Emerson Tank Contents Transmitter MAS 2600 User Manual

4.8 (4)
Installation & User Manual
Ed 19UK
June 2013
MAS2600
Installation & User Manual
Ed 19UK June 2013
Page 2 of 28
Table of contents
Description and Operation ............................................................................................. 3
MAS2600 Tank Contents Tra nsmit ter ..............................................................................................3
Application .........................................................................................................................................3
Intrinsically Safe in Hazardous Areas ...............................................................................................3
Type Approvals .................................................................................................................................3
Technical Specifications ................................................................................................ 4
MAS2600 Ordering Information ................................................................................. 5
Type ...................................................................................................................................................6
Measuring Ranges .............................................................................................................................6
Selecting the Measuring Range .....................................................................................................7
Selecting the Transducer Type ......................................................................................................7
Absolute Transducers ....................................................................................................................8
Basic Rules ....................................................................................................................................8
Forepeak Tank ...............................................................................................................................8
Draft ...............................................................................................................................................9
Temperature Sensor ...........................................................................................................................9
Cable ..................................................................................................................................................9
Brackets for Interna l Mounting - drawing no. G022 P010 ......................................................... 10
Pole Mounting - drawing no. G022P 011 ................................................................................... 10
1” Pipe End Mounting - drawing no. G022P015 ....................................................................... 11
Flange Mounting - drawing no. G022P013 ................................................................................ 11
Flexible rubber tube mounting 80 .............................................................................................. 12
Flexible PTFE tube mounting .................................................................................................... 12
DN25 flange with 1” ball va lve drawing no. G022 P019 ........................................................ 13
Amplifier Box ................................................................................................................................. 14
Deck Box 165B9035 .................................................................................................... 15
Handling ....................................................................................................................... 16
Installation .................................................................................................................... 17
Intrinsically Safe Installation ....................................................................................... 19
Testing and Recalibrating ............................................................................................ 22
Testing ............................................................................................................................................. 22
Recalibrating Gauge Tra nsmitter u si ng Te st Cup ty pe G022 S100 ................................................ 22
Recalibrating Gauge Transmitter using Vacuum (for gauge transmitters only) ............................ 23
Recalibrating the Absolu t e Tra nsm itter us ing Te st Cup type G022S100 ...................................... 24
Maintenance and Trouble Shooting ............................................................................. 26
Maintenance .................................................................................................................................... 26
Trouble Shooting ............................................................................................................................ 26
MAS2600 Test sheet ...................................................................................................................... 27
Installation & User Manual
June 2013 Ed 19UK
Page 3 of 28
CERTIFICATE REF.:
4-20 mA
Li nt = 20 uH
x
MARINE AUTOMAT ION DENMARK
S/N:
Umax = 33 V
T
Ci nt = 1 0 nF
C
i
EE
X
a
90-C.95948
T5
amb.: -40 to +85 °C
I 45 mA
K=
<
2600
TWO WI RE T RANSMITTER
2600 SERIES
S/N 46374
1.5 bar g
PDCR-941-1
MAS 2600
DMS

Description and Operation

MAS2600 Tank Contents Transmitter

The MAS2600 is a 2-wire 4-20 mA level
transmitter consisting of a transducer and an
amplifier interconnected by a 6-core vented
cable.
Transducer:
The transducer is a pressure sensitive silicon
micro strain gauge sensor mounted in a glass
to metal seal. The sensor is protected by an
isolation diaphragm, electron beam welded
to the transducer housing, with an oil filling
between the sensor and the diaphragm.
Pressure changes on the front of the
diaphragm will bring a resistance change in
the Wheatstone bridge of the transducer.
This change in the Wheatstone bridge will
be transmitted to the amplifier as a change in
the electrical signal.
The transducer is fully welded, housed in
titanium with a titanium diaphragm.
All transducer types are submersible (IP68).
The transducer is available in three versions:
Gauge version.
Absolute version.
High temperature gauge vers io n.
As optional the transducer is available with a
built-in Pt100 temperature sensor.
Amplifier:
The amplifier is available in the following
options:
Programmable version: Calibration is
made by dip switches and potentiometers.
Differential version: For measuring of
both pressure and vacuum measuring.
The amplifier is housed in a sea water
resistant polyester casing (IP56).

