UNVENTED (VENT-FREE) GAS COMPACT CLASSIC HEARTH®
DUAL BURNER FIREPLACE
OWNER’S OPERATION AND INSTALLATION MANUAL
Shown with Optional Cabinet Mantel/Hearth Base Accessory
THERMOSTAT MODELS
VDCFTNA AND VDCFTPA
REMOTE-READY MODELS
VDCFRPA AND VDCFRNA
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
—Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
—WHAT TO DO IF YOU SMELL GAS
•Do not try to light any appliance.
•Do not touch any electrical switch; do not use any phone in your building.
•Immediatelycallyourgassupplierfromaneighbor’s phone. Follow the gas supplier’s instructions.
•If you cannot reach your gas supplier, call the fire department.
—Installationandservicemustbeperformedbyaqualified installer, service agency or the gas supplier.
Save this manual for future reference. For more information, visit www.desatech.com
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause injury or propertydamage.Refertothismanualforcorrectinstallation and operational procedures. For assistance or additional information consult a qualified installer, service agency or the gas supplier.
WARNING: This is an unvented gas-fired heater. It uses air (oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must beprovided.RefertoAirforCombustionandVentilation section on page 6 of this manual.
This appliance may be installed in an aftermarket,* permanently located, manufactured (mobile) home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
State of Massachusetts: The installation must be made by a licensed plumber or gas fitter in the Commonwealth of Massachusetts.
Sellers of unvented propane or natural gas-fired supplemental room heaters shall provide to each purchaser a copy of 527 CMR 30 upon sale of the unit.
Vent-free gas products are prohibited for bedroom and bathroom installation in the Commonwealth of Massachusetts.
TABLE OF CONTENTS
Safety Information ............................................... |
3 |
Product Identification........................................... |
5 |
Optional Remote Control Accessories................. |
5 |
Local Codes ........................................................ |
5 |
Product Features................................................. |
5 |
Unpacking ........................................................... |
5 |
Hood Assembly ................................................... |
6 |
Air for Combustion and Ventilation...................... |
6 |
Installation ........................................................... |
9 |
Operating Fireplace........................................... |
21 |
Inspecting Burners ............................................ |
27 |
Cleaning and Maintenance |
................................ |
27 |
Wiring Diagram.................................................. |
|
28 |
Troubleshooting................................................. |
|
29 |
Specifications .................................................... |
|
33 |
Illustrated Parts Breakdown .......and Parts List |
34 |
|
Accessories....................................................... |
|
40 |
Replacement Parts............................................ |
|
42 |
Service Hints ..................................................... |
|
42 |
Technical Service .............................................. |
|
42 |
Warranty Information........................... |
Back Cover |
2 |
www.desatech.com |
113133-01B |
WARNING:Thisproductcontainsand/orgenerateschemicals known to the State of California to cause cancer or birth defects or other reproductive harm.
IMPORTANT: Read this owner’s manualcarefullyandcompletely before trying to assemble, operate or service this fireplace.
Improper use of this fireplace can cause serious injury or death from burns, fire, explosion,electricalshockandcarbon monoxide poisoning.
DANGER:Carbonmonoxide poisoning may lead to death!
CarbonMonoxidePoisoning:Earlysignsofcarbon monoxide poisoning resemble the flu, with headaches, dizziness or nausea. If you have these signs, the fireplace may not be working properly. Get fresh air at once! Have fireplace serviced. Some people are more affected by carbon monoxide than others.Theseincludepregnantwomen,peoplewith heart or lung disease or anemia, those under the influence of alcohol and those at high altitudes.
Natural and Propane/LP Gas: Natural and pro- pane/LPgasesareodorless.Anodor-makingagent isaddedto the gas.Theodorhelps youdetecta gas leak. However, the odor added to the gas can fade. Gas may be present even though no odor exists.
Makecertainyoureadandunderstandallwarnings. Keep this manual for reference. It is your guide to safe and proper operation of this fireplace.
WARNING: Any change to this fireplace or its controls can be dangerous.
WARNING:Donotuseablower insert, heat exchanger insert orotheraccessorynotapproved for use with this fireplace.
WARNING:Donotallowfans toblowdirectlyintothefireplace. Avoidanydraftsthatalterburner flame patterns. Ceiling fans can create drafts that alter burner flame patterns. Altered burner patterns can cause sooting.
