Desa VYS24PB, VYS18NB, VYS18PB, VYD30, VYS24NB User Manual

...
0 (0)
Desa VYS24PB, VYS18NB, VYS18PB, VYD30, VYS24NB User Manual

UNVENTED (VENT-FREE) GAS LOG HEATER OWNER’S OPERATION AND INSTALLATION MANUAL

AUTO OFF ON

HI

LO

N

O TO

O

F F LIP

Golden Oak Logs Shown

FLAME-MAX® Golden Oak Log Design

Remote-Ready Models VYD18(N,P)RB, VYD24(N,P)RB and VYD30(N,P)RB

FLAME-MAX® Vintage Oak Log Design

Variable Manually-Controlled Models VYS18(N,P)B and VYS24(N,P)B

Also Design-Certified As Vented Decorative Appliances

WARNING: If the information in this manual is not followedexactly,afireorexplosionmay resultcausing property damage, personal injury or loss of life.

Do not store or use gasoline or other ­flammable vapors and liquidsin the ­vicinity of this or any other appliance.

WHAT TO DO IF YOU SMELL GAS

Do not try to light any appliance.

Donottouchanyelectricalswitch;donotuseany phone in your building.

Immediatelycallyourgassupplierfromaneighbor’s phone. Follow the gas supplier’s instructions.

If you cannot reach your gas supplier, call the fire department.

Installationandservicemustbeperformedbyaqualified installer, service agency or the gas supplier.

INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.

For more information, visit www.desatech.com

Table of Contents

Safety...................................................................

2

Local Codes.........................................................

5

Product Identification............................................

5

Optional Remote Control Accessories.................

5

Unpacking............................................................

5

Air for Combustion and Ventilation.......................

6

Product Features..................................................

6

Installation............................................................

8

Operation...........................................................

18

Inspecting Burners.............................................

23

Cleaning and Maintenance.

............................... 24

Replacement Parts.............................................

25

Wiring Diagram..................................................

25

Troubleshooting.................................................

26

Specifications.....................................................

30

Service Hints......................................................

30

Technical Service...............................................

30

Accessories........................................................

31

Parts...................................................................

32

Warranty ..............................................

Back Cover

Safety

WARNING: Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual for correct installation and operational procedures. For assistance or additional information consult a qualified installer, service agency or the gas supplier.

WARNING: This appliance is for installation only in a solid-fuel burning masonry or UL127 fac- tory-built fireplace or in a listed ventless firebox enclosure. It is design-cer- tifiedfortheseinstallations in accordance with ANSI

Z21.11.2.Exception:Donot install this appliance in a factory-built fireplace that includes instructions stating it has not been tested or should not be used with unvented gas logs.

WARNING: This is an unvented gas-fired heater. It uses air (oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must be provided. Refer to Air for Combustion and Ventilation section on page 6 of this manual.

This appliance may be installed in an aftermarket,* permanently located, manufactured (mobile) home, where not prohibited by local codes.

This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.

* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer

2

www.desatech.com

113093-01H

SAFETY

Continued

WARNING:Thisproductcontainsand/orgenerateschemicals known to the state of California to cause cancer or birth defects or other reproductive harm.

IMPORTANT: Read this owner’s manualcarefullyandcompletely before trying to assemble, operate or service this fireplace. Improper use of this fireplace can cause serious injury or death from burns, fire, explosion,electricalshockandcarbon monoxide poisoning.

DANGER:Carbonmonoxide

poisoning may lead to death!

Carbon Monoxide Poisoning: Early signs of carbon monoxide poisoning resemble the flu, with headaches, dizziness or nausea. If you have these signs, the heater may not be working properly. Get fresh air at once! Have heater serviced. Some people are more affected by carbon monoxide than others. These include pregnant women, people with heart or lung disease or anemia, those under the influence of alcohol and those at high altitudes.

Natural and Propane/LP Gas: Natural and propane/LP gases are odorless. An odormaking agent is added to the gas. The odor helps you detect a gas leak. However, the odor added to the gas can fade. Gas may be present even though no odor exists.

Make certain you read and understand all warnings. Keep this manual for reference. It is your guide to safe and proper operation of this heater.

