UNVENTED (VENT-FREE) GAS FIREPLACE OWNER’S OPERATION AND INSTALLATION MANUAL
Patent Pending |
Shown with optional |
|
|
|
cabinet mantel and hearth |
|
base accessories. |
LMFP33NR(A) and LMFP33PR(A) Remote Control
Gas Fireplace Systems
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
—Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
—WHAT TO DO IF YOU SMELL GAS
•Do not try to light any appliance.
•Do not touch any electrical switch; do not use any phone in your building.
•Immediatelycallyourgassupplierfromaneighbor’s phone. Follow the gas supplier’s instructions.
•If you cannot reach your gas supplier, call the fire department.
—Installationandservicemustbeperformedbyaqualified installer, service agency or the gas supplier.
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
For more information, visit www.desatech.com
Contents
Safety Information................................................ |
2 |
Product identification............................................ |
4 |
Local Codes......................................................... |
5 |
Unpacking............................................................ |
5 |
Product Features.................................................. |
5 |
Air for Combustion and Ventilation....................... |
5 |
Installation............................................................ |
8 |
Operating Heater................................................ |
20 |
Inspecting Burners............................................. |
23 |
Cleaning and Maintenance................................ |
24 |
Troubleshooting................................................. |
|
25 |
Specifications..................................................... |
|
29 |
Wiring Diagram.................................................. |
|
29 |
Technical Service............................................... |
|
29 |
Service Hints...................................................... |
|
29 |
Replacement Parts............................................. |
|
29 |
Illustrated Parts Breakdown and Parts List........ |
30 |
|
Accessories........................................................ |
|
34 |
Warranty Information............................ |
Back Cover |
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage.
Refer to this manual for correct installation and operational procedures.
For assistance or additional information consult a qualified installer, service agency or the gas supplier.
WARNING: This is an unvented gas-fired heater. It uses air (oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must be provided. Refer to Air for Combustion and Ventilation section on page 5 of this manual.
This appliance may be installed in an aftermarket,* permanently located, manufactured (mobile) home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
State of Massachusetts: The installation must be made by a licensed plumber or gas fitter in the Commonwealth of Mas- sachusetts.
Sellers of unvented propane or natural gas-fired supplemental room heaters shall provide to each purchaser a copy of 527 CMR 30 upon sale of the unit.
Vent-free gas products are prohibited for bedroom and bathroom installation in the
Commonwealth of Massachusetts.
|
www.desatech.com |
111604-01N |
SAFETY INFORMATION
Continued
WARNING:Thisproductcontainsand/orgenerateschemicals known to the State of California to cause cancer or birth defects or other reproductive harm.
IMPORTANT: Read this owner’s manual carefully and completely beforetryingtoassemble,operate or service this heater. Improper use of this heater can cause seriousinjuryordeathfromburns,fire, explosion, electrical shock and carbon monoxide poisoning.
DANGER:Carbonmonoxide poisoning may lead to death!
CarbonMonoxidePoisoning:Earlysignsofcarbon monoxide poisoning resemble the flu, with head- aches, dizziness or nausea. If you have these signs, the heater may not be working properly. Get fresh air at once! Have heater serviced. Some people are more affected by carbon monoxide than others. These include pregnant women, people with heart orlungdiseaseoranemia,thoseundertheinfluence of alcohol and those at high altitudes.
Natural and Propane/LP Gas: Natural and pro- pane/LPgasesareodorless.Anodor-makingagent is added to the gas. The odor helps you detect a gas leak. However, the odor added to the gas can fade. Gas may be present even though no odor exists.
Make certain you read and understand all warn- ings. Keep this manual for reference. It is your guide to safe and proper operation of this heater.
WARNING: Any change to this heater or its controls can be dangerous.
WARNING: Do not allow fans toblowdirectlyintothefireplace. Avoidanydraftsthatalterburner flame patterns. Ceiling fans can create drafts that alter burner flame patterns. Altered burner patterns can cause sooting.
WARNING: Do not use a blower insert, heat exchanger insertorotheraccessorynotapproved for use with this heater.
Due to high temperatures, the applianceshouldbelocatedout oftrafficandawayfromfurniture and draperies.
Do not place clothing or other flammable material on or near the appliance. Never place any objects on the heater.
Fireplace and screen become veryhotwhenrunningfireplace.
