FISCHER DE43 Operating Manual

Page 1
Modbus
Operating manual
DE43
Digital 2-channel transmitter
for direct connection to
bus-capable automation devices
09005642 • BA_EN_DE43 • Rev. ST4-A • 11/18
Page 2
| Impressum FISCHER Mess- und Regeltechnik GmbH

Impressum

Manufacturer:
Technical editorial team:
FISCHER Mess- und Regeltechnik GmbH
Bielefelderstr. 37a D-32107 Bad Salzuflen
Telephone: +49 5222 974 0 Telefax: +49 5222 7170
eMail: info@fischermesstechnik.de web: www.fischermesstechnik.de
Documentation representative: T. Malischewski Technical editor: R. Kleemann
All rights, also those to the translation, reserved. No part of this document may be reproduced or processed, duplicated or distributed using electronic systems or any other form (print, photocopy, microfilm or another process) without the written consent of the company FISCHER Mess- und Regeltechnik GmbH, Bad Salzuflen.
Reproduction for internal use is expressly allowed.
Brand names and procedures are used for information purposes only and do not take the respective patent situation into account. Great care was taken when compiling the texts and illustrations; Nevertheless, errors cannot be ruled out. The company FISCHER Mess- und Regeltechnik GmbH will not accept any legal responsibility or liability for this.
Subject to technical amendments.
© FISCHER Mess- und Regeltechnik 2018

Version history

Rev. ST4-A 11/18 Version 1 (first edition)
2 / 28 BA_EN_DE43
Page 3
FISCHER Mess- und Regeltechnik GmbH Table of contents

Table of contents

1 Safety instructions .........................................................................................................................................4
1.1 General .....................................................................................................................................................4
1.2 Personnel Qualification.............................................................................................................................4
1.3 Risks due to Non-Observance of Safety Instructions ...............................................................................4
1.4 Safety Instructions for the Operating Company and the Operator............................................................4
1.5 Unauthorised Modification ........................................................................................................................4
1.6 Inadmissible Modes of Operation .............................................................................................................4
1.7 Safe working practices for maintenance and installation work .................................................................5
1.8 Pictogram explanation ..............................................................................................................................5
2 Product and functional description ..............................................................................................................6
2.1 Delivery scope ..........................................................................................................................................6
2.2 Equipment versions ..................................................................................................................................6
2.3 Function diagram ......................................................................................................................................8
2.4 Design and mode of operation..................................................................................................................8
2.5 Intended use .............................................................................................................................................8
3 Assembly.........................................................................................................................................................9
3.1 General .....................................................................................................................................................9
3.2 Process connection ..................................................................................................................................9
3.3 Electrical connections .............................................................................................................................10
4 Start-up..........................................................................................................................................................13
4.1 Generalities.............................................................................................................................................13
4.2 Config select ...........................................................................................................................................13
4.3 Modbus functional description ................................................................................................................15
4.4 LED flash codes......................................................................................................................................21
5 Servicing .......................................................................................................................................................22
5.1 Maintenance ...........................................................................................................................................22
5.2 Transport ................................................................................................................................................22
5.3 Service....................................................................................................................................................22
5.4 Disposal ..................................................................................................................................................22
6 Technical data...............................................................................................................................................23
6.1 General ...................................................................................................................................................23
6.2 Input variables ........................................................................................................................................23
6.3 Communication parameter .....................................................................................................................23
6.4 Auxiliary energy ......................................................................................................................................24
6.5 Operating conditions...............................................................................................................................24
6.6 Construction design ................................................................................................................................24
7 Order codes ..................................................................................................................................................26
8 Attachments..................................................................................................................................................28
BA_EN_DE43 3 / 28
Page 4
1 | Safety instructions FISCHER Mess- und Regeltechnik GmbH

1 Safety instructions

1.1 General

This operating manual is an integral part of the product and therefore needs to be kept close to the instrument in a place that is accessible at all times to the re­sponsible personnel.
The following sections, in particular instructions about the assembly, commis­sioning and maintenance, contain important information, non-observance of which could pose a threat to humans, animals, the environment and property.
The instrument described in these operating instructions is designed and manu­factured in line with the state of the art and good engineering practice.

1.2 Personnel Qualification

The instrument may only be installed and commissioned by specialized person­nel familiar with the installation, commissioning and operation of this product.
Specialized personnel are persons who can assess the work they have been assigned and recognize potential dangers by virtue of their specialized training, their skills and experience and their knowledge of the pertinent standards.

1.3 Risks due to Non-Observance of Safety Instructions

Non-observance of these safety instructions, the intended use of the device or the limit values given in the technical specifications can be hazardous or cause harm to persons, the environment or the plant itself.
The supplier of the equipment will not be liable for damage claims if this should happen.

1.4 Safety Instructions for the Operating Company and the Operator

The safety instructions governing correct operation of theinstrument must be observed. The operating company must make them available to the installation, maintenance, inspection and operating personnel.
Dangers arising from electrical components, energy discharged by the medium, escaping medium and incorrect installation of the device must be eliminated. See the information in the applicable national and international regulations.
Please observe the information about certification and approvals in the Tech­nical Data section.