WARNING: Any change to this heater or its controls can be dangerous.

WARNING: Do not use a blower insert, heat exchanger insertorotheraccessorynotapproved for use with this heater.

WARNING: Do not allow fans toblowdirectlyintothefireplace.

Avoidanydraftsthatalterburner flame patterns. Ceiling fans can create drafts that alter burner flame patterns. Altered burner patterns can cause sooting.

Due to high temperatures, the applianceshouldbelocatedout oftrafficandawayfromfurniture and draperies.

Do not place clothing or other flammable material on or near the appliance. Never place any objects on the heater.

Heaterbaseassemblybecomes very hot when running heater. Keep children and adults away from hot surface to avoid burns or clothing ignition. Heater will remain hot for a time after shutdown.Allowsurfacetocool before touching.

Carefully supervise young children when they are in the room withheater.Whenusingthehandheldremoteaccessory(RemoteReadyModelsOnly),keepselector switch in the OFF position to preventchildrenfromturningon burners with remote.

You must operate this heater with a fireplace screen in place. Make sure fireplace screen is closed before running heater.

Keep the appliance area clear and free from combustible materials, gasoline and other flammable vapors and liquids.

113093-01H

www.desatech.com

3

SAFETY

Continued

1.This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.

2.Do not place propane/LP supply tank(s) inside any structure. Locate propane/LP supply tank(s) outdoors (propane/LP units only).

3.If you smell gas

shut off gas supply

do not try to light any appliance

do not touch any electrical switch; do not use any phone in your building

immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions

if you cannot reach your gas supplier, call the fire department

4.This heater shall not be installed in a bedroom or bathroom, unless installed as a vented appliance. See Installing Damper Clamp Accessory for Vented Operation, page 12. This gas log set may not be installed as a vented appliance in a bedroom or bathroom in the Commonwealth of Massachusetts.

5.Before installing in a solid fuel burning fireplace, the chimney flue and firebox must be cleaned of soot, creosote, ashes and loose paint by a qualified chimney cleaner. Creosote will ignite if highly heated.Adirty chimney flue may create and distribute soot within the house. Inspect chimney flue for damage. If damaged, repair flue and firebox before operating heater.

6.Do not burn solid-fuel in a masonry or

UL127 factory-built fireplace in which a vent-free room heater is installed.

7.If fireplace has glass doors, never operate this heater with glass doors closed. If you operate heater with doors closed, heat buildup inside fireplace will cause glass to burst. Make sure there are no obstructions across openings of fireplace.

8.To prevent the creation of soot, follow the instructions in Cleaning and Maintenance, page 24.

9.Before using furniture polish, wax, carpet cleanerorsimilarproducts,turnheateroff.If heated,thevaporsfromtheseproductsmay createawhitepowderresiduewithinburner box or on adjacent walls and furniture.

10.This heater needs fresh, outside air ventilation to run properly. This heater has an Oxygen Depletion Sensing (ODS) safety shutoff system. The ODS shuts down the heater if enough fresh air is not available. See Air for Combustion and Ventilation, page 6. If heater keeps shutting off, see

Troubleshooting, page 26.

11.Do not run heater

where flammable liquids or vapors are used or stored

under dusty conditions

12.Do not use this heater to cook food or burn paper or other objects.

13.Do not use heater if any part has been exposed to or under water. Immediately call a qualified service technician to inspect the room heater and to replace any part of the control system and any gas control which has been under water.

14.Do not operate heater if any log is broken. Do not operate heater if a log is chipped

(dime-sized or larger).

15.Turn heater off and let cool before servicing, installing or repairing. Make sure the selector switch is in the OFF position

(Remote-Ready Models Only). Only a qualified service person should install, service or repair heater.

16.Make sure the selector switch is in the OFF position when you are away from home for long periods of time (RemoteReady Models Only).

17.Operating heater above elevations of

4,500 feet may cause pilot outage.

18.To prevent performance problems, do not use propane/LP fuel tank of less than 100 lb. capacity (propane/LP units only).

19.Provide adequate clearances around air openings.