Due to high temperatures, the applianceshouldbelocatedout oftrafficandawayfromfurniture and draperies.
Do not place clothing or other
flammable material on or near the appliance. Never place any objects on the heater.
Fireplace front and screen become very hot when running heater.Keepchildrenandadults awayfromhotsurfacestoavoid burns or clothing ignition. Fireplace will remain hot for a time after shutdown. Allow surfaces to cool before touching.
Carefully supervise young children when they are in the room with fireplace. When using the hand-held remote accessory
(Remote-Ready Models Only), keep selector switch in the OFF positiontopreventchildrenfrom turning on burners with remote.
You must operate this fireplace withthefireplacescreeninplace.
Make sure fireplace screen is closed before running fireplace.
Keep the appliance area clear and free from combustible materials, gasoline and other flammable vapors and liquids.
113133-01B |
www.desatech.com |
3 |
SAFETY INFORMATION
Continued
1.This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
2.Do not place propane/LP supply tank(s) inside any structure. Locate propane/LP supply tank(s) outdoors.
3.If you smell gas
•shut off gas supply
•do not try to light any appliance
•donottouchanyelectricalswitch;donotuse any phone in your building
•immediately call your gas supplier from a neighborʼs phone. Follow the gas supplierʼs instructions
•if you cannot reach your gas supplier, call the fire department
4.This fireplace shall not be installed in a bedroom or bathroom.
5.Do not use this fireplace as a wood-burning fireplace. Use only the logs provided with the fireplace.
6.Do not add extra logs or ornaments such as pine cones, vermiculite or rock wool. Using these added items can cause sooting. Do not add lava rock around base. Rock and debris could fall into the control area of fireplace.
7.This fireplace is designed to be smokeless. If logs ever appear to smoke, turn off fireplace and call a qualified service person. Note:Duringinitialoperation,slightsmoking could occur due to log curing and fireplace burning manufacturing residues.
8.To prevent the creation of soot, follow the instructions in Cleaning and Maintenance, page 27.
9.Before using furniture polish, wax, carpet cleaner or similar products, turn fireplace off. If heated, the vapors from these products may create a white powder residue within burner box or on adjacent walls or furniture.
10.Thisfireplaceneedsfreshairventilationtorun properly.This fireplace has an Oxygen DepletionSensing(ODS)safetyshutoffsystem.The ODS shuts down the fireplace if not enough fresh air is available. See Air for Combustion and Ventilation, page 6. If fireplace keeps shutting off, see Troubleshooting, page 29.
11.Do not run fireplace
•where flammable liquids or vapors are used or stored.
•under dusty conditions.
12.Do not use this fireplace to cook food or burn paper or other objects.
13.Never place any objects in the fireplace or on logs.
14.Do not use fireplace if any part has been under water. Immediately call a qualified service technician to inspect the room fireplace and to replace any part of the control system and any gas control which has been under water.
15.Turn off and unplug fireplace and let cool before servicing. Only a qualified service person should service and repair fireplace.
16.Operating fireplace above elevations of 4,500 feet could cause pilot outage.
17.Do not operate fireplace if log is broken. Do not operate fireplace if log is chipped (dimesized or larger).
18.To prevent performance problems, do not use propane/LP fuel tank of less than 100 lbs. capacity.
19.Provide adequate clearances around air openings.
4 |
www.desatech.com |
113133-01B |
PRODUCT
IDENTIFICATION
Fireplace
Cabinet
Hood
Screen
Log |
|
Ignitor Button |
Control |
|
|
|
Knob |
Fireplace Cabinet |
|
Hood |
|
Logs |
|
Ignitor |
|
Button |
|
Remote Control Control Knob |
|
(Optional) |
|
Figure 1 - Vent-Free Compact Dual Flame |
|
Fireplace |
|
OPTIONAL REMOTE |
|
CONTROL ACCESSORIES |
|
(For Remote-Ready Models Only) |
|
There are four optional remote controls that |
|
can be purchased separately for Remote-Ready |
|
Models only: |
|
•wall switch
•hand-held ON/OFF remote
•wall thermostat
•hand-held thermostat remote
See Accessories, page 40.