Keep children and adults away fromhotsurfacestoavoidburns or clothing ignition. Fireplace will remain hot for a time after shutdown. Allow surfaces to cool before touching.
Carefully supervise young children when they are in the room with fireplace. When using the optional hand-held remote accessory, keep selector switch in the OFF position to prevent childrenfromturningonburners with remote.
You must operate this fireplace with the fireplace screen and hood in place. Make sure fireplace screen and hood are in place before running heater.
Keep the appliance area clear and free from combustible materials, gasoline and other flammable vapors and liquids.
111604-01N |
www.desatech.com |
SAFETY INFORMATION
Continued
1.This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
2.Donotplacepropane/LPsupplytank(s)inside any structure. Locate propane/LP supply tank(s) outdoors (propane/LP units only).
3.If you smell gas
•shut off gas supply
•do not try to light any appliance
•donottouchanyelectricalswitch;donotuse any phone in your building
•immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions
•if you cannot reach your gas supplier, call the fire department
4.This fireplace shall not be installed in a bed- room or bathroom.
5.Do not use this fireplace as a wood-burning fireplace. Use only the logs provided with the fireplace.
6.Do not add extra logs or ornaments such as pine cones, vermiculite or rock wool. Using these added items can cause sooting. Do not add lava rock around base. Rock and debris could fall into the control area of fireplace.
7.Topreventthecreationofsoot,followtheinstruc- tions in Cleaning and Maintenance, page 24.
8.Before using furniture polish, wax, carpet cleaner or similar products, turn heater off. If heated, the vapors from these products may create a white powder residue within burner box or on adjacent walls or furniture.
9.Thisfireplaceneedsfreshairventilationtorun properly.ThisfireplacehasanOxygenDeple- tionSensing(ODS)safetyshutoffsystem.The ODS shuts down the fireplace if enough fresh air is not available. See Air for Combustion and Ventilation, page 5. If fireplace keeps shutting off, see Troubleshooting, page 25.
10.Do not run fireplace
•where flammable liquids or vapors are used or stored
•under dusty conditions
11.Do not use this fireplace to cook food or burn paper or other objects.
12.Donotusefireplaceifanyparthasbeenexposed to or under water. Immediately call a qualified servicetechniciantoinspectthefireplaceandto replace any part of the control system and any gas control which has been under water.
13.Do not operate fireplace if any log is broken. Do not operate fireplace if a log is chipped (dime-sized or larger).
14.Turn fireplace off and let cool before servic- ing. Only a qualified service person should service and repair fireplace.
15.Operating fireplace above elevations of 4,500 feet could cause pilot outage.
16.Topreventperformanceproblemsinpropane/LP units, do not use propane/LP fuel tanks of less than 100 lbs. capacity (propane/LP units only).
17.Provide adequate clearances around air openings.
4-Piece Log Set (A Models shown)
Control |
|
|
Knob |
|
|
Piezo |
|
|
Ignitor |
Remote |
|
Remote Control |
||
Receiver |
||
|
||
Figure 1 - Log Base Assembly |
Top Louver Top Outer Casing |
Blower |
Assembly |
Assembly |
Firebox |
(Optional) |
|
|
Hood |
|
Firebox |
|
Support |
|
Screen
Assembly
Bottom Louver Assembly
Figure 2 - Fireplace (LMFP33PR Shown)
www.desatech.com |
111604-01N |
Install and use fireplace with care. Follow all local codes. In the absence of local codes, use the lat- est edition of The National Fuel Gas Code ANSI Z223.1/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
Note: Where listed vented decorative logs are required, thermostat operation is not permitted.
CAUTION:Donotremovethe dataplatesattachedtotheheater base assembly. The data plates contain important warranty and safety information.
1.With utility knife, cut the carton all the way around above the staples on the bottom tray. Liftthecartonofftheheater.Removepacking. Note: The hood is located in the packing on the right hand side of the heater front. Lift the heater off the bottom tray.
2.Locate two screws above top corners of the fireplace screen. Remove and discard these screws. Lift fireplace screen up and pull out to remove.
3.Remove protective packaging applied to logs, log base assembly and fireplace.
4.Remove fireplace hood from carton insert.
5.Check all items for any shipping damage. If damaged, promptly inform dealer where you bought fireplace.
