and
585R Size 50 Actuators with 2 Inch Travel
For additional information concerning mounting, setup,
calibration, and maintenance of the DVC6000 or
DVC6000f Series digital valve controller refer to the
appropriate instruction manual.
Installation Instructions
June 2007
Note
Neither Emerson, Emerson Process
Management, nor any of their affiliated
entities assumes responsibility for the
ROLLER
(KEY 13)
FOLLOWER
ARM
EXTENSION
(KEY 12)
selection, use and maintenance of any
product. Responsibility for the selection,
use and maintenance of any product
remains with the purchaser and
end-user.
6
4
5
3
2
9
1
12
7
11
10
8
Figure 2. Installing Roller
PARTS LIST
KEY
1
2
3
4
5
6
7
8
9
10
11
12
13
DESCRIPTION
QTY
CAM
1
5/16-18 X 1.25 HEX HEAD CAP SCREW
2
10-24 X 0.20 HEX HEAD MACHINE SCREW
2
No. 10 LOCK SPRING WASHER
2
MACHINE SCREW HEX NUT
2
HEX HEAD CAP SCREW
4
MOUNTING ADAPTER
1
5/16-18 X 0.62 HEX SOCKET CAP SCREW
4
.344 X .625 X .50 SPACER
4
VENT ADAPTER
1
3/8-18 NPT VENT
1
FOLLOWER ARM EXTENSION
1
ROLLER ASSEMBLY (PART OF DVC6020)
1
13
NOTE: A SCREEN AND HEX SOCKET PIPE PLUG ARE INCLUDED IN THIS MOUNTING KIT. THESE ARE ONLY
NEEDED WHEN CONVERTING A DVC6020 OR DVC6020f FROM DOUBLE-ACTING TO SINGLE-ACTING.
29B2079 Rev C
Figure 1. Mounting Parts Identification
FIELDVUE and Fisher are marks owned by Fisher Controls International LLC, a member of the Emerson Process Management business division of
Emerson Electric Co. Emerson Process Management, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co.
All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are
not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability.
We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Neither Emerson, Emerson Process Management, nor any of their affiliated entities assumes responsibility for the selection, use and
maintenance of any product. Responsibility for the selection, use and maintenance of any product remains with the purchaser and end-user.
Emerson Process Management
Marshalltown, Iowa 50158 USA
Cernay 68700 France
Sao Paulo 05424 Brazil
Singapore 128461
www.Fisher.com
2
EFisher Controls International LLC 2007; All Rights Reserved