Emerson NX 30-200kVA, NX 50 and 60 Hz, NX 400V User Manual

5 (2)
Emerson NX 30-200kVA, NX 50 and 60 Hz, NX 400V User Manual

AC Power

For Business-Critical Continuity

Liebert NX™

User Manual

50 and 60 Hz, 30-200kVA, 400V

TABLE OF CONTENTS

1.0 SINGLE MODULE UPS INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

1.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 1.2 Preliminary Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 1.3 Location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

1.3.1 UPS Room . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.3.2 External Battery Room . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.3.3 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

1.4 Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

1.4.1 System Cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.4.2 30 to 40kVA UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.4.3 60-200kVA UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.4.4 Moving the Cabinets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.4.5 Clearances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 1.4.6 Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 1.4.7 Final Positioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 1.4.8 Floor Anchoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 1.4.9 Cable Entry. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

1.5 External Protective Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

1.5.1 Rectifier and Bypass Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 1.5.2 External Battery. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 1.5.3 UPS Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

1.6 Power Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

1.6.1 Cable Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

1.7 Control Cables and Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

1.7.1 Monitor Board Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

1.8 Dry Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

1.8.1 Input Dry Contacts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 1.8.2 Maintenance Bypass Cabinet Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 1.8.3 External Circuit-Breaker Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 1.8.4 Output Dry Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 1.8.5 Emergency Power Off Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 1.8.6 External Bypass Switch Interlock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

2.0 BATTERY INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17

2.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

2.2 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

2.3 Battery Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

2.3.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

2.3.2 Temperature Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

2.3.3 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

2.3.4 Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

2.3.5 Circuit Breaker Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

2.3.6 Moving the Battery Cabinets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

2.3.7 Cable Entry. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

2.3.8 General Arrangement Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

i

2.4 Battery Power Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

2.4.1 Connection Principles. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

2.4.2 Fitting the Batteries. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

2.4.3 Connecting the Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

2.4.4 Battery Room Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

2.5 Battery Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

2.6 Battery Circuit Breaker Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

2.6.1 Battery Temperature Sensor—Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

3.0 UPS MULTI-MODULE INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45

3.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

3.2 Paralleled UPS Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

3.2.1 Cabinet Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

3.2.2 External Protective Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

3.2.3 Power Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

3.2.4 Control Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

3.3 Hot-Standby UPS Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

3.3.1 Cabinet Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

3.3.2 External Protective Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

3.3.3 Power Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

3.4 Dual Bus System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

3.4.1 Cabinet Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

3.4.2 External Protective Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

3.4.3 Power Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

3.4.4 Control Wires . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

3.4.5 Extended Dual Bus Synchronization Option (DBS Interface Box) . . . . . . . . . . . . . . . . . . . . . 51

4.0 EXTERNAL OPTIONAL CABINETS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52

4.1 External Maintenance Bypass Cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 4.2 Interlock with UPS Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 4.3 Isolation Transformer Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 4.4 Top Cable Entry Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

5.0 INSTALLATION DRAWINGS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55

6.0 OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75

6.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75

6.1.1 Split-Bypass Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76 6.1.2 Static Transfer Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76 6.1.3 Battery Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76 6.1.4 Battery Temperature Compensation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76 6.1.5 Redundant Control Power Supply Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76 6.1.6 Socket Outlet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76

6.2 Multi Module UPS—1+N . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77

6.2.1 Features of NX Multi-Module UPS Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 6.2.2 Requirements for Paralleling of UPS Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78

ii

6.3 Modes of Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78

6.3.1 Normal Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78 6.3.2 Battery Mode (Stored Energy Mode). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78 6.3.3 Auto-Restart Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78 6.3.4 Bypass Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 6.3.5 Maintenance Mode (Manual Bypass) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 6.3.6 ECO Mode (Single UPS Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 6.3.7 Parallel Redundancy Mode (System Expansion) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 6.3.8 Hot-Standby Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 6.3.9 Frequency Converter Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 6.3.10 Source Share Mode (Co-Generation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79

6.4 Battery Management—Set During Commissioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80

6.4.1 Normal Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 6.4.2 Advanced Functions (Software Settings Performed by the Commissioning Engineer) . . . . . 80

6.5 Battery Protection (settings by commissioning engineer) . . . . . . . . . . . . . . . . . . . . . . . . . . . 80

7.0 OPERATING PROCEDURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .81

7.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81 7.2 Startup in Normal Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81 7.3 Startup into ECO Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 7.4 Battery Test Mode Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83

7.4.1 Test Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83

7.5 UPS Self-Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84

7.5.1 UPS Self-Test Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84

7.6 Maintenance Bypass Procedure and UPS Shutdown. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84 7.7 Isolation of One Module in a Multi-Module System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86

7.7.1 Multi-Module Systems With External Output CB1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86 7.7.2 Multi-Module System Without External Output Circuit Breaker 1 . . . . . . . . . . . . . . . . . . . . 87

7.8 Insertion of One Module in a Multi-Module System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88 7.9 Shutdown Procedure—Complete UPS and Load Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . 89 7.10 Emergency Shutdown With EPO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89 7.11 Reset After Shutdown for Emergency Stop (EPO Action) or Other Conditions . . . . . . . . . . 90 7.12 Auto Restart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 7.13 Language Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91 7.14 Changing the Current Date and Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91 7.15 Command Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91

8.0 OPERATOR CONTROL PANEL AND DISPLAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .92

8.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92

8.1.1 Mimic Power Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93 8.1.2 Audible Alarm (Buzzer) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93 8.1.3 Direct Access Push Buttons (Keys) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94 8.1.4 LCD Monitor and Menu keys. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94 8.1.5 Detailed Description of Menu Items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96

8.2 All Status and Event Messages Displayed on the UPS Front Panel. . . . . . . . . . . . . . . . . . . 98

iii

8.3 Prompt (Pop-Up) Windows. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103 8.4 Dynamic Energy Flow Chart and UPS Help Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104 8.5 Default Screen Saver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104

9.0 OPTIONS—FOR ASSEMBLY INSIDE THE UPS CABINET . . . . . . . . . . . . . . . . . . . . . . . . . .105

9.1 Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105

9.1.1 Redundant Back-Feed Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105 9.1.2 Seismic Anchors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105 9.1.3 Degree of Protection for the UPS Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105 9.1.4 Battery Start Facility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105 9.1.5 Bypass Current Sharing Inductors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106 9.1.6 Battery Ground Fault Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108 9.1.7 Replacing Dust Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109 9.1.8 Redundant Fan for Power Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109

9.2 Communication and Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110

9.2.1 OC Web Card - SNMP/HTTP Network Interface Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111 9.2.2 Relay Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112 9.2.3 Multiport-4 Card. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113 9.2.4 OC485 Web Card – Modbus, Jbus, IGM Net . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114 9.2.5 Remote Alarm Monitor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114