1.5 Unauthorised Modification

Modifications of or other technical alterations to the instrument by the customer are not permitted. This also applies to replacement parts. Only the manufacturer is authorised to make any modifications or changes.

1.6 Inadmissible Modes of Operation

The operational safety of this instrument can only be guaranteed if it is used as intended. The instrument model must be suitable for the medium used in the system. The limit values given in the technical data may not be exceeded.
The manufacturer is not liable for damage resulting from improper or incorrect use.
4 / 28 BA_EN_DE43
Page 5
FISCHER Mess- und Regeltechnik GmbH Safety instructions | 1

1.7 Safe working practices for maintenance and installation work

The safety instructions given in this operating manual, any nationally applicable regulations on accident prevention and any of the operating company's internal work, operating and safety guidelines must be observed.
The operating company is responsible for ensuring that all required mainten­ance, inspection and installation work is carried out by qualified specialized per­sonnel.

1.8 Pictogram explanation

DANGER
Type and source of danger
This indicates a direct dangerous situation that could lead to death or serious injury (highest danger level).
a) Avoid danger by observing the valid safety regulations.
WARNING
Type and source of danger
This indicates a potentially dangerous situation that could lead to death or ser­ious injury (medium danger level).
a) Avoid danger by observing the valid safety regulations.
CAUTION
Type and source of danger
This indicates a potentially dangerous situation that could lead to slight or seri­ous injury, damage or environmental pollution (low danger level).
a) Avoid danger by observing the valid safety regulations.
NOTICE
Note / advice
This indicates useful information of advice for efficient and smooth operation.
BA_EN_DE43 5 / 28
Page 6
2 | Product and functional description FISCHER Mess- und Regeltechnik GmbH
Attachment boreholes for tapping screws Wall mounting plate
Item no.
Silicone-free
Measuring range Measuring range Ub Interface Prod. No..
Δ P1 Δ P2
DE435554P6M92MMW
0 ... 1600 Pa 0 ... 1000 Pa
24 V DC
RS 485
1808689.04.004
Silicone-free
Item no. Measuring range
Measuring range Ub Interface Prod. No.
DE435455P6L92MMW
0 ... 1000 Pa
0 ... 1600 Pa
24 V DC
RS 485
1808689.04.005
Δ P1
Δ P2
Standard version 90° rotated
Attention!Do not disconnect from the mains or open the case while energized.
Attention!Do not disconnect from the mains or open the case while energized.
Aluminium CK screw connection
for 6/4 or 8/6 mm hose
Pneumatic plug connection
for 6/4 or 8/6 mm hose
P1
+
+
P2

2 Product and functional description

2.1 Delivery scope

• DE43 digital 2-channel transmitter
• Operating Manual

2.2 Equipment versions

Assembly
Fig.1: Wall mounting
Fig.2: Type plate
Process connection
Fig.3: Process connection
6 / 28 BA_EN_DE43
Page 7
FISCHER Mess- und Regeltechnik GmbH Product and functional description | 2
M12 Plug 1 (male)
M12 Plug 2 (female)
2 1
3 4
5
A
1 2
4 3
5
A
2 Digital inputs (3,4) left 4 Digital inputs (1...4) 2 Digital inputs (1,2) right
E1
E2
E3
E4
E1
E2
E4
E3
1
4
3
M8 Bush (female)
Item no.
Silicone-free
Measuring range Measuring range
Ub Interface Prod. No..
Δ P1 Δ P2
DE435554P6M92MMW
0 ... 1600 Pa 0 ... 1000 Pa
24 V DC
RS 485
1808689.04.004
Silicone-free
Item no. Measuring range
Measuring range Ub Interface Prod. No.
DE435455P6L92MMW
0 ... 1000 Pa
0 ... 1600 Pa
24 V DC
RS 485
1808689.04.005
Δ P1
Δ P2
Horizontal
Vertical
Order code
Techn. Data
Serial number
Electrical connections
Fig.4: Electrical connections

2.2.1 Type plate

The presented type plates serve to show an example of the information shown. The data shown is purely fictive, but does correspond to the actual conditions. For more information, please see the order code at the end of these instruc­tions.
Fig.5: Type plate
BA_EN_DE43 7 / 28
Page 8
2 | Product and functional description FISCHER Mess- und Regeltechnik GmbH
DIP
µC
D
A
D
A
E1
E2
E3
E4
BUS
POWER
+
+
P1
P2
2
Input 1
Input 2
Input 3
Input 4
1 Modbus IN
Modbus OUT
1
2
3
4
5
6
7

2.3 Function diagram

Fig.6: Function diagram
1 Sensor element 2 Micro-controller 3 AD converter 4 Digital inputs 5 Modbus interface 6 Power Supply 7 Modbus configuration

2.4 Design and mode of operation

The basis of the DE43 transmitter comprises two piezoresistive sensor ele­ments.
The pressure that is to be measured acts upon a silicone membrane that is equipped with a resistor bridge. The acting pressure causes the membrane to move and therefore a change in resistance. The bridge signal is analysed by the integrated electronics and converted to a pressure value.
The DE43 transmitter communicates with an overriding control system via an RS 485 interface and a Modbus RTU protocol. The currently measured value is forwarded by the overriding control system on request.
The device also has a connecting slot for two or four proximity switches whose signals can also be queried through the Modbus by the overriding control sys­tem.

