Desa VJM50, VJM42, VJM36 User Manual

0 (0)

RESIDENTIAL AND OUTDOOR WOODBURNING FIREPLACE OWNER’S OPERATION AND INSTALLATION MANUAL

(V)JM36, (V)JM42 AND (V)JM50

WOOD BURNING MASONRY FIREPLACES WITH INSULATION

SAVE THIS BOOK

This book is valuable. In addition to instructing you on how to install and maintain your appliance, it also contains information that will enable you to obtain replacementpartsoraccessoryitemswhenneeded.Keep it with your other important papers.

This fireplace is approved for use as a wood burning fireplace or for use with a vented gas log approved to ANS Z21.60, Z21.84 or RGA 2-72 standards or for use withavent-freegaslogheaterapprovedtoANSZ21.11.2 standard.

This wood burning fireplace complies with UL127- CAN/ULS-S610-M87 standard as a FACTORY BUILT APPLIANCE.

FOR CANADA: The authority having jurisdiction (such as the municipal building department, fire department, etc.) should be contacted before installation to determine the need to obtain a permit.

Save this manual for future reference. For more information, visit www.desatech.com

WARNING: Improper installation, adjustment, alteration, service or maintenance can cause injury, property damage or loss of life. Refer to this manual for assistance or additional information. Consult a qualified installer or local distributor.

TABLE OF CONTENTS

Safety Information ...............................................

2

Brick Installation ................................................

13

Specifications ......................................................

5

Glass Door Installation ......................................

20

Fireplace Installation ...........................................

6

Operation and Maintenance Guidelines............

21

Venting Installation ..............................................

8

Technical Service ..............................................

22

Optional Gas Line Installation ...........................

12

Replacement and Accessory Parts ...................

23

SAFETY INFORMATION

IMPORTANT: Check local codes before installing this fireplace.

Before beginning the installation of the fireplace, read these instructions through completely.

This DESA fireplace and its components are safewheninstalledaccordingtothisinstallation manual. Unless you use DESA components, which have been designed and tested for the fireplace system, you may cause a fire hazard.

The DESA warranty will be voided by and DESA disclaims any responsibility for the following actions.

a.Modification of the fireplace, components, doors, air inlet system and damper control.

b.Use of any component part not manufacturedorapprovedbyDESAincombination with a DESA fireplace system.

Proper installation is the most important step in ensuring safe and continuous operation of the fireplace. Consult the local building codes as to the particular requirements concerned with the installation of all factory built fireplaces.

WARNING: Do not install a

fireplaceinsertinthisboxunless themanufacturer'sinstructions with the insert specifically state thisfireplacehasbeentestedfor use with this insert.

FOR YOUR SAFETY

Do not store or use gasoline oranyotherflammablevapors orliquidsinthevicinityofthis or any other appliance.

Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.

Do not place clothing or other flammablematerialsonornear the appliance.

Never leave children unattended when a fire is burning in the fireplace.

WARNING: Use solid wood or processed solid fuel firelogs only. Whenprocessedwoodfuel firelogsareused,donotpokeor stir the logs while they are burning. Use only fire logs that have beenevaluatedfortheapplication in fireplace and refer to fire log warnings and caution markings on packaging prior to use.

Thisfireplaceisnotintendedtobe usedasasubstituteforafurnace to heat an entire home. Use for supplemental heat only.

2

www.desatech.com

117541-01A

SPECIFICATIONS Continued

MODELS VJM36 AND JM36

67.000

58.000

49.000

8.000

ROUND TOP TERMINATION

1" CHIMNEY AIRSPACE CLEARANCE TO COMBUSTIBLE MATERIAL

11/2" AIR SPACE

BACK AND SIDES

OUTSIDE AIR

GAS LINE

KNOCKOUTS

0" TO

12" EACH SIDE

BOTTOM

 

 

12.000

 

26.625

 

30.000

SQUARE CHASE-TOP

TERMINATION

NO COMBUSTIBLE

MATERIAL ON FACE

COMBUSTIBLE

WALL BOARD

MINIMUM 12" TO

PERPENDICULAR

SIDEWALL

HEARTH EXTENSION 60" X 20"

29.00

7.500

22.000

0.625

45.000

 

 

 

36.000

 

 

45.000

 

 

1.000

 

AIR KIT

 

 

21.500

LEFT SIDE

KNOCK OUT

 

GAS LINE

 

 

 

 

KNOCK OUTS

 