Install and use fireplace with care. Follow all local codes. In the absence of local codes, use the latest edition of The National Fuel Gas Code ANSI Z223.1/NFPA 54*.
*Available from:
American National Standards Institute, Inc. 1430 Broadway New York, NY 10018
National Fire Protection Association, Inc. Batterymarch Park Quincy, MA 02269
SAFETY PILOT
This fireplace has a pilot with an Oxygen Depletion Sensing (ODS) safety shutoff system. The ODS/pilot is a required feature for vent-free room fireplaces. The ODS/pilot shuts off the fireplace if there is not enough fresh air.
PIEZO IGNITION SYSTEM
This fireplace has a piezo ignitor. This system requires no matches, batteries or other sources to light fireplace.
THERMOSTATIC HEAT CONTROL FOR THERMOSTAT-CONTROLLED MODELS
Thermostat-Controlled models have a thermostat sensing bulb and a control valve. The thermostat will automatically modulate the heat output to maintain a consistent room temperature. This results in greater fireplace comfort. This can also result in lower gas bills.
1.Remove fireplace and hood from carton. Log is wrapped and inside fireplace. Do not remove at this time.
2.Remove all protective packaging applied to fireplace for shipment.
3.Make sure your fireplace includes one hardware packet.
4.Check fireplace for any shipping damage. If fireplace is damaged, promptly inform dealer where you bought fireplace.
113133-01B |
www.desatech.com |
5 |
WARNING: Always have screen in place before operating
fireplace. This prevents excessive temperatures on fireplace surfaces.
WARNING:Failuretoposition thepartsinaccordancewiththese diagrams or failure to use only parts specifically approved with this fireplace may result in property damage or personal injury.
Tools Required: |
|
|
|
• |
Phillips screwdriver |
• |
slotted screwdriver |
• |
5/16" hex wrench |
• |
scissors |
1.Lift fireplace screen up and pull out to remove (see Figure 2). Set screen aside until installation has been completed.
2.Cut two plastic straps to remove the log from the firebox cavity. Set log aside.
3.An optional blower is available. See Accessories, page 40. Install optional blower now. Follow installation instructions provided with blower and see page 14 or 15, depending on your installation.
4.Locate four black phillips sheet metal screws in hardware packet.
5.Slidehoodbetweenlouverandfireboxtopand align screw holes.
6.Insert screws as shown in Figure 3. Tighten screws firmly.
Shoulder Screw
Screen
Sheet Metal
Screws
Hood
Louver
Firebox
Top
Figure 3 - Assembling Hood
WARNING: This fireplace shall not be installed in a confined space or unusually tight construction unless provisions are provided for adequate combustionandventilationair.Read the following instructions to insureproperfreshairforthisand otherfuel-burningappliancesin your home.
Todayʼs homes are built more energy efficient than ever. New materials, increased insulation and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want their homes as airtight as possible.
While it is good to make your home energy efficient, your home needs to breathe. Fresh air must enter your home.All fuel-burning appliances need fresh air for proper combustion and ventilation.
Exhaust fans, fireplaces, clothes dryers and fuel burning appliances draw air from the house to operate. You must provide adequate fresh air for these appliances. This will insure proper venting of vented fuel-burning appliances.
Figure 2 - Removing and Installing
Screen
6 |
www.desatech.com |
113133-01B |
AIR FOR COMBUSTION
AND VENTILATION
Continued
PROVIDING ADEQUATE VENTILATION
The following are excerpts from National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three following ventilation classifications:
1.Unusually Tight Construction
2.Unconfined Space
3.Confined Space
The information on pages 6 through 8 will help you classify your space and provide adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.
Unusually tight construction is defined as construction where:
a.walls and ceilings exposed to the outside atmosphere have a continuous water vapor retarder with a rating of one perm (6 x 10-11 kg per pa-sec-m2) or less with openings gasketed or sealed and
b.weather stripping has been added on openable windows and doors and
c.caulking or sealants are applied to areas such as joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines and at other openings.
If your home meets all of these three criteria, you must provide additional fresh air. See Ventilation Air From Outdoors, page 8.
If your home does not meet all of the three criteria above, proceed to Determining Fresh-Air Flow For Fireplace Location, column 2.