10.0 TECHNICAL SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115

10.1 Conformity and Standards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115

iv

FIGURES

Figure i Model number nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ix Figure 1 Residual current circuit breakers (RCCB) symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Figure 2 Monitoring board (U2) auxiliary terminal block detail. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Figure 3 Input dry contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Figure 4 Output dry contacts and EPO wiring for firmware before M162 . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Figure 5 EPO wiring for firmware M200 or later . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Figure 6 Narrow battery cabinet with top and bottom cable entry locations. . . . . . . . . . . . . . . . . . . . . . . . 21 Figure 7 Narrow battery cabinet with top cable entry location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Figure 8 Wide battery cabinet with top and bottom cable entry locations . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Figure 9 Wide battery cabinet with bottom cable entry location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Figure 10 Wide battery cabinet with fuse or optional circuit breaker locations . . . . . . . . . . . . . . . . . . . . . . 25 Figure 11 Large battery cabinet dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Figure 12 Large battery cabinet with fuse or optional circuit breaker locations . . . . . . . . . . . . . . . . . . . . . . 27 Figure 13 SENXA0NBCN4LCB.eps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Figure 14 SENXA0NBCN4LF. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Figure 15 SENXA0NBCN5LCB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Figure 16 SENXA0NBCN5LF. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Figure 17 SENXA0NBCWXX3LCB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Figure 18 SENXA0NBCWXX3LF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Figure 19 SENXA0NBCWXX4LCB_2x4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Figure 20 SENXA0NBCWXX4LCB_4x2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Figure 21 SENXA0NBCWXX4LF_2x4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Figure 22 SENXA0NBCWXX4LF_4x2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Figure 23 Battery room design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 Figure 24 Battery circuit breaker box—30-120kVA and 140-200kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Figure 25 Battery circuit breaker box connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Figure 26 Single temperature sensor and monitor board—U2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Figure 27 Multiple temperature sensors, battery circuit breaker box and UPS module. . . . . . . . . . . . . . . . 44 Figure 28 Emergency power off connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

Figure 29 Typical 1+N system block diagram with common input supply, with separate batteries

and optional output / bypass distribution panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 Figure 30 Dry contacts, multiple UPS modules with distribution panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 Figure 31 Connection of 1+N system parallel control cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Figure 32 Hot standby configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Figure 33 Typical dual bus system configuration with static transfer switch and Load Bus Synch . . . . . . 50 Figure 34 Connections of a typical dual bus system utilising Load Bus Synch . . . . . . . . . . . . . . . . . . . . . . . 51 Figure 35 External maintenance bypass cabinet with separate bypass input. . . . . . . . . . . . . . . . . . . . . . . . 52

Figure 36 Equipment arrangement—UPS, battery cabinet and top-entry Isolation Transformer

Cabinet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 Figure 37 Single input external isolation transformer cabinet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 Figure 38 Dual input external isolation transformer cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 Figure 39 Output external isolation transformer cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 Figure 40 Electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Figure 41 General arrangement—30-40kVA UPS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 Figure 42 Front view, door open30-40kVA NX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 Figure 43 Cable terminal layout—30-40kVA NX. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 Figure 44 Location of parallel logic board M3 and options—30-40kVA NX . . . . . . . . . . . . . . . . . . . . . . . . . . 59 Figure 45 Internal battery layout and connections—30-40kVA NX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 Figure 46 General arrangement—60-80kVA NX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

v

Figure 47 Front view doors open—60-80kVA NX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 Figure 48 Cable terminal layout—60-80kVA NX. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 Figure 49 General arrangement—100-120kVA NX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 Figure 50 Front view, door open—100-120kVA NX. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 Figure 51 Parallel logic board location—100-120kVA NX. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 Figure 52 Cable terminal layout—100-120kVA NX. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 Figure 53 General arrangement—140-200kVA NX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 Figure 54 Front view, door open—140-200kVA NX. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67 Figure 55 Parallel logic board location—140-200kVA NX. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67 Figure 56 Cable terminal layout—140-200kVA NX. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68 Figure 57 Optional external Maintenance Bypass Cabinet, 600mm wide . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 Figure 58 Optional external Maintenance Bypass Cabinet, 800mm wide . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 Figure 59 Optional External Maintenance Bypass Cabinet, 850mm wide . . . . . . . . . . . . . . . . . . . . . . . . . . 71 Figure 60 Cabling diagram, 30-200kVA, MBP-T cabinet, configuration 1.1.1. . . . . . . . . . . . . . . . . . . . . . . . 72 Figure 61 Cabling diagram, 30-200kVA, MBP-T cabinet, configuration 1.1.3. . . . . . . . . . . . . . . . . . . . . . . . 73 Figure 62 Cabling diagram, 30-200kVA, MBP-T cabinet, configuration 1.1.5. . . . . . . . . . . . . . . . . . . . . . . . 74 Figure 63 Single unit block diagram with split-bypass input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 Figure 64 1+N multi-module UPS with external maintenance bypass switch . . . . . . . . . . . . . . . . . . . . . . . 77 Figure 65 Example of configuration for single UPS with external Maintenance Bypass Cabinet . . . . . . . . 85

Figure 66 Typical 1+N system block diagram with common input supply, with separate batteries

and optional output / bypass distribution panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86 Figure 67 UPS control and display panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92 Figure 68 Graphic LCD monitor windows and keypad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94 Figure 69 Menu tree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95 Figure 70 Help screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104 Figure 71 Default screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104 Figure 72 Battery Start Option for UPS with external battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106 Figure 73 Bypass current sharing inductances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107 Figure 74 Battery ground fault detection set connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108 Figure 75 Replacing the dust filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109 Figure 76 Communication bays and cable location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110 Figure 77 OC Web Card data summary window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111 Figure 78 OC Web Card battery data summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111 Figure 79 SiteNet MultiPort4 Intellislot pin configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113 Figure 80 OC485 Web card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114

vi

TABLES

Table 1 Maximum steady state AC and DC currents. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Table 2 Distance from floor to connection point on the equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Table 3 Input dry contacts at X3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Table 4 Maintenance bypass cabinet interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Table 5 External circuit-breaker interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Table 6 Output dry contact relays for firmware before M162 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Table 7 EPO input contact relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Table 8 Dimensions and weight. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Table 9 UPS-circuit breaker configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 Table 10 Battery circuit breaker box legend. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Table 11 Battery control label description (X102) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Table 12 UPS control and display panel components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92 Table 13 Rectifier indicator—1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93 Table 14 Battery indicator—2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93 Table 15 Bypass indicator—3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93 Table 16 Inverter indicator—4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93 Table 17 Load indicator—5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93 Table 18 Status (Alarm) indicator—6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93 Table 19 Audible alarm key. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93 Table 20 Menu key Icons and their meaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94 Table 21 UPS system window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96 Table 22 Descriptions of UPS menus and data window items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96 Table 23 UPS messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98 Table 24 Prompt windows, meanings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103 Table 25 Seismic anchor sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105 Table 26 Bypass current sharing inductors-dimensions, values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106 Table 27 Dry contact fault alarm signal is available for remote monitoring . . . . . . . . . . . . . . . . . . . . . . . 108 Table 28 Relay Card pin configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112 Table 29 SiteNet MultiPort4 Intellislot pin assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113 Table 30 NX communication options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114 Table 31 Compliance with European, international standards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115 Table 32 Environmental characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115 Table 33 Efficiency, AC/AC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116 Table 34 Mechanical characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116 Table 35 Rectifier AC input (mains) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116 Table 36 Intermediate DC circuit, battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117 Table 37 Inverter output to critical load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118 Table 38 Bypass input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119

vii

Dear Customer:

Please allow us to congratulate you on choosing a Liebert manufactured Uninterruptible Power System.