4

www.desatech.com

113093-01H

Local Codes

Install and use heater with care. Follow all local codes. In the absence of local codes, use the latest edition of The National Fuel Gas Code, ANSI Z223.1/NFPA 54*.

*Available from:

American National Standards Institute, Inc.

1430 Broadway

New York, NY 10018

National Fire Protection Association, Inc.

Batterymarch Park

Quincy, MA 02269

Note: Where listed vented decorative logs are required, thermostat operation is not permitted.

State of Massachusetts: The installation must be made by a licensed plumber or gas fitter in the Commonwealth of

Massachusetts.

Sellers of unvented propane or natural gas-fired supplemental room heaters shall provide to each purchaser a copy of 527 CMR 30 upon sale of the unit.

Vent-free gas products are prohibited for bedroom and bathroom installation in the

Commonwealth of Massachusetts.

Product Identification

Flame-Max® Golden

Flame-Max® Vintage Oak

Oak Logs Three

Logs One Piece Log Set

Piece Log Set

 

Piezo

Ignitor

 

Optional

 

 

Piezo

 

 

 

Ignitor

 

Selector

 

 

 

 

Base

 

 

Switch

 

Base

 

Flame

Control

Assembly

Optional

Assembly Control

Adjustment

Knob

 

Remote

Knob

 

 

Knob

Control

Figure 1 - Product Identification

 

Optional Remote Control Accessories

There are four optional remote controls that can be purchased separately for Remote-Ready Models Only:

• wall switch

• wall thermostat

hand-held ON/OFF remote

hand-held thermostat remote

See Accessories, page 31.

The wall thermostat or hand-held thermostat may not be used where vented decorative

listing is required.

Unpacking

CAUTION:Donotremovedata platesfromgrateassembly.Data platescontainimportantwarranty and safety information.

1.Remove logs and heater base assembly from carton.

Note: Do not pick up heater base assembly by burners. This could damage heater. Always handle base assembly by grate.

2.Remove all protective packaging applied to logs and heater for shipment.

3.Check heater for any shipping damage. If heaterisdamagedcallDESAHeating,LLC at 1-866-672-6040 for replacement parts before returning to dealer.

113093-01H

www.desatech.com

5

Product Features

Operation

This heater is clean burning. It requires no outside venting. There is no heat loss out a vent or up a chimney. Heat is generated by both realistic flames and glowing coals. This heater is designed for vent-free operation with flue damper closed. It has been tested and approved to ANSI Z21.11.2 standard for unvented heaters. State and local codes in some areas prohibit the use of vent-free heaters. This heater may also be operated as a vented decorative (ANSI Z21.60) product by opening the flue damper.

Safety Device

This heater has a pilot with an Oxygen Depletion Sensing (ODS) safety shutoff system. The ODS/pilot is a required feature for vent-free room heaters. The ODS/pilot shuts off the heater if there is not enough fresh air.

Piezo Ignition System

This heater has a piezo ignitor.This system requires no matches, batteries or other sources to light heater.

Air for Combustion and Ventilation

WARNING: This heater shall notbeinstalledinaroomorspace unless the required volume of indoorcombustionairisprovided by the method described in the

National Fuel Gas Code, ANSI Z223.1/NFPA54, the International Fuel Gas Code, or applicable local codes. Read the following instructionstoinsureproperfresh airforthisandotherfuel-burning appliances in your home.

Today’s homes are built more energy efficient than ever. New materials, increased insulation and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want their homes as airtight as possible.

While it is good to make your home energy efficient, your home needs to breathe. Fresh air must enter your home. All fuel-burning appliances need fresh air for proper combustion and ventilation.

Exhaust fans, fireplaces, clothes dryers and fuelburningappliancesdrawairfromthehouse to operate. You must provide adequate fresh air for these appliances.This will insure proper venting of vented fuel-burning appliances.

PROVIDING ADEQUATE VENTILATION

The following are excerpts from National Fuel Gas Code, ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation.

All spaces in homes fall into one of the three following ventilation classifications:

1.Unusually Tight Construction

2.Unconfined Space

3.Confined Space

The information on pages 6 through 8 will help you classify your space and provide adequate ventilation.