Confined and Unconfined Space
The National Fuel Gas Code, ANSI Z223.1/NFPA 54 defines a confined space as a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed*, through openings not furnished with doors, are considered a part of the unconfined space.
* Adjoining rooms are communicating only if therearedoorlesspassagewaysorventilationgrills between them.
DETERMINING FRESH-AIR FLOW FOR FIREPLACE LOCATION
Determining if You Have a Confined or Unconfined Space
Use this work sheet to determine if you have a confined or unconfined space.
Space: Includes the room in which you will install fireplace plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.
1.Determine the volume of the space (length x width x height).
Length x Width x Height =__________cu. ft. (volume of space)
Example: Space size 16 ft. (length) x 14 ft. (width) x 8 ft. (ceiling height) = 1792 cu. ft. (volume of space)
If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.
2.Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.
__________ (volume of space) x 20 = (Maximum Btu/Hr the space can support)
Example: 1792 cu. ft. (volume of space) x 20 = 35,840 (maximum Btu/Hr the space can support)
3.Add the Btu/Hr of all fuel burning appliances in the space.
Vent-free fireplace |
___________ Btu/Hr |
Gas water heater* |
___________ Btu/Hr |
Gas furnace |
___________ Btu/Hr |
Vented gas heater |
___________ Btu/Hr |
Gas fireplace logs |
___________ Btu/Hr |
Other gas appliances* +___________ |
Btu/Hr |
|
Total |
=___________ |
Btu/Hr |
* Do not include direct-vent gas appliances. Di- rect-ventdrawscombustionairfromtheoutdoors and vents to the outdoors.
113133-01B |
www.desatech.com |
7 |
AIR FOR COMBUSTION AND VENTILATION
Continued
Example: |
|
30,000 |
Gas water heater |
|
|
|
_________ Btu/Hr |
|
Vent-free fireplace |
+ |
10,000 |
|
_________ Btu/Hr |
|
Total |
= |
40,000 |
|
_________ Btu/Hr |
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 4).You
4.Compare the maximum Btu/Hr the space can can also remove door into adjoining room (see
support with the actual amount of Btu/Hr used.
_________ Btu/Hr(maximumthespacecansupport)
_________ Btu/Hr (actual amount of Btu/Hr used)
Example: 35,840 Btu/Hr (maximum the space can support)
40,000 Btu/Hr (actual amount of Btu/Hr used)
The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support.You must provide additional fresh air. Your options are as follows:
A.Reworkworksheet,addingthespaceofanadjoiningroom.Iftheextraspaceprovidesanunconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building.
B.Vent room directly to the outdoors. See Ventilation Air From Outdoors.
C.Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.
WARNING: If the area in whichthefireplacemaybeoperatedissmallerthanthatdefined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air byoneofthemethodsdescribed in the National Fuel Gas Code, ANSIZ223.1/NFPA54Section5.3 or applicable local codes.
option 3, Figure 4). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.
|
|
12" |
|
Ventilation |
|
Ventilation Grills |
|
Grills |
|
||
Into Adjoining |
Or |
Into Adjoining Room, |
|
Room, |
Option 2 |
||
Remove |
|||
Option 1 |
|
||
Door into |
|
||
|
|
||
|
Adjoining |
|
|
|
Room, |
|
|
|
Option |
|
|
|
3 |
|
12"
Figure 4 - Ventilation Air from Inside Building
Ventilation Air From Outdoors
Provideextrafreshairbyusingventilationgrillsor ducts.You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the
National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3,Air for Combustion and Ventilation for required size of ventilation grills or ducts.
IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostatcontrolledpowervent.Heatedairenteringtheattic will activate the power vent.
|
Outlet |
Ventilated |
|
Attic |
|
|
Air |
|
|
|
|
Outlet |
|
|
Air |
|
To Attic |
|
|
|
|
|
To |
|
|
Crawl |
Inlet |
|
Space |
|
|
|
Air |
|
|
|
Inlet Air |
Ventilated |
|
Crawl Space |
|
|
|
Figure 5 - Ventilation Air from Outdoors
8 |
www.desatech.com |
113133-01B |
NOTICE:Thisheaterisintended for use as supplemental heat. Use this heater along with your primary heating system. Do not install this heater as your primary heat source. If you have a centralheatingsystem,youmay run system’s circulating blower whileusingheater.Thiswillhelp circulatetheheatthroughoutthe house. In the event of a power outage, you can use this heater as your primary heat source.