If this is your first Liebert UPS, we cordially welcome you to a lifetime relationship of after-sales support designed to keep your Liebert UPS and your systems permanently at their peak performance.

If you already own and use a Liebert UPS, then we are doubly honoured by your decision to continue this valued relationship.

Our philosophy is reflected in our mission statement “Keeping Business in Business,” and with this we strive to contribute to the growth & success of your business.

Please give us your valued feedback to help us realise our mission.

EMERSON NETWORK POWER

viii

Figure i Model number nomenclature

NXa

0

A0

Revision to Base Unit

NX Product Line

Feature Set for Region A0 - EMEA B0 - Aust/NZ C0 - Japan D0 - China

E0 - Latin Amer

F0 - Other

200

U

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input &

 

 

 

 

 

 

 

 

 

50/60Hz

 

 

 

Output

 

 

 

 

 

 

 

 

 

 

 

 

Voltage

 

 

Voltage

 

Code

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

220/380

 

F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

230/400

 

U

 

 

 

 

 

 

 

 

 

 

 

 

 

 

240/415

 

G

Output kVA

 

 

 

 

 

 

 

 

 

 

 

 

UPS Single Module

Liebert NXa UPS module ratings: 30 & 40kVA (with internal battery)

60, 80, 100, 120, 140, 160, 200kVA (without internal battery)

Example: NXA0A0200U =

200kVA module for Europe and Middle East, 400V/230V output

Options

Model Identification

Note

Narrow battery cabinet

NXA0BCN

Specify: UPS kVA rating,

 

 

3, 4 or 5-shelves

 

 

fuse or circuit breaker protection

Wide battery cabinet

NXA0BCW

 

 

 

 

Battery Circuit Breaker Box

NXA0BCB

Specify UPS kVA rating

Battery Start Kit

NXA0UFXBB

 

 

 

Battery Ground Fault detection kit

NXA0UFXBGF

 

 

 

Battery temperature probe (for external battery)

NXA0UFXBTS

Maintenance bypass cabinet (separate bypass input)

NXA0MBX

Specify total system kVA

 

 

 

Transformer cabinet

NXA0TCX

Specify UPS kVA & I/O Voltage

 

 

 

Fan Redundancy kit

NXA0UFXRF

Specify UPS kVA rating

Seismic Anchor kit

NXA0UFXSAN

 

 

 

Bypass current sharing inductance

NXA0UFXBK

 

 

 

Dual bus control cable 05-10-15 metres

NXA0UFXD

Specify length in metres

Parallel control cable kit 05-10-15 metres

NXA0UFXP

Specify length in metres

 

 

 

Relay Card (On Bat, Bat Low, On Byp, Sum, UPS Fail)

RELAYCARD-INT

Intellislot plug-in cards—3 slots available.

Relay Card 4 (4 sets On Bat, bat Low)

MULTIPORT 4

 

Webbrowser/TCPIP/SNMP Card

OCWEB-LB

 

Jbus/Modbus Card

OC485CARD

 

RAM - Remote Alarm Monitor

NXA0CFXRAM

Requires RELAYCARD-INT

Modem card

NXA0CFXMOD

 

 

 

Large Battery Cabinet

NXA0NBCL

 

 

 

Maintenance bypass cabinet (separate bypass input)

NXA0NMBX

Transformer cabinet

NXA0NTCX

 

 

 

Air Filter (One Filter)

NXA0UFXARF

 

 

 

Dual Bus Extension Kit 50-150 Meters

NXXXXMLBSKIT

(XXX: 050 or 150)- 'Specify Length in metres.

 

 

Used for extension in length or dual bus

 

 

arrangement between Nx and non-Nx

 

 

sources'

Individual Battery Monitoring

BDS 40 or BDS 256

Specify number of blocks. Consult Emerson

 

 

Network Power representatives for complete

 

 

configuration

 

 

 

 

ix

 

x

SAFETY PRECAUTIONS

This manual contains information concerning the installation and operation of this Emerson Network Power Liebert NX Uninterruptible Power System (UPS).

This manual should be read before commencing installation.

The UPS must be commissioned and serviced by an engineer approved by the manufacturer (or agent).

Failure to do so could result in personnel safety risk, equipment malfunction and invalidation of warranty.

The Liebert NX has been designed for Commercial/Industrial use only, and is not recommended for use in life support applications.

This is a low emission CLASS A Uninterruptible Power System (UPS) product. In a residential environment, this product may nevertheless cause radio interference, in which case, the user may be required to take additional measures.

Conformity and Standards

This equipment complies with CE directives 73/23 & 93/68 (LV Safety) and 89/336 (EMC), with Australia and New Zealand EMC Framework (C-Tick) and with the following product standards for Uninterruptible Power System (UPS).

EN / IEC / AS 62040-1-1—General and safety requirements for use in operator access area

EN / IEC / AS 62040-2—EMC requirements; Class A compliant

EN / IEC / AS 62040-3—Performance requirements and test methods

For more details, see 10.0 - Technical Specifications

Continued compliance requires installation in accordance with these instructions and the use of manufacturer approved accessories only.

! WARNING

High Leakage Current

EARTH CONNECTION IS ESSENTIAL BEFORE CONNECTING THE INPUT SUPPLY.

Earth leakage current exceeds 3.5 mA and is less than 1000 mA for 30-80kVA, less than 2000mA for 100-120kVA. models and less than 2500mA for 140-200kVA models.

Transient and steady-state earth leakage currents, which may occur when starting the equipment, should be taken into account when selecting instantaneous RCCB or RCD devices.

Residual Current Circuit Breakers (RCCBs) must be selected sensitive to DC unidirectional pulses (class A) and insensitive to transient current pulses.

Note also that the earth leakage currents of the load will be carried by this RCCB or RCD. This equipment must be earthed in accordance with the local electrical code of practice.

! WARNING

Back-Feed Protection Notice

This UPS is fitted with a voltage-free contact closure signal for use with an external automatic disconnect device (supplied by others) to protect against back-feeding voltage into the bypass input. If this signal is not used by the installer, a label must be added at the external bypass input disconnect device to warn service personnel that the circuit is connected to a UPS.

