Fedders C42ACD1VF, C48ACD1VF, C30ABD1VF, C60ACD1VF, C24ABD1VF User Manual

...
0 (0)
Fedders C42ACD1VF, C48ACD1VF, C30ABD1VF, C60ACD1VF, C24ABD1VF User Manual

Residential & Light Commercial HVAC

Split System Air Conditioner

112 thru 5 Tons

208/230 Volt, 1-Phase, 60 Hz

Rated in Accordance with ARI Standard 210. Certification Applies Only When Used with Proper Components as Listed with ARI. Additional rating information can be found at www.aridirectory.org

Performance:

Efficiency rating of 13 SEER and 14 SEER Cooling capacities from 112 to 5 tons

Refrigerant Circuit:

Factory installed liquid line filter drier Long life copper tubes, aluminum fins State-of-the-art compressors

Large, wrap-around coil surface

Quality Built:

Galvanized steel exterior cabinet with 1,000-hour salt spray, powder-coated finish

Powder-coated fan guard

Full louvered panel to protect coil Formed base with 212" ground clearance Limited 5-year warranty on parts

Easy To Install:

Factory-charged with R-22 refrigerant

Only three screws to access electrical controls Easy access to service valves

 

 

 

 

 

 

 

 

 

 

 

Model

Size

Nominal

Min. Circuit

Max. Fuse or

Operating Dimensions

Min. Mounting

Ship / Operating

 

 

Number

(tons)

BTUH

Ampacity

Breaker

H x W x D (inches)

Pad Size (inches)

Weight (lbs)

 

 

C18ABD1VF

1 12

18,000

9.1

15

26 12 X 21 12 X 21 12

24 x 24

144 / 138

 

 

 

 

 

 

 

 

 

 

 

 

C24ABD1VF

2

24,000

11.5

15

26 12 X 21 12 X 21 12

24 x 24

142 / 136

 

 

C30ABD1VF

2 12

30,000

14.3

20

32 12

X 21 12

X 21 12

24 x 24

169 / 163

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C36ACD1VF

3

36,000

18.7

30

32 12

X 29 12

X 29 12

32 x 32

189 / 180

 

 

C42ACD1VF

3 12

42,000

20.3

35

32 12

X 29 12

X 29 12

32 x 32

213 / 204

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C48ACD1VF

4

48,000

23.1

40

32 12

X 29 12

X 29 12

32 x 32

217 / 208

 

 

C60ACD1VF

5

60,000

30.1

50

39 X 29 12 X 29 12

32 x 32

230 / 220

 

 

 

 

 

 

 

 

 

 

 

 

 

Product Specifications

PHYSICAL DATA

 

MODEL SIZE

18

24

30

36

42

48

60

 

 

 

 

 

 

 

 

 

 

 

 

PERFORMANCE DATA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOMINAL CAPACITY (BTUH)

18,000

24,000

30,000

36,000

42,000

48,000

60,000

 

 

 

 

 

 

 

 

 

 

 

 

FAN DATA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN MOTOR TYPE

PSC

PSC

PSC

PSC

PSC

PSC

PSC

 

 

 

 

 

 

 

 

 

 

 

 

HP

1/6

1/6

1/5

1/3

1/3

1/3

1/3

 

 

 

 

 

 

 

 

 

 

 

 

DIAMETER

18"

18"

18"

22"

22"

22"

24"

 

 

 

 

 

 

 

 

 

 

 

 

BLADE

3

3

3

3

3

3

3

 

 

 

 

 

 

 

 

 

 

 

 

RPM

1,050

1,050

1,050

1,050

1,050

1,050

950

 

 

 

 

 

 

 

 

 

 

 

 

CFM

1,800

1,800

1,800

3,400

3,400

3,400

4,000

 

 

 

 

 

 

 

 

 

 

 

 

OUTDOOR COIL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TYPE

 

Enhanced Aluminum Plate Fin / Rifled Copper Tube

 

 

 

 

 

 

 

 

 

 

 

 

 

COIL FACE AREA (ft2)

9.5

9.5

12.2

18.2

18.2

18.2

22.2

 

 

 

 

 

 

 

 

 

 

 

 

O.D.

7mm

7mm

7mm

7mm

7mm

7mm

7mm

 

 

 

 

 

 

 

 

 

 

 

 

FPI / ROWS

18 -2

18-2

18-2

18-1

18-2

18-2

18-3

 

 

 

 

 

 

 

 

 

 

 

 

ELECTRICAL DATA (208/230 – 1-60, VOLTAGE RANGE 197V - 253V)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MINIMUM CIRCUIT AMPACITY - MCA (amps) 1

9.1

11.5

14.3

18.7

20.3

23.1

30.1

 

 

 

 

 

 

 

 

 

 

 

 

MAXIMUM OVERCURRENT PROTECTIVE DEVICE-MOCP(amps)2

15

15

20

30

35

40

50

 

 

COMPRESSOR RLA (Rated Load Amps)

6.5

8.4

10.3

13.5

14.8

17

22.1

 

 

 

 

 

 

 

 

 

 

 

 

COMPRESSOR LRA (Locked Rotor Amps)

48

39

61

78

78

86

137

 

 

 

 

 

 

 

 

 

 

 

 

FAN MOTOR FLA (Full Load Amps)

1.0

1.0

1.4

1.8

1.8

1.8

1.9

 

 

 

 

 

 

 

 

 

 

 

 

REFRIGERANT CONNECTIONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LIQUID LINE CONNECTION SIZE (In. OD)

3/8

3/8

3/8

3/8

3/8

3/8

1/2

 

 

 

 

 

 

 

 

 

 

 

 

SUCTION LINE CONNECTION SIZE (In. OD)

3/4

3/4

7/8

7/8

7/8

7/8

1 1/8

 

 

 

 

 

 

 

 

 

 

 

 

RECOMMENDED LINE SET LIQUID TUBE DIAMETER (In. OD)

3/8

3/8

3/8

3/8

3/8

3/8

1/2

 

 

 

 

 

 

 

 

 

 

 

 

RECOMMENDED LINE SET SUCTION DIAMETER (In. OD)

3/4

3/4

7/8

7/8

7/8

7/8

1 1/8

 

 

 

 

 

 

 

 

 

 

 

 

FACTORY CHARGE R-22 - OZ.

72

106

91

87

128

150

204

 

 

 

 

 

 

 

 

 

 

 

NOTE: Control circuit is 24V on all units and requires external power source. Copper wire must be used from service disconnect to unit. ALL motors/compressors contain internal overload protection.

1.Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.

2.Time delay fuses may be used in place of HACR circuit breaker.

2

Specifications subject to change without notice.

Loading...