Emerson FTA1100-H Brochures and Data Sheets

0 (0)
Emerson FTA1100-H Brochures and Data Sheets

DieselEngine Fire PumpControllerforClass1,Division2 Hazardous Locations

Class 1, Division 2 hazardous locations, T3 temperature rating.

Firetrol® FTA1100H combined automatic and manual Mark II based diesel engine fire pump controllers are intended for starting and monitoring fire pump diesel engines in Class1, Division 2 hazardous locations. The controllers have a temperature rating of T3. They are available for use with 12 or 24 volt negative ground systems using lead acid or Nickel-Cadmium batteries, and available with 10 or 20 amp charging circuits. The controller monitors, displays and records fire pump system information.

Metering

The controller provides display of incoming AC power line voltages.

Total engine run time may be displayed.

Pressure is displayed in PSI or Bars in 1 psi increments (0.1 bar). The controller is supplied as standard with a 0-300 psi (0-20.7 bars) stainless steel pressure transducer for fresh water applications and optionally with a 0-600 psi (0-41.4 bars) pressure transducer. Controllers can be ordered for copper corrosive applications.

Battery voltages and charging currents are displayed on the main screen

Engine Control

The controller provides the following programmable engine control functions:

Sequential Start Time (On Delay) - 0-60 Seconds

Minimum Run Time - 0-60 Minutes

Off Delay Time - 0-60 Minutes

Weekly Test Time/Duration/Frequency

AC Power Loss Start Delay Time - 5-300 Seconds

Manual Stop Only - Yes/No

time and date stamp. The display is a 128x64 Backlit LCD capable of customized graphics. The display and interface are NEMA rated for Type 2, 3R, 4, 4X, and 12 protection and is fully accessible without opening the controller door. The user interface utilizes multiple levels of password protection for system security. A minimum of 3 password levels are provided.

Enclosures

The standard enclosures are NEMA Type 4X (IEC IP66), 12 Gauge, Seam Welded, #316 Stainless Steel, Polished and Brushed finish. The controller should be installed in an area with protection from direct sunlight and with an ambient temperature above 41º F (5º C). Optional enclosure types include:

– NEMA Type 4X (IEC IP66), 12 Gauge, Seam Welded, #316 Stainless Steel, Painted Finish

NEMA enclosures listed meet or exceed referenced IEC designations.

Operator Interface

The fire pump controllers feature an operator interface with user keypad. The interface monitors and displays motor operating conditions, including all alarms, events, and pressure conditions. All alarms, events, and pressure conditions are displayed with a

Approvals

Firetrol fire pump controllers are listed by Underwriters’ Laboratories, Inc., in accordance with UL1604, Electrical Equipment for Use in Class 1 and II, Division 2, and Class III Hazardous (Classified) Locations and UL698, Industrial Control Equipment for Use