 

3.50

20.000

10.50

9.50

 

 

 

7.0

 

 

10.75

 

 

15.375

 

36.000

 

 

117541-01A

www.desatech.com

3

Desa VJM50, VJM42, VJM36 User Manual

SPECIFICATIONS Continued

MODELS VJM42 AND JM42

ROUND TOP TERMINATION SQUARE CHASE-TOP

TERMINATION

2" CHIMNEY AIRSPACE CLEARANCE TO COMBUSTIBLE MATERIAL

 

 

NO COMBUSTIBLE

 

 

MATERIAL ON FACE

 

 

COMBUSTIBLE

 

 

WALL BOARD

 

11/2" AIR SPACE

 

 

BACK AND SIDES

 

 

OUTSIDE AIR

 

 

 

MINIMUM 18" TO

 

 

PERPENDICULAR

 

GAS LINE

SIDEWALL

 

 

 

KNOCKOUTS

HEARTH EXTENSION

 

 

 

 

66" X 20"

 

0" TO

12" EACH SIDE

 

BOTTOM

 

 

 

 

12.000

 

 

30.500

 

 

11.000

67.000

 

21.250

58.000

 

 

 

49.000

 

30.000

28.500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.625

51.000

 

 

42.000

 

 

 

8.000

 

 

 

 

51.000

 

 

 

 

 

 

 

 

 

 

1.000

 

 

 

AIR KIT

 

 

 

 

 

 

24.250

 

 

LEFT SIDE

KNOCK OUT

 

 

 

 

GAS LINE

 

 

 

 

 

 

 

 

 

 

KNOCK OUTS

 

 

 

 

 

3.50

 

 

23.500

10.50

 

9.50

 

 

 

 

 

 

 

 

 

8.50

 

 

 

 

 

13.00

 

 

41.250

 

 

17.00

 

 

 

 

 

 

4

www.desatech.com

117541-01A

SPECIFICATIONS

MODELS VJM50 AND JM50

67.000

58.000

49.000

8.000

ROUND TOP TERMINATION

SQUARE CHASE-TOP

 

TERMINATION

2" CHIMNEY AIRSPACE CLEARANCE TO COMBUSTIBLE MATERIAL

NO COMBUSTIBLE

MATERIAL ON FACE

COMBUSTIBLE

WALL BOARD

11/2" AIR SPACE BACK AND SIDES

OUTSIDE AIR

 

MINIMUM 18" TO

 

PERPENDICULAR

 

SIDEWALL

GAS LINE

 

KNOCKOUTS

HEARTH EXTENSION

 

0" TO

74" X 20"

12" EACH SIDE

BOTTOM

12.000

38.500

11.000

21.250

28.500

 

 

30.000

 

 

0.625

59.000

 

50.000

 

 

 

59.000

 

 

1.000

 

 

 

 

AIR KIT

 

LEFT SIDE

KNOCK OUT

32.750

 

 

GAS LINE

 

 

 

 

KNOCK OUTS

 

 

3.50

10.50

 

9.50

23.500

 

 

 

8.50

 

 

13.00

 

50.000

17.00

 

 

 

117541-01A

www.desatech.com

5

FIREPLACE INSTALLATION

SELECTING LOCATION

To determine the safest and most efficient location for the fireplace, you must take into consideration the following guidelines:

1.The location must allow for proper clearances (see Figures 1 and 2).

2.Consider a location where the fireplace will not be affected by drafts, air conditioning ducts, windows or doors.

3.A location that avoids the cutting of joists or roof rafters will make installation easier.

4.Anoutsideairkitisavailablewiththisfireplace (see Optional Outside Air Kit on page 8).

MINIMUM CLEARANCE TO

COMBUSTIBLES

Back and sides of fireplace

1 1/2" minimum*

Front of fireplace

48" minimum

Floor**

0" minimum

Perpendicular wall to opening

18" minimum

 

12" min. JM36

Top spacers

0" minimum

Mantel clearances

see Mantels, page 7

Chimney outer pipe surface

2" minimum

 

1" min. JM36

* Not required at nailing flanges ** See step 2 of Framing

WARNING: Do not pack requiredairspaceswithinsulation or other materials.