2.5 Intended use

The digital 2-channel transmitter DE43 is suitable for measuring pressure, un­der-pressure, and differential pressure in neutral gaseous media. The measured value is transferred to an overriding control system via an RS 485 interface with a Modbus RTU protocol.
Optionally, the device can monitor up to four external potential-free contacts, and send their switching status to the overriding control system.
8 / 28 BA_EN_DE43
Page 9
FISCHER Mess- und Regeltechnik GmbH Assembly | 3
CK Screw connection Pneumatic Plug connection
Channel 2Channel1
+ +
Channel 2Channel1
+ +
Differential pressure Pressure Under-pressure
+
higher pressure
lower pressure
+
Pressure
open
+
open
Under-pressure

3 Assembly

3.1 General

The device is designed for installation onto flat assembly plates. For screw con­nection to the assembly plate, the device features four assembly bores on its back, which can be used for Ø 3.5 mm tapping screws.
Optionally, the device can be delivered with a wall-mounting plate. This is also available as accessory.
At the factory, the device is calibrated for vertical installation, but the installation position is arbitrary.
The enclosure protection type IP 65 is only guaranteed, if a suitable power sup­ply cable is used (see accessories).
If the device is intended for outdoor use, we recommend permanent protection against against constant rain or snow, however at the least a sufficiently dimen­sioned canopy.

3.2 Process connection

• By authorized and qualified specialized personnel only.
• The pipes need to be depressurized when the instrument is being connec­ted.
• Appropriate steps must be taken to protect the device from pressure surges.
• Check that the device is suitable for the medium being measured.
• Maximum pressures must be observed (cf. Tech. data)
The pressure lines must be installed on a gradient so that no water pockets for gas measurements can be created. If the required gradient is not reached, wa­ter filters need to be installed at suitable points.
The pressure lines must be kept as short as possible and installed without any tight bends to avoid delays.
The process connections are marked with (+) and (-) symbols on the device. The pressure lines must be mounted according to these symbols.
Fig.7: Process connection
The process connections are suitable for hoses made of various materials (PA, PU, Teflon, etc.) with the following dimensions:
Process connection for Hose 8/6 Hose 6/4 Outer diameter 8 mm 6 mm Inner diameter 6 mm 4 mm
BA_EN_DE43 9 / 28
Page 10
3 | Assembly FISCHER Mess- und Regeltechnik GmbH
Plug 1
Plug 2
E1
E2
E3
E4
Access
Modbus configuration
2 1
3 4
5
A
1 2
4 3
5
A
1
4
3

3.3 Electrical connections

• By authorized and qualified specialized personnel only.
• When connecting the unit, the national and international electro-technical regulations must be observed.
• Disconnect the system from the mains, before electrically connecting the device.
• Do not connect the connector if strained.
Fig.8: Electrical connections
WARNING!Please note for the power supply to the devices that the M12 plugs are only suitable for max. 2A.
Fig.9: M12 connector 5-pin
Fig.10: M12 bush 5-pin
Plug 1 (Input)
Supply and bus connection
PIN Signal name Cable colour
A Coding
1 “Supply” dialogue +U
brown
b
2 BUS-D1 white 3 “Supply” dialogue -U
blue
b
4 BUS-D0 black 5 BUS-R grey
Plug 2 (Output)
Supply and bus connection
PIN Signal name Cable colour
A Coding
1 “Supply” dialogue +U
brown
b
2 BUS-D1 white 3 “Supply” dialogue -U
blue
b
4 BUS-D0 black 5 BUS-R grey
Digital inputs (E1 … E4)
Input for external potential-free contacts.
Fig.11: M8 bush
10 / 28 BA_EN_DE43
PIN Signal name Cable colour
1 Supply contact 1 (+) +U 3 Supply contact 1 (-) -U
brown
E1
blue
E1
4 Input E1 black
The assignment of the M8 bushes is the same for all contacts, which is why only the assignment of digital input E1 is shown here as a example.
Page 11
FISCHER Mess- und Regeltechnik GmbH Assembly | 3
MASTER DE43
1 2
DE43
1 2
DE43
1 2
Address 1 Address 2 Address 127
Bus termination
DC
AC
M
Feed
1 2E
Modbus 5
MASTER
M
TAP
M
Slave
TAP
LT LT
M
Slave
TAP
DE43
1 2
Supply
1 2E
DC
AC

