Desa VG36H, VG36R, VG36, VG36HR User Manual

0 (0)

36" Wood Burning Masonry Fireplace

OWNER’S OPERATION AND INSTALLATION MANUAL

(V)G36 - Smooth Face with Insulation

(V)G36R - Smooth Face with Insulation and Bottom Door Rail (V)G36H - Smooth Face with Insulation and Herringbone Refractory (V)G36HR - Smooth Face with Insulation, Bottom Door Rail

and Herringbone Refractory

SAVE THIS BOOK

This book is valuable. In addition to instructing you on how to install and maintain your appliance, it also contains information that will enable you to obtain replacement parts or accessory items when needed. Keep it with your other important papers.

This fireplace is approved for use as a wood burning fireplace or for use with a vented gas log approved to

ANS Z21.60, Z21.84 or RGA 2-72 standards or for use with a vent-free gas log heater approved to ANS Z21.11.2 standard.

This wood burning fireplace complies with UL127- CAN/ULS-S610-M87 standard as a FACTORY BUILT APPLIANCE.

FOR CANADA: The authority having jurisdiction (such as the municipal building department, fire department, etc.) should be contacted before installation to determine the need to obtain a permit.

Save this manual for future reference.

For more information, visit www.desatech.com

WARNING: Improper installation, adjustment, alteration, service or maintenance can cause injury, property damage or loss of life. Refer to this manual for assistance or additional information. Consult a qualified installer or local distributor.

Table of Contents

Safety Information................................................

2

Glass Door Installation........................................

11

Specifications.......................................................

3

Operation and Maintenance Guidelines.............

12

Fireplace Installation............................................

4

Technical Service...............................................

14

Venting Installation...............................................

6

Replacement Parts.............................................

14

Optional Gas Line Installation............................

10

Accessories........................................................

15

Safety Information

IMPORTANT: Check local codes before installing this fireplace.

Before beginning the installation of the fireplace, read these instructions through completely.

This DESA fireplace and its components are safewheninstalledaccordingtothisinstallation manual. Unless you use DESA components, which have been designed and tested for the fireplace system, you may cause a fire hazard.

The DESA warranty will be voided by and DESA disclaims any responsibility for the following actions.

a.Modification of the fireplace, components, doors, air inlet system and damper control.

b.Use of any component part not manufac- turedorapprovedbyDESAincombination with a DESA fireplace system.

Proper installation is the most important step in ensuring safe and continuous operation of the fireplace. Consult the local building codes as to the particular requirements concerned with the installation of all factory built fireplaces.

WARNING: Do not install a fireplaceinsertinthisfireboxunless the manufacturer's instructions with the insert specifically state this fireplace has been tested for use with the insert.

Thisfireplaceisnotintendedtobe used as a substitute for a furnace to heat an entire home. Use for supplemental heat only.

FOR YOUR SAFETY

Do not store or use gasoline oranyotherflammablevapors or liquids in the vicinity of this or any other appliance.

Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.

Do not place clothing or other flammablematerialsonornear the appliance.

Never leave children unattended when a fire is burning in the fireplace.

WARNING: Use solid wood or processed solid fuel firelogs only. When processed wood fuel fire logs are used, do not poke or stir the logs while they are burning. Use only fire logs that have been evaluated for the application in fireplace and refer to fire log warnings and caution markings on packaging prior to use.

WARNING: Always leave glass doors fully opened or fully closed when operating fireplace.

 

www.desatech.com

116010-01C

Desa VG36H, VG36R, VG36, VG36HR User Manual

Specifications

ROUND TOP TERMINATION SQUARE CHASE-TOP

TERMINATION

1" CHIMNEY AIRSPACE CLEARANCE TO COMBUSTIBLE MATERIAL

 

 

NO COMBUSTIBLE

 

 

MATERIAL ON FACE

 

 

COMBUSTIBLE

 

 

WALL BOARD

11/2" AIR SPACE

 

 

BACK AND SIDES

 

 

OUTSIDE AIR

 

 

 

 

MINIMUM 12" TO

 

 

PERPENDICULAR

 

 

SIDEWALL

GAS LINE

 

HEARTH EXTENSION

KNOCKOUTS

 

 

74" X 20"

 

 

0" TO

12" EACH SIDE

 

BOTTOM

 

 

 

12"

38.5"

 

 

7.5"

67"

 

22"

58"

26.625"

 

 

 

 

 

49"

30"

 

 

 

0.625"

45"

 

 

 

 

8"

36"

 

 

45"

 

 

 

 

 

 

1"

 

AIR KIT

 

 

 

 

21.5"

LEFT SIDE

KNOCK OUT

 

 

GAS LINE

 

 

 

 

 

 

KNOCK OUTS

 

 

 

3.5"

 

10.5"

 

9.5"

 

20"

 

 

 

 

7"

 

 

 

10.75"

 

 

 

15.375"

 

 

36"

 

 

116010-01C

www.desatech.com

Fireplace Installation

selecting location

To determine the safest and most efficient location for the fireplace, you must take into consideration the following guidelines:

1.The location must allow for proper clearances (see Figures 1 and 2).