Unusually Tight Construction

The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.

Unusually tight construction is defined as construction where:

a.walls and ceilings exposed to the outside atmosphere have a continuous water vapor retarder with a rating of one perm (6 x 10-11 kg per pa-sec-m2) or less with openings gasketed or sealed and

b.weather stripping has been added on openable windows and doors and

c.caulking or sealants are applied to areas such as joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines and at other openings.

If your home meets all of the three criteria above, you must provide additional fresh air.

See Ventilation Air From Outdoors, page 8.

If your home does not meet all of the three criteria above, proceed to Determining FreshAir Flow For Heater Location, page 7.

6

www.desatech.com

113093-01H

AIR FOR COMBUSTION AND VENTILATION

Continued

Confined and Unconfined Space

The National Fuel Gas Code, ANSI Z223.1/ NFPA 54 defines a confined space as a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed*, through openings not furnished with doors, are considered a part of the unconfined space.

* Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them.

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height).

Length x Width x Height =__________cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft.

(volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.

_ ________ (volume of space) x 20 = (Maximum Btu/Hr the space can support)

Example: 2560 cu. ft. (volume of space) x 20

= 51,200 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free fireplace

___________ Btu/Hr

Gas water heater*

___________ Btu/Hr

Gas fireplace logs ___________ Btu/Hr Other gas appliances* +_________ Btu/Hr Total =__________ Btu/Hr

* Do not include direct-vent gas appliances.

Direct-vent draws combustion air from the outdoors and vents to the outdoors.

Example:

 

 

Gas water heater

40,000

Btu/Hr

Vent-free fireplace

+ 33,000

Btu/Hr

Total

73,000

= Btu/

Hr

 

 

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_ _____ Btu/Hr (maximum the space can support)

_______Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support)

73,000 Btu/Hr (actual amount of

Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 8.

B.Vent room directly to the outdoors. See

Ventilation Air From Outdoors, page 8.

C.Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING:Iftheareainwhich theheatermaybeoperateddoes notmeettherequiredvolumefor indoorcombustionair,combustion and ventilation air shall be provided by one of the methods described in the National Fuel GasCode,ANSIZ223.1/NFPA54, the International Fuel Gas Code, or applicable local codes.

Gas furnace

___________ Btu/Hr

Vented gas heater

___________ Btu/Hr

113093-01H

www.desatech.com

7

AIR FOR COMBUSTION AND VENTILATION

Continued

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermo- stat-controlled power vent. Heated air entering the attic will activate the power vent.

 

 

12"

 

 

 

 

 

 

 

Outlet

Ventilated

 

 

 

 

Attic

 

 

 

 

Air

Ventilation

 

 

 

 

 

Ventilation Grills

 

 

 

Grills Into

 

Outlet

 

 

Adjoining

 

Into Adjoining Room,

 

 

Or

Air

 

To Attic

Room,

Option 2

 

Remove

 

 

Option 1

 

 

 

 

Door into

 

 

 

 

 

 

 

 

 

 

Adjoining

 

 

 

To

 

Room,

 

 

 

 

 

 

 

Crawl

 

Option

 

 

 

 

 

 

 

Space

 

3

 

Inlet

 

 

 

 

 

 

 

 

 

 

 

 

 

Air

 

 

 

12"

 

 

Inlet Air

Ventilated

 

 

 

Crawl Space

 

 

 

 

 

Figure 3 - Ventilation Air from Outdoors

Figure 2 - Ventilation Air from Inside

Building

Installation

NOTICE: This heater is intended for use as supplemental heat. Use this heater along with your primary heating system. Do not install this heater as your primary heat source. If you have a centralheatingsystem,youmay run system’s circulating blower whileusingheater.Thiswillhelp circulatetheheatthroughoutthe house. In the event of a power outage, you can use this heater as your primary heat source.

WARNING: A qualified service person must install heater. Follow all local codes.

NOTICE:Stateorlocalcodesmay onlyallowoperationofthisappliance in a vented configuration.

Check your state or local codes.

WARNING: Make sure the selector switch is in the OFF positionbeforeinstallingheater (Remote-Ready Models Only).