3.3.1 Modbus RTU network

The DE43 is usually connected in a line network structure as a so-called slave to the Modbus RTU network. Up to 123 bus participants can be operated without an amplifier on one strand
NOTICE!Star-shaped networks are not allowed.
Fig.12: Modbus RTU network
Communication is effected solely via a Modbus master that is also connected to the bus system. The connected slaves only react to direct commands from the master, which is why communication between the slaves is not possible.
To guarantee fault-free data transmission, we recommend terminating the end point of the Modbus RTU network with a 120Ω resistor. These bus terminating resistors are available as accessories.
It can be connected to an existing Modbus network via a conventional T-piece (passive TAP).
Fig.13: Modbus connection
BA_EN_DE43 11 / 28
Page 12
3 | Assembly FISCHER Mess- und Regeltechnik GmbH
BUS-D1 BUS-D0
BUS-R
DC
AC
BUS-D1 BUS-D0
BUS-R
Ub+ Ub-
1 3
2 4
5
DE43 SlaveMaster
+
DE43
1 2
Address 24
DC
AC
2. Feed
1 2E
DE43
1 2
Address 23
U
b1
U
b2
3
2
5 5
Modbus
Ix< 2 A
x=1
k
Supply circuit
Fig.14: Supply
Please note that the M12 plugs are suitable for max. 2A. This value may already be exceeded if there are more than 23 bus participants (without digital inputs). For this reason, an intermediate feed should be provided at a suitable place.
Fig.15: Intermediate supply
Please note that a DE43 with digital inputs has a higher power draw. If the bus participants are equipped with digital inputs, the number of possible bus parti­cipants of a supply circuit are reduced.
The power draw of a device x with n digital inputs is calculated as follows: Ix = 55 mA + (n*4.5 mA)
This is calculated for the first bus participant and each of its successors. The results are accumulated in sequence until the result exceeds the limit value 2 A. The interim feed is then set after the bus participant k at which the total current of the supply circuit last lay below 2 A.
12 / 28 BA_EN_DE43
Page 13
FISCHER Mess- und Regeltechnik GmbH Start-up | 4
Sealing plug
Seal
DIP-switch
OFF
ON
Switch position
S1 S2 S3 S4 S5 S6 S7 S8
Baudrate Parität
Stoppbit
X ON

4 Start-up

4.1 Generalities

A prerequisite for commissioning is correct installation of all electrical supply lines and the pressure lines. All connections are arranged so that there are no mechanical forces acting on the device.
Also, know-how of the Modbus RTU protocol and the bus architecture are re­quired to commission the bus system.

4.2 Config select

The DE43 Transmitter can be configured using an 8-digit DIP switch. To this end, the sealing plug in the front plate needs to be removed. Below this is an 8­pin DIP switch which can be used to configure both the Modbus address and also the interface.
Fig.16: Access to the DIP switch
After all settings have been made, close the front plate with the plug. Always use the original seal in this case. The sealing plug is screwed in tightly by hand.

4.2.1 Interfaces configuration

NOTICE!An X marks a random switch setting
Fig.17: DIP switches
The switch S8 is used to select between the interface configuration and Modbus address setting. For the interface configuration, ensure that the switch S8 is al­ways in the setting ON.
BA_EN_DE43 13 / 28
Page 14
4 | Start-up FISCHER Mess- und Regeltechnik GmbH
S1 S2 S3 S4 S5 S6 S7 S8
Modbus Address OFF
Baud rate S1 S2 S3 S4 S5 S6 S7 S8
1200 OFF OFF OFF X ON 2400 ON OFF OFF X ON 4800 ON ON OFF X ON 9600 OFF ON OFF X ON 19200 ON OFF ON X ON 38400 OFF OFF ON X ON 57600 ON ON ON X ON
Parity S1 S2 S3 S4 S5 S6 S7 S8
None OFF OFF X X ON Identical parity ON OFF OFF X ON Not identical parity OFF ON OFF X ON
It is not possible to combine identical or non-identical parity with 2 stopbits.
Stopbits S1 S2 S3 S4 S5 S6 S7 S8
1 stopbit OFF X ON 2 stopbits ON X ON
The device needs to be restarted to confirm the settings. To do this, disconnect the device briefly from the power supply (plug 1).

4.2.2 Modbus address

To set the Modbus address, the switch S8 must be in the position OFF.
Fig.18: DIP switches
The address is entered in the dual system. The switches S1 to S7 represent the respective setting value as follows:.
S1 S2 S3 S4 S5 S6 S7
Binary 2
0
Decimal 1 2 4 8 16 32 64
For example:
The Modbus address 24 should be set.
S1 S2 S3 S4 S5 S6 S7 S8
Switch set­ting
Priority 0*2 Total 0 +0 +0 +8 +16 +0 +0 =24
OFF OFF OFF ON ON OFF OFF OFF
1
2
0
0*2
1
2
0*2
2
2
1*2
3
2
3
1*2
4
2
4
0*2
5
2
5
0*2
6
2
6
The device needs to be restarted to confirm the settings. To do this, disconnect the device briefly from the power supply (plug 1).
14 / 28 BA_EN_DE43
Page 15
FISCHER Mess- und Regeltechnik GmbH Start-up | 4
Master Slave
Init Request
Function Code Data Request
Instruction executed
&
Modbus response
Receive Response
Function Code Data Response
Master Slave
Init Request
Function Code Data Request
Error detected
&
Modbus response
Receive Response
Error CodeFunction Code (error)
Frame 1
3.5 char
3.5 char
4.5 char
Frame 2
3.5 char
Frame 3
t
0
Starting
≥3.5 char
Address
8 bit
Function
8 bit
Data
N x 8 bit
CRC Check
16 bits
End
≥3.5 char
Modbus message

