FISCHER DE28 Instruction Manual

Page 1
Instruction Manual
DE28 Differential Pressure Transmitter
Table of Contents
1. Safety Instructions
2. Intended Applications
3. Product Description and Functions
4. Installation
5. Commissioning
6. Maintenance
7. Transport
8. Service
9. Accessories
10. Disposal
11. Specifications
12. Dimensions
13. Ordering Code
14. CE-Certificate

1. Safety Instructions

1.1. General

equipment must read this thoroughly before at­tempting to install or operate this equipment. A copy of this manual must always be kept accessi­ble at the place of work for reference by concerned personnel.
Chapter 1 (sections 1.2 through 1.7) contains ge-
2.6.08 BA_GB_DE28.fm
neral as well as specific safety instructions. Chap­ters 2 through 10, covering topics ranging from intended purpose of the equipment to its final dis­posal, also include important points relating to safety. Overlooking or ignoring any of these safety points can endanger humans and animals, and possibly cause damage to other equipment.
This manual contains detailed information about the product, and instructions for its installati­on, operation and maintenance. Operators and other technical personnel responsible for the

1.2. Personnel Qualification

Personnel responsible for installation, operation, maintenance and inspection of this product must have the qualifications, training and experience necessary to carry out such work on this type of equipment.

1.3. Risks of Disregarding Safety Instructions

Disregarding safety instructions, use of this pro­duct for purposes for which it is not intended, and/ or operation of this product outside the limits spe­cified for any of its technical parameters, can result in harm to persons, the environment, or the plant on which it is installed. Fischer Mess- und Regel­technik GmbH will not be responsible for conse­quences in such circumstances.

1.4. Safety Instructions for Operators

Safety instructions for the proper use of this pro­duct must be followed.
Page 2
This information must be available at all times to by per-
1 pressure chamber 2 inductive displacement transducer 3 measuring springs 4 measuring diaphragm
sonnel responsible for installation, operation, mainte­nance and inspection of this product. Adequate steps must be taken to prevent the occurrence of hazardous conditions that can be caused by electric energy and the convertible energy of the process media. Such conditi­ons can, for example, be the result of improper electrical or process connections. Detailed information is available in relevant published norms (DIN EN, UVW in Germany; and equivalents in other countries), industrial standards such as DVWG, Ex-, GL-, VDE guidelines, as well as re­gulations of the local authorities (e.g., EVUs in Germa­ny).

1.5. Modifications Forbidden

Modification or other technical alteration of the product is not permissible. This also applies to the use of unautho­rized spare parts for repair / maintenance of the product. Any modifications to this product, if and as necessary, should be done only by Fischer Mess- und Regeltechnik GmbH.

1.6. Operational Restrictions

The operational reliability of the product is guaranteed only when used for intended purposes. The product must be selected and configured for use specifically with defi­ned process media. The limiting values of operating pa­rameters, as given in the product specification sheet, must never be crossed.

1.7. Safety Considerations during Installation and Maintenance

The safety instructions given in this manual, existing na­tional regulations relating to accident prevention, and the internal safety rules and procedures of the user organi­zation regarding safety during installation, operation and servicing must all be followed meticulously.
It is the responsibility of the users to ensure that only sui­tably qualified and experienced technical personnel are used for installation, operation and servicing of this equipment.

2. Intended Applications

Measuring Transmitter for overpressure, partial vacuum and differential pressure of liquid and aerial media. The product may be used only for applications and under conditions specified by the manufacturer. Please confer with Fischer Mess- und Regeltechnik prior to using this transmitter along with polluted or aggressive media. For use with this media it needs to be adjusted in every part with direct contact to the media.

3. Product Description and Functions

3.1. Block Schematic Diagram

3.2. Principles of Operation

This transmitter is based on a rugged and uncomplicated diaphragm movement. The operating principle of the sy­stem is identical for all applications of this type. In a state of equilibrium, the forces of the springs on both sides of the diaphragm are balanced.
The pressure or differential pressure to be measured creates an unbalanced force of the springs for the measuring range until a new equilibrium is reached.
A centre-mounted tappet transfers the motion of the dia­phragm system to the core of an inductive displacement transducer. The subsequent converter circuit converts this motion into an electrical output signal 0(4) - 20 mA li­near, 3-wire connection.

4. Installation

The electronic module is mounted on a flat plate or panel, for which it has integral hole flanges. The pressure trans­mitters are calibrated at the factory while mounted up­right, pressure ports downward and must be mounted this way.

4.1. Process Connections

Only technicians who are qualified and authorized for this type of work should undertake installation.
Only for intended mechanic process connection - see ordering code on type plate on the instrument for mo­del specification.
Ensure that the process equipment and pressure li­nes are at atmospheric pressure before making pres­sure connections to the instrument.
The instrument should be provided with suitable pro­tection against pressure surges.
Ensure that the mechanical configuration and materi­als of construction of the instrument are compatible with the process media.
Ensure that process pressure is always less than the specified safe pressure rating.
2
Page 3

4.2. Electrical Connections

connectors
Signal
24 V DC / AC
Only technicians who are qualified and authorized for this type of work should undertake installation.
Electrical connections must conform to relevant inter­national, national and local regulations and norms re­lating to electrical and instrumentation installations.
Switch off electrical power to the plant before attemp­ting electrical installation work of any kind.
Make electrical connections to the transmitter though a suitable energy-limiting safety device (isolation or zener barrier).

