Desa CGR50BNA, CGR65BNA, CGR65NA, CGR50NA, CGR35NA User Manual

0 (0)

®

VENTED NATURAL

GAS HEATERS

OWNER’S OPERATION AND INSTALLATION MANUAL

Models: CGR65BNA, CGR65NA, CGR50BNA, CGR50NA, CGR35NA

WARNING: If the information in this manual

WARNING: Improper installation,

is not followed exactly, a fire or explosion

adjustment, alteration, service, or

may result causing property damage, per-

maintenance can cause property

sonal injury, or loss of life.

damage, personal injury or loss of

 

FOR YOUR SAFETY

life. Refer to this manual for cor-

— Do not store or use gasoline or other

rect installation and operational

flammable vapors and liquids in the

procedures. For assistance or

vicinity of this or any other appliance.

additional information consult a

— WHAT TO DO IF YOU SMELL GAS

qualified installer, service agency,

• Do not try to light any appliance.

or the gas supplier.

Do not touch any electrical switch; do not use any phone in your building.

Immediately call your gas supplier from

a neighbor’s phone. Follow the gas supplier’s instructions.

• If you cannot reach your gas supplier,

call the fire department.

®

 

Installation and service must be performed by a qualified installer, service agency, or the gas supplier.

Save this manual for future reference.

CONTENTS

2

SECTION

PAGE

Safety Information .........................................................................

3

Product Identification ....................................................................

5

Local Codes ...................................................................................

6

Unpacking ....................................................................................

6

Product Features ............................................................................

6

Installing Heater ............................................................................

6

Check Gas Type ......................................................................

6

Installation Items .....................................................................

6

Locating Heater .......................................................................

7

Venting Heater ........................................................................

8

Connecting to Gas Supply ......................................................

11

Checking Gas Connections .....................................................

13

Installing Radiants ..................................................................

14

Installing Glass Panel .............................................................

15

Air For Combustion and Ventilation .............................................

17

Determining Fresh-Air Flow for Heater Location

 

Example 1: Locating Heater in Unconfined (Open) Area 18

Draft Hood Spillage Test ............................................

18

Providing Permanent Fresh-Air Ventilation ..............

19

Example 2: Locating Heater in Confined (Closed) Area ..

20

Ventilating Confined Area .........................................

20

Operating Heater ...........................................................................

21

For Your Safety Read Before Lighting ..................................

21

Lighting Instructions ...............................................................

21

Manual Lighting Procedure ....................................................

23

Blower Operation (For Models with Blower) ........................

23

To Turn Off Gas To Appliance ..............................................

23

Inspecting Pilot and Burner Flame ................................................

24

Pilot Flame Pattern ..................................................................

24

Burner Flame Pattern ..............................................................

24

Cleaning and Maintenance ............................................................

26

Troubleshooting .............................................................................

27

Service Procedures ........................................................................

32

Removing Control Valve and Burner Tube ............................

32

Removing Burner ....................................................................

33

Changing Burner Orifice ........................................................

34

Blower Wiring Diagram ................................................................

34

Technical Service ..........................................................................

35

Specifications ................................................................................

35

Service Hints .................................................................................

35

Ordering Replacement Parts ..........................................................

36

Parts Centrals .................................................................................

36

Accessories ....................................................................................

37

Illustrated Parts List ......................................................................

38-41

Warranty Information ....................................................................

Back Cover

100792

SAFETY INFORMATION

WARNINGS

IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, operate, or service this heater. Improper use of this heater can cause serious injury or death from burns, fire, explosion, electrical shock, and carbon monoxide poisoning.

DANGER

WARNING ICON

G 001

Carbon monoxide poisoning may lead to death!

Carbon Monoxide Poisoning: Early signs of carbon monoxide poisoning resemble the flu, with headaches, dizziness, or nausea. If you have these signs, the heater may not be operating or venting properly. Get fresh air at once! Have heater or heater venting system serviced. Some people are more affected by carbon monoxide than others. These include pregnant women, people with heart or lung disease or anemia, those under the influence of alcohol, and those at high altitudes.