Operation
Thisvent-freefireplaceiscleanburning.Itrequires no outside venting. There is no heat loss out a vent or up a chimney. Heat is generated by both realisticflames.Whenusedwithouttheblower,the fireplace requires no electricity making it ideal for emergency backup heat. This heater is designed for vent-free operation. It has been tested and ap- proved to ANSI Z21.11.2 standard for unvented heaters. State and local codes in some areas pro- hibit the use of vent-free heaters.
Safety Device
ThisfireplacehasapilotwithanOxygenDepletion Sensing (ODS) safety shutoff system. The ODS/ pilot is a required feature for vent-free room heat- ers. The ODS/pilot system shuts off the fireplace if there is not enough fresh air.
Piezo Ignition System
This fireplace has a piezo ignitor. This system requires no matches, batteries or other sources to light fireplace.
Optional Blower Assembly
(GA3750 Series & GA3650TB
Series)
Thisfireplaceacceptsanoptionalblowerassembly (not included). The GA3650TB Series blower operates thermostatically and features a variable speedcontrol.TheGA3750Seriesbloweroperates manuallyandalsofeaturesavariablespeedcontrol. The blower circulates heated air from the fireplace into the room. See Accessories, page 34.
WARNING: This heater shall not be installed in a confined spaceorunusuallytightconstructionunlessprovisionsareprovided for adequate combustion and ventilationair.Readthefollowing instructionstoinsureproperfresh air for this and other fuel-burning appliances in your home.
Today’s homes are built more energy efficient than ever. New materials, increased insulation and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want their homes as airtight as possible.
While it is good to make your home energy effi- cient, your home needs to breathe. Fresh air must enter your home.All fuel-burning appliances need fresh air for proper combustion and ventilation.
Exhaust fans, fireplaces, clothes dryers and fuel burning appliances draw air from the house to operate. You must provide adequate fresh air for these appliances. This will insure proper venting of vented fuel-burning appliances.
111604-01N |
www.desatech.com |
AIR FOR COMBUSTION
AND VENTILATION
Continued
PROVIDING ADEQUATE
VENTILATION
The following are excerpts from National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three fol- lowing ventilation classifications:
1.Unusually Tight Construction
2.Unconfined Space
3.Confined Space
The information on pages 5 through 7 will help you classify your space and provide adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.
Unusually tight construction is defined as construction where:
a.walls and ceilings exposed to the outside atmosphere have a continuous water vapor retarder with a rating of one perm (6 x 10-11 kg per pa-sec-m2) or less with openings gasketed or sealed and
b.weather stripping has been added on openable windows and doors and
c.caulking or sealants are applied to areas such as joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines and at other openings.
If your home meets all of the three criteria above, you must provide additional fresh air. See Ventilation Air From Outdoors, page 7.
If your home does not meet all of the three criteria above, proceed to Determining Fresh-Air Flow For Heater Location.
Confined and Unconfined Space
The National Fuel Gas Code, ANSI Z223.1/NFPA 54 defines a confined space as a space whose vol- umeislessthan50cubicfeetper1,000Btuperhour (4.8 m3 per kw) of the aggregate input rating of all appliancesinstalledinthatspaceandanunconfined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of theaggregateinputratingofallappliancesinstalled in that space. Rooms communicating directly with the space in which the appliances are installed*, through openings not furnished with doors, are considered a part of the unconfined space.
* Adjoining rooms are communicating only if therearedoorlesspassagewaysorventilationgrills between them.
DETERMINING FRESH-AIR FLOW FOR FIREPLACE LOCATION
Determining if You Have a Confined or
Unconfined Space
Use this work sheet to determine if you have a confined or unconfined space.
Space: Includes the room in which you will install fireplaceplusanyadjoiningroomswithdoorlesspas- sageways or ventilation grills between the rooms.
1.Determine the volume of the space (length x width x height).
Length x Width x Height =__________cu. ft. (volume of space)
Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2,560 cu. ft. (volume of space)
If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.
2.Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.
___________ (volume of space) x 20 = (Maxi- mum Btu/Hr the space can support)
Example: 2,560 cu. ft. (volume of space) x 20 = 51,200 (maximum Btu/Hr the space can support)
3.Add the Btu/Hr of all fuel burning appliances in the space.