8

www.desatech.com

113093-01H

Installation

Continued

WARNING: Before installing in a solid fuel burning fireplace, thechimneyflueandfireboxmust be cleaned of soot, creosote, ashesandloosepaintbyaqualified chimney cleaner. Creosote willigniteifhighlyheated.Adirty chimneyflueandfireboxmaycreateanddistributesootwithinthe house. Inspect chimney flue for damage. If damaged, repair flue before operating heater.

WARNING: Seal any fresh air vents or ash clean-out doors located on floor or wall of fireplace. If not, drafting may cause pilot outage or sooting. Use a heat-resistant sealant. Do not seal chimney flue damper.

WARNING: Never install the heater

in a bedroom or bathroom unless installed as a vented appliance, see page 12

in a recreational vehicle

where curtains, furniture, clothing or other flammable objects are less than 36" from front and 42" from top of heater; for side clearances see Figure 4, page 10

in high traffic areas

in windy or drafty areas

CAUTION: This heater creates warm air currents. These currents move heat to wall surfaces next to heater. Installing heater next to vinyl or cloth wall coverings or operating heater where impurities (such as, but not limited to, tobacco smoke, aromatic candles, cleaning fluids,oilorkerosenelamps,etc.)in the air exist, may discolor walls or cause odors.

Important: Vent-free heaters add moisture to the air.Although this is beneficial, installing heater in rooms without enough ventilation air may cause mildew to form from too much moisture. See Air for Combustion and Ventilation, page 6.

CHECK GAS TYPE

Use the correct gas type (natural or propane/ LP) for your unit. If your gas supply is not correct, do not install log set. Call dealer where you bought log set for proper type fireplace.

WARNING:Thisapplianceis equipped for either natural gas or propane/LPgas but not both. Gas type is indicated on the ratingplate.Fieldconversionisnot permitted.

INSTALLATION AND CLEARANCES

For Vent-Free Operation

WARNING: Maintain the minimumclearances.Ifyoucan, provide greater clearances from floor, ceiling and adjoining wall.

MINIMUM FIREPLACE CLEARANCE TO

COMBUSTIBLE MATERIALS

Side Wall 16", Ceiling 42", Front 36"

Carefully follow these instructions. This will ensuresafeinstallationintoamasonry,UL127listedmanufacturedfireplace or listedvent-free firebox.

113093-01H

www.desatech.com

9

Installation

Continued

LOG SIZING REQUIREMENTS

Minimum Firebox

Log

Front

Rear *

Size

Height Depth Width

Width

18" 17" 14" 24" 20"

24" 17" 14" 28" 21"

30" 17" 14" 34" 24"

* Measured at 14" depth.

Minimum Clearances For Side Combustible Material, Side Wall and Ceiling

A.Clearances from the side of the fireplace cabinet to any combustible material and wall should follow diagram in Figure 4.

Example: The face of a mantel, bookshelf, etc. is made of combustible material and protrudes 3 1/2" from the wall. This combustible material must be 4" from the side of the fireplace cabinet (see Figure 4).

Note: When installing your gas logs into a manufactured firebox, follow firebox manufacturer’s instructions for minimum clearances to combustible materials.

B.Clearances from the top of the fireplace opening to the ceiling should not be less than 42".

NOTICE: Manual control heaters maybeusedasaventedproduct.

If so, you must always run heater with chimney flue damper open. If running heater with damper open, noncombustible material above fireplace opening is not needed. Go to Installing Damper Clamp Accessory for Vented

Operation, page 12.

Example

*

*Minimum 16 inches from Side Wall

Figure 4 - Minimum Clearance for Combustible to Wall

Minimum Noncombustible Material

Clearances If Not Using Mantel

Note: If using a mantel proceed to If Using Mantel, page 11. If not using a mantel, follow the information on this page.

You must have noncombustible material(s) above the fireplace opening. Noncombustible materials(suchasslate,marble,tile,etc.)must beatleast1/2inch thick. With sheet metal, you must have noncombustible material behind it. Noncombustible material must extend at least 8" up (for all models). If noncombustible material is less than 12", you must install the fireplace hood accessory (24" and 30"

Models Only). See Figure 5 for minimum clearances.

