Emerson 320, 330 Installation Manual

0 (0)
Emerson 320, 330 Installation Manual

Power Switching & Controls

For Business-Critical Continuity

300 Series

330/320 Surge Protective Device

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual

IO-70105 Rev 1, 1/2014

EMERSON NETWORK POWER SURGE PROTECTIVE DEVICE

 

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

 

TABLE OF CONTENTS

 

INSTALLATION

 

Environment............................................................................................................

2

Mounting ................................................................................................................

2

Wire Sizing/Routing.................................................................................................

2

Conduit Connection ................................................................................................

2

Wiring Connections....................................................................................................................

2

ApplyingPower...........................................................................................................................

3

PRODUCT RATINGS AND LIMITATIONS

 

Voltage Protection Ratings.......................................................................................

3

Circuit Ampacity Limitations ....................................................................................

3

TROUBLESHOOTING/SERVICING/MAINTENANCE

 

Troubleshooting ......................................................................................................

3

MODEL NUMBER CONFIGURATION

 

Model Number Configuration ..................................................................................

3

Configuration & Voltage (Chart)...............................................................................

4

330 SURGE PROTECTIVE DEVICE

 

Suggested Circuit Breaker and Wire Size ..................................................................

5

330 Dimensional Information ..................................................................................

5

320 SURGE PROTECTIVE DEVICE

 

Suggested Circuit Breaker and Wire Size ..................................................................

6

320 Dimensional Information ..................................................................................

6

PARALLEL WIRING DIAGRAM

 

Parallel Wiring Diagram ...........................................................................................

6

Installation, Operation and Maintenance Manual

1

IO-70105 Rev 1, 1/2014

The Emerson Network Power 330 & 320 Surge Protective Devices are high quality, high energy surge current diversion system designed to protect sensitive equipment from damaging transient voltage surges resulting from load switching, lightning strikes and other sources.

The installer should perform the following steps to assure a quality installation. Please read all instructions before starting the installation of this product. These instructions do not replace national or local electrical codes — check applicable codes to ensure compliance.

INSTALLATION

DANGER! ONLY QUALIFIED PERSONNEL SHOULD INSTALL OR SERVICE THIS SYSTEM. ELECTRICAL SAFETY PRE- CAUTIONS MUST BE FOLLOWED WHEN INSTALLING OR SERVICING THIS EQUIPMENT. TO PREVENT RISK OF ELECTRICAL SHOCK, TURN OFF AND LOCK OUT ALL POWER SOURCES TO THE UNIT BEFORE MAKING ELECTRICAL

CONNECTIONS OR SERVICING.

DANGER! SEULEMENT LE PERSONNEL QUALIFIÉ DOIT INSTALLER OU MAINTENIR CE SYSTÈME. DES PRÉCAUTIONS DE SÉCURITÉ EN ÉLECTRICITÉ DOIVENT ÊTRE SUIVIS LORS DE L'INSTALLATION OU DE LA MAINTENANCE DE CET EQUIPEMENT. POUR EVITER TOUT RISQUE DE CHOC ÉLECTRIQUE, DÉBRANCHEZ ET VEROUILLER TOUTES LES SOURCES D’ ALIMENTATION DE CET EQUIPEMENT AVANT DE LE BRANCHER OU LE MAINTENIR.

Environment — The unit is designed for operation indoors in ambient temperatures of - 40ºC (-40ºF) to +60ºC (+140ºF) with a relative humidity of 0% to 95% (non-condensing). The unit is provided in an industrial enclosure, which should not be installed in areas with excessive dust, corrosive vapors, flammable materials or explosive atmospheres.

Mounting — Mount unit as close as possible to the service panel in close proximity to the breaker that will feed the SPD. Use #10 (330 units) or #6 (320 units) mounting hardware. For best performance, unit should be positioned so that the length of the wiring to the surge protective device (SPD) unit is minimized.

Wire Sizing/Routing — #10 or 12 AWG wiring is provided with unit. To reduce the wiring impedance to surge currents, the phase, neutral (if required), and ground conductors are recommended to be twisted together and routed in the same raceway (conduit). Avoid any sharp bends in the conductors. All wiring must comply with the National Electrical Code (NEC) and applicable local codes.

Conduit Connection — Feed all wires into the panel through the knockout selected and secure.

Wiring Connections — Before making connections to the unit, verify that the unit model number and nameplate voltage rating are appropriate for connection to the intended power source (See table).

1.It is recommended that a circuit breaker be used for installation and connection to the service panel. See pages 5-6 for recommended amperage.

2.Connect the white wire (if provided) of the SPD to the neutral of the supply, and connect the green wire (if provided) of the SPD to source ground.

3.Connect each Black Phase Wire to corresponding phase on the service panel.

4.If not using the relay contact wires for remote sensing, cut and dress the wires. If using remote sensing, these wires are connected to COM (orange), NC (blue), and NO (yellow) respectively. (Relay’s maximum switching capacity is 125VAC, 5A.)

(continued)

Installation, Operation and Maintenance Manual

2

IO-70105 Rev 1, 1/2014