Vent-free fireplace |
__________ Btu/Hr |
Gas water heater* |
__________ Btu/Hr |
Gas furnace |
__________ Btu/Hr |
Vented gas heater |
__________ Btu/Hr |
Gas fireplace logs |
__________ Btu/Hr |
Other gas appliances* |
+_ ________ Btu/Hr |
Total |
=_ ________ Btu/Hr |
* Do not include direct-vent gas appliances. Di- rect-ventdrawscombustionairfromtheoutdoors and vents to the outdoors.
www.desatech.com |
111604-01N |
AIR FOR COMBUSTION AND VENTILATION
Continued
Example: |
|
40,000 |
|
Gas water heater |
|
Btu/Hr |
|
Vent-free fireplace |
+_ |
33,000 |
Btu/Hr |
Total |
=_ |
73,000 |
Btu/Hr |
4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
__________Btu/Hr (maximum the space can support)
__________Btu/Hr (actual amount of Btu/Hr used)
Example: 51,200 Btu/Hr (maximum the space can support)
73,000 Btu/Hr (actual amount of Btu/Hr used)
The space in the example is a confined space because the actual Btu/Hr used is more than the maximum
Btu/Hr the space can support. You must provide ad- ditional fresh air. Your options are as follows:
A.Reworkworksheet,addingthespaceofanadjoin- ingroom.Iftheextraspaceprovidesanunconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building.
B.Vent room directly to the outdoors. See Ventilation Air From Outdoors.
C.Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an un- confined space. You will need no additional fresh air ventilation.
WARNING: If the area in which the heater may be operatedissmallerthanthatdefined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air byoneofthemethodsdescribed in the National Fuel Gas Code, ANSIZ223.1/NFPA54Section5.3 or applicable local codes.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining un- confined space. When ventilating to an adjoining unconfined space, you must provide two perma- nent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 3).You can also remove door into adjoining room (see option 3, Figure 3). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.
|
|
12" |
|
Ventilation |
|
Ventilation Grills |
|
Grills |
|
||
Into Adjoining |
Or |
Into Adjoining Room, |
|
Room, |
Option 2 |
||
Remove |
|||
Option 1 |
|
||
Door into |
|
||
|
|
||
|
Adjoining |
|
|
|
Room, |
|
|
|
Option |
|
|
|
3 |
|
12"
Figure 3 - Ventilation Air from Inside Building
Ventilation Air From Outdoors
Provideextrafreshairbyusingventilationgrillsor ducts.You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the
National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.
IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostatcontrolledpowervent.Heatedairenteringtheattic will activate the power vent.
|
Outlet |
Ventilated |
|
Attic |
|
|
Air |
|
|
|
|
Outlet |
|
|
Air |
|
To Attic |
|
|
|
|
|
To |
|
|
Crawl |
Inlet |
|
Space |
|
|
|
Air |
|
|
|
Inlet Air |
Ventilated |
|
Crawl Space |
|
|
|
Figure 4 - Ventilation Air from Outdoors
111604-01N |
www.desatech.com |
|
NOTICE: This heater is intended for use as supplemental heat. Use this heater along with your primary heating system. Do not install this heater as your primary heat source. If you have a centralheatingsystem,youmay run system’s circulating blower whileusingheater.Thiswillhelp circulatetheheatthroughoutthe house. In the event of a power outage, you can use this heater as your primary heat source.
WARNING: A qualified service person must install fireplace. Follow all local codes.
WARNING: Never install the fireplace
•in a bedroom or bathroom
•in a recreational vehicle
•where curtains, furniture, clothing or other flammable objectsarelessthan42inches from the front, top or sides of the heater
•in high traffic areas
•in windy or drafty areas
CAUTION:Thisfireplacecreates warm air currents. These currents move heat to wall surfacesnexttofireplace.Installing fireplace next to vinyl or cloth wall coverings or operating heater where impurities (such as, but not limited to, tobacco smoke,aromaticcandles,cleaningfluids,oilorkerosenelamps, etc.)intheairexist,maydiscolor walls or cause odors.
Note: Yourfireplaceis designedtobeusedinzero clearance installations. Wall or framing material can be placed directly against any exterior surface on the rear, sides or top of your fireplace, except where standoff spacers are integrally attached. If standoff spacers are attached to your fireplace, these spacers can be placed directly against wall or framing materials.
Use the dimensions shown for rough openings to create the easiest installation. See Built-In Fireplace Installation, page 11.