WARNING: A qualified service person must install fireplace. Follow all local codes.
WARNING: Never install the fireplace
•in a bedroom or bathroom
•in a recreational vehicle
•where curtains, furniture, clothing or other flammable objectsarelessthan36inches from the front, top or sides of the fireplace
•as a fireplace insert
•in high traffic areas
•in windy or drafty areas
WARNING: Never install in a bedroomorbathroom.Anyheating product with a Btu/Hr rating over 10,000 cannot be used in a bedroom.
CAUTION:Thisfireplacecreates warm air currents. These currents move heat to wall surfacesnexttofireplace.Installing fireplace next to vinyl or cloth wall coverings or operating
fireplacewhereimpurities(such as, but not limited to, tobacco smoke,aromaticcandles,cleaningfluids,oilorkerosenelamps, etc.)intheairexist,maydiscolor walls or cause odors.
IMPORTANT: Vent-free fireplaces add moisture totheair.Althoughthisisbeneficial,installingfireplace in rooms without enough ventilation air may causemildewtoformfromtoomuchmoisture.See
Air for Combustion and Ventilation, page 6.
Note:Your fireplace is designed to be used in zero clearance installations. Wall or framing material can be placed directly against any exterior surface on the rear, sides or top of your fireplace, except where standoff spacers are integrally attached. If standoff spacers are attached to your fireplace, these spacers can be placed directly against wall or framing materials.
Note:Wheninstallingfireplacedirectlyoncarpeting, tile or other combustible material, other than wood flooring, the fireplace shall be installed on a metal or wood panel extending the full width and depth of the fireplace.
Use the dimensions shown for rough openings to create the easiest installation (see Built-In Fireplace Installation, page 11).
CHECK GAS TYPE
Use the correct gas type (natural or propane/LP) for your unit. If your gas supply is not correct, do not install fireplace. Call dealer where you bought fireplace for proper type fireplace.
WARNING: This appliance is equipped for (natural or propane/LP) gas. Field conversion is not permitted.
113133-01B |
www.desatech.com |
9 |
INSTALLATION
Continued
INSTALLATION ITEMS
Before installing fireplace, make sure you have the items listed below.
•external regulator (supplied by installer, for propane/LP units only)
•piping (check local codes)
•sealant (resistant to propane/LP gas)
•equipment shutoff valve *
•test gauge connection*
•ground joint union
•sediment trap
•tee joint
•pipe wrench
*ACSAdesign-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the optional CSA design-certifiedequipmentshutoffvalvefromyour dealer. See Accessories, page 40.
Note: If desired, purchase a four-sided perimeter trim kit for built-in installations. See Accessories, page 40.
FIREPLACE CLEARANCES
WARNING: Maintain the minimum clearances shown in Figure 6. If you can, provide greater clearances from floor, ceiling and joining wall.
If your fireplace is to be used with an optional mantel, the installation instructions included with your mantel shows an CSA approved method of attaching the fireplace/mantel system to a wall. IMPORTANT: Only use optional cabinet or corner mantels specified in this manual. Purchase the optional mantel from your dealer (see Accessories, page 40).
If your fireplace is to be recessed into the wall, see Built-In Fireplace Installation on page 11 to secure your fireplace into the wall.
CAUTION: If you install the fireplace in a home garage
•fireplacepilotandburnermust be at least 18 inches above floor.
•locatefireplacewheremoving vehicle will not hit it.
For convenience and efficiency, install fireplace
•wherethereiseasyaccessforoperation,inspection and service
•in coldest part of room
An optional blower kit is available from your dealer.SeeAccessories, page40.Ifplanningtouse blower, follow instructions provided with blower for power source.
Minimum Clearances For Side Combustible Material, Side Wall and Ceiling
A.Clearances from the side of the fireplace cabinet to any combustible material and wall should follow diagram in Figure 6.
Example: The face of a mantel, bookshelf, etc. is made of combustible material and protrudes 3 1/2" from the wall. This combustible material must be 4" from the side of the fireplace opening (see Figure 6).
B.Clearancesfromthetopofthefireplaceopening to the ceiling should not be less than 36 inches.
C.For mantel clearances, see Figure 10 on page 12.
MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS
Top |
Left and |
Bottom |
|
Right Sides |
and Rear |
36" |
6" |
0" |
|
Example |
|
|
|
* |
*Minimum 16 inches from Side Wall
Figure 6 - Minimum Clearance for Combustible to Wall
10 |
www.desatech.com |
113133-01B |
INSTALLATION
Continued
BUILT-IN FIREPLACE INSTALLATION
Built-in installation of this fireplace involves installing fireplace into a framed-in enclosure. This makes the front of fireplace flush with wall. An optional trim kit accessory is available (see Accessories, page 40).Trim will extend past sides offireplaceapproximately1/2inch.Thiswillcover the rough edges of the wall opening. If installing a built-in mantel above the fireplace, you must follow the clearances shown in Figure 10, page 12. Follow the instructions below to install the fireplace in this manner.
|
Actual |
Framing |
Height |
26" |
26 7/8" |
Front Width |
26 3/4" |
26 7/8" |
Depth |
14 1/4" |
15 1/4" |
1.Frameinroughopening.Usedimensionsshown inFigure7fortheroughopening.Ifinstallingin a corner, use dimensions shown in Figure 8 for the rough opening. The height is 26 7/8" which is the same as the wall opening above.
2.If installing GA3450TAblower accessory, do so at this time. Follow instructions included with blower accessory.
Note: If not installing blower accessory, you may wish to run electrical wiring to your fireplace for future blower installation (see Accessories, page 40). Use only approved three-wire electrical wiring.
15 1/4"
267/8"
267/8"
Figure 7 - Rough Opening for Installing in Wall
435/16"
305/8"
267/8"
611/4"
Figure 8 - Rough Opening for Installing in Corner
WARNING: If pre-wiring, do notconnectwiringtoanyelectrical source at this time.
Install fireplace electrical outlet and connect wiring to outlet before connecting to electrical source. The fireplace electrical outlet is included with the GA3450TA blower accessory.
Only use the fireplace electrical outlet supplied with the GA3450TA blower accessory.
Note:Aqualified installer should make all electrical connections.
3.Install gas piping to fireplace location. This installation includes an approved flexible gas line(ifallowedbylocalcodes)aftertheequipment shutoff valve.The flexible gas line must be the last item installed on the gas piping.
4.If you have not installed hood, follow instructions on page 6.
5.Carefullysetfireplaceinfrontofroughopening with back of fireplace inside wall opening.
6.Attachflexiblegaslinetofireplacegasregulator. See Connecting Equipment Shutoff Valve to Heater Control, page 17.
7.Bend four nailing flanges on outer casing with pliers (see Figure 9).
8.Attach fireplace to wall studs using nails or wood screws through holes in nailing flange.
9.Checkallgasconnectionsforleaks.SeeChecking Gas Connections, page 17.
Wall Studs
Nails or Wood Screws
Nailing Flanges
Figure 9 - Attaching Fireplace to Wall Studs
113133-01B |
www.desatech.com |
11 |
INSTALLATION
Continued
10.If using optional trim kit, install the trim after final finishing and/or painting of wall. See instructions included with trim accessory for attaching trim.
IMPORTANT: When finishing your firebox, combustible materials such as wall board, gypsum board, sheet rock, drywall, plywood, etc. may be butted up next to the sides and top edge of the firebox. Combustible materials should never overlap the firebox front facing.
WARNING: Do not allow any combustiblematerialstooverlap the firebox front facing.
IMPORTANT:Noncombustible materials such as brick, tile, etc. may overlap the front facing, but should never cover any necessary openings like louvered slots.
WARNING: Do not allow noncombustible materials to cover any necessary openings like louvered slots.
WARNING: Never modify or cover the louvered slots on the front of the firebox.
WARNING:Useonlynoncombustiblemortaroradhesiveswhen overlapping the front facing with noncombustible facing material.
Mantel Clearances for Built-In Installation
Ifplacingmantelabovebuilt-infireplace,youmust meetminimumclearancebetweenmantelshelfand top of fireplace opening.
NOTICE: Surface temperatures ofadjacentwallsandmantelsbecomehotduringoperation.Walls and mantels above the firebox may become hot to the touch. If installed properly, these temperatures meet the requirement ofthenationalproductstandard.