The text to use is the following or equivalent:

ISOLATE THE UNINTERRUPTIBLE POWER SYSTEM BEFORE WORKING ON THIS CIRCUIT.

1

User-Serviceable Parts

All equipment maintenance and servicing procedures involving internal access requires the use of a tool and should be carried out only by trained personnel. There are no user-serviceable parts behind covers requiring a tool for removal.

This UPS is fully compliant with safety regulations for equipment located in an operator accessible area. Hazardous voltage is present within the UPS and battery enclosure but out of reach of non-ser- vice personnel. Contact with hazardous voltage is minimized by housing live parts behind safety panels that require a tool for their removal. No risk exists to any personnel when operating the equipment in the normal manner, following the recommended operating procedures.

Battery Voltage Exceeds 400VDC

All physical battery maintenance and servicing requires the use of a tool or a key and should be carried out only by trained personnel.

! WARNING

Special care should be taken when working with the batteries associated with this equipment.

When connected together, the battery terminal voltage will exceed 400VDC and is potentially lethal.

Battery manufacturers supply details of the necessary precautions to be observed when working on, or in the vicinity of, a large bank of battery cells. These precautions should be followed implicitly at all times.

Attention should be paid to the recommendations concerning local environmental conditions and the provision of protective clothing, first aid and fire-fighting facilities.

2

Single Module UPS Installation

1.0SINGLE MODULE UPS INSTALLATION

1.1Introduction

This following section describes the requirements that must be taken into account when planning the positioning and cabling of the Liebert NX uninterruptible power supply and related equipment.

This chapter is a guide to general procedures and practices that should be observed by the installing engineer. The particular conditions of each site will determine the applicability of such procedures.

! WARNING

Professional Installation Required

Do not apply electrical power to the UPS equipment before being authorised to do so by the commissioning engineer.

The UPS equipment shall be installed by a qualified electrical tradesperson in accordance with the information contained in this manual. All equipment not referred to this manual is shipped with details of its own mechanical and electrical installation.

NOTE

Three-phase, 4-wire input supply required.

The standard Liebert NX UPS is suitable for connection to 3-phase, 4-wire (+ Earth) TN, TT and IT AC power distribution systems (IEC60364-3). Optional 3-wire to 4-wire conversion transformers are available. If it is used in IT AC power distribution systems, a 4-pole circuit breaker must be used on the input and refer to the relative IT Systems’ standard

! WARNING

Battery Hazards

Special care should be taken when working with the batteries associated with this equipment. When connected together, the battery terminal voltage will exceed 400VDC and is hazardous.

Eye protection should be worn to prevent injury from accidental electrical arcs. Remove rings, watches and all other metal objects.

Use only tools with insulated handles. Wear rubber gloves.

If a battery leaks electrolyte or is otherwise physically damaged, it must be replaced, stored in a container resistant to sulfuric acid and disposed of in accordance with local regulations.

If electrolyte comes into contact with the skin, the affected area should be washed immediately with water.

1.2Preliminary Checks

Before installing the UPS, please carry out the following preliminary checks:

1.Visually examine the UPS and battery equipment for transit damage, both internally and externally. Report any damage to the shipper immediately.

2.Verify that the correct equipment is being installed. The equipment supplied has an identification tag on the back of the main door reporting: the type, size and main calibration parameters of the UPS.

3

Single Module UPS Installation

1.3Location

1.3.1UPS Room

The UPS and its internal battery is intended for indoor installation and should be located in an environment with clean air and with adequate ventilation to keep the ambient temperature within the specified operating range (see Table 33).

All models in the Liebert NX UPS range are air-cooled with the aid of internal fans. Cold air enters through ventilation grilles at the front of the cabinet for NXa 30-120kVA and through ventilation grilles located at the front and bottom of the cabinet for NXa 140-200kVA. Hot air is released through grilles at the top. Do not cover the ventilation openings.

If necessary to avoid room temperature build-up, install a system of room extractor fans. Optional air filters are available if the UPS is to operate in a dusty environment.

The UPS heat dissipation detailed in Table 34 can be used as a guide for air conditioning sizing, depending on the selected mode of operation:

Normal Mode (VFI SS 111 Double Conversion UPS)

ECO Mode (VFD SS 311 Stand By UPS)

If in doubt use Normal Mode figures.

NOTE

The UPS is suitable for mounting on concrete or other non-combustible surface only.

1.3.2External Battery Room

Batteries should be mounted in an environment where the temperature is consistent and even over the whole battery. Temperature is a major factor in determining the battery life and capacity. Typical battery manufacturer performance data are quoted for an operating temperature between 20 and 25°C (68 and 77°F). Operating above this range will reduce the battery life while operation below this range will reduce the battery capacity. In a normal installation the battery temperature is maintained between 15°C and 25°C (59 and 77°F). Keep batteries away from main heat sources or main air inlets etc.

Where the batteries are located externally to the main UPS cabinet, a battery protection device

(e.g., fuses or circuit breakers) must be mounted as close as possible to the batteries themselves, and connected using the most direct route possible.

1.3.3Storage

Should the equipment not be installed immediately, it must be stored in a room for protection against excessive humidity and or heat sources (see Table 33).

! CAUTION

An unused battery must be recharged periodically per battery manufacturer recommendation. Temporarily connecting the UPS to a suitable AC supply mains and activating it for the time required for recharging the batteries can achieve this.

4

Single Module UPS Installation

1.4Positioning

The cabinet is mounted on four casters for ease of positioning and for moving short distances. Jacking feet are provided to prevent the UPS from moving once it has been wheeled to its final position.

For optimal design life, the place chosen must offer:

Easy connection

Enough space to easily work on the UPS

Sufficient air exchange of enough to dispel heat produced by UPS

Protection against atmospheric agents

Protection against excessive humidity and very high heat sources

Protection against dust

Compliance with the current fire prevention requirements

Operating environment temperature between 20°C and 25°C (68 and 77°F). The batteries are at maximum efficiency in this temperature range (see Table 33).

The UPS cabinet is constructed around a steel chassis with removable panels. The top and side panels are secured to the chassis by screws.

Access to the power terminals, auxiliary terminals blocks and power switches is from the front. Operational status and alarm information is provided through the front door operator control panel. Models 40kVA and below house both the power components and an internal battery. Cooling air enters in the front of the NXa 30-120kVA and the front and bottom of NXa 140-200kVA; it is exhausted out the top of each.

1.4.1System Cabinets

A UPS may comprise a number of cabinets, depending on design requirements (e.g., UPS cabinet, external battery cabinet, external bypass cabinet). In general, all the Liebert cabinets used in a particular installation are of the same height and designed to be positioned side-by-side to form a matching array. Refer to 5.0 - Installation Drawings for assistance on positioning the cabinets described below.