4.3 Modbus functional description

The following describes the Modbus functions that support the DE43 Transmit­ter. The descriptions are initially kept general as explained in the Modbus Pro-
tocol Specification and are then supplemented with the unique features of the
DE43.

4.3.1 Modbus Transaction

A Modbus transaction comprises two parts. A request from the Master and a re­sponse from the Slave.
Fig.19: Error-free request/response cycle
If an error occurs during a Modbus transaction, the Function Code is replaced with a special Function Code with an error indicator in the Modbus Response message and a more detailed description of the error in the data field is sent.
Fig.20: Faulty request/response cycle

4.3.2 Modbus telegram

The maximum size of a Modbus telegram is 256Byte. The telegram comprises a 1 byte slave address, a 1 byte function code, the data and a 2byte CRC-check­sum.
BA_EN_DE43 15 / 28
Fig.21: Modbus Message Frame
Page 16
4 | Start-up FISCHER Mess- und Regeltechnik GmbH
0x02 MSB LSB MSB LSB
51 2 3 4Byte
0x02 N Byte1 Byte N
1 2 3Byte
...
0x82 Code
1 2Byte

4.3.3 Function code 0x02: Read Discrete Inputs

This function code is used to read digital inputs.
Request
The query contains the address of the first bits that are to be read and their number.
Byte Field name Size Value range
1 Function Code 1 byte 0x02
2.3 Start Address 2 bytes 0x0000 to 0xFFFF
4.5 Number of inputs 2 bytes 1 to 2000 (0x7D0)
The DE43 can be equipped with up to four digital inputs.
Bit Data type Description State
0 Boolean Digital input 1 0 or 1 1 Boolean Digital input 2 0 or 1 2 Boolean Digital input 3 0 or 1 3 Boolean Digital input 4 0 or 1
Response
Error
The states of the digital inputs are summarised as bytes in the response. The number of bytes (N) is the result of the number of inputs divided by 8. If there is a rest, the number of bytes increases (N=N+1).
However, as the DE43 only has a maximum of 4 inputs, only 1 byte is trans­ferred as a response.
The states of the digital inputs from the bit with the lowest value are saved within a byte. A bit value of 0 corresponds to the status OFF; a bit value of 1 corresponds to the status ON.
Byte Field name Size Value range
1 Function Code 1 byte 0x02 2 Number of bytes 1 byte N 3… Number of inputs N Bytes 8 Bit value
Byte Field name Size Value range
1 Function Code (error) 1 byte 0x82 2 Error code 1 byte
Code s. table Error codes [}21]
16 / 28 BA_EN_DE43
Page 17
FISCHER Mess- und Regeltechnik GmbH Start-up | 4
0x03 MSB LSB MSB LSB
51 2 3 4Byte
0x03 2N MSB
1 2 3Byte
...
4
LSB MSB LSB
Register 1 Register N

4.3.4 Function code 0x03: Read Holding Registers

This Function Code is used to read the Holding Register. The maximum pos­sible number of registers that can be addressed in one message is 125.
Request
The request contains the address of the first register that is to be read and the number of registers that need to be read. The addressing of the register starts with 0; the numbering of the registers starts with 1.
Byte Field name Size Value range
1 Function Code 1 byte 0x03
2.3 Start Address 2 bytes 0x0000 to 0xFFFF
4.5 Number of registers 2 bytes 0x0001 to 0x007D (1…125)
The DE43 Transmitter has precisely 1 Holding Register with the address 0x0000.
Bit Data type Description State
0 Unsigned Integer Pressure sensor1Sensor error 0 or 1
Response
1 Unsigned Integer Pressure sensor1Pressure too low 0 or 1
2 Unsigned Integer Pressure sensor1Pressure too high 0 or 1
3 Unsigned Integer RESERVED 0 or 1 4 Unsigned Integer Pressure sensor2Sensor error 0 or 1
5 Unsigned Integer Pressure sensor2Pressure too low 0 or 1
6 Unsigned Integer Pressure sensor2Pressure too high 0 or 1
7 Unsigned Integer RESERVED 0 or 1 8 Unsigned Integer Temp. sensor Sensor error 0 or 1 9 Unsigned Integer Temp. sensor Temperature too low 0 or 1 10 Unsigned Integer Temp. sensor Temperature too high 0 or 1 11 Unsigned Integer RESERVED 0 or 1 12 Unsigned Integer General System error 0 or 1 13 Unsigned Integer RESERVED 0 or 1 14 Unsigned Integer RESERVED 0 or 1 15 Unsigned Integer RESERVED 0 or 1
The response contains two bytes for each read register; therefore the number of bytes is twice of the number of registers (N).
Byte Field name Size Value range
1 Function Code 1 byte 0x03 2 Number of bytes 2 bytes 2N
3.4 Holding Register N x 2 Byte 16 Bit value
BA_EN_DE43 17 / 28
Page 18
4 | Start-up FISCHER Mess- und Regeltechnik GmbH
0x83 Code
1 2Byte
0x04 MSB LSB MSB LSB
51 2 3 4Byte
0x04 2N MSB
1 2 3Byte
...
4
LSB MSB LSB
Register 1 Register N
0x84 Code
1 2Byte
Error
Byte Field name Size Value range
1 Function Code (error) 1 byte 0x83 2 Error code 1 byte
Code s. table Error codes [}21]