Minimum/Maximum Chimney Height for Residential Installation

The minimum height of the chimney, measured from the base of the fireplace to the flue gas outlet of the termination, is 16 feet for straight flue or a flue with one elbow set. The maximum distance between elbows is 6 feet. For systems with two elbow sets, the minimum height is 22 feet. The maximum height of any system is 50 feet. This measurement includes the fireplace, chimney sections and the height of the termination assembly at the level of the flue gas outlet (see Figure 15, page 11).

Minimum/Maximum Chimney Height for Outdoor Installation

The minimum height of the chimney, measured from the base of the fireplace to the flue gas outlet of the termination, is 9.5 feet (minimum of 4 feet of chimney pipe sections required for outdoor installation).

FRAMING

1.Frame the opening for the fireplace using the dimensions shown in Figures 1 and 2.

2.If the fireplace is to be installed directly on carpeting, tile (other than ceramic) or any combustible material other than wood flooring, the fireplace must be installed upon a metal or wood panel extending the full width and depth of the fireplace.

3.Set the fireplace directly in front of this opening and slide the unit back until the nailing flanges touch the side framing.

4.Check the level of the fireplace and shim with sheet metal if necessary.

5.Beforesecuringfireplacetopreparedframing, theemberprotector(provided)mustbeplaced between the hearth extension (not supplied) and under the bottom front edge of the fireplacetoprotectagainstglowingembersfalling through. If the fireplace is to be installed on a raised platform, a Z-type ember protector (not supplied) must be fabricated to fit your requiredplatformheight.Theemberprotector should extend under the fireplace a minimum

of 1 1/2". The ember protector should be made ofgalvanizedsheetmetal(28gaugeminimum to prevent corrosion.

6.Using screws or nails, secure the fireplace to the framing through flanges located on the sides of the fireplace.

59.250 (50")

51.250 (42") 45.250 (36")

67.125

58.125

30.125 28.250 (36")

Figure 1 - Framing Dimensions

61.000 (36")

65.000 (42")

71.000 (50")

MAINTAIN 1 1/2"

CLEARANCE AT

SIDES AND BACK

OF FIREPLACE

1 1/2" CLEARANCE

NOT REQUIRED AT

NAILING FLANGES

86.500 (36")

92.000 (42")

100.000 (50")

Figure 2 - Corner Installation

6

www.desatech.com

117541-01A

FIREPLACE INSTALLATION

Continued

Note: For outdoor installations, the fireplace enclosuremustallowforadequatedrainageandfresh air ventilation. It is recommended that a sealed, corrosion resistant catch pan with provision for drainage be installed under the fireplace within the fireplace enclosure.

HEARTH EXTENSION

A hearth extension projecting a minimum of 20" in front of and a minimum of 12" beyond each side of the fireplace opening is required to protect combustible floor construction in front of the fireplace.Fabricateahearthextensionusingamaterial which meets the following specifications: a layer of noncombustible, inorganic material having a thermal conductivity of K=0.84 BTU IN/FT, HR. F (or less) at 1" thick. For example, if the material selected has a K factor of 0.25, such as glass fiber, the following formula would apply:

0.25 x 1.0" = 0.30" thickness required

0.84

Thermal conductivity "K" of materials can be obtained from the manufacturer or supplier of the noncombustible material. If the hearth extension istobecovered,usenoncombustiblematerialsuch as tile, slate, brick, concrete, metal, glass, marble, stone, etc. Provide a means to prevent the hearth extension from shifting and seal gap between the fireplace frame and hearth extension with a noncombustible material (see Figure 3).

MANTELS

 

 

 

A mantel may be installed if desired (see Figure

4).Woodwork such as wood trims, mantels or any

other combustible material projecting from the

frontface mustnotbe placedwithin 12"(JM36)or

18" (JM42/50) of the fireplace opening. Combus-

tiblematerialsabove12"(JM36)or18"(JM42/50)

and projecting more than 1 1/2" from the fireplace

must not be placed less than 15" (JM36) or 21"

(JM42/50) from the top opening of the fireplace

(NFPA STD 211, Sec. 7-3.3.3).

 

Mantels or any other combustible material also

may come up to the side edge of the black metal

face of the fireplace just as long as the projection

from the front face fall within the limit shown in

Figure 4.

 

 

 

 

 

12

 

/4" Ref.

Combustible

 

1

Material

 

 

 

 

Safe

6"

 

 

 

Zone for

Ref.

33°

 

Projection of

 

 

Combustible

 

 

 

 

 

3" Nom.

Materials

 

 

15" Min.

1

/2" Max.

 

(JM36)

 

 

1

 

 

 

21" Min.