IMPORTANT: Vent-free heaters add moisture to the air. Although this is beneficial, installing fireplace in rooms without enough ventilation air may cause mildew to form from too much moisture. See Air for Combustion and Ventilation, page 5. IMPORTANT: Make sure the fireplace is level. If fireplace is not level, log set will not work properly.
CHECK GAS TYPE
Use the correct gas type (natural or propane/LP) for your fireplace. If your gas supply is not cor- rect, do not install fireplace. Call dealer where you bought fireplace for proper type fireplace.
WARNING: This appliance is equipped for (natural or propane/LP) gas. Field conversion is not permitted.
ELECTRICAL HOOKUP
(Models GA3750 Series and GA3650TB
Series Blower Accessories and GA3555
Internal Duplex Kit)
This fireplace accepts a blower assembly with an electrical cord. The electrical cord is five feet in length. You must locate fireplace within reach of a 120 volt grounded electrical outlet. If not, you must install an electrical outlet within reach of fireplace power cord. The GA3555 outlet acces- sory is used for built-in applications with blower accessory installed.
www.desatech.com |
111604-01N |
INSTALLATION
Continued
INSTALLING HOOD
Install hood to top of firebox as shown in Figure 5. Use 3 Phillips screws provided
Figure 5 - Installing Hood to Firebox
Assembling and attaching OPTIONAL trim
(Included with Mantel Accessory)
IMPORTANT: Ifyouarerecessingthefireboxina wall, do not attach trim at this time. See page 11. Note: The instructions below show assembling and attaching trim to fireplace.
1.Remove packaging from three pieces of trim.
2.Locate four brass screws, two adjusting plates with setscrews and twoshims in thehardware packet.
3.Align shim under adjusting plate as shown in
Figure 6.
4.Slide one end of adjusting plate/shim in slot on mitered edge of top trim (see Figure 6).
5.Slide other end of adjusting plate/shim in slot on mitered edge of side trim (see Figure 6).
6.While firmly holding edges of trim together, tighten both set screws on the adjusting plate with slotted screwdriver.
7.Repeat steps 1 through 6 for other side.
8.Tighten trim hanging screws (#10 x 6.25 shoulder) into holes in cabinets. Place the assembled trim onto fireplace cabinet. Align hanging notches on trim with hanging screws on side of fireplace (see Figure 7). Push trim firmlyintoplace,slidinghangingnotchesover hanging screws.
Set Screws Adjusting Top Trim
Side Trim Plate
Mitered |
Shim |
Slot Edge |
Slot |
|
Figure 6 - Assembling Trim
Trim
Hanging
Screws
Hanging
Notches on Trim
Assembled
Trim
Figure 7 - Attaching Trim to Fireplace
INSTALLATION CLEARANCES
WARNING: Maintain the minimum clearances. If you can, provide greater clearances from floor, ceiling and adjoining wall.
Carefully follow the instructions below. This will ensure safe installation.
Minimum Clearances For Side
Combustible Material, Side Wall and
Ceiling
A. Clearances from the side of the fireplace cabinet to any combustible material and wall should follow diagram in Figure 8.
Example: The face of a mantel, bookshelf, etc. is made of combustible material and protrudes 3 1/2" from the wall. This combus- tible material must be 4" from the side of the fireplace opening (see Figure 8).
B. Clearancesfromthetopofthefireplaceopening to the ceiling should not be less than 42 inches.
MINIMUM CLEARANCE TO
COMBUSTIBLE MATERIALS
Top |
Left and |
Bottom |
|
Right Sides |
and Rear |
|
|
|
42" |
16" |
0" |
Example |
* |
*Minimum 16 inches from Side Wall
Figure 8 - Minimum Clearance for Combustible to Wall
111604-01N |
www.desatech.com |
INSTALLATION
Continued
Conventional Fireplace
Installation
Conventionalinstallationofthisfireplaceinvolves installing fireplace along with the corner, face or cabinetmantelwithhearthbaseaccessoriesagainst awallinyourhome.Followtheinstructionsbelow to install the fireplace in this manner.
Note: The instructions in this section show instal- lation using the cabinet mantel and hearth base accessories. The hearth base accessory shown is optional for this installation. You can install fire- place and cabinet mantel directly on the floor.
1.Assemble cabinet mantel, hearth base and trim accessories. Assembly instructions are included with each accessory.