5. Commissioning

Power supply, pressure lines, switching lines and signal cabling to the pressure transmitter must be correctly sel­ected to meet operational requirements, and installed in a way that does not cause physical stress to the instru­ment.

5.4. Electrical Connection

6. Maintenance

The instrument is inherently maintenance-free.
However, to ensure reliable operation and maximize the operating life of the instrument, it is recommended that the instrument is regularly inspected, e.g.:

5.1. Pressure Connections

The instruments pressure ports are marked by + and symbols. The pressure applications need to be installed according to the label.
Differential pressure measurement:+ higher pressure
lower pressure Pressure measurement: + pressure port Negative pressure measurement: negative pressure
port

5.2. Shock Pressure Moderation

During pulsating pressure on the plant mechanical wear and disturbances in functional capability may occur. To avoid this we recommend installing absorbers into the pressure lines.

5.3. Location of Connectors

Check the output signal.
Check the pressure connections for leaks.
Check the electrical connection (screw terminals).
Inspection and test schedules depend on operating and site conditions. The operating manuals of other equip­ment to which the differential pressure transmitter is con­nected must be read thoroughly to ensure that all of them work correctly when connected together.

7. Transport

The product must be protected against shock and vibra­tion during transport. It must therefore be properly pak­ked, preferably in the original factory packaging, whenever it is to be transported.

8. Service

Any defective devices or devices with missing parts should be retourned to Fischer Mess- und Regeltechnik GmbH. For quick service contact our service department.
Remaining medium in and on dismant­led measuring instruments may cause danger to persons, environment and equipment. Take reasonable precauti-
ons! Clean the instrument thoroughly if necessary.

9. Accessories

N.A.
3
Page 4

10. Disposal

Protect your environment! Use the product in accordance with re­levant regulations. Please be aware of environmental consequences of dispo­sal at the end of the product's life, and take care accordingly.
4
Page 5

11. Specifications

General
Measuring ranges 0-0.4 0-0.6 0-1 0-1.6 0-2.5 0-4 0-6 bar
Nominal pressure 16 bar
Max. pressure load one-sided overpressure protected up to nominal pressure,
on (+) and (-) side of diaphragm, partial vacuum protected
Permissible ambient temperature 0 up to +70°C
Max. storage temperature 70 °C
Protection class IP54 per DIN EN 60529
Linearity 2% FS
Hysteresis 1% FS
Electrical
Electrical connection 3-wire
Operating voltage 24 V DC / AC 24 V DC / AC
range 15...30 V DC range 15...30 V DC
Output signal 0...20 mA 0...10 V
4...20 mA
20...30 V AC 20...28 V AC
Load 380 Ω for all 2 K Ω
operating voltages
Connections
Pressure connection female thread G 1/8
cutting ring connection (brass) for 6mm tube cutting ring connection (brass) for 8mm tube
Electrical connection fixed numbered cable, prewired
Materials
Case material polycarbonate
Pressure chamber brass
Measuring
diaphragm NBR / Viton
®
Mounting
Mounting position upright, pressure ports downward
Measuring transmitter is reverse battery and short circuit protected.
5
Page 6

12. Dimensions (all units in mm unless stated otherwise)

cutting ring connection for ø 6 mm M12x1.5 cable gland
6
Page 7

13. Ordering Code

0
0 L 0 0
Differential Pressure Transmitter DE 28
Measuring Range
0 ... 400 mbar....................................................................>
0 ... 0.6 bar....................................................................>
0 ... 1 bar....................................................................>
0 ... 1.6 bar....................................................................>
0 ... 2.5 bar....................................................................>
0 ... 4 bar....................................................................>
0 ... 6 bar....................................................................>
Pressure Chamber / Gaskets
pressure chamber, measuring diaphragm, gasket: Ms/NBR ............ >
pressure chamber, measuring diaphragm, gasket: Ms/Viton®..........>
Pressure Connection
Female thread G 1/8................................................................................>
Cutting ring connection (brass) for 6mm tube..........................................>
Cutting ring connection (brass) for 8mm tube..........................................>
83 01 02 03 04 05 06
M N
00 28 29
Electrical Connection
Numbered cable, 1m, prewired.................................................................................>
Numbered cable, 2.5m, prewired..............................................................................>
Numbered cable, 5m, prewired.................................................................................>
1 2 5
Output Signal
0 - 20 mA linear, 3-wire connection ..................................................................................>
4 - 20 mA linear, 3-wire connection ..................................................................................>
0 - 10 V DC linear, 3-wire connection ...............................................................................>
Power supply
24 V DC / AC ...........................................................................................................................>
A P C
L
7
Page 8

14. CE-Certificate

Technische Änderungen vorbehalten • Subject to change without notice • Changements techniques sous réserve
Fischer Mess- und Regeltechnik GmbH • Bielefelder Str. 37a • D-32107 Bad Salzuflen • Tel. +49 5222 9740 • Fax +49 5222 7170
eMail: info@fischermesstechnik.de • www.fischermesstechnik.de
8