Natural Gas: Natural gas is odorless. An odor-making agent is added to natural gas. The odor helps you detect a natural gas leak. However, the odor added to natural gas can fade. Natural gas may be present even though no odor exists.

Make certain you read and understand all Warnings. Keep this manual for reference. It is your guide to safe and proper operation of this heater.

1.A qualified service person must install heater and venting system.

2.Use only natural gas. Do not convert heater to use different fuel type.

3.If you smell gas

Shut off gas supply.

Do not try to light any appliance.

Do not touch any electrical switch; do not use any phone in your building.

Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.

If you cannot reach your gas supplier, call the fire department.

4.This heater must have fresh air for proper operation. If not, poor fuel combustion and improper venting of flue gases will result. Carbon monoxide poisoning from backed-up flue gases could occur. The State of California lists carbon monoxide as a reproductive toxin under Proposition 65. Read the instructions under Air for Combustion and Ventilation, pages 17 through 20 for complete information.

5.Never install the heater

in a mobile home or a recreational vehicle.

where curtains, furniture, clothing, or other flammable objects are less than 48 inches from the front, 53 inches from top, or 12 inches from right side and 6 inches from left side and back of heater.

directly on carpeting, tile, or other combustible materials other than wood flooring. Place heater on metal or wood panel extending the full width and depth of heater.

as a fireplace insert.

in high traffic areas.

in windy or drafty areas.

Continued

3

100792

SAFETY INFORMATION

Continued

4

WARNINGS Continued

WARNING ICON

G 001

6.Provide the following minimum heater clearances from combustibles (as viewed from the front of heater):

Front: 48 inches

Back: 6 inches

Top: 53 inches

Right Side: 12 inches

Left Side: 6 inches

7.Do not run heater

where flammable liquids or vapors are used or stored

under dusty conditions

8.Never place clothing or any flammable objects on the heater or venting system.

9.Heater and venting system surfaces are very hot during operation. Keep children and adults away from hot surfaces to avoid burns or clothing ignition. Carefully supervise young children when they are in the same room as heater. Heater will remain hot for a time after shutdown. Let surface cool before touching.

10.Do not use heater as a cooking device.

11.Do not alter heater or its controls. Any change may create a safety hazard.

12.Turn off heater and unplug (if equipped with blower) and let cool before servicing. Unless you need gas supply for testing, shut off manual shutoff valve before servicing. Only a qualified service person should service and repair heater and venting system.

13.Replace any safety screen or guard removed for servicing before running heater.

14.Do not use heater if any part has been under water. Immediately call a qualified service person to inspect the heater and to replace any part of the control system and any gas control which has been under water.

100792

Desa CGR50BNA, CGR65BNA, CGR65NA, CGR50NA, CGR35NA User Manual

PRODUCT IDENTIFICATION

Control

Blower Switch

(on models

Knob

equipped with

 

blower)

Ignitor

Button

Burner

Radiants

Lower Front

Access Panel

Figure 1 - Vented Natural Gas Heater

Draft Hood

Outlet for

Venting

System

Control

Valve

Blower (on models

equipped with blower)

Figure 2 - Vented Natural Gas Heater, Rear View

5

 

 

100792

LOCAL CODES

UNPACKING

PRODUCT

FEATURES

INSTALLING HEATER

6

Install and use heater with care. Follow all local codes. In the absence of local codes, use the latest edition of the following:

National Fuel Gas Code ANSI Z223.1, also known as NFPA 54 *

National Electrical Code ANSI/NFPA 70 *

*Available from: American National Standards Institute, Inc. 1430 Broadway

New York, NY 10018

National Fire Protection Association, Inc.

Batterymarch Park

Quincy, MA 02269

1.Remove heater from carton.

2.Remove all protective packaging applied to heater for shipment.

3.Check heater for any shipping damage. If heater is damaged, promptly inform dealer where you bought heater.

Piezo Ignition System

This heater has a piezo ignitor. This system requires no matches, batteries, or other sources to light heater.

Thermostatic Heat Control

This heater has a thermostat sensing bulb and a control valve. This results in the greatest heating comfort. This can also result in lower gas bills.

WARNING

WARNING ICON

G 001

A qualified service person must install heater and venting system. Have them inspect heater before use and at least annually. Follow all local codes.