1.4.230 to 40kVA UPS

The UPS consist of a single cabinet, which uses typically forty (40) 12V battery blocks, fitted internally and connected in series to provide a nominal battery voltage. The UPS may be shipped without the batteries fitted.

An extended battery option is available. This comprises a separate cabinet containing additional batteries that can be connected to the UPS to increase its battery run time. Battery cabinets and batteries are usually shipped separately.

1.4.360-200kVA UPS

The 60 to 200kVA consist of a single cabinet without any internal battery. Usually, with 60 to 200kVA UPS installations, the batteries are contained in a purpose-built battery cabinet, which sits alongside the main UPS equipment. Batteries are accessible in the external cabinet from the front, making it unnecessary to allow for side access.

1.4.4Moving the Cabinets

! WARNING

Ensure that any equipment used to move the UPS cabinet has sufficient lifting capacity.

The UPS is fitted with casters. Take care to prevent the NX from moving when unbolting the unit from its shipping pallet. Ensure that adequate personnel and lifting aids are available when removing the shipping pallet.

Ensure that the UPS weight is within the designated surface weight loading of any handling equipment. See Table 35.

UPS and optional cabinets (battery cabinets, top cable entry cabinets, etc.) can be handled by means of a forklift or similar equipment.

The UPS cabinet also can be moved short distances by its casters.

NOTE

Care must be taken when maneuvering units fitted with batteries. Keep such moves to a minimum.

5

Single Module UPS Installation

1.4.5Clearances

The Liebert NX has no ventilation grilles at either side of the UPS. To enable routine tightening of power terminations within the UPS, in addition to meeting any local regulations, Liebert recommends providing adequate clearance in the front of the equipment for unimpeded passage of personnel with the doors fully opened. It is important to leave 800mm (31.5") clearance above the UPS to permit adequate circulation of air coming out of the unit.

1.4.6Access

The component layout of the UPS supports front and top access while servicing, diagnosing and repairing the UPS, thus reducing the space requirement for side and rear access.

1.4.7Final Positioning

The UPS cabinets are fitted with casters on the base to allow ease of movement and positioning.

! WARNING

Casters are strong enough for movement across even surfaces only. Caster failure could occur if they are subjected to shock loading.

When the equipment has been finally positioned, ensure the adjustable feet are set so that the UPS will remain stationary and stable.

1.4.8Floor Anchoring

Diagrams in 5.0 - Installation Drawings show the location of the holes in the base plate through which the equipment may be bolted to the floor. If the equipment is to be installed on a raised floor it should be mounted on a pedestal suitably designed to accept the equipment point loading.

1.4.9Cable Entry

Cables can enter the Liebert NX UPS and battery cabinet from below. Cable entry is made possible by removing a blanking piece fitted at the bottom of equipment to reveal the cable entry hole.

Top Cable Entry—Optional

Optionally a top cable entry extension may be used. The cabinet extends the overall width of the UPS and permits connection of all incoming AC/DC power cables from above.

The top cable entry option is fitted on the side of the UPS cabinet and is supplied without side panels; the side cover from the UPS being used.

The cabinet with cables coming in from the top for the 30-40 kVA UPS must be positioned on the left side; the cabinet for the 60 to 200 kVA UPS can be positioned on either side.

This facilitates cable entry through the top metal panel after the appropriate cable entry holes have been cut.

NOTE

The top cable entry also includes the power connection cables between the cabinet and the UPS.

1.5External Protective Devices

Circuit breakers or other protective devices must be installed in the AC supply, external to the UPS. This chapter provides guidelines for qualified installers who must have knowledge of local wiring practices pertaining to the equipment to be installed.

6

Single Module UPS Installation

1.5.1Rectifier and Bypass Input

Overcurrent protection must be installed at the distribution panel of the incoming main supply. The protection must discriminate with the power cables current capacity and with the overload capacity of the system (see Table 38). As a guideline, a thermomagnetic circuit breaker, with an IEC 60947-2 trip curve C (normal) for 125% of the current listed in Table 1 is suitable.

Split-Bypass—If a split-bypass is used, install separate protective devices for the rectifier and for the bypass in the incoming mains distribution panel.

NOTE

Rectifier and bypass input sources must be referenced to the same neutral potential.

NOTE

For IT power systems, four-pole protective devices must be used, external to the UPS, both upstream of the input distribution panel and downstream (toward the load).

Earth Leakage (RCD)

Any residual current detector (RCD) installed upstream of the UPS input supply must be:

sensitive to DC unidirectional pulses (Class A)

insensitive to transient current pulses, and

must have an average sensitivity, adjustable between 0.3 and 1A.

Figure 1 Residual current circuit breakers (RCCB) symbols

To avoid false alarms, earth leakage monitoring devices when used in systems with split-bypass input or when used in paralleled UPS configurations, must be located upstream of the common neutral sinking point. Alternatively, the device must monitor the combined four-wire rectifier and splitbypass input currents.

The residual earth current introduced by the RFI suppression filter inside the UPS is greater than 3.5mA, 1000mA for 30-80kVA, 2000mA for 100-120kVA models and less than 2500mA for 140-200kVA models. Liebert recommends verifying the selectivity with all other differential devices both upstream of the input distribution board and downstream (toward the load).

1.5.2External Battery

The UPS and its associated batteries are protected against overcurrents through a DC compatible disconnect device.

1.5.3UPS Output

Any external distribution board used for load distribution shall be fitted with protective devices that discriminate with those used at the bypass input to the UPS and with the UPS overload characteristics (see Table 38).

7

Single Module UPS Installation

1.6Power Cables

The cable design must comply with the voltages and currents provided in this section, follow local wiring practices and take into consideration the environmental conditions (temperature and physical support media).

For cable entry terminal, refer to Figures 43, 48, 52 and 56.

! WARNING

Before starting the UPS, ensure that you are aware of the location and operation of the external isolators that connect the ups input/bypass supply to the mains distribution panel.

Check that these supplies are electrically isolated and post any necessary warning signs to prevent their inadvertent operation.

