PowerSure™ PST
Quick-Start Guide for 350-500VA; 120V
•Quick-Start guide
•PowerSure family user manual on CD (also at www.liebert.com)
•Warranty card
•RJ-11 cord, 7 ft. (2.1 m)
•USB cable, 6 ft. (1.8m)
For more details, refer to the PowerSure user manual on CD.
Para una información más detallada, consulte el manual del usuario de la familia PowerSure en el CD.
TOP OF UPS |
|
LEFT SIDE OF UPS |
Power cord |
|
|
|
|
|
|
|
Output receptacles |
|
|
6.5 ft. (2m) |
|
|
|
|
|
|
(surge protection |
|
|
Data Line |
|
only) |
|
|
Protection |
|
|
|
Cautionary Markings |
Connectors |
|
|
|
Refer to Bottom for |
|
|
Power ON/OFF/ |
|
Circuit |
RIGHT SIDE OF UPS |
|
Alarm Silence |
|
protector |
|
|
Utility Indicator* |
|
|
|
Output receptacles |
(Green) |
|
|
|
Site Wiring Fault Indicator |
|
|
||
(battery backup and |
USB port |
|
||
(Red) |
|
|
||
surge protection) |
|
|
|
|
Fault Indicator* (Red/Green) |
|
|
||
|
|
|
INSTALLATION |
Plug this type of equipment |
|||
Read all safety, installation and operating instructions in the PowerSure family user |
into black receptacles ONLY |
|||
|
|
|
||
manual on the included CD or at www.liebert.com before operating the UPS. Adhere |
|
|
|
|
to all warnings on the unit and in the manual. |
Inkjet |
Scanners |
|
|
1. Install the UPS indoors in a controlled environment, where it cannot be accidentally |
Fax |
|||
printers |
|
|||
turned off. Place it in an area of unrestricted airflow around the unit, away from |
|
|
machines |
|
|
|
|
||
water, flammable liquids, gases, corrosives and conductive contaminants. Maintain |
Plug computers, monitors, |
|||
a minimum clearance of 4 inches (100mm) on each side of the UPS. Maintain an |
||||
routers and cash registers into |
||||
ambient temperature range of 32°F to 104°F (0°C to 40°C). |
orange receptacles |
|
2.Plug the PST’s power cord into an AC outlet. Check the Site Wiring Fault Indicator on the rear; if it is illuminated, refer to the Troubleshooting section.
3.Plug any computers and monitors into the orange receptacles for battery backup and surge protection; other office machines that do not exceed the capacity of the UPS may be plugged into either of the two (2) black receptacles, which provide surge protection only.
4.Connect Phone/Fax/DSL/Internet/Modem devices to data line connectors.
5.Press and release the ON/OFF/Alarm Silence button to turn on the UPS. The UPS will beep and the Utility Indicator will illuminate (green).
6.Turn on connected equipment.
This button controls output power to the connected load and has three functions:
•Turns the PowerSure PST ON
•Turns the PowerSure PST OFF •Silences PowerSure PST alarms
TURN THE UPS ON: Press and release the main ON/OFF button to start the UPS. An audible alarm will sound briefly.
TURN THE UPS OFF: When the PST is ON, hold the main ON/OFF button down for more than 2 seconds to shut it down. An audible alarm will sound briefly.
SILENCE AN ALARM: When a UPS alarm is active, press and release the main ON/OFF button to silence the audible alarm (Exceptions: low battery, overload and overtemperature). DO NOT hold the button down for more than 2 seconds or the PST will shut down.
CHECK THE PST’S CONDITION: Three status indicators on the front of the UPS illuminate to specify the status of the UPS (see Troubleshooting section for details).
SITE WIRING FAULT INDICATOR (AMBER)
The Site Wiring
Fault Indi-
cator on the top of
thePST, as shown,
illumi-
nates amber when the UPS detects a lineneutral reversal or a poor neutral-ground. (See Troubleshooting Chart if indicator is illuminated.)