NOTICE

This heater must be electrically grounded if equipped with blower. Follow all local codes. In the absence of local codes, follow the National Electric Code, ANSI/NFPA 70.

CHECK GAS TYPE

Use only natural gas. If your gas supply is not natural gas, do not install heater. Call dealer where you bought heater for proper type heater.

INSTALLATION ITEMS

Before installing heater, make sure you have all items below.

piping (check local codes)

sediment trap

sealant (resistant to propane gas)

tee joint

• manual shutoff valve *

• pipe wrench

ground joint union

venting materials

test gauge connection * (see Figure 7, page 12)

* An A.G.A. design-certified manual shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the optional A.G.A. design-certified manual shutoff valve from your dealer. See Accessories, page 37.

100792

INSTALLING HEATER

Continued

LOCATING HEATER

WARNING

WARNING ICON

G 001

Maintain the minimum clearances shown in Figure 3, below. If you can, provide greater clearances.

WARNING ICON G 001 WARNING

Never install the heater

in a mobile home or a recreational vehicle.

where curtains, furniture, clothing, or other flammable objects are less than 48 inches from the front, 53 inches from the top, 12 inches from the right side and 6 inches from the left side and back of heater.

directly on carpeting, tile, or other combustible materials other than wood flooring. Place heater on metal or wood panel extending the full width and depth of heater.

as a fireplace insert.

in high traffic areas.

in windy or drafty areas.

CAUTION

WARNING ICON

G 001

If you install the heater in a home garage

heater pilot and burner must be at least 18 inches above floor

locate heater where moving vehicle will not hit it.

For convenience and efficiency, install heater

where there is easy access for operation, inspection, and service.

in coldest part of room.

near an electrical outlet if heater has blower or if you are planning to add blower to heater. See Accessories, page 37 for blower.

 

CEILING

6"

 

Minimum

53"

 

Minimum

Left

Right

 

 

Side

 

 

Side

 

 

 

 

 

 

 

6" Minimum

 

 

 

from Back

 

 

 

12"

 

 

48" Minimum from

Minimum

 

 

 

 

 

Front of Heater

Continued

 

 

Figure 3 - Heater Clearances

7

 

 

100792

INSTALLING HEATER

Continued

8

VENTING HEATER

Note: Venting/chimney materials are not supplied with heater.

WARNING

A qualified service person must install the venting system for this heater. If venting system is not properly installed and maintained, the vent safety shut-off system will prevent the heater from running. Follow all local codes.

WARNING

This heater has a vent safety shut-off system. This system shuts off the heater gas supply if you do not vent heater properly or the venting system is blocked. Do not operate heater if not properly vented. Do not tamper with the vent safety shut-off system. Carbon monoxide poisoning and death may result.

WARNING

When venting this heater, follow the safety information listed below.

Never vent heater to another room or inside a building. Only vent heater to the outdoors.

Do not vent heater exhaust to a chimney or flue serving another solid-fuel-burning or gas appliance.

We recommend you use flues classified as prefabricated or masonry all-fuel chimney or type-B vent. See

Vent Types, page 10.

If using old vent, check vent for soot, creosote, and loose particles. If vent is damaged, repair or replace it before using heater.

Extend the vertical section of vent pipe at least three feet above roof penetration.

Extend the vertical section of vent pipe at least two feet above the highest point of any roof within ten feet.

The horizontal run of vent pipe should rise at least 1/4 inch for each foot of run.

Support the vent pipe at least every five feet along its length. Do not use combustible materials to support vent pipe.

Never extend vent pipe horizontally through outside wall and terminate. You must connect a vertical run of vent pipe to the horizontal run. The vertical run must be at least 25% longer than the horizontal run.

Install vent or chimney cap that is approved for use with vented gas room heaters.

Do not use vent pipe smaller in diameter than that of the heater draft hood outlet.

Do not use dampers in the vent pipes.

Vertical height of vent must be greater than five feet above vent connection at draft hood.