Application

The MAS2600 has been developed for level
measuring in ballast, oil, service and fresh
water tanks as well as tanks containing
media which are not hostile to titanium.

Intrinsically Safe in Hazardous Areas

The MAS2600 is DEMKO approved for use
with standard transmitter zener barriers or
Ex isolation amplifiers and is Ex ia IIC T4
compliant in accordance with IEC 60079-
0:2007 and IEC 60079-11:2006.

Type Approvals

DNV, GL, LRS, MRS, BV, RINA, KRS,
ABS.
CE marked in accordance with EU directive.
Transducer
Amplifier box
Installation & User Manual
Ed 19UK June 2013
Page 4 of 28
0
100
200
300
400
500
600
700
17
20
23
26
29
32
Load resistance (ohm)
Power supply (V)
Max. load resistance
at various power supply

Technical Specifications

Transducer Ranges:
Gauge: 0-3.5 / 0-7 / 0-16 / 0-35 m H
2
O.
Absolute: 0-20.394 / 0-35.690 m H
2
O.
Programmable Measuring Ranges:
Each transducer range is programmable in 8
steps.
Accuracy:
± 0.25% F.S. at 20°C.
Stability:
Max. ± 0.1% / Year.
TEB (Total Error Band):
± 2.0% F.S. at -20 to +80°C.
EMC immunity influence < ±0.5%FS
Overload Capability:
Min. 4 x transducer range with no changes in
calibration.
6 x transducer range burst pressure.
Built-in Temperature Sensor Pt100:
Optional.
Power Supply:
The Power Supply can vary from 17-33
VDC. Permissible load resistance is shown
graphically below. Calculation formula:
R
loop max.
(Kohm) =
mA25
17V-U
Loop
Output Current:
4-20 mA DC, loop powered 2-wire system.
Current Limiting:
Max: 25 mA
Sensor Materials:
Housing: Titanium Grade 2
Diaphragm: Titanium Grade 4
Operating Temperature Ranges:
Transducer: -20 to +125°C
Standard cable: -20 to + 80°C
High temperature cable: -20 to +125°C
Amplifier: -40 to + 85°C
Protection Class:
Transducer: IP 68
Amplifier: IP 56
Intrinsic Safety:
Ex ia IIC T4 compliant.
Max. 75 m cable between transducer and
transmitter amplifier.
Transmitter dimensions
Amplifier box:
MARINE AUTOMATION DENMARK
Cint = 10 nF
2600 SERIES
4-20 mA
CERTIFICATE REF.:
Lint = 20 uH
x
EE
X
i
a
C
amb.: -40 to +85 °C
I 45 mA
S/N:
Umax = 33 V
T5
90-C.95948
2600
T
K=
<
TWO WIRE TRANSMITTER
55.0
110.0
75.0
45.0
98.0
PG11
cable gland
1/8" NPT
vent fitting
4 pcs. ø4.5
Use 4x20mm bolts and nuts
for suspension on a 4mm
thick surface
Transducer:
120.0
3.0
30.0
25.0
6-core vented cable, ø8.0
Front view
Installation & User Manual
June 2013 Ed 19UK
Page 5 of 28