4.3.5 Function code 0x04: Read Input Register

This Function Code is used to read the input register. The maximum possible number of registers that can be addressed in one message is 125.
Request
The request contains the address of the first register that is to be read and the number of registers that need to be read. The addressing of the register starts with 0; the numbering of the registers starts with 1.
Byte Field name Size Value range
1 Function Code 1 byte 0x04
2.3 Start Address 2 bytes 0x0000 to 0xFFFF
4.5 Number of registers 2 bytes 0x0001 to 0x007D (1…125)
Response
Error
The DE43 Transmitter has 3 Input Registers.
Reg.No. Address Data type Description Unit Contents
1 0x0000 Integer Measured value channel1PA Measured
value
2 0x0001 Integer Measured value channel2PA Measured
value
3 0x0002 Integer Temperature measured
value
°C Measured
value
The response contains two bytes for each read register; therefore the number of bytes is twice of the number of registers.
Byte Field name Size Value range
1 Function Code 1 byte 0x04 2 Number of bytes 2 bytes 2N
3.4 Content Register N x 2 Byte 16 Bit value
Byte Size Value range
1 Function Code (error) 1 byte 0x84 2 Error code 1 byte
18 / 28 BA_EN_DE43
Code s. table Error codes [}21]
Page 19
FISCHER Mess- und Regeltechnik GmbH Start-up | 4
0x2B 0x0E DevID ObjID
1 2 3 4Byte

4.3.6 Function code 0x2B/0x0E: Device Identification

This Function Code is used to read certain information about identification of the unit. The following object types are used in the FISCHER units:
Object ID Object Name Type Category
0x00 VendorName ASCII String Basic 0x01 ProductCode ASCII String Basic 0x02 MajorMinorRevision ASCII String Basic 0x03 VendorUrl ASCII String Regular 0x04 ProductName ASCII String Regular 0x05 ModelName ASCII String Regular 0x06 UserApplicationName ASCII String Regular
NOTICE!There are no objects of the Extended category.
Request
Byte Field name Size Value range
1 Function Code 1 byte 0x2B 2 MEI Type 3 Read Device ID Code 1 byte 01 / 02 / 04 4 Object ID 1 byte 0x00 to 0xFF
+)
MEI = Modbus Encapsulated Interface
+)
1 byte 0x0E
Read Device ID
The Read Device ID Code (DevID) serves to specify the access. If the code is not correct, an error message with the code 0x03 is sent.
01 Access to objects of the Basic category stream access 02 Access to objects of the Regular category stream access 04 Access to a single object individual access
If the length of the requested information exceeds the maximum possible length of the PDU, several transactions (Request/Response) must be carried out.
Object ID
The Object ID Code states on which object of the 'stream access‘ should start. If the Object ID does not match the existing objects, the 'stream access‘ starts with the first object of the category. In the event of an 'individual access‘, an er­ror message is generated with the error code 0x02.
BA_EN_DE43 19 / 28
Page 20
4 | Start-up FISCHER Mess- und Regeltechnik GmbH
0x2B 0x0E DevID
1 2 3 4Byte
Conf5Follow
6
Num ObjID Len Val
1
ObjID Len Val
Object NObject 0
...
List
Val
k
Val
... ...
...
0
1 k
...
N
Next
7
Response
The response comprises several bytes with status information followed by a list with the requested object information.
Byte Field name Size Value range
1 Function Code 1 byte 0x2B 2 MEI Type 1 byte 0x0E 3 Read Device ID Code 1 byte 01 / 02 / 03 / 04 4 Conformity Level 1 byte 0x83 5 More Follows 1 byte 0x00 / 0xFF 6 Next Object ID 1 byte Object ID Number 7 Number of Objects 1 byte
List of object data
Object(N).ID 1 byte Object(N).Length 1 byte Object(N).Value k Byte
Conformity Level
The Conformity Level specifies the information category and the access type that is supported.
0x83 Extended Identification stream and individual access
More Follows
If the length of the requested information exceeds the maximum possible length of the PDU, several transactions (Request/Response) must be carried out. The 'More Follows‘ byte signalises whether or not further requests are required to transfer all information.
0x00 no further objects 0xFF other objects available other transaction necessary
Next Object ID
If a further transaction is required (More Follows = FF), the Object ID for the fol­lowing Request is stated at this point.
Otherwise (More Follows = 00) this value is useless and is set to 00.
Number of Objects
This byte states the number N of the objects that are transferred in the re­sponse. In the case of 'individual access‘ the number of objects is = 01.
List of object data
Object(0).ID Object ID of the first object in the response Object(0).Length Length of the object Object(0).Value Value of the object … Object(N).ID Object ID of the last object in the response Object(N).Length Length of the object Object(N).Value Value of the object
20 / 28 BA_EN_DE43
Page 21
FISCHER Mess- und Regeltechnik GmbH Start-up | 4
0xAB Code
1 2Byte
Error
Byte Field name Size Value range
1 Function Code (error) 1 byte 0xAB (0x2B + 0x80) 2 Error code 1 byte
Code s. table Error codes [}21]

