Emerson PowerSure 350-500VA, PA350-120U, PA500-120U User Manual

0 (0)
Emerson PowerSure 350-500VA, PA350-120U, PA500-120U User Manual
Top of UPS
Site Wiring Fault Indicator (Amber)

PowerSurePST

Quick-Start Guide for 350-500VA; 120V

WHATS IN THE BOX

Quick-Start guide

PowerSure family user manual on CD (also at www.liebert.com)

Warranty card

RJ-11 cord, 7 ft. (2.1 m)

USB cable, 6 ft. (1.8m)

For more details, refer to the PowerSure user manual on CD.

Para una información más detallada, consulte el manual del usuario de la familia PowerSure en el CD.

TOP OF UPS

 

LEFT SIDE OF UPS

Power cord

 

 

 

 

 

Output receptacles

 

 

6.5 ft. (2m)

 

 

 

 

 

(surge protection

 

 

Data Line

 

only)

 

 

Protection

 

 

 

Cautionary Markings

Connectors

 

 

 

Refer to Bottom for

 

 

Power ON/OFF/

 

Circuit

RIGHT SIDE OF UPS

 

Alarm Silence

 

protector

 

 

Utility Indicator*

 

 

 

Output receptacles

(Green)

 

 

 

Site Wiring Fault Indicator

 

 

(battery backup and

USB port

 

(Red)

 

 

surge protection)

 

 

 

Fault Indicator* (Red/Green)

 

 

 

 

 

INSTALLATION

Plug this type of equipment

Read all safety, installation and operating instructions in the PowerSure family user

into black receptacles ONLY

 

 

 

manual on the included CD or at www.liebert.com before operating the UPS. Adhere

 

 

 

to all warnings on the unit and in the manual.

Inkjet

Scanners

 

1. Install the UPS indoors in a controlled environment, where it cannot be accidentally

Fax

printers

 

turned off. Place it in an area of unrestricted airflow around the unit, away from

 

 

machines

 

 

 

water, flammable liquids, gases, corrosives and conductive contaminants. Maintain

Plug computers, monitors,

a minimum clearance of 4 inches (100mm) on each side of the UPS. Maintain an

routers and cash registers into

ambient temperature range of 32°F to 104°F (0°C to 40°C).

orange receptacles

 

2.Plug the PST’s power cord into an AC outlet. Check the Site Wiring Fault Indicator on the rear; if it is illuminated, refer to the Troubleshooting section.

3.Plug any computers and monitors into the orange receptacles for battery backup and surge protection; other office machines that do not exceed the capacity of the UPS may be plugged into either of the two (2) black receptacles, which provide surge protection only.

4.Connect Phone/Fax/DSL/Internet/Modem devices to data line connectors.

5.Press and release the ON/OFF/Alarm Silence button to turn on the UPS. The UPS will beep and the Utility Indicator will illuminate (green).

6.Turn on connected equipment.

CONTROLS AND INDICATORS

This button controls output power to the connected load and has three functions:

•Turns the PowerSure PST ON

•Turns the PowerSure PST OFF •Silences PowerSure PST alarms

TURN THE UPS ON: Press and release the main ON/OFF button to start the UPS. An audible alarm will sound briefly.

TURN THE UPS OFF: When the PST is ON, hold the main ON/OFF button down for more than 2 seconds to shut it down. An audible alarm will sound briefly.

SILENCE AN ALARM: When a UPS alarm is active, press and release the main ON/OFF button to silence the audible alarm (Exceptions: low battery, overload and overtemperature). DO NOT hold the button down for more than 2 seconds or the PST will shut down.

CHECK THE PST’S CONDITION: Three status indicators on the front of the UPS illuminate to specify the status of the UPS (see Troubleshooting section for details).

SITE WIRING FAULT INDICATOR (AMBER)

The Site Wiring

Fault Indi-

cator on the top of

thePST, as shown,

illumi-

nates amber when the UPS detects a lineneutral reversal or a poor neutral-ground. (See Troubleshooting Chart if indicator is illuminated.)

SPECIFICATIONS

Model Number

PA350-120U

PA500-120U

Model Rating VA / W

350/225

500 / 300

DIMENSIONS: in (mm)

 

 

Unit W x D x H

6.6 x 9.8 x 3.7

6.6 x 9.8 x 3.7

(168 x 250 x 95)

(168 x 250 x 95)

 

Shipping W x D x H

9.4 x 13.8 x 5.6

9.4 x 13.8 x 5.6

(238 x 350 x 142)

(238 x 350 x 142)

 

WEIGHT: lbs (kg)

 

 

 

 

 

Unit

11.7 (5.3)

13.5 (6.1)

Shipping

12.1 (5.5)

13.9 (6.3)

INPUT AC PARAMETERS

 

 

 

 

 

Surge Protection

603J

Voltage Range Without

98VAC - 140VAC ±3VAC

Battery Operation

 

 

Frequency

57 - 63 Hz (±0.4Hz)

Input Power Cord

6.5 ft.attached, w/ NEMA 5-15 P

OUTPUT AC PARAMETERS

 

 

 

 

 

(3) NEMA 5-15R (orange) battery

Output Receptacles

backup+surge protection

(2) NEMA 5-15R (black) surge

 

 

protection

Voltage (Battery Mode)

120VAC ±8%

Output Current

2.9 A

4.2 A

Waveform (Battery Mode)

Stepped Sinewave

Frequency (Battery Mode)

60Hz ±1Hz

Overload Warning

>100%

Overload Shutdown

>110%

BATTERY PARAMETERS

 

 

 

 

 

Type

Valve-regulated, nonspillable, lead

acid

 

Quantity x Voltage x Rating

1 x 12V x 5 Ah

1 x 12V x 7 Ah

Transfer Time

4 – 6 ms typical

Back-up Time:

At 77°F (25°C), resistive loading, w/

fully charged batteries:

 

Full load

5 minutes

3 minutes

Half load

16 minutes

15 minutes

Recharge Time

12 hours to 90% capacity, after full

discharge into resistive load

 

ENVIRONMENTAL

Operating

+32°F to + 104°F

Temperature

(0°C to +40°C)

Storage

+5°F to + 122°F (-

Temperature

15°C to +50°C)

Relative

0% to 95%, non-

Humidity

condensing

Operating

Up to 10,000 ft.

(3000 m) at 86°F

Elevation

(30°C) w/o

 

derating

Audible Noise

< 40 dBA, at 1

meter

 

AGENCY

 

 

 

Safety

UL 1778, c-UL

Listed

 

 

ANSI C62.41,

 

Category A, Level

Surge

3, (IEEE 587,

Category A);

 

 

EN61000-4-5,

 

Level 3, Criteria A

ESD

EN61000-4-2,

Level 3, Criteria A

 

Susceptibility

EN61000-4-3,

Level 2, Criteria A

 

Electrical Fast

EN61000-4-4,

Transient/Burst

Level 3, Criteria A

Emissions

FCC Part 15,

Subpart B,

 

Class B

Harmonics

EN61000-3-2

Conducted

EN61000-4-6

Immunity

 

Flicker

EN61000-3-3

Transportation

ISTA Procedure

1A

 

COMMUNICATIONS

The PowerSure PST has a USB interface port for communication that will work with the built-in Microsoft Power Manager software on the user’s PC, if the PC is so equipped. It will provide UPS status and manages the automatic, orderly shutdown of the computer. The UPS (USB) communications meets HID standard, version 1.11. All USB models are compatible with Microsoft Windows 2000, Windows XP and Mac OS 10.2 or later. All USB models ship with a 6 ft. (1.8m) USB cable.