Table 1

Maximum steady state AC and DC currents

 

 

 

 

 

 

 

NOMINAL CURRENT: Amps

 

 

BUSBAR STUD SIZE

 

 

 

 

 

 

 

 

 

 

 

 

Input Mains

Bypass/Output

Battery at

Input/Output/

 

 

 

with full battery

 

 

 

minimum

 

 

 

 

recharge

 

at full load

Bypass

Battery

Torque

UPS

 

 

battery

 

3ph + N

 

 

3ph + N

 

Cables

RATING

 

 

 

 

voltage

Cables

Load, Nm

 

 

 

 

 

 

 

 

 

 

 

(kVA)

380V

 

400V

 

415V

380V

400V

 

415V

(400VDC)

Bolt

Ø holes

(Bolts)

(lb/ft)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

50

 

47

 

45

46

43

 

42

64

M6

7

-

5 (1.12)

40

65

 

62

 

60

61

58

 

56

85

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

97

 

92

 

88

91

86

 

83

128

M8

9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80

128

 

122

 

117

121

115

 

111

170

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100

160

 

152

 

146

152

145

 

139

213

 

 

 

M8: 13 (2.9)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

120

191

 

181

 

175

182

174

 

167

255

 

 

M10 Ø11

 

 

 

 

 

M10: 26 (5.8)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

140

222

 

211

 

204

212

201

 

194

298

M10

11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

160

254

 

241

 

232

242

230

 

222

340

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200

317

 

301

 

290

303

288

 

277

426

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For terminal location – refer to 5.0 - Installation Drawings

 

 

 

 

 

Table 2

Distance from floor to connection point on the equipment

 

 

 

 

 

Minimum Distance, mm (in)

 

 

UPS

 

 

 

 

UPS 30/40 kVA

UPS 60-80 kVA

UPS 100-120 kVA

UPS 140-200 kVA

 

 

 

 

 

 

Rectifier AC Input supply

350 (13.8)

 

305 (12)

324 (12.8)

 

 

 

 

 

Bypass AC Input supply

300 (11.8)

 

250 (9.8)

310 (12.2)

 

 

 

 

 

UPS Output AC

260 (10.2)

 

250 (9.8)

310 (12.2)

 

 

 

 

 

Battery Power

1030 (40.5)

 

230 (9)

360 (14.2)

 

 

 

 

 

 

Auxiliary cables:

1320(52)

 

1500 (59)

Monitor board (U2)

 

 

 

 

 

Communications

1070(42.1)

 

1250(49.2)

 

 

 

 

 

 

 

Earth

 

350 (13.8)

 

275 (10.8)

338 (13.3)

 

 

 

 

 

 

 

! WARNING

Failure to follow adequate earthing procedures may result in electromagnetic interference or in hazards involving electric shock and fire.

8

Single Module UPS Installation

1.6.1Cable Termination

NOTE

The operations described in this section must be performed by authorised electricians or qualified technical personnel. If you have any difficulties, do not hesitate to contact our Customer Service and Support Department. See the back page of this manual for contact information.

Once the equipment has been finally positioned and secured, connect the power cables as described in the following procedure.

Refer to the appropriate cable connection drawing in 5.0 - Installation Drawings.

1.Verify that the UPS equipment is isolated from its external power source and all the UPS power isolators are open. Check that these supplies are electrically isolated and post any necessary warning signs to prevent their inadvertent operation.

2.Open the door to the UPS cabinet and remove one of the two protective cover to gain access to the desired connection bars.

the lower protective cover houses the 60-200kVA connection bars

the left protective cover houses the 30-40kVA connection bars

The protective cover on the UPS cabinet of 60 to 200kVA models must be removed after the handles on the power isolators have been removed.

3.Connect the safety earth and any necessary bonding earth cables to the copper earth busbar located on the floor of the equipment below the power connections. All cabinets in the UPS must be connected to the user’s ground connection.

NOTE

The earthing and neutral bonding arrangement must be in accordance with local and national codes of practice.

Identify and make power connections for incoming cables according to one of the two procedures below, depending on the type of installation.

Common Input Connections

4.For common bypass and rectifier inputs, connect the AC input supply cables between the mains distribution panel and the UPS input (U1-V1-W1-N terminals) and tighten the connections to 5Nm for M6 bolts, to 13Nm for M8 bolts or to 26Nm for M10 bolts. Ensure correct phase rotation.

Split-Bypass Connections

5.If a split-bypass configuration is used, connect the AC input supply cables to the rectifier input busbars (U1-V1-W1-N terminals) and the AC bypass supply cables to the bypass input (U3-V3-W3-N terminals) and tighten the connections to 5Nm for M6 bolts, to 13Nm for M8 bolts or to 26Nm (M10 bolt). Ensure correct phase rotation.

NOTE

For split-bypass operation, ensure that the linking busbars between bypass and rectifier input are removed.

The AC input and the AC bypass supplies must be referenced to the same neutral point.

Frequency Converter Mode

If a frequency converter configuration is used, connect the AC input supply cables to the rectifier input busbars (U1-V1-W1-N terminals). Torque to 5Nm for M6 bolts, to 13Nm for M8 bolts or to 26Nm (M10 bolt). Ensure correct phase rotation. There will not be any AC bypass supply cables to the bypass input (U3-V3-W3-N terminals) and tighten the connections.

NOTE

For frequency converter operation, ensure that the linking busbars between bypass and rectifier input are removed.

9

Single Module UPS Installation

Output System Connections

6.Connect the system output cables between the UPS output (U2-V2-W2-N terminals) and the critical load and tighten the connections to 5Nm for M6 bolts, to 13Nm for M8 bolts or to 26Nm for M10 bolts. Ensure correct phase rotation.

External UPS Battery Connection (60kVA Models and Above, Option for 30-40kVA Models)

Connect the battery cables between the UPS terminals (+\-) and its associated battery circuit breaker. Observe the battery cable polarity.

NOTE

When connecting the cables between the battery extremities to the circuit breaker always

connect the circuit breaker end of the cable first.

! WARNING

If the load equipment will not be ready to accept power on the arrival of the commissioning engineer, ensure that the system output cables are safely isolated at their ends.

Internal UPS Battery Connection (30/40kVA only)

7.The battery consists of a series string connection of 5 x 8 (or 10) x 12V 6-cell battery blocks.

a.Ensure that the eight (or 10) battery blocks in each tier (tray) are interconnected.

b.Connect the positive and negative cables to the UPS terminals.

c.Plug in the cables between the tiers.

d.Ensure correct polarity battery string series connections (i.e., intertier and interblock connections are from positive to negative terminals.

! WARNING

Hazardous Battery Terminal Voltage 480VDC

Ensure correct polarity of string end connections to the UPS terminals, i.e., positive to positive and negative to negative, but leave these UPS terminal cables disconnected until connection is authorised by the commissioning engineer.

Ensure correct polarity of string end connections to the battery circuit breaker and from the battery circuit breaker to the UPS terminals, i.e., positive to positive and negative to negative, but disconnect one or more battery cell links in each tier.

Do not reconnect these links and do not close the battery circuit breaker before authorised by the commissioning engineer.