4.3.7 Error codes

0x01 The function is not supported 0x02 An invalid address is referenced 0x03 The request does not correspond to the expected format 0x04 Am error that could not be remedied occurred

4.4 LED flash codes

The operational status of the device is continuously signalised via two LEDs. The green LED signalises correct operation and will go off in the event of an er­ror. The error type is communicated via flash codes of the red LED.
ON The LED shines permanently Flash The LED flashes regularly for 0.2 s short The LED shines for approx. 0.5 s long The LED shines for approx. 1 s OFF The LED does not shine
green LED Red LED Description
ON OFF The DE43 is ready for operation ON Flash The DE43 sends an answer to the master via the
Modbus
OFF 1 x long
1 x short
OFF 1 x long
2 x short
OFF 1 x long
3 x short
OFF 1 x long
Pressure sensor 1: Error reading the sensor signal
Pressure sensor 2: Error reading the sensor signal
Temperature sensor: Error reading the sensor signal
Error reading the configuration parameter
10 x short
OFF 1 x long
Error writing the configuration parameter
11 x short
OFF 1 x long
12 x short
Wrong configuration of the MODBUS parameter (Baud rate, parity, stopbits)
BA_EN_DE43 21 / 28
Page 22
5 | Servicing FISCHER Mess- und Regeltechnik GmbH

5 Servicing

5.1 Maintenance

The instrument is maintenance-free. We recommend the following regular in­spection to guarantee reliable operation and a long service life:
• Check the function in combination with downstream components.
• Check the leak-tightness of the pressure connection lines.
• Check the electrical connections.
The exact test cycles need to be adapted to the operating and environmental conditions. In combination with other devices, the operating instructions for the other devices also need to be observed.

5.2 Transport

The measuring device must be protected against impacts. It should be transpor­ted in the original packaging or a suitable transport container.

5.3 Service

All defective or faulty devices should be sent directly to our repair department. Please coordinate all shipments with our sales department.
WARNING
Process media residues
Process media residues in and ondismantled devices can be a hazard to people, animals and the environment. Take adequate preventive measures. If required, the devices must be cleaned thoroughly.
Return the device in the original packaging or a suitable transport container.

5.4 Disposal

Please help to protect the environment by always disposing of the work pieces and packaging materials in compliance with the valid national waste and recyc­ling guidelines or reuse them.
22 / 28 BA_EN_DE43
Page 23
FISCHER Mess- und Regeltechnik GmbH Technical data | 6

6 Technical data

6.1 General

General information
Type designation DE43 Pressure type Differential pressure, relative pressure Measurement principle Piezo-resistive
Reference conditions (acc. to IEC 61298-1)
Temperature +15 … +25 °C Relative humidity 45 … 75 % Air pressure 86 … 106 kPa 860 … 1060 mbar Installation position User-defined

6.2 Input variables

Measuring variable Pressure, under-pressure and differential pres-
sure for neutral gaseous media
Damping (P=10…90%) 1 sec
Unit + ranges (0 … +p) + ranges (-p … +p)
Measuring range (p) PA 400 600 1000 1600 2500 ±250 ±400 ±600 ±1000 ±1600
kPa 0.4 0.6 1 1.6 2.5 ±0.25 ±0.4 ±0.6 ±1 ±1.6
mbar 4 6 10 16 25 ±2.5 ±4 ±6 ±10 ±16 Max. stat. operating pressure mbar 50 50 100 100 100 50 50 50 100 100 Bursting pressure mbar 150 150 300 300 300 150 150 150 300 300 Characteristic curve
deviation
TK Span
(*)
**)
Max. %FS 1.0 Type %FS 0.5 Max. %FS/10K 1.0 1.0 0.3 0.3 0.3 1.0 0.5 0.3 0.3 0.3 Type %FS/10K 0.3
TK zero-point
**)
Max. %FS/10K 1.0 1.0 0.4 0.4 0.4 1.0 0.5 0.4 0.4 0.4 Type %FS/10K 0.2
*)
Characteristic curve deviation (non-linearity and hysteresis) at 25°C
**)
Compensation range 0…60 °C

