AC Power
For Business-Critical Continuity™
Liebert® GXT3™ 208V, 5000-10,000VA, 6000RTL630
User Manual
TABLE OF CONTENTS
1.0 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2.0 SYSTEM DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2.1 Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters. . . . . . . . . . . . . . . . . . . . 5
2.2 Rectifier/Power Factor Correction (PFC) Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.3 Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.4 Battery Charger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.5 DC-to-DC Converter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.6 Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.7 Dynamic Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.0 MAJOR COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
3.1 Main Frame and Electronics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.2 Removable Power Distribution Box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.3 Internal Battery Packs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.0 WHAT’S INCLUDED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.0 INSTALLATION AND CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
5.1 Install the Main Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
|
5.1.1 |
Tower UPS Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
12 |
|
5.1.2 |
Rack-Mount UPS Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
13 |
|
5.1.3 Installing the Adjustable Rack-Mount Kit—Sold Separately . . . . . . . . . . . . . . . . . . . . . . . . . |
13 |
|
5.2 |
External Battery Cabinet Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
16 |
|
5.3 |
Connect Input/Output Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
17 |
|
|
5.3.1 Remove the Power Distribution Box from 5000 and 6000VA Models . . . . . . . . . . . . . . . . . . . |
17 |
|
|
5.3.2 Remove the Power Distribution Cover from 8000 and 10,000VA Models . . . . . . . . . . . . . . . . |
18 |
|
|
5.3.3 Install the Power Distribution Box on 5000 and 6000VA Models . . . . . . . . . . . . . . . . . . . . . . |
18 |
|
|
5.3.4 Install the Power Distribution Box on 8000 and 10,000VA Models . . . . . . . . . . . . . . . . . . . . |
19 |
|
|
5.3.5 Distribution Box Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
19 |
|
5.4 |
IT Power System Configuration—Liebert® GXT3-6000RTL630™ Only . . . . . . . . . . . . . . . . |
21 |
|
6.0 |
CONFIGURATION PROGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
22 |
|
6.1 |
Configuration Program Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
22 |
|
|
6.1.1 What You Will Need . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
22 |
|
7.0 |
CONTROLS AND INDICATORS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
23 |
|
7.1 |
ON/Alarm Silence/Manual Battery Test Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
23 |
|
7.2 |
Standby/Manual Bypass Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
23 |
|
7.3 |
Load Level Indicators (4 Green, 1 Amber) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
24 |
|
7.4 |
Battery Level Indicators (5 Green) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
24 |
|
7.5 |
UPS Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
25 |
|
8.0 |
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
26 |
|
8.1 |
Startup Checklist for the Liebert GXT3™. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
26 |
|
8.2 |
Initial Startup and Electrical Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
26 |
|
8.3 |
Manual Battery Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
27 |
i
8.4 Put the Liebert® GXT3™ in Manual Bypass. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 8.5 Shut Down the Liebert GXT3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 8.6 Disconnecting Input Power from the Liebert GXT3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 8.7 Maintenance Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
9.0 COMMUNICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
9.1 Communication Interface Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 9.2 Terminal Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
9.2.1 Any-Mode Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 9.2.2 Battery Mode Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 9.2.3 On Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
9.2.4 Low Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
9.3 Liebert IntelliSlot® Communication Cards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
9.3.1 Liebert® MultiLink®. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
30 |
9.4 Remote Emergency Power Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
10.0 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
10.1 Replacing the Internal Battery Pack. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
10.1.1 Battery Replacement Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
10.2 Battery Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 10.3 Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 10.4 Checking UPS Status. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 10.5 Checking UPS Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 10.6 Replacing the Power Module on 8000 and 10,000VA models . . . . . . . . . . . . . . . . . . . . . . . . 33
11.0 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
11.1 UPS Symptoms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
11.1.1 Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 11.1.2 Audible Alarm. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
11.2 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
12.0 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
12.1 Auto-Learning Battery Run Times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
ii
|
FIGURES |
|
Figure 1 |