8. Refit all protective covers removed for cable installation.

10

Single Module UPS Installation

1.7Control Cables and Communication

1.7.1Monitor Board Features

Based on your site’s specific needs, the UPS may require auxiliary connections to manage the battery system (external battery circuit breaker, battery temperature sensor), communicate with a personal computer or provide alarm signaling to external devices or for Remote Emergency Power Off (REPO). The monitor board, arranged for this purpose, is located on the rear of the operator access door. The main features are:

Input and Output dry contacts signal (one pair of contacts of relay)

Emergency Power Off control (EPO)

Environmental parameter input interface

User communication (for data setting and user background monitor)

Intellislot™ interface

Modem interface

Temperature detect interface

Figure 2 Monitoring board (U2) auxiliary terminal block detail

 

 

J8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J3

J1

 

 

LCD

 

 

 

 

 

 

 

 

 

J22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J23

 

 

 

 

 

 

 

 

 

 

J12

 

 

 

 

 

 

 

 

 

 

J9

J2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J15

 

 

 

 

 

 

 

 

 

 

J16

 

 

 

 

 

 

 

 

 

 

J17

 

 

 

 

 

 

 

 

Intellislot

2

X4

 

 

 

 

 

 

 

 

 

 

J13

J21

J25

J28

J4

J26

J30

J10

Intellislot

1

J24

 

 

 

 

 

 

 

 

 

 

Intellislot

3

 

BFP

INV

ACF

EPO

Dry In

MBC

 

BCB

The black square ( )

 

 

 

 

 

 

 

 

 

X1

 

X2

 

X3

 

 

on each slot indicates Pin 1.

X7

X6

PWR

Modem X5

SNMP Card

X4

11

Single Module UPS Installation

1.8Dry Contacts

The UPS provides input dry contacts and output dry contacts.

1.8.1Input Dry Contacts

There are several input dry contacts at the X3 slot.

X3 Ancillary Control and Alarms

X3 IN DRY: Environmental, Battery Ground Fault and Generator Contacts

The UPS accepts external signalling from voltage-free (dry) contacts connected to finger-proof, pushin terminal X3 IN DRY. Subject to prior software programming, the signalling is accepted by the UPS when connection between the relevant terminal and the +12V terminal is altered. Cables connected to

X3 IN DRY must be segregated from power circuits (for screening purposes), double insulated and of a typical 0.5 to 1mm2 cross-section area for maximum runs between 25 and 50 meters (82-164 ft), respectively.

Figure 3 Input dry contacts

12V 12V

12V

12V

X3

 

J4

 

 

 

J26

 

 

J30

 

 

 

 

J10

 

 

12V

GEN

BtG

ENV

GND

12V

AUX I

T IT

AUX O

T OT

F FAN

FUSE

OL

GND

FB

DRV

 

Table 3

Input dry contacts at X3

 

 

 

 

 

 

 

 

 

 

Position

 

Name

Description

 

 

 

 

 

 

 

 

 

 

 

J4.1

 

ENV3

Battery Room Alarm (NC)

 

 

 

 

 

 

 

 

 

J4.2

 

BtG

Battery Ground Fault Detection (NC)

 

 

 

 

 

 

 

 

J4.3

 

GEN1,2

On Generator (NO)

 

 

 

 

 

 

 

 

 

 

J4.4

 

+12V

+12V Power

 

 

 

 

 

 

 

 

 

 

1 - Must be configured by configuration software before becoming active.

2 - When activated, the charger current can be limited, via software, to a percentage of the full charger current (0-100%). 3 - Activating this feature turns the battery charger off.

NOTE

All auxiliary cables of terminal must be double-insulated. Wire should be 0.5-1.5mm2 (16-20AWG) stranded for maximum runs between 25 and 50m (82-164 ft.) respectively.

12

Single Module UPS Installation

1.8.2Maintenance Bypass Cabinet Interface

J26 and J30 are the MBC interface.

Table 4 Maintenance bypass cabinet interface

Position

Name

Description

J26.1

T_IT1

Input transformer overtemperature (NC)

J26.2

AUX_I

Reserved

 

 

 

J26.3

+12V

+12V Power

 

 

 

J26.4

GND

Power Ground

 

 

 

J30.1

FUSE

Reserved

 

 

 

J30.2

F_FAN

Fan Fail Alarm (NC)

 

 

 

J30.3

T_OT1

Output Transformer Overtemperature (NC)

J30.4

AUX_O

Reserved

 

 

 

1 - Must be configured by software before becoming active

NOTE

All auxiliary cables of terminal must be double-insulated. Wire should be 0.5-1.5mm2 (16-20AWG) stranded for maximum runs between 25 and 50m (82-164 ft.) respectively.

1.8.3External Circuit-Breaker Interface

J10 is the interface to any external battery circuit breaker (BCB).

Table 5 External circuit-breaker interface

Position

Name

Description

J10.1

DRV

BCB Driver Signal - Output (N.O.)

 

 

 

J10.2

FB

BCB Contact State - Input (N.O.)

 

 

 

J10.3

GND

Power Ground

 

 

 

J10.4

OL

BCB On-Line - Input - This pin will become active when

BCB interface is connected. (N.O.)

 

 

NOTE

All auxiliary cables of terminal must be double insulated. Wire should be 0.5-1.5mm2 (16-20AWG) stranded for maximum runs between 25 and 50 meters (82-164ft.) respectively.

13

Single Module UPS Installation

1.8.4Output Dry Contacts

There are three output dry contact relays at the X1 slot (see Figure 4 and Table 6)

NOTE

All auxiliary cables of terminal must be double-insulated. Wire should be 0.5-1.5mm2 (16-20AWG) stranded for maximum runs between 25 and 50m (82-164 ft.) respectively.

Figure 4 Output dry contacts and EPO wiring for firmware before M162

X1

J13

 

 

J21

 

 

J25

 

 

 

 

 

 

 

BFP C

BFP S

BFP O

INV C

INV S

INV O

ACF C

ACF S

ACF O

Table 6 Output dry contact relays for firmware before M162

+12V

 

J25

X2

 

EPO-H

EPO-L

Position

Name

Description

J13.2

BFP_O

Bypass feedback protection relay; normally open. Closed when bypass SCR is shorted.

J13.3

BFP_S

Bypass feedback protection relay center

J13.4

BFP_C

Bypass feedback protection relay; normally closed. Open when bypass SCR is shorted.

J21.2

INV_O

Inverter mode relay; normally open. Closed when UPS is in inverter mode.

J21.3

INV_S

Inverter mode relay center

J21.4

INV_C

Inverter mode relay; normally closed. Open when UPS is in inverter mode.

J25.2

ACF_O

Main input fault relay; normally open. Closed when main input is in fault.

J25.3

ACF_S

Main input fault relay center

J25.4

ACF_C

Main input fault relay; normally closed. Open when main input is in fault.

Figure 5 EPO wiring for firmware M200 or later

X2

J28

EPO-NO EPO-NC

1.8.5Emergency Power Off Input

The UPS has an Emergency Power Off (EPO) function that operates by a button on the control panel or by a remote contact provided by the user. The EPO button is under a hinged, clear plastic shield.

The X2 slot, shown in Figure 4, is the remote EPO input interface. The EPO has an NO/NC contact point that becomes active when shorting terminals X2: 3 and 4 or open terminal connection X2: 2 and 1

If an external emergency stop facility is required, it is connected terminals X2: 1&2 or X2: 3&4 of the auxiliary terminal block (X2). It also is connected to the normally open or normally closed remote stop

14

Single Module UPS Installation

switch between these two terminals using shielded cable (see Figure 4 and Table 7). If this function is not used, terminals X2: 3&4 must be opened and X2: 1&2 must be closed.