 

 

 

 

(JM42/50)

 

 

 

 

12" Min. (JM36)

Upper

18" Min. (JM42/50)

Section of

 

 

 

 

Fireplace

WARNING:Hearthextension

is to be installed only as shown

in Figure 3.

Seal Gap

Fireplace Front

Ember Protector

Fireplace Front

Raised Hearth

Ember Protector

Fireplace Front

Elevated

Hearth

Extension

Seal Gap

Ember Protector

Fireplace

 

Opening

 

Top View of Fireplace

 

7.75" (JM36)

FIREBOX

11.5" (JM42/50)

 

 

3" Max.

SAFE ZONE

4.5"

33°

 

Min. to

 

Perpendicular

 

Side Wall

 

12" - JM36

 

18" - JM42/50

 

Figure 4 - Mantel Clearances to

Combustible Material

Figure 3 - Hearth Extension

117541-01A

www.desatech.com

7

STL-12D

VENTING INSTALLATION

OPTIONAL OUTSIDE AIR KIT (MODEL AK4/AK4F)

The installation of an outside air kit should be performed during the rough framing of the fireplace due to the nature of it's location. Outside combustion air is accessed through a vented crawl space (AK4F) or through a sidewall (AK4).

CAUTION: Combustion air inlet ducts shall not terminate in attic space.

Secure to Collars with Metal Tape, Screws or Straps (Min. of 1/4" x 20" in size)

Air Inlet

Location

Must Allow

For Bushes

or Snow

Vented Crawl Space

(Check Local Codes

Before Installing in a

Vented Crawl Space)

Air Inlet Eyebrow

Vent Hood Required for Wall Installation

Figure 5 - Outside Air Kit

CHIMNEY PIPE

The DESAchimney system consists of 12, 18, 24, 36 and 48" snap-lock, double-wall pipe segments, planned for maximum adaptability to individual site requirements. Actual lengths gained after fitting overlaps must be taken into consideration (lineal gain) and are given in the lineal gain chart (see Figure 6). Lineal Gain is the actual measurable length of a part after two or more parts are connected. For Canada, use chimney parts designated "HT".

WARNING: The opening in the collar around the chimney at the top of the fireplace must not be obstructed.Neveruseblowninsulation to fill the chimney enclosure.

LINEAL GAIN

PART NO.

DESCRIPTION

GAIN (IN)

Georgian

Fireplace

66 1/2"

12-12DM

Pipe Section

10 5/8"

12-12HT

 

 

18-12DM

Pipe Section

16 5/8"

18-12HT

 

 

24-12DM

Pipe Section

23 5/8"

24-12HT

 

 

36-12DM

Pipe Section

34 5/8"

36-12HT

 

 

48-12DM

Pipe Section

46 5/8"

48-12HT

 

 

RLT-12D

Round Termination

7 3/4"*

RLT-12HT

 

 

Square Chase-Top 7" to 15"* with Slip Section

* The lineal gain for the terminations is measured to the flue gas outlet height.

12" Galvanized

 

 

 

 

 

 

 

 

 

Outer Pipe

 

 

 

 

 

 

 

12

3

/8"

 

 

 

 

 

 

Hemmed

 

 

 

 

 

 

 

 

End

Stainless

 

Inner Pipe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 6 - Lineal Gain

 

ASSEMBLY AND INSTALLATION OF

DOUBLE WALL CHIMNEY SYSTEM

Each double wall chimney section consists of a

galvanized outer pipe, a stainless steel inner flue

pipeandawirespacer.Thepipesectionsmustbeas-

sembled independently as the chimney is installed.

Whenconnectingchimneydirectlytothefireplace,

theinnerfluepipesectionmustbeinstalledfirstwith

the lanced side up. The outer pipe section can then

be installed over 5 the flue pipe section with the

hemmed end up. Press down on each pipe section

untilthelancessecurelyengagethehemonthefire-

placestarter.Thewirewillassuretheproperspacing

between the inner and outer pipe sections.

Continuetoassemblechimneysectionsasoutlined

above, making sure that both the inner and outer

pipe sections are locked together. When install-

ing double wall snap-lock chimney together, it is

important to assure the joint between the chimney

sections is locked. Check by pulling chimney

upward after locking. The chimney will not come

apart if properly locked. It is not necessary to add

screws to keep the chimney together (exception

- see Figure 9, page 10).

 

8

www.desatech.com

117541-01A