Liebert GXT3 front view—rack-mount and tower configurations . . . . . . . . . . . . . . . . . . . . . . . . . |
. 7 |
Figure 2 |
Liebert GXT3 5000VA and 6000VA rear view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
. 7 |
Figure 3 |
Input power hardwire boxes—5000 and 6000VA models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
7 |
Figure 4 |
Liebert® GXT3-6000RTL630™, rear view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
8 |
Figure 5 |
Liebert GXT3 8000VA and 10,000VA rear view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
8 |
Figure 6 |
Power distribution models for 5000VA and 6000VA models of Liebert® GXT3™. . . . . . . . . . . . . . |
9 |
Figure 7 Power distribution models for 8000VA and 10,000VA models of Liebert® GXT3™ . . . . . . . . . . . |
10 |
|
Figure 8 |
Internal battery pack features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
10 |
Figure 9 |
Support bases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
12 |
Figure 10 |
Remove the front plastic bezel cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
12 |
Figure 11 |
Rotate the operation and display panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
13 |
Figure 12 |
External battery cabinets connected to 6000VA Liebert GXT3 . . . . . . . . . . . . . . . . . . . . . . . . . . . |
16 |
Figure 13 |
Power distribution box removal from 5000 and 6000VA models . . . . . . . . . . . . . . . . . . . . . . . . . . |
17 |
Figure 14 |
Power distribution box removal from 8000 and 10,000VA models . . . . . . . . . . . . . . . . . . . . . . . . |
18 |
Figure 15 |
Distribution box electrical connections diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
19 |
Figure 16 |
Terminal block connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
20 |
Figure 17 |
Remove cover from IT Power System Connectors compartment . . . . . . . . . . . . . . . . . . . . . . . . . . |
21 |
Figure 18 |
Liebert® GXT3™ control panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
23 |
Figure 19 |
Load level indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
24 |
Figure 20 Battery level indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
24 |
|
Figure 21 |
Terminal block communication pin layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
28 |
Figure 22 |
Removing the front plastic bezel cover and battery door . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
31 |
Figure 23 |
Disconnecting the battery plug and battery receptacle (front view) . . . . . . . . . . . . . . . . . . . . . . . |
31 |
Figure 24 |
Pulling out the battery packs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
32 |
Figure 25 |
Removing power module from Liebert® GXT3™ 8000 and 10,000VA models . . . . . . . . . . . . . . . . |
34 |
Figure 26 Battery level indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
35 |
|
|
TABLES |
|
Table 1 |
Branch circuit breaker ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
19 |
Table 2 |
Electrical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
20 |
Table 3 |
UPS status indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
25 |
Table 4 |
Indicator descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
35 |
Table 5 |
Audible alarm description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
36 |
Table 6 |
Troubleshooting table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
36 |
Table 7 |
UPS specifications—5000, 6000, 8000 and 10,000 models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
38 |
Table 8 |
UPS specifications—Liebert® GXT3-6000RTL630™. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
39 |
Table 9 |
Operating temperature parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
40 |
Table 10 |
Internal battery cabinet specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
40 |
Table 11 |
External battery cabinet specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
41 |
Table 12 |
Power distribution specifications: GXT3-5000RT208, GXT3-6000RT208 and |
|
|
GXT3-6000RTL630 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
41 |
Table 13 |
Power distribution box specifications for GXT3-8000RT208 and GXT3-10000RT208 . . . . . . . . . |
42 |
Table 14 Battery run time, minutes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
43 |
iii
iv
This manual contains important safety instructions. Read all safety and operating instructions before operating the uninterruptible power system (UPS). Adhere to all warnings on the unit and in this manual. Follow all operating and user instructions. This equipment can be operated by individuals without previous training.
This product is designed for commercial/industrial use only. It is not intended for use with life support and other designated “critical” devices. Maximum load must not exceed that shown on the UPS rating label. The UPS is designed for data processing equipment. If uncertain, consult your dealer or local Emerson Network Power representative.
This UPS is designed for use on a properly grounded (earthed), 100/200, 110/220, 115/230, 120/208,120/240 or 127/220VAC, 50 or 60Hz supply. The factory default setting is 120/208VAC, 60Hz. Installation instructions and warning notices are in this manual.
The Liebert® GXT3™ 208VAC 5000 - 10000 is designed for use with a four-wire input (L1, L2, N, G).
The Liebert GXT3-6000RTL630™ is designed be used with a three-wire, two-phase utility source (L1, L2, G).
! WARNING
The battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed when replacing the battery pack:
• Wear rubber gloves and boots
• Remove rings, watches and other metal objects.
• Use tools with insulated handles.
• Do not lay tools or other metal objects on the batteries.
• If the battery kit is damaged in any way or shows signs of leakage, contact your local Emerson representative immediately.
• Do not dispose of batteries in a fire. The batteries may explode.