100792

INSTALLING HEATER

Continued

VENTING HEATER (continued)

WARNING

Do not vent heater in any of the following ways (see Figure 4)

Heater must be vented to the out-

The vertical section of vent pipe must

doors. Never vent heater to another

extend at least two feet above the

room or inside a building.

highest point of any roof within ten

 

 

 

 

 

feet.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Never extend vent pipe horizontally

Never extend vent pipe horizontally

through a chimney or flue. You must

through outside wall and terminate.

connect a vertical run of vent pipe to

You must connect a vertical run of

the horizontal run. The vertical run

vent pipe to the horizontal run. The

must be at least 25% longer or five

vertical run must be at least 25%

feet minimum than the horizontal run.

longer than the horizontal run.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Less than 5' between elbows

Vertical run of pipe must be at least five feet from elbow to elbow.

Figure 4 - Improper Venting Systems

Continued

 

9

 

 

 

 

 

 

100792

Terminate at least 5' above draft hood. If vent extends over 5' above roof, support with guy wires or braces.

INSTALLING

VENTING HEATER (continued)

HEATER

Proper Size Vent

 

To safely vent heater, the vent connector pipe must be the same diameter as the draft Continued hood outlet on the rear of the heater. Pipe that is too small can cause flue gas to spill

from the heater. Fasten vent connector to the draft hood outlet with a sheet metal screw.

Vent Types

Prefabricated or Masonry All-Fuel Chimney - This is a masonry chimney or a residential-type prefabricated chimney. Only use prefabricated chimneys listed by Underwriters Laboratories (UL), Inc.

Type-B Vent - These vents are made of noncombustible, corrosion resistant material. They are certified by a nationally recognized testing agency. Type-B vents are double-walled pipe. Clearances to combustible construction must be in accordance with the listing of the particular type-B vent. Type-B vents are currently listed as B-1, B-1 1/2, and B-2.

The illustrations below show both vent types. The illustration shows typical construction of each type of venting system. Minimum clearances and lengths are added to the illustrations.

Vent Cap

Seal Around

Collar and

Must Be At

Flashing

Least 2 Feet

 

Above

 

Highest Point

 

Within 10

 

Feet.

 

 

Maintain Listed

 

Lock

 

Clearance of Vent

 

 

 

Joints

 

 

 

 

 

Position

Support

 

 

Firestop

 

Support If

Laterals

 

 

 

 

 

 

Necessary

 

 

 

Lock Joints

Maintain Listed

 

 

Clearance of

53"

 

6"

Vent

5'

 

Min.

Min.

Min.

Vertical Vent

 

 

 

Lock Joints

 

 

 

Heater

Heater

 

 

Vent

 

 

 

 

 

Connector

 

 

 

Prefabricated or Ma-

Type-B Vent

 

sonry All-Fuel Chimney

Continued

 

 

10

Figure 5 - Typical Construction of Venting Systems

 

 

 

 

 

 

100792

INSTALLING HEATER

Continued

CONNECTING TO GAS SUPPLY

WARNING

A qualified service person must connect heater to gas supply. Follow all local codes.

WARNING

Never connect heater to private (non-utility) gas wells. This gas is commonly known as well-head gas.

IMPORTANT: Check gas line pressure at gas meter before connecting heater to gas line. Gas line pressure must be no greater than 14 inches of water. If gas line pressure is higher, heater regulator damage could occur.

Gas Meter

Figure 6 - Connecting Heater to Utility Gas Line

CAUTION

Use only new, black iron or steel pipe. Internally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe that is 1/2" in diameter or greater to allow proper gas volume to heater. If pipe is too small, undue loss of pressure will occur.

The gas supply line to your heater must be 1/2 inch in diameter or larger. If the supply line branches to serve two or more heaters, the line from the branch back to the gas meter must be doubled or tripled, etc., in size (depending upon the number of heaters). Example for 1/2 inch diameter supply line: If the supply line branches to serve two heaters, the line diameter from the branch back to the gas meter must be at least 1 inch. If three heaters are served, the line diameter from the branch back to the gas meter must be at least 1 1/2 inches.

Note: If gas supply line total length exceeds forty feet, use a larger diameter pipe.

Use pipe that is the next size larger than the heater control valve fitting.