MAS2600 Ordering Information

Type
A absolute transducer
G gauge transducer
H high temperature gauge transducer
Transducer Ranges
1 3,5 mH
2
O gauge or high temp.
2 7,0 mH
2
O gauge or high temp.
3 16,0 mH
2
O gauge or high temp.
4 35,0 mH
2
O gauge or 0,8 – 3,5 bar absolute
7 0,8 – 2,0 bar absolute
Temperature Sensor
0 without
1 Built-in Pt100 (Not available for IS installations )
Cable Max. 300 meters – max 75 meters for IS installations
XX XLPE standard cable length in meters (up to 80°C).
XX FEP high temperature cable length in meters (up to 125°C) (Not IS inst).
Mounting
0 without fittings
1 brackets for internal mounting
2 pole mounting
3 1" pipe end mounting
4 flange mounting DN 25
5 flange mounting DN 40
6 flange mounting DN 50
9 flexible rubber tube mounting – 80 ºC (add length in meters)
P flexible PTFE tube mounting – 125 ºC (add length in meters) (Not IS inst)
V DN25 flange / 1” ball valve
A-M replacement
Amplifier Box
0 not supplied
1 standard box with PG 11 / PG 11
2 standard box with PG 11 / PG 13,5
3 standard box with PG 11 / PG 16
5 standard box with PG 13,5 / PG 13,5
6 standard box with PG 11 / PG 11 – filling hole
7 standard box with PG 11 / PG 13,5 – filling hole
8 standard box with PG 11 / PG 16 – filling hole
Amplifier PCB
0 not supplied
without terminals for temperature sensors:
P programmable output range gauge
D differential output range gauge
with terminals for temperature sensors:
S programmable output range gauge
M differential output range gauge
X
X
X
-
XX
-
X
/
X
X
Installation & User Manual
Ed 19UK June 2013
Page 6 of 28
Type MAS2600-XXX-XX-X/XX
A: Absolute Transducer. The absolute transducer has no breather pipe, because it refers to
absolute vacuum. An atmospheric pressure sensor is used to compensate for the atmospheric
pressure. The absolute transducer is especially suitable for open deck applications, where the
amplifier box may be exposed to flooding.
G: Gauge Transducer. The gauge transducer is fitted with a breather pipe at the back of the
diaphragm to compensate for the atmospheric pressure. The breather pipe is connected to a
vent plug in the amplifier box. The gauge transducer is suitable for most applications.
H: High Temperature Transducer. The high temperature transducer is available in gauge version
only. The transducer is mounted with a special high temperature cable and designed for
heated tanks e.g. HFO tanks, and other applications with high tank media temperatures. The
transducer can be flange mounted or internally mounted.
Measuring Ranges MAS2600-XXX-XX-X/XX
Gauge Transmitter:
The MAS2600 Gauge Transmitter is supplied in 4 ranges. In the programmable amplifier the
measuring range is divided into 8 sub-ranges and operated by means of the range select switch.
The transmitter output signal can be adjusted to 20 mA within the following sub-ranges.
Range No.
Transducer type
Type 1:
0 – 3.5 mH
2
O
Type 2:
0 – 7.0 mH
2
O
Type 3:
0 – 16.0 mH
2
O
Type 4:
0 – 35.0 mH
2
O
1 0.20 – 0.37 mH
2
O 0.20 – 0.30 mH
2
O 0.50 – 0.75 mH
2
O 1.00 – 1.90 mH
2
O
2 0.37 – 0.54 mH
2
O 0.30 – 0.50 mH
2
O 0.75 – 1.00 mH
2
O 1.90 – 2.80 mH
2
O
3 0.54 – 0.73 mH
2
O 0.50 – 0.70 mH
2
O 1.00 – 1.50 mH
2
O 2.80 – 3.90 mH
2
O
4 0.73 – 1.10 mH
2
O 0.70 – 1.10 mH
2
O 1.50 – 2.50 mH
2
O 3.90 – 5.80 mH
2
O
5 1.10 – 1.92 mH
2
O 1.10 – 1.80 mH
2
O 2.50 – 4.00mH
2
O 5.80 – 9.90 mH
2
O
6 1.92 – 3.10 mH
2
O 1.80 – 3.00 mH
2
O 4.00 – 6.00 mH
2
O 9.90 – 15.30 mH
2
O
7 3.10 – 3.50 mH
2
O 3.00 – 4.80 mH
2
O 6.00 – 10.00 mH
2
O 15.30 – 25.10 mH
2
O
8
NOT
APPLICABLE
4.80 – 7.10 mH
2
O 10.00 – 16.00 mH
2
O 25.10 – 35.60 mH
2
O
Installation & User Manual
June 2013 Ed 19UK
Page 7 of 28
MAS 2600 A m plifier box
Flange mounted
G022P013
Sensor pos. above
lowest point
Tankheight
Vent pipe height
TWO WIRE TRANSMITTER
2600 SERIES
90-C.95948
T5
Cint = 10 nF
C
CERTIFICATE REF.:
4-20 mA
Lint = 20 uH
x
i
EE
X
a
MARINE AUTOMATION DENMARK
S/N:
Umax = 33 V
T
amb.: -40 to +85 °C
I 45 mA
K=
<
2600
Absolute Transmitter:
The MAS2600 Absolute Transmitter is available in two ranges.
The output signals are calibrated as follows:
Transducer type 4 : 0.8 - 3.5 bar abs
Transducer type 7 : 0.8 - 2.0 bar abs
Selecting the Measuring Range:
When selecting the measuring range it is important to consider the tank height, vent pipe height,