6.3 Communication parameter

interface RS 485 Report Modbus RTU Modbus specification Application Protocol Specification
V1.1b3 (April 26, 2012) Address 1 … 127 Baud rate 1200 … 57600 Baud Parity Even, uneven, parity Stopbits 1…2
BA_EN_DE43 23 / 28
Page 24
6 | Technical data FISCHER Mess- und Regeltechnik GmbH
Pre-set data format
Baud rate 9600 Baud Parity None Stopbit 1
Supported Modbus functions
0x02 Read Discrete Inputs 0x03 Read Holding Registers 0x04 Read Input Registers 0x2B / 0x0E Read Device Identification
For more information about this, please refer to the operating instructions and online http://www.modbus.org/docs/Modbus_Application_Protocol_V1_1b3.pdf.

6.4 Auxiliary energy

nominal voltage 24 V DC Admissible operating voltage 18 … 30 V DC Absorbed power Max. 2 W

6.5 Operating conditions

Ambient temperature range -10 … +70 °C Storage temperature range -20 … +70 °C Medium temperature range -10 … +70 °C Protection IP65 EMC EN 61326-1:2013
RoHS EN50581:2012

6.6 Construction design

Installation position User-defined Max. dimensions (WxHxT) 116 x 103 x 76 mm Weight 375 g

6.6.1 Connections

Modbus connector 1 M12 round plug connector
Modbus connector 2 M12 round plug connector
Digital inputs E1 … E4 M8 round plug connector (3-pin, female)
Process connection option 1 Aluminium CK screw connection for 6/4 or 8/6
Process connection option 2 Pneumatic plug connector for 6/4 or 8/6 mm
EN 61326-2-3:2013
(5-pin, male, max. 2A)
Plug 1 for supply and bus signals
(5-pin, female, max. 2A)
Plug 2 for forwarding the signals to the next BUS participant or to connect a BUS termina­tion plug
Depending on the model, 0, 2 or 4 proximity switches can be connected
mm hose
hose
24 / 28 BA_EN_DE43
Page 25
FISCHER Mess- und Regeltechnik GmbH Technical data | 6
20
18,5
26
76
70.5
61.5
90 76
758394
78
63
M12 Plug 1
M12 Plug 2
CK Screw connection
Pneumatic plug connection
27,5
13
20
Digital inputs E1 ... E4
116
E1
E2
E3
E4
E3
E4
E1
E2
2 inputs left 2 inputs right without inputs4 inputs

6.6.2 Materials

Housing Polyamide PA 6.6 Media-contacting material Silicon, PVC, aluminium, brass

6.6.3 Dimensional drawings

BA_EN_DE43 25 / 28
Fig.22: Dimensional picture
Page 26
7 | Order codes FISCHER Mess- und Regeltechnik GmbH
Process connection
Digital inputs
Operating voltage
Interface
Interface protocol
Electronic connection
Assembly
Type
Measuring range Channel 1
Code no.
D E 4 3 9 2 M M
1 2 5 6 7 8 9 10 11 123 4
Measuring range Channel 2

7 Order codes

Measuring range channel 1:
[1.2] [Pa]
D7 0 … 400 D8 0 … 600 D9 0 … 1000 E1 0 … 1600 E2 0 … 2500 Pa S6 -250 … +250 R1 -400 … +400 R2 -600 … +600 R3 -1000 … +1000 R4 -1600 … +1600
Measuring range channel 2:
[1.2] [Pa]
D7 0 … 400 D8 0 … 600 D9 0 … 1000 E1 0 … 1600 E2 0 … 2500 Pa S6 -250 … +250 R1 -400 … +400 R2 -600 … +600 R3 -1000 … +1000 R4 -1600 … +1600
Process connection:
[5.6]
40 CK aluminium screw connection for 6/4 mm hose
41 CK aluminium screw connection for 8/6 mm hose P6 Pneumatic plug connector MS nickel-plated for 6/4 mm hose P8 Pneumatic plug connector MS nickel-plated for 8/4 mm hose
26 / 28 BA_EN_DE43
Page 27
FISCHER Mess- und Regeltechnik GmbH Order codes | 7
Digital inputs:
[7] M8 round plug connector 3-pin, female
0 Without digital inputs
L Two digital inputs (E3, E4) left K Two digital inputs (E1, E2) right C Four digital inputs (E1, E2) right and (E3, E4) left
Operating voltage:
[8]
9 24 V DC
Interface:
[9]
2 RS 485
Interface protocol:
[10] (Code no.)
C Modbus RTU Protocol
Electrical connection:
[11]
C M12 round plug connector (Modbus, power supply)
M8 round plug connector (Digital inputs, optional→[7])
Assembly:
[12]
0 Standard (attachment boreholes on rear side) W Horizontal wall mounting
V Vertical wall mounting
BA_EN_DE43 27 / 28
Page 28
8 | Attachments FISCHER Mess- und Regeltechnik GmbH

8 Attachments

Fig.23: CE_DE_DE43
28 / 28 BA_EN_DE43
Loading...