Table 7

EPO input contact relays

 

 

 

Position

Name

Description

J28.1

 

EPO_NC

EPO Activated when opened to J28.2

 

 

 

 

J28.2

 

EPO_NC

EPO Activated when opened to J28.1

 

 

 

 

J28.3

 

EPO_NO

EPO Activated when shorted to J28.4

 

 

 

 

J28.4

 

EPO_NO

EPO Activated when shorted to J28.3

 

 

 

 

NOTE

The emergency stop action within the UPS shuts down the rectifier, inverter and static bypass. It does not internally disconnect the input power supply. To disconnect ALL power to the UPS, open the upstream feeder breaker(s) when the remote EPO is activated.

NOTE

Normally closed EPO – X2: 1,2, these terminals are supplied factory-linked on the monitor board and must remain installed if using NC contacts.

NOTE

All auxiliary cables of terminal must be double insulated. Wire should be 0.5-1.5mm2 (16-20AWG) stranded for maximum runs between 25 and 50 meters (82-164ft.) respectively.

X5: Auxiliary DC Power Output

Auxiliary DC power for modem or external SNMP card. The voltage is between 9V to 12V. The maximum current is 500mA.

X6: Analog Input Interface

Two analog signal channels with an input range is from 0 to +12V. The precision of detection is ÷3%.

X6 pin 1: Not used

X6 pin 2: +12V

X6 pin 3: ENV-T – environment temperature detection

X6 pin 4: GND

X7: External Battery Temperature Detector Interface

Interface for TMP12Z temperature detector, normally connected to an external battery cabinet (see

Figure 26). Pin reference:

X7 pin 1: Not used

X7 pin 2: +12V (Power supply for Temperature Monitoring Probe)

X7 pin 3: BAT-T (Battery Temperature signal)

X7 pin 4: GND

15

Single Module UPS Installation

Serial Ports RS232-1 and RS232-2

RS232-1 provides serial data and is intended for direct use with Liebert MultiLink monitoring and server shutdown software.

RS232-2 provides serial data and is intended for use by authorized commissioning and service personnel.

These serial ports are shared with the optional Web browser, SNMP, ModBus and relay cards. Refer to Table 31 regarding compatibility of simultaneous use.

Intellislot Web Browser, SNMP, ModBus and Relay Cards Interface

There are three interface slots available for optional Web browser, SNMP, ModBus and Relay cards as illustrated in 9.0 - Options—For Assembly Inside the UPS Cabinet.

1.8.6External Bypass Switch Interlock

EXT-Maint X3-1&2 on UPS Parallel Board M3 (leave open if no external bypass switch is used)

Provides external maintenance bypass interlock protection for the UPS. Short circuit means external bypass closed.

EXT-Out (X3-3&4) on UPS Parallel Board (leave shorted if no external output switch is used). Provides external output interlock protection for paralleled UPS modules. Short circuit means external output switch closed.

NOTE

UPS Parallel Board M3 is located behind protective covers accessible after opening the UPS front door—removal of this barrier requires the use of a tool and is restricted to service personnel.

NOTE

Jumper JP1 (located next to X3) needs to be removed for X3:3&4 to work properly.

16

Battery Installation

2.0BATTERY INSTALLATION

2.1Introduction

The UPS battery bank consists of battery blocks connected in series to provide a D.C. string voltage as required by the UPS converter. The 'AUTONOMY TIME' (the time during which the battery can maintain supply to the load in the event of a mains failure) is limited by the ampere-hour capacity of the battery blocks and in some cases this results in several strings being connected in parallel.

The NX 30-40kVA has internal batteries, but longer run time is available by using an external battery cabinet.

The battery cabinet will be supplied in one of the following forms:

1.Complete installation, comprising the battery cabinet, batteries and protective device.

2.Battery cabinets and protective device only—batteries supplied by others

3.Battery cabinet only—batteries and circuit breaker supplied by others.

NOTE

30kVA to 40kVA UPS models contain an internal battery compartment that can accommodate up to 42 blocks 24 Ah/12V batteries.

The battery bank may be disconnected from the UPS for maintenance or service. The circuit breaker can be switched ON or OFF manually and further battery isolation control is achieved through the use of either a battery circuit-breaker undervoltage coil or through an automatic contactor inside the UPS.

17

Battery Installation

2.2Safety

Special care should be taken when working with the batteries associated with the Liebert NX UPS system. When all the cells are connected together, the battery terminal voltage is potentially hazardous. The battery installation must be segregated from all but appropriately qualified maintenance personnel by locating the cells in a key-lockable cabinet or in a purpose-designed, dedicated battery room.

NOTE

Full safety instructions concerning the use and maintenance of UPS batteries are provided in

the appropriate battery manufacturers manuals. The battery safety information contained in this section relates to key considerations that must be taken into account during the installation design process and might affect the design outcome depending on localised conditions.

! WARNING

Hazardous battery voltage present behind covers

No user-serviceable parts are located behind covers that require a tool for their removal. Only qualified service personnel are authorised to remove such covers.

When using internal batteries in 30 and 40kVA units, the batteries are always connected through power fuses to the UPS and to the segregated terminal bars available for connection to an external battery.

Isolate any internal battery connections before attempting to access the segregated terminal bars available for connection to an external battery.

The following general battery safety precautions and warnings should be observed at all times:

A battery can present risk of electric shock or burn from high- short-circuit currents.

The full nominal string voltage, when the battery blocks are interconnected, is 480VDC, which is hazardous

Only qualified personnel should install or service batteries.

Eye protection should be worn to prevent injury from electrical arcs.

Remove rings, watches, necklaces, bracelets and all other metal objects.

Use only tools with insulated handles.

Wear rubber gloves and a rubber apron when handling batteries.

If a battery leaks electrolyte or is otherwise damaged, it should be placed in a container resistant to sulfuric acid and disposed of in accordance with local regulations.

If electrolyte comes into contact with the skin the affected area should be washed immediately with plenty of clean water.

Batteries must always be disposed of according to local environmental laws.

When replacing batteries, use the same number and type that were originally fitted.

Disconnect charging source before connecting or disconnecting battery terminals.

Determine whether the battery is inadvertently grounded. If it is inadvertently grounded, remove the source of the ground. Contact with any part of a grounded battery can result in electrical shock.

2.3Battery Cabinet

2.3.1Introduction

This cabinet can also be used in conjunction additional cabinets, to provide the necessary accommodation required by the larger cells associated with system’s having a long autonomy time.

Where two (or more) cabinets are used they are positioned alongside each other and secured and bonded together. If the cabinet(s) is located immediately adjacent to the main UPS equipment the two units are bolted together.

18

Loading...
+ 102 hidden pages