11

100792

INSTALLING HEATER

Continued

12

Installation must include a manual shutoff valve, ground joint union, plugged 1/8" NPT tap, and a sediment trap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from heater (see Figure 7).

Apply pipe joint sealant lightly to male threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.

CAUTION

Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.

Install sediment trap in supply line as shown in Figure 7. Locate sediment trap where it is within reach for cleaning. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater may not run properly.

IMPORTANT: Use two pipe wrenches when connecting gas piping to gas control valve of heater. This will prevent turning or damaging control valve.

 

Acceptable

 

construction

Control

of inlet gas

line

Valve

 

 

 

 

From Gas

 

 

 

Meter (5" W.C.

 

 

Manual

Min** to 7"

 

 

W.C. Max)

 

 

Shutoff

 

Ground

Valve *

 

 

 

Joint

 

 

 

Union

 

 

Preferred

 

 

 

construction

 

 

 

of inlet gas

 

Reducer

 

line

 

 

 

 

Bushing to

 

 

Test

1/8" NPT

 

 

1/8" NPT

 

From

Gauge

 

 

Gas

Connection*

Plug Tap

Tee Joint

Meter (5"

 

Tee Joint

 

Pipe

W.C.

 

 

 

Sediment

Min** to

 

Nipple

 

Trap

7" W.C.

 

 

Cap

Max)

 

Figure 7 - Gas Connection

*An A.G.A. design-certified manual shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the optional A.G.A. design-certified manual shutoff valve from your dealer. See Accessories, page 37.

**For purposes of input adjustment.

100792

INSTALLING HEATER

Continued

CHECKING GAS CONNECTIONS

WARNING

Test all gas piping and connections for leaks after installing or servicing. Correct all leaks at once.

WARNING

Never use an open flame to check for a leak. Apply a mixture of liquid soap and water to all joints. Bubbles forming show a leak. Correct all leaks at once.

Pressure Testing Gas Supply Piping System

Test Pressures In Excess of 1/2 PSIG

1.Disconnect heater and its individual manual shutoff valve from gas supply pipe. Pressures in excess of 1/2 PSIG will damage heater regulator.

2.Cap off open end of gas pipe where manual shutoff valve was connected.

3.Pressurize supply piping system by either using compressed air or opening main gas valve located on or near gas meter.

4.Check all joints of gas supply piping system. Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.

5.Correct all leaks at once.

Test Pressures Equal To or Less Than 1/2 PSIG

1.Close manual shutoff valve (see Figure 8).

2.Pressurize supply piping system by either using compressed air or opening main gas valve located on or near gas meter.

3.Check all joints from propane supply tank to manual shutoff valve. Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.

4.Correct all leaks at once.

Pressure Testing Heater Gas Connections

1.Open manual shutoff valve (see Figure 8).

2.Open main gas valve located on or near gas meter.

3.Make sure control knob of heater is in the OFF position.

4.Check all joints from manual shutoff valve to control valve on heater. Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Light heater (see Operating Heater, pages 21 through 23). Check the rest of the internal joints for leaks.

7.Turn off heater (see To Turn Off Gas to Appliance,page 23).

PO On Position

Off Position

Figure 8 - Manual Shutoff Valve

Continued 13

100792

INSTALLING HEATER

Continued

14

INSTALLING RADIANTS

WARNING

WARNING ICON

G 001

Carefully handle the glass panel. Glass edges are rounded and buffed to prevent cuts, however, chipped or broken sections of glass can present sharp edges. These sharp edges can cut skin.

1.Remove glass guard from across opening at front of heater (see Figure 8).

2.Place radiants into combustion chamber through opening at front of heater. Front of radiant sits on front radiant support (see Figure 9, page 14). Back of radiant rests on back radiant support (see Figures 8 and 9).

Note: Radiants should never come in contact with burner flame. Contact with flame may cause carbon or soot deposits on radiants.

Burner

Glass

Guard

Combustion

Chamber

Back Radiant

Support

Lower

Front Access

Panel

Lower Front

Access Area

Glass Retaining Channel

Figure 9 - Location of Radiants

Back Radiant Support

Radiant

Front Radiant

Support

Burner

Figure 10 - Position of Radiant

100792