Follow all minimum clearances shown in this manual.
Mantel Shelf
Note: |
10" |
|
8" |
||
All vertical |
measurements 6"
are from top of fireplace 2 1/2"
opening to bottom of mantel shelf. All measurements are in inches.
15" |
18" |
21" |
23" |
Side of Firebox
Figure 10 - Minimum Mantel Clearances
for Built-In Installation
NOTICE:Ifyourinstallationdoes not meet the minimum clearances shown, you must do one of the following:
•raise the mantel to an acceptable height
•remove the mantel
OPTIONAL MANTEL INSTALLATION
Note:Refertoinstructionsprovidedwiththemantel for assembly instructions. Refer to the following instructionsforsysteminstallation.Refertoinstructionsonpage4forhoodassembly.Bloweraccessory should be installed if it is being used (see Installing Optional Blower Accessory GA3450TA, page 13).
1.Unscrew four screws that attach top louver to fireplace. Remove louver from fireplace and set aside (see Figure 11).
2.Placebaseassemblynexttowallatinstallation location.
3.Place fireplace on wood base (see Figure 12).
Top
Louver
Bottom Louver
Figure 11 - Removing Top Louver and
Opening Bottom Louver
12 |
www.desatech.com |
113133-01B |
INSTALLATION
Continued
4.Place mantel around fireplace on base (see Figure 12).
5.Assemble perimeter trim kit. See Assembling Perimeter Trim.
6.Firmly snap perimeter trim kit on shoulder screws. Shoulder screws are located on fireplace cabinet (see Figure 12).
7.Align perimeter trim kit for flush fit around opening.
8.Centermantellefttorightonbasemakingsure mantel is flush against wall.
9.Use two 3" wood screws provided and attach base of fireplace to wooden mantel base (see Figure 12).
10.Remove perimeter trim kit and mantel. Be careful not to damage wall or mantel.
11.Cut an access hole in base to run flexible gas line to fireplace (see Figure 12). Make sure to locate access hole so mantel will cover it when installed. Note: You can secure base to floor using wood screws. Countersink screw heads and putty over.
|
|
Hole for |
|
|
|
3" Wood |
|
|
|
Screw for |
|
|
|
Attaching |
|
Shoulder |
|
Fireplace |
|
Screw |
|
to Mantel |
|
|
|
||
|
|
Gas |
|
|
|
Line |
|
|
|
Access |
|
|
|
Hole |
|
Mantel |
|
|
|
Base |
|
|
|
Assembled |
Hole for 3" Wood |
Shoulder |
|
Perimeter |
Screws |
||
|
|||
Screw for Attaching |
|||
Trim |
|||
Fireplace to |
|
||
|
|
Wooden Base
Figure 12 - Attaching Perimeter Trim to Fireplace
12.Install gas line. See Connecting To Gas Supply, page 16.
13.Check for leaks. See Checking Gas Connections, page 17.
14.Place mantel around fireplace. Be careful not to damage wall or mantel.
15.Placeperimetertrimkitontheshoulderscrews located on the side and top of the fireplace. Firmly snap trim over shoulder screws on fireplace (see Figure 12).
16.Adjust assembly to remove any gaps. Attach remaining two 3" wood screws from hardware pack through openings inside of fireplace sides into the mantel. The openings are located at top behind the area for top louver (see Figure 12).
17.Reinstall top louver.
Assembling Perimeter Trim (Perimeter trim shipped with mantel)
1.Remove packaging from three remaining pieces of trim.
2.Locate two adjusting plates with set screws and two shims in the hardware packet.
3.Align shim under adjusting plate as shown in Figure 13.
4.Slideoneendofadjustingplate/shiminsloton mitered edge of top trim (see Figure 13).
5.Slide other end of adjusting plate/shim in slot on mitered edge of side perimeter trim (see Figure 13).
6.While firmly holding edges of perimeter trim together, tighten both setscrews ontheadjusting plate with slotted screwdriver.
7.Repeat steps 1 through 6 for other corner.
8.Set perimeter trim assembly aside for later installation.