2.Consider a location where the fireplace will not be affected by drafts, air conditioning ducts, windows or doors.

3.A location that avoids the cutting of joists or roof rafters will make installation easier.

4.Anoutsideairkitisavailablewiththisfireplace

(see Optional Outside Air Kit on page 6).

Minimum clearance to combustibles

Back and sides of fireplace

1 1/2" min.*

Front of fireplace

48" min.

Floor**

0" min.

Perpendicular wall to opening

12" min.

Top spacers

0" min.

Mantel clearance

see Mantels, page 5

Chimney outer pipe surface

1" min.

* Not required at nailing flanges

 

** See step 2 of Framing

 

WARNING: Do not pack required air spaces with insulation or other materials.

Minimum/Maximum Chimney Height

The minimum height of the chimney, measured from the base of the fireplace to the flue gas outlet of the termination, is 16 feet for straight flue or a fluewithoneelbowset.Themaximumdistancebe- tweenelbowsis6feet.Forsystemswithtwoelbow sets,theminimumheightis22feet.Themaximum height of any system is 50 feet.This measurement includes the fireplace, chimney sections and the height of the termination assembly at the level of the flue gas outlet (see Figure 15, page 9).

Framing

1.Frame the opening for the fireplace using the dimensions shown in Figures 1 and 2.

2.If the fireplace is to be installed directly on carpeting, tile (other than ceramic) or any combustible material other than wood floor- ing, the fireplace must be installed upon a metal or wood panel extending the full width and depth of the fireplace.

3.Set the fireplace directly in front of this open- ing and slide the unit back until the nailing flanges touch the side framing.

4.Check the level of the fireplace and shim with sheet metal if necessary.

5.Beforesecuringfireplacetopreparedframing, theemberprotector(provided)mustbeplaced between the hearth extension (not supplied) and under the bottom front edge of the fire- placetoprotectagainstglowingembersfalling through. If the fireplace is to be installed on a raised platform, a Z-type ember protector (not supplied) must be fabricated to fit your requiredplatformheight.Theemberprotector should extend under the fireplace a minimum of 1 1/2". The ember protector should be made ofgalvanizedsheetmetal(28gaugeminimum to prevent corrosion.

6.Using screws or nails, secure the fireplace to the framing through flanges located on the sides of the fireplace.

 

67.125"

 

58.125"

45.25"

28.25"

 

Figure 1 - Framing Dimensions

 

Maintain 11/2"

 

Clearance at Sides

61"

and Back of Fireplace

11/2" Clearance

 

 

Not Required at

 

Nailing Flanges

86.5"

Figure 2 - Corner Installation

www.desatech.com

116010-01C

Fireplace Installation

Continued

Hearth Extension

A hearth extension projecting a minimum of 20" in front of and a minimum of 12" beyond each side of the fireplace opening is required to protect combustible floor construction in front of the fire- place.Fabricateahearthextensionusingamaterial which meets the following specifications: a layer of noncombustible, inorganic material having a thermal conductivity of K=0.84 BTU IN/FT, HR. F (or less) at 1" thick. For example, if the material selected has a K factor of 0.25, such as glass fiber, the following formula would apply:

0.25 x 1.0" = 0.30" thickness required

0.84

Thermal conductivity "K" of materials can be obtained from the manufacturer or supplier of the noncombustible material. If the hearth extension istobecovered,usenoncombustiblematerialsuch as tile, slate, brick, concrete, metal, glass, marble, stone, etc. Provide a means to prevent the hearth extension from shifting and seal gap between the fireplace frame and hearth extension with a non- combustible material (see Figure 3).

WARNING:Hearthextension

is to be installed only as shown

in Figure 3.

Seal Gap

Fireplace Front

Mantels

Amantel may be installed if desired (see Figure 4). Woodworksuchaswoodtrims,mantelsoranyother combustible material projecting from the front face mustnotbeplacedwithin12"ofthefireplaceopen- ing.Combustiblematerialsabove12"andprojecting morethan11/2"fromthefireplacemustnotbeplaced less than 15" from the top opening of the fireplace (NFPASTD 211, Sec. 7-3.3.3).

Mantels or any other combustible material also may come up to the side edge of the black metal face of the fireplace just as long as the projection from the front face fall within the limit shown in Figure 4.

 

 

Combustible

 

12 1/4" Ref.

Material

 

 

Safe

6"

 

Zone for

Ref.

33°

Projection of

 

Combustible

 

 

 

3" Nom.

Materials

 

 

11/2" Max.

15" Min.

12" Min.

Upper

 

Section of

Fireplace

Fireplace

Opening

Ember Protector

Fireplace Front

Raised Hearth

Ember Protector

Fireplace Front

Elevated

Ember Protector

Top View of Fireplace

 

 

FIREBOX

 

7.75"

 

 

 

3" Max.

Hearth

SAFE ZONE

4.5"

 

Extension

33°

 

Seal Gap

Min. to

Combustible

 

 

Perpendicular

 

Material Must

 

Side Wall

 

Not Overlap

 

12"

 

Front Face

 

 

Figure 3 - Hearth Extension

Figure 4 - Mantel Clearances to

Combustible Material

116010-01C

www.desatech.com