• Handle, transport and recycle batteries in accordance with local regulations.
! WARNING
Although the Liebert GXT3 has been designed and manufactured to ensure personal safety, improper use can result in electrical shock or fire. To ensure safety, observe the following precautions:
•Turn Off and unplug the Liebert GXT3 before cleaning it.
•Clean the UPS with a dry cloth. Do not use liquid or aerosol cleaners.
•Never block or insert any objects into the ventilation holes or other openings of the UPS.
•Do not place the Liebert GXT3 power cord where it might be damaged.
1
ELECTROMAGNETIC COMPATIBILITY—The Liebert® GXT3™ complies with the limits for a Class A digital device, pursuant to Part 15 of FCC rules.
Operation is subject to the following conditions:
•This device may not cause harmful interference.
•This device must accept any interference received, including interference that may cause undesired operation. Operating this device in a residential area is likely to cause harmful interference that users must correct at their own expense.
The Liebert GXT3 series complies with the requirements of EMC Directive 2004/108/EC and the published technical standards. Continued compliance requires installation in accordance with these instructions and use of accessories approved by Emerson.
NOTICE
This is a product for restricted sales distribution to informed partners. Installation restrictions or additional measures may be needed to prevent radio interference.
Operate the UPS in an indoor environment only in an ambient temperature range of 0-40°C (32-104°F). Install it in a clean environment, free from moisture, flammable liquids, gases and corrosive substances.
The Liebert GXT3-5000RT208™, Liebert GXT3-6000RT208™ and the Liebert GXT3-6000RTL630™ contain no user-serviceable parts except the internal battery pack. The Liebert GXT3-10000RT208™ and the Liebert GXT3-8000RT208™ contain no user-serviceable parts except the internal battery pack and the Power Module. The UPS On/Off push buttons do not electrically isolate internal parts. Under no circumstances attempt to gain access internally due to the risk of electric shock or burn.
Do not continue to use the UPS if the front panel indications are not in accordance with these operating instructions or the UPS performance alters in use. Refer all faults to your dealer.
Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from the batteries. Keep unauthorized personnel away from the batteries. Proper disposal of batteries is required. Refer to your local laws and regulations for disposal requirements.
Never block or insert any object into the ventilation holes or other openings.
DO NOT CONNECT equipment that could overload the UPS or demand DC current from the UPS, for example: electric drills, vacuum cleaners, laser printers, hair dryers or any appliance using halfwave rectification.
Storing magnetic media on top of the UPS may result in data loss or corruption.
Turn Off and isolate the UPS before cleaning it. Use only a soft cloth, never liquid or aerosol cleaners.
UPS SERVICING—This UPS makes use of components dangerous for the environment (electronic cards, electronic components). The components removed must be taken to specialized collection and disposal centers.
2
Risk of electrical shock
!Indicates caution followed by important instructions
AC input
AC output
i
Requests the user to consult the manual
- |
+ |
Indicates the unit contains a valve-regulated lead acid battery |
|
PbH2SO4 |
|||
|
RRecycle
DC voltage
Equipment grounding conductor
Bonded to ground
AC voltage
ON/Alarm Silence/Manual Battery Test
OFF/Bypass
WEEE
3
1.0INTRODUCTION
Congratulations on your choice of the Liebert® GXT3™ uninterruptible power system (UPS). The Liebert GXT3 comes in nominal power ratings of 5000VA, 6000VA, 8000VA and 10,000VA. It is designed to provide conditioned power to microcomputers and other sensitive electronic equipment.
When it is generated, alternating current is clean and stable. However, during transmission and distribution it is subject to voltage sags, spikes and complete power failure that may interrupt computer operations, cause data loss and even damage equipment. The Liebert GXT3 protects equipment from these disturbances.
The Liebert GXT3 is a compact, on-line UPS. An on-line UPS continuously conditions and regulates its output voltage, whether utility power is present or not. It supplies connected equipment with clean, sinewave power. Sensitive electronic equipment operates best from sinewave power.
For ease of use, the Liebert GXT3 features a light-emitting diode (LED) display to indicate both load percentage and battery capacity. It also provides self-diagnostic tests, a combination ON/Alarm Silence/Manual Battery Test button, a Standby/Manual Bypass button and a configuration program.
The Liebert GXT3 has a Liebert IntelliSlot® port for communication between the UPS and a network server or other computer systems. This port provides detailed operating information including voltages, currents and alarm status to the host system when used in conjunction with Liebert MultiLink®. Liebert MultiLink can also remotely control UPS operation.