Set |
Screws |
|
Adjusting |
|
|
Plate |
|
|
|
Slot |
Top Trim |
Shim |
|
Mitered Edge |
|
|
|
Side Trim |
|
|
Figure 13 - Assembling Perimeter Trim |
INSTALLING OPTIONAL BLOWER ACCESSORY GA3450TA
Removing Upper Louver To install the blower accessory, you must first remove the upper louver.
1.Lift screen off fireplace and remove log set if installed.
113133-01B |
www.desatech.com |
13 |
INSTALLATION
Continued
2.Remove 4 screws from upper louver (see Figure 11, page 12). Save these screws.
3.Pullupperlouverstraightoutfromthecabinet.Be careful not to scratch the paint. Set louver aside.
4.Open lower louver door by swinging door down (see Figure 11, page 12).
Installing Blower Accessory
CAUTION: Label all wires priortodisconnectionwhenservicingcontrols.Wiringerrorscan cause improper and dangerous operation.
CAUTION: Verify proper operation after servicing.
Note:Ifyouareusingamantelwithyourfireplace, use the following instructions. If your fireplace is built-in, see For Built-In Installation, page 15.
1.Install snap bushings found in blower kit into hole in left side of outer casing and into one of the holes in rear of remote/blower bracket.
2.Makesurethewireharnessisfirmlyconnectedto the terminals on the blower bracket assembly.
3.Note the wire locations on back of AUTO/ OFF/ON switch. The terminals on back of switch are numbered 1, 2 and 3. Carefully remove red wire from terminal 3 and blue wire from terminal 1. Black wire can remain on middle terminal 2 (see Figure 14).
Blower |
Wiring Routing |
||
Bracket |
Wire Hole in Baffle |
Blower |
|
Assembly |
Harness |
||
Mounting |
|||
Screw |
|
||
|
Holes |
Switch |
Power |
|
|
Cord |
|
3 |
|
|
2 |
|
|
1 |
|
|
Switch |
|
|
Plate |
Remote/ |
|
Wire |
||
Blower |
Harness Bracket
Lower Louver Door
Figure 14 - Installing Blower Bracket
Assembly (Remote-Ready Unit Shown)
4.Carefully disconnect green and white wires at their insulated connectors (see Figure 15).
5.In top of the fireplace cabinet, locate the four mounting holes on the outer casing. Align these four holes with those on the blower bracket assembly. Attach blower bracket assembly to the outer casing with 4 #10 screws provided (see Figure 14).
6.Route the wire harness through the hole in left sideofbaffleandbetweenfireboxwrapperand outer casing.
7.Insert the 4 wire harnesses from behind the remote/blower bracket through hole in rear of bracketwithbushingandthroughtheleftrectangular hole to front of fireplace (see Figure 14).
8.Reconnect red wire to switch position 3. Reconnect blue wire to switch position 1. Reconnect green and white wires.
9.Install the switch plate on the remote/blower bracket with 2 #10 screws provided (see Figure 16).Routepowercordoutofthecabinetbyinsertingitthroughthebushingontheoutercasing(see Figure 14). Plug fan kit into 120-Volt grounded power supply and test operation. Note: When switchisintheAUTOposition,thefanwillstart afterthefireplacehasrunforafewmoments.The fanwillcontinuetorunforseveralmomentsafter thefireplacehasbeenturnedoff.Whenswitchis in the ON position, the fan will run until turned to OFF.
10.Reinstall upper louver beginning with bottom screws (see Figure 11, page 12). Close lower louver door.
Fan Switch (Auto/Off/On)
1Auto
Off |
2 |
|
|
|
3 |
Blue |
Thermostat |
||
|
||||
|
|
|||
|
On |
|
Switch |
|
|
|
(N.O.) |
||
|
|
|
Blue |
|
110/115 |
Red |
|
Blower |
|
V.A.C. |
|
|
||
|
|
Motor |
||
Black |
|
|
||
|
|
Red |
||
|
|
|
||
White |
|
|
White |
|
Green |
|
|
Green |
|
Figure 15 - Wiring Diagram For Blower |
||||
Accessory Standard Installation |
||||
|
|
|
Remote/ |
|
|
|
|
Blower |
|
|
|
|
Bracket |
|
Switch |
|
|
|
|
Plate |
|
|
|
|
Screw |
|
|
|
|
Figure 16 - Installing Switch Plate to |
||||
Remote/Blower Bracket |
14 |
www.desatech.com |
113133-01B |