36" Wood Burning Masonry Fireplace
OWNER’S OPERATION AND INSTALLATION MANUAL
(V)G36 - Smooth Face with Insulation
(V)G36R - Smooth Face with Insulation and Bottom Door Rail (V)G36H - Smooth Face with Insulation and Herringbone Refractory (V)G36HR - Smooth Face with Insulation, Bottom Door Rail
and Herringbone Refractory
SAVE THIS BOOK
This book is valuable. In addition to instructing you on how to install and maintain your appliance, it also contains information that will enable you to obtain replacement parts or accessory items when needed. Keep it with your other important papers.
This fireplace is approved for use as a wood burning fireplace or for use with a vented gas log approved to
ANS Z21.60, Z21.84 or RGA 2-72 standards or for use with a vent-free gas log heater approved to ANS Z21.11.2 standard.
This wood burning fireplace complies with UL127- CAN/ULS-S610-M87 standard as a FACTORY BUILT APPLIANCE.
FOR CANADA: The authority having jurisdiction (such as the municipal building department, fire department, etc.) should be contacted before installation to determine the need to obtain a permit.
Save this manual for future reference.
For more information, visit www.desatech.com
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause injury, property damage or loss of life. Refer to this manual for assistance or additional information. Consult a qualified installer or local distributor.
Table of Contents
Safety Information................................................ |
2 |
Glass Door Installation........................................ |
11 |
Specifications....................................................... |
3 |
Operation and Maintenance Guidelines............. |
12 |
Fireplace Installation............................................ |
4 |
Technical Service............................................... |
14 |
Venting Installation............................................... |
6 |
Replacement Parts............................................. |
14 |
Optional Gas Line Installation............................ |
10 |
Accessories........................................................ |
15 |
IMPORTANT: Check local codes before installing this fireplace.
Before beginning the installation of the fireplace, read these instructions through completely.
•This DESA fireplace and its components are safewheninstalledaccordingtothisinstallation manual. Unless you use DESA components, which have been designed and tested for the fireplace system, you may cause a fire hazard.
•The DESA warranty will be voided by and DESA disclaims any responsibility for the following actions.
a.Modification of the fireplace, components, doors, air inlet system and damper control.
b.Use of any component part not manufac- turedorapprovedbyDESAincombination with a DESA fireplace system.
Proper installation is the most important step in ensuring safe and continuous operation of the fireplace. Consult the local building codes as to the particular requirements concerned with the installation of all factory built fireplaces.
WARNING: Do not install a fireplaceinsertinthisfireboxunless the manufacturer's instructions with the insert specifically state this fireplace has been tested for use with the insert.
Thisfireplaceisnotintendedtobe used as a substitute for a furnace to heat an entire home. Use for supplemental heat only.
FOR YOUR SAFETY
•Do not store or use gasoline oranyotherflammablevapors or liquids in the vicinity of this or any other appliance.
•Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.
•Do not place clothing or other flammablematerialsonornear the appliance.
•Never leave children unattended when a fire is burning in the fireplace.
WARNING: Use solid wood or processed solid fuel firelogs only. When processed wood fuel fire logs are used, do not poke or stir the logs while they are burning. Use only fire logs that have been evaluated for the application in fireplace and refer to fire log warnings and caution markings on packaging prior to use.
WARNING: Always leave glass doors fully opened or fully closed when operating fireplace.
|
www.desatech.com |
116010-01C |
ROUND TOP TERMINATION SQUARE CHASE-TOP
TERMINATION
1" CHIMNEY AIRSPACE CLEARANCE TO COMBUSTIBLE MATERIAL
|
|
NO COMBUSTIBLE |
|
|
MATERIAL ON FACE |
|
|
COMBUSTIBLE |
|
|
WALL BOARD |
11/2" AIR SPACE |
|
|
BACK AND SIDES |
|
|
OUTSIDE AIR |
|
|
|
|
MINIMUM 12" TO |
|
|
PERPENDICULAR |
|
|
SIDEWALL |
GAS LINE |
|
HEARTH EXTENSION |
KNOCKOUTS |
|
|
|
74" X 20" |
|
|
|
|
0" TO |
12" EACH SIDE |
|
BOTTOM |
|
|
|
12" |
38.5" |
|
|
7.5" |
67" |
|
22" |
58" |
26.625" |
|
|
|
|
|
|
49" |
30" |
|
|
|
0.625" |
45" |
|
|
|
|
|
8" |
36" |
|
|
45" |
|
|
|
|
|
|
|
|
1" |
|
AIR KIT |
|
|
|
|
|
21.5" |
LEFT SIDE |
KNOCK OUT |
|
|
GAS LINE |
|
|
|
|
|
|
|
|
KNOCK OUTS |
|
|
|
3.5" |
|
10.5" |
|
9.5" |
|
20" |
|
|
|
|
7" |
|
|
|
10.75" |
|
|
|
15.375" |
|
|
36" |
|
|
116010-01C |
www.desatech.com |
selecting location
To determine the safest and most efficient location for the fireplace, you must take into consideration the following guidelines:
1.The location must allow for proper clearances (see Figures 1 and 2).
2.Consider a location where the fireplace will not be affected by drafts, air conditioning ducts, windows or doors.
3.A location that avoids the cutting of joists or roof rafters will make installation easier.