4
2.0SYSTEM DESCRIPTION
Input |
|
|
|
Output |
|
|
|
|
Static |
|
|
|
|
|
Bypass |
|
|
L1 |
|
|
|
L1 |
|
TVSS & |
Rectifier/PFC |
|
|
||
L2 |
|
L2 |
|||
N |
EMI/RFI |
DC-to-DC |
Inverter |
|
|
Filters |
Converter |
N |
|||
|
Battery |
|
|
|
Battery |
|
|
|
||
|
|
|
Charger |
|
|
|
|
|
|
G G
These UPS components provide surge protection and filter both electromagnetic interference (EMI) and radio frequency interference (RFI). They minimize any surges or interference present in the utility line and keep the sensitive equipment protected.
In normal operation, the rectifier/power factor correction (PFC) circuit converts utility AC power to regulated DC power for use by the inverter while ensuring that the waveshape of the input current used by the UPS is near ideal. Extracting this sinewave input current achieves two objectives:
•The utility power is used as efficiently as possible by the UPS.
•The amount of distortion reflected on the utility is reduced.
This results in cleaner power being available to other devices in the building not being protected by the Liebert® GXT3™.
2.3Inverter
In normal operation, the inverter utilizes the DC output of the power factor correction circuit and inverts it into precise, regulated sinewave AC power. Upon a utility power failure, the inverter receives its required energy from the battery through the DC-to-DC converter. In both modes of operation, the UPS inverter is on-line and continuously generating clean, precise, regulated AC output power.
The battery charger utilizes energy from the utility power and precisely regulates it to continuously float charge the batteries. The batteries are being charged whenever the Liebert GXT3 is connected to utility power.
2.5DC-to-DC Converter
The DC-to-DC converter utilizes energy from the battery system and raises the DC voltage to the optimum operating voltage for the inverter. This allows the inverter to operate continuously at its optimum efficiency and voltage, thus increasing reliability.
5
System Description
The Liebert® GXT3™ utilizes valve-regulated, nonspillable, lead acid batteries. To maintain battery design life, operate the UPS in an ambient temperature of 15°C to 25°C (59°F to 77°F). Optional external battery cabinets are available to extend battery run times. For run times, see Table 14.
The Liebert GXT3 provides an alternate path for utility power to the connected load in the unlikely event of a UPS malfunction. Should the UPS have an overload, overtemperature or any other UPS failure condition, the UPS automatically transfers the connected load to bypass. Bypass operation is indicated by an audible alarm and illuminated amber Bypass LED (other LEDs may be illuminated to indicate the diagnosed problem). To manually transfer the connected load from the inverter to bypass, press the Standby/Manual Bypass button once and hold it for about 2 seconds.
NOTE
The bypass power path does NOT protect the connected equipment from disturbances in the utility supply.
6
3.0MAJOR COMPONENTS
The Liebert® GXT3™ is composed of three major assemblies to provide easier handling, installation and versatility.
All models of the Liebert GXT3 are shipped without the internal batteries installed. Power distribution varies by model and rating.
•Liebert GXT3 5000 and 6000VA models ship with a basic hardwire distribution box attached and ready to be connected to the load (see Figure 2).
•Liebert GXT3RTL630™ ships with a power distribution box attached (see (Figure 4).
•Liebert GXT3 8000 and 10,000VA models with a cover plate installed over connections for any of several optional power distribution boxes (see Figure 5).
Upper Bezel
Status Indicators
and Controls
Lower Bezel and
Battery Access
Door
USB Port |
|
|
|
Liebert |
Knockouts for Hardwired |
||
|
|
||||||
REPO |
|
|
|
|
|
IntelliSlot Port |
Power Input |
|
|
||||||
|
|
|
|
|
|
|
|
Terminal Block
Communication
|
|
|
|
External Battery |
|
|
|
|
|
Input Breaker |
|
|
|
Connector |
|
|
Input
Breaker
|
Maintenance |
|
|
|
|
|
|
|
|
||
|
Bypass Breaker |
||||
PD2-HDWR |
Input Breaker |
|
|
||
|
|||||
|
|
|
|
PD2-HDWR-MBS - 5000 |
|
5000 and 6000VA models |
|
|
|
|
and 6000VA models |
NOTE
Hardwire and hardwire/receptacle boxes that include a manual bypass switch permit AC power to continue to flow from the utility input to the load while the box is removed from the UPS. For details, refer to 3.2 - Removable Power Distribution Box.