2.When installing blower, install a properly grounded, 120 volt three-prong electrical out- let at fireplace location if an outlet is not there. Ifpossible,locateoutletsocabinetmantelwill cover it when installed (see Figure 9).
3.Install gas piping to fireplace location. This installation includes an approved flexible gas line(ifallowedbylocalcodes)aftertheequip- ment shutoff valve.The flexible gas line must be the last item installed on the gas piping. See
Installing Gas Piping to Fireplace Location, page 13.
4.Placehearthbaseaccessoryagainstwallatinstal- lation location. Cut an access hole in hearth top to run flexible gas line to fireplace (see Figure 9). Make sure to locate access hole so cabinet mantel will cover it when installed. Note: You can secure base to floor using wood screws. Countersink screw heads and putty over.
5.Route flexible gas line through access hole in hearth base.
6.Centercabinetmantelonhearthbase(seeFigure 10). Make sure mantel is flush against wall.
7.Break off nailing flanges (see Figure 11) with hammer or pliers.
Hearth |
Electrical Outlet |
Gas Line |
Rigid Gas Line |
Access |
|
Base |
|
Hole |
|
|
Figure 9 - Placing Hearth Base
Accessory Against Wall
8.Place cardboard or other protective material on top of hearth base. Carefully set fireplace on protective material, with back of fireplace inside mantel opening.
9.Attach flexible gas line from fireplace gas regulator to gas supply. See Connecting Fireplace to Gas Supply, page 15.
10.Ifblowerisinstalled,routeblowerelectricalcord through access holes in either side of fireplace. Note: Bushingmaybemovedifnecessary.Plug electrical cord into electrical outlet.
11.Carefully insert fireplace into cabinet mantel. Becarefulnottoscratchordamagehearthbase, cabinet mantel or any laminate trim on hearth base. Remove protective material from top of hearth base and from front of fireplace (if any). Note: You can secure fireplace to hearth or floor.Openlowerlouver.Locatescrewholesin bottom of base. Tighten wood screws through these holes and into hearth or floor.
12.Check all gas connections for leaks. See
Checking Gas Connections, page 16.
Cabinet
Mantel
Figure 10 - Installing Cabinet Mantel
Nailing
Flanges
Figure 11 - Location of Nailing Flanges
10 |
www.desatech.com |
111604-01N |
INSTALLATION
Continued
Figure 12 - Inserting Fireplace Into
Cabinet Mantel
Built-In Fireplace
Installation
Built-in installation of this fireplace involves installing fireplace into a framed-in enclosure. This makes the front of fireplace flush with wall. If installing a mantel above the fireplace, you must followtheclearancesshowninFigure18,page13. Followtheinstructionsbelowtoinstallthefireplace in this manner.
|
Actual |
Framing |
Height |
32 3/8" |
33" |
Front Width |
34 5/16" |
35 1/8" |
Depth |
16 11/16" |
17 3/4" |
WARNING:Aqualifiedelectricianmustconnectelectricalwiring to duplex outlet for built-in installation. Follow all local codes.
1.Frame in rough opening. Use dimensions shown in Figure 13 for the rough opening. If installing in a corner, use dimensions shown inFigure14fortheroughopening.Theheight is 33" which is the same as the wall opening above.
2.If using blower, install duplex outlet to the right support bracket in the bottom of firebox (see Figure 15). See Accessories, page 34. If not using blower, go to step 7.
3.Route wires from electrical box through smallestholeinoutercasingusingstrainrelief fitting provided (see Figure 15).
4.Connect wires from the electrical box to duplex outlet. Match wire colors to those indicated on duplex outlet. Be sure to connect ground wire.
5.Install shield to end of right support bracket and behind the firebox wrapper with 2 screws provided (see Figure 16, page 12).
6.Plug blower cord into duplex outlet.
7.Replace bottom of firebox and reconnect remote receiver module to valve.
17 3/4"
33"
35 1/8"
Figure 13 - Rough Opening for Installing in Wall
39 3/8"
27 7/8"
35 1/8" 55 5/8"
Figure 14 - Rough Opening for Installing in Corner
Blower |
Blower |
Cable from |
|
Power Cord |
|||
Electrical Source |
|||
|
|
Duplex |
Outlet |
Support
Bracket
Strain
Relief
Fitting
Screw
Figure 15 - Connecting Duplex Outlet
111604-01N |
www.desatech.com |
11 |