4.Anoutsideairkitisavailablewiththisfireplace
(see Optional Outside Air Kit on page 6).
Minimum clearance to combustibles
Back and sides of fireplace |
1 1/2" min.* |
Front of fireplace |
48" min. |
Floor** |
0" min. |
Perpendicular wall to opening |
12" min. |
Top spacers |
0" min. |
Mantel clearance |
see Mantels, page 5 |
Chimney outer pipe surface |
1" min. |
* Not required at nailing flanges |
|
** See step 2 of Framing |
|
WARNING: Do not pack required air spaces with insulation or other materials.
Minimum/Maximum Chimney Height
The minimum height of the chimney, measured from the base of the fireplace to the flue gas outlet of the termination, is 16 feet for straight flue or a fluewithoneelbowset.Themaximumdistancebe- tweenelbowsis6feet.Forsystemswithtwoelbow sets,theminimumheightis22feet.Themaximum height of any system is 50 feet.This measurement includes the fireplace, chimney sections and the height of the termination assembly at the level of the flue gas outlet (see Figure 15, page 9).
Framing
1.Frame the opening for the fireplace using the dimensions shown in Figures 1 and 2.
2.If the fireplace is to be installed directly on carpeting, tile (other than ceramic) or any combustible material other than wood floor- ing, the fireplace must be installed upon a metal or wood panel extending the full width and depth of the fireplace.
3.Set the fireplace directly in front of this open- ing and slide the unit back until the nailing flanges touch the side framing.
4.Check the level of the fireplace and shim with sheet metal if necessary.
5.Beforesecuringfireplacetopreparedframing, theemberprotector(provided)mustbeplaced between the hearth extension (not supplied) and under the bottom front edge of the fire- placetoprotectagainstglowingembersfalling through. If the fireplace is to be installed on a raised platform, a Z-type ember protector (not supplied) must be fabricated to fit your requiredplatformheight.Theemberprotector should extend under the fireplace a minimum of 1 1/2". The ember protector should be made ofgalvanizedsheetmetal(28gaugeminimum to prevent corrosion.
6.Using screws or nails, secure the fireplace to the framing through flanges located on the sides of the fireplace.
|
67.125" |
|
58.125" |
45.25" |
28.25" |
|
Figure 1 - Framing Dimensions
|
Maintain 11/2" |
|
|
Clearance at Sides |
|
61" |
and Back of Fireplace |
|
11/2" Clearance |
||
|
||
|
Not Required at |
|
|
Nailing Flanges |
86.5"
Figure 2 - Corner Installation
www.desatech.com |
116010-01C |
Fireplace Installation
Continued
Hearth Extension
A hearth extension projecting a minimum of 20" in front of and a minimum of 12" beyond each side of the fireplace opening is required to protect combustible floor construction in front of the fire- place.Fabricateahearthextensionusingamaterial which meets the following specifications: a layer of noncombustible, inorganic material having a thermal conductivity of K=0.84 BTU IN/FT, HR. F (or less) at 1" thick. For example, if the material selected has a K factor of 0.25, such as glass fiber, the following formula would apply:
0.25 x 1.0" = 0.30" thickness required
0.84
Thermal conductivity "K" of materials can be obtained from the manufacturer or supplier of the noncombustible material. If the hearth extension istobecovered,usenoncombustiblematerialsuch as tile, slate, brick, concrete, metal, glass, marble, stone, etc. Provide a means to prevent the hearth extension from shifting and seal gap between the fireplace frame and hearth extension with a non- combustible material (see Figure 3).
WARNING:Hearthextension
is to be installed only as shown
in Figure 3.
Seal Gap
Fireplace Front
Mantels
Amantel may be installed if desired (see Figure 4). Woodworksuchaswoodtrims,mantelsoranyother combustible material projecting from the front face mustnotbeplacedwithin12"ofthefireplaceopen- ing.Combustiblematerialsabove12"andprojecting morethan11/2"fromthefireplacemustnotbeplaced less than 15" from the top opening of the fireplace (NFPASTD 211, Sec. 7-3.3.3).
Mantels or any other combustible material also may come up to the side edge of the black metal face of the fireplace just as long as the projection from the front face fall within the limit shown in Figure 4.
|
|
Combustible |
|
12 1/4" Ref. |
Material |
|
|
Safe |
6" |
|
Zone for |
Ref. |
33° |
Projection of |
|
Combustible |
|
|
|
|
|
3" Nom. |
Materials |
|
|
11/2" Max.
15" Min.
12" Min. |
Upper |
|
Section of
Fireplace
Fireplace
Opening
Ember Protector
Fireplace Front
Raised Hearth
Ember Protector
Fireplace Front
Elevated
Ember Protector
Top View of Fireplace
|
|
FIREBOX |
|
|
7.75" |
|
|
|
|
3" Max. |
|
Hearth |
SAFE ZONE |
4.5" |
|
|
|||
Extension |
33° |
||
|
|||
Seal Gap |
Min. to |
Combustible |
|
|
|||
|
Perpendicular |
||
|
Material Must |
||
|
Side Wall |
||
|
Not Overlap |
||
|
12" |
||
|
Front Face |
||
|
|
Figure 3 - Hearth Extension
Figure 4 - Mantel Clearances to
Combustible Material
116010-01C |
www.desatech.com |