7
|
|
|
|
|
|
Major Components |
||
|
|
|
|
|
|
|||
Figure 4 Liebert® GXT3-6000RTL630™, rear view |
|
|
|
|||||
Terminal Block |
REPO Connection |
Output Breaker for |
Output Breaker |
|||||
L6-20R #2 and #3 |
for L6-30R #4 |
|||||||
Block |
||||||||
Communication |
|
|
|
|||||
USB Port |
|
|
|
|||||
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
External |
|
Liebert |
|
|
|
|
|
|
Battery |
|
|
|
|
|
|
|
Connector |
||
IntelliSlot Port |
|
|
|
|||||
|
|
|
|
|||||
Input Breaker |
|
|
|
|
|
IT Power |
||
for L6-30P #1 |
|
|
|
|
|
System |
||
|
|
|
|
|
|
|
Access |
|
|
|
|
|
|
|
|
Cover |
|
Maintenance |
|
|
|
|
|
Output Breaker |
||
|
|
|
|
|
||||
|
|
|
|
|
for L6-30R #5 |
|||
Bypass Breaker |
|
5 |
|
|||||
|
|
|
||||||
|
|
|
|
|
|
|
||
1 |
|
2 |
|
3 |
|
4 |
|
|
|
|
|
|
|
|
|
||
Figure 5 Liebert GXT3 8000VA and 10,000VA rear view |
|
|
|
|||||
|
|
|
|
Liebert |
Terminal Block |
|
|
|
Maintenance |
|
|
IntelliSlot Port |
Communication |
REPO Connection Block |
Bypass
Switch
Cover for Power
Distribution Box USB Port Connections
Output |
|
|
|
|
|
|
Input |
|
|
|
|
|
|
|
|||
Breaker |
|
|
|
|
|
|||
|
|
|
|
|
||||
|
|
|
|
|
Breaker |
|||
Switch |
|
|
|
|
|
|||
|
|
|
|
|
Switch |
|||
|
|
|
|
|
|
|
||
External Battery |
|
|
|
|
|
|
Knockouts |
|
|
|
|
|
|
|
for Hardwired |
||
Connector |
|
|
|
|
|
|
||
|
|
|
|
|
|
|||
|
|
|
|
|
|
Power Input |
||
|
|
|
|
|
|
|
|
8
Major Components
The UPS is shipped with a power distribution pack installed. This box contains the UPS input circuit breaker.
Maintenance |
Output Power Breakers |
for Pigtails |
|
Bypass Breaker |
|
Input Power
Breaker
L14-30 Input
Power Connector
PD2-001 shown as example; similar features on other distribution boxes arranged differently
Push Button Output Power Breakers for Two L5-20 Receptacles (second push button breaker obscured)
PD2-001
Receptacles: four 5-20; one
L14-30; one L6-30R
PD2-002
Receptacles: two 5-20R; two L6-20R PD2-005
Receptacles: four L5-20R; two L6-30R
PD2-003 |
PD2-006 |
|
Receptacles: four L6-20R |
||
receptacles: four 5-20R; two L6-30 |
||
|
PD2-004
Receptacles: four L5-20R; two L5-30R
9
Major Components
5-20R Output
Receptacles
Push Button Circuit Breakers
for 5-20R Receptacles
5-20R Output
Receptacles
PD2-101 Receptacles: two L6-30; eight 5-20R
PD2-102
Receptacles: four L6-20R four 5-20R
PD2-103
Receptacles: four L6-30R four 5-20R
PD2-104
Receptacles: four 5-20R two L6-30R two L6-20R
similar features on other distribution boxes arranged differently
Output Circuit Breaker
Switch for L6-30R Pigtail #1
L6-30ROutput
Receptacles
2
1
Output Circuit Breaker Switch for L6-30R Pigtail #2
PD2-105
Receptacles: four 5-20R two L5-30R two L5-20R
PD2-106
Receptacles: four L6-20R four L5-20R
The UPS has two internal battery packs behind a battery access door on the front of the unit. Each internal battery pack is fitted with a connector to link to the UPS.
Battery Handle
Battery Connector
Liebert GXT3 8000 and 10,000VA
battery packs shown; 5000 and 6000VA battery packs
have same features
Front of Battery Pack
10