Noncombustible

 

 

Requirements for Safe

Material Distance

 

 

 

 

 

Installation

(A)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12" or more

Noncombustible material

 

 

okay.

Between 8" and

24" or 30" Models: Install

12"

 

fireplace hood accessory

 

 

(GA6050, GA6052 or

 

 

GA6053 see Accesso-

 

 

ries, page 31).

 

 

18" Model: Noncombus-

 

 

tible material okay.

Less than 8"

Noncombustible material

 

 

must be extended to at

 

 

least 8". See Between

 

 

8" and 12", above. If you

 

 

cannot extend material,

 

 

you must operate heater

 

 

with flue damper open.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 5 - Heat Resistant Material (Slate,

Marble, Tile, etc.) Above Fireplace

10

www.desatech.com

113093-01H

Installation

Continued

If Using Mantel

You must have noncombustible material(s) above the fireplace opening. Noncombustible materials(suchasslate,marble,tile,etc.)must be at least 1/2" thick. With sheet metal, you must have noncombustible material behind it. Noncombustible material must extend at least 8 inches up (for all models). If noncombustible material is less than 12", you must install the fireplace hood accessory (24" and 30" Models Only). Even if noncombustible material is more than 12", you may need the hood accessory to deflect heat away from your mantel shelf. See Figure 5, page 10, and Figures 6 and 7 for minimum clearances.

 

 

10"

 

Mantel Shelf

 

 

 

 

 

 

 

 

 

 

8"

 

 

 

Underside of

 

 

6"

 

 

 

Mantel Shelf

 

 

2 ½"

 

 

 

 

 

Minimum

 

(A)

 

 

 

 

Log Set

Noncombustible

 

 

 

 

 

 

 

 

24"/30"

 

 

 

 

 

Material

 

 

 

 

 

 

 

12"

18"

20"

22"

24"

Models

 

 

8"

8"

14"

17"

20"

18" Model

 

 

 

 

 

 

Top of

 

 

 

 

 

 

Fireplace

 

 

Minimum Non-

Distances to Opening

 

 

Combustible

 

Underside of

 

 

 

Material Height

Mantel

 

 

Figure 6 - Minimum Mantel Clearances

 

Without Using Hood

 

 

 

 

12"

Mantel Shelf

 

 

 

 

 

 

 

 

 

 

10"

 

 

 

 

Undersid

 

 

8"

 

 

 

 

 

 

 

 

 

 

of Mante

 

 

6"

 

 

 

 

Shelf

 

 

2½"

 

 

 

 

 

Minimum

Noncombustible

Material

8"

12"

15"

18"

20"

 

Min.

 

 

 

 

 

Hood

 

 

 

Top of

 

Distances to

Fireplac

 

(GA6050,

Underside of

Opening

 

GA6052 or

Mantel

 

 

 

GA6053)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IMPORTANT: If you cannot meet these minimum clearances, you must operate heater with chimney flue damper open. Go to Installing Damper Clamp Accessory for Vented Operation, page 12.

Mantel Clearances

In addition to meeting noncombustible material clearances, you must also meet required clearances between fireplace opening and mantel shelf. If you do not meet the clearances listed below, you will need a hood.

Determining Minimum Mantel Clearance

If you meet minimum clearance between mantel shelf and top of fireplace opening, a hood is not required (see Figure 6).

Determining Minimum Mantel Clearance When Using a Hood

If minimum clearances in Figure 6, are not met, you must have a hood. When using a hood there are still certain minimum mantel clearances required. Follow minimum clearances shown in Figure 7 when using hood.

NOTICE: Surface temperatures of adjacent walls and mantels become hot during operation.

Walls and mantels above the firebox may become hot to the touch. If installed properly, these temperatures meet the requirement of the national product standard. Follow all minimum clearances shown in this manual.

Notice:Ifyourinstallationdoes not meet the minimum clearances shown, you must do one of the following:

operate the logs only with the flue damper open

raise the mantel to an acceptable height

remove the mantel

Figure 7 - Minimum Mantel Clearances

When Using Hood

113093-01H

www.desatech.com

11