the tank type and the specific gravity (SG) of the tank contents.
The transducer measures the height of the fluid (water gauge) from the transducer diaphragm to
the surface of the fluid, including the fluid in the vent pipe.
To ensure measuring accuracy a transducer type within the range no. 4, 5, 6, 7 and 8 is
recommended.
Guidelines for selection of transducer measuring ranges are set out in the following.
Selecting the Transducer Type:
Gauge and High Temperature Gauge Transducers:
The Gauge Transmitter is normally used on dry and pressure neutral locations.
The Gauge Transmitter is available in 4 ranges:
0-3.5 mH
2
O.
0-7.0 mH
2
O.
0-16.0 mH
2
O.
0-35.0 mH
2
O.
Installation & User Manual
Ed 19UK June 2013
Page 8 of 28
Absolute Transducers
:
The Absolute Transmitter is typically used if the amplifier is exposed to water, e.g. on open deck.
The Absolute Transmitter is available in 2 ranges: 0-20 and 0-35 mH
2
O. In practice this means 10
mH
2
O less than the nominal range because of the atmospheric pressure which must be taken into
consideration when choosing the transducer.
A transducer with an effective range larger than the tank height should be selected.
Basic Rules:
1. The selected measuring range must be larger than the tank height.
2. The selected measuring range must be larger than
tank height + vent pipe height
2
EXAMPLE: Tank height = 6 m
Vent pipe height = 14 m
1. The selected measuring range must be larger than 6 m due to the height of the tank.
2. The selected measuring range must be larger than
6+14
2
= 10 m due to the total height of the
tank and the vent pipe combined.
Select a transducer with a measuring range of 16 mH
2
O as this is the next measuring range larger
than 10 m.
Turn the range select switch on the amplifier to range No. 7.
Normally the selection of transducer, range select and calibration are done by DAMCOS.
Special consideration applies to e.g. forepeak tanks and draft measuring when selecting the
measuring range of the transducer.
Forepeak Tank:
Transducer measuring range > tank height: Select the next measuring range.
EXAMPLE: Tank height 12 m.
Based on the tank height a transducer with a measuring range of 16 mH
2
O should be selected.
However, due to the dynamic conditions in the forepeak tank, a transducer with a measuring
range of 35 mH
2
O, i.e. the next in line, should be selected.
Turn amplifier range select switch to range No. 6.
Installation & User Manual
June 2013 Ed 19UK
Page 9 of 28
Class approved
Sea valve
TWO WIRE TRANSMITTER
2600 SERIES
90-C.95948
T5
Cint = 10 nF
C
CERTIFICATE REF.:
4-20 mA
Lint = 20 uH
x
i
EE
X
a
MARINE AUTOMATION DENMARK
S/N:
Umax = 33 V
T
amb.: -40 to +85 °C
I 45 mA
K=
<
2600
Weather deck
MAS2600 amplifier box
Sensor pos. above
Ships hull
Ships hull
Vent pipe min. 1”
Min. draft
Draft
:
Transducer measuring range > max. draft minus sensor position.
This rule applies provided the transducer is mounted in accordance with the installation drawing
for draft transmitters (vent pipe min. 1"). The sensor may be mounted direct on the sea valve with
an air release valve if the ship is sailing in calm waters.
If the transducer is installed in tanks which may have excessive dynamic stresses such as e.g.
high pump pressure, long bottomed tanks with a risk of slashing etc., contact Emerson Process
Management Marine Solutions, Damcos.
Temperature Sensor MAS2600-XXX-XX-X/XX
The transducer can be supplied with a built-in Pt100 temperature sensor. The temperature sensor
will only give a proper reading, if the transducer is an internally mounted type.
0: Without temperature sensor.
1: With temperature sensor
Cable MAS2600-XXX-XX-X/XX
Two types of transducer cable is available. The standard cable for applications with temperatures
never exceeding 80°C, and high temperature cable for applications with temperatures up to
125°C. The transducer cable is delivered in whole meters.
For further information require data sheet.
To make the MAS2600 transmitter easy to install, and for later service purposes, the transducer
cable should be as short as possible, though considering the position of the transducer and
amplifier box.
Max. cable length: 300 m.
When installing in hazardous areas max. cable length: 75 m.