Model Number |
PA350-120U |
PA500-120U |
|
Model Rating VA / W |
350/225 |
500 / 300 |
|
DIMENSIONS: in (mm) |
|
|
|
Unit W x D x H |
6.6 x 9.8 x 3.7 |
6.6 x 9.8 x 3.7 |
|
(168 x 250 x 95) |
(168 x 250 x 95) |
||
|
|||
Shipping W x D x H |
9.4 x 13.8 x 5.6 |
9.4 x 13.8 x 5.6 |
|
(238 x 350 x 142) |
(238 x 350 x 142) |
||
|
|||
WEIGHT: lbs (kg) |
|
|
|
|
|
|
|
Unit |
11.7 (5.3) |
13.5 (6.1) |
|
Shipping |
12.1 (5.5) |
13.9 (6.3) |
|
INPUT AC PARAMETERS |
|
|
|
|
|
|
|
Surge Protection |
603J |
||
Voltage Range Without |
98VAC - 140VAC ±3VAC |
||
Battery Operation |
|||
|
|
||
Frequency |
57 - 63 Hz (±0.4Hz) |
||
Input Power Cord |
6.5 ft.attached, w/ NEMA 5-15 P |
||
OUTPUT AC PARAMETERS |
|
||
|
|
|
|
|
(3) NEMA 5-15R (orange) battery |
||
Output Receptacles |
backup+surge protection |
||
(2) NEMA 5-15R (black) surge |
|||
|
|||
|
protection |
||
Voltage (Battery Mode) |
120VAC ±8% |
||
Output Current |
2.9 A |
4.2 A |
|
Waveform (Battery Mode) |
Stepped Sinewave |
||
Frequency (Battery Mode) |
60Hz ±1Hz |
||
Overload Warning |
>100% |
||
Overload Shutdown |
>110% |
||
BATTERY PARAMETERS |
|
|
|
|
|
|
|
Type |
Valve-regulated, nonspillable, lead |
||
acid |
|||
|
|||
Quantity x Voltage x Rating |
1 x 12V x 5 Ah |
1 x 12V x 7 Ah |
|
Transfer Time |
4 – 6 ms typical |
||
Back-up Time: |
At 77°F (25°C), resistive loading, w/ |
||
fully charged batteries: |
|||
|
|||
Full load |
5 minutes |
3 minutes |
|
Half load |
16 minutes |
15 minutes |
|
Recharge Time |
12 hours to 90% capacity, after full |
||
discharge into resistive load |
|||
|
ENVIRONMENTAL
Operating |
+32°F to + 104°F |
|
Temperature |
(0°C to +40°C) |
|
Storage |
+5°F to + 122°F (- |
|
Temperature |
15°C to +50°C) |
|
Relative |
0% to 95%, non- |
|
Humidity |
condensing |
|
Operating |
Up to 10,000 ft. |
|
(3000 m) at 86°F |
||
Elevation |
(30°C) w/o |
|
|
derating |
|
Audible Noise |
< 40 dBA, at 1 |
|
meter |
||
|
||
AGENCY |
|
|
|
|
|
Safety |
UL 1778, c-UL |
|
Listed |
||
|
||
|
ANSI C62.41, |
|
|
Category A, Level |
|
Surge |
3, (IEEE 587, |
|
Category A); |
||
|
||
|
EN61000-4-5, |
|
|
Level 3, Criteria A |
|
ESD |
EN61000-4-2, |
|
Level 3, Criteria A |
||
|
||
Susceptibility |
EN61000-4-3, |
|
Level 2, Criteria A |
||
|
||
Electrical Fast |
EN61000-4-4, |
|
Transient/Burst |
Level 3, Criteria A |
|
Emissions |
FCC Part 15, |
|
Subpart B, |
||
|
Class B |
|
Harmonics |
EN61000-3-2 |
|
Conducted |
EN61000-4-6 |
|
Immunity |
||
|
||
Flicker |
EN61000-3-3 |
|
Transportation |
ISTA Procedure |
|
1A |
||
|
The PowerSure PST has a USB interface port for communication that will work with the built-in Microsoft Power Manager software on the user’s PC, if the PC is so equipped. It will provide UPS status and manages the automatic, orderly shutdown of the computer. The UPS (USB) communications meets HID standard, version 1.11. All USB models are compatible with Microsoft Windows 2000, Windows XP and Mac OS 10.2 or later. All USB models ship with a 6 ft. (1.8m) USB cable.