Extension Digital I/O Module

Instruction Sheet

Warning

3Please read this instruction carefully before use.

3DOP series Extension Digital I/O Module should be used with DOP-AE series HMI product. Ensure to switch off the power before wiring.

3Please install this DOP series Extension Digital I/O Module in an enclosure free of airborne dust, humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device (e.g. key or specific tools are required for opening the enclosure) in case danger and damage on the device may occur.

3DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check all the wiring again before switching on the power.

3DO NOT touch any internal circuit in 1 minute after the power is switched off. Do NOT touch any terminal when the power is switched on.

3Make sure the ground terminal is correctly grounded in order to prevent electromagnetic interference.

3DO NOT place any heavy objects on the connection port of DOP series Extension Digital I/O Module. Doing so may damage the product.

X Introduction

1.1 Model Explanation

 

DOP

-

EXIO

14

R

AE

(1)

 

(2)

 

(3)

(4)

(5)

 

 

 

 

 

 

 

 

 

(1)

Product Name

 

 

 

DOP: Delta Operation Panel

 

 

 

 

 

 

 

 

 

 

 

 

(2)

Series

 

 

 

 

EXIO: Extension Digital I/O

 

 

 

 

 

 

 

 

 

 

 

(3)

Input / Output Point

 

 

14: 8 input points / 6 output points

 

 

 

 

28: 16 input points / 12 output points

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(4)

Output Contact Type

 

 

R: Relay

 

 

 

 

 

 

 

 

 

 

 

 

 

(5) Applicable HMI Series

 

 

AE: DOP-AE Series HMI

 

 

 

 

 

 

 

 

 

 

 

1.2 Product Outline

3

1

4

2

1.Connection Port

2.Direct Mounting Hole

3.Input / Output Terminals

4.Nameplate

1.3 Model Name

Model Name

 

 

Input / Output

 

 

Power

Input Unit

Output Unit

 

Point

Type

Point

Type

 

 

DOP-EXIO14RAE

 

8

DC Type

6

Relay

 

 

 

 

 

 

 

 

Sink or

 

 

 

 

 

DOP-EXIO28RAE

 

5VDC,

16

12

Relay

 

 

Source

 

 

 

 

 

supplied

 

 

 

 

 

 

 

 

 

 

 

 

by HMI

 

 

 

 

 

 

 

Y Function Specifications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Item

 

 

 

Specifications

 

 

 

 

Remark

Control Method

 

 

Stored program, cyclic scan system

 

-

 

 

 

I/O Processing Method

 

 

Batch I/O (refresh)

 

 

 

Immediate refresh command available

 

 

 

 

 

only with I/O of the MPU

 

 

 

 

 

 

 

 

 

 

Execution Speed

 

 

Basic command (average approx. 30

 

Application command (30 ~ hundreds

 

 

us)

 

 

 

us)

 

 

 

 

 

 

 

 

 

 

 

Program Language

 

 

Commands + Ladder Diagram +

 

Step commands included

 

 

SFC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Item

 

 

Specifications

 

Remark

Program Capacity

 

999 Steps

 

Built-in EEPROM

Commands

 

Basic commands: 32 (including the

 

Application commands: 59

 

STL commands)

 

 

 

 

 

 

 

 

Step Relay

 

 

General

 

128 Points

 

S10 ~ S127

(Latched)

 

 

Step Point

 

 

 

 

 

 

 

 

Auxiliary

 

 

General

 

1280 Points

 

M0 ~ M511, M768 ~ M999, 744 points;

 

 

 

 

M1000 ~ M1279, 280 points*1

 

 

 

 

 

Relay

 

 

Latched

 

256 Points

 

M512 ~ M767

 

 

 

 

 

Timer

 

 

Digital

 

64 Points

 

T0~T63 (100 ms time base)

 

 

 

63 Points

 

T64~T126 (10 ms time base)

 

 

 

 

 

1 Points

 

T127 (1 ms time base)

 

 

 

General

 

112 Points

 

C0 ~ C111

Counter

 

 

Latched

 

16 Points

 

C112 ~ C127

 

 

 

 

 

 

C235,C236,C237,C238,C241,C242,

 

 

 

32bit

 

13 Points

 

C244,C246,C247,C249,C251,C252,

 

 

 

 

 

 

 

C254 (all of them are latched type)

Data Register

 

General

 

408 Points

 

D0 ~ D407

 

Latched

 

192 Points

 

D408 ~ D599

 

 

 

 

 

Pointer

 

 

P

 

64 Points

 

P0 ~ P63

Index

 

 

E / F

 

2

 

E, F

Register

 

 

 

 

 

 

 

 

 

 

 

Constant

 

 

Decimal K

 

16bit: -32768 ~ +32767

 

32bit: -2147483648 ~ +2147483647

 

 

Hexadecim

 

16bit: 0000 ~ FFFF

 

32bit: 00000000 ~ FFFFFFFF

 

 

 

al H

 

 

 

 

 

 

 

 

 

Self Diagnosis / Protection

 

I/O check, system execution timeout check, invalid command check, program

 

check and password settings

 

 

 

 

 

 

 

 

 

Monitor / Debug

 

Program execution time display, bit / word, device settings

*1: M1000, M1001, M1002, M1003, M1020, M1021, M1022, M1067, M10068, and M1161 are the special auxiliary relays (special M).

Z Electrical Specifications

Item / Model Name

 

DOP-EXIO14RAE

 

 

DOP-EXIO28RAE

Power Supply Voltage

 

5VDC, 1A (supplied by HMI)

Power Consumption

 

0.25W

 

 

0.5W

 

 

RS: Frequency: 80MHz ~ 1GHz,

 

1.4GHz ~ 2.0GHz, Test level 10V/m

 

 

CS: Frequency: 0.15MHz ~ 80MHz, Test level 10V (HMI power port & I/O line)

Noise Immunity

 

ESD: Air discharge ±8KV

 

EFT: ±1.5KV (HMI power port)

 

 

 

 

 

±1KV (I/O line)

 

 

Surge: ±2KV (HMI power port)

Ambient Temperature /

 

Operation: 0°C ~ 50°C (Temperature), 10 ~ 90% (Humidity),

Humidity

 

Storage: -40°C ~ 85°C (Temperature), 10 ~ 90% (Humidity)

 

 

 

IEC 61131-2 Compliant

Vibration / Shock

 

5Hz f 9Hz = Continuous: 1.75mm / Occasional: 3.5mm

 

9Hz f 150Hz = Continuous: 0.5g / Occasional: 1.0g

 

 

 

 

X, Y, Z directions for 10 times

Weight

 

Approx. 95.5g

 

 

Approx. 116g

 

 

Input Point Electric Specifications

 

 

Input Type

 

DC (SINK or SOURCE)

Input Voltage

 

24VDC (5mA)

Active Level

 

Off→On, above 16VDC

 

On→Off, below 14.4VDC

 

 

Response Time

 

Approx. 10ms

 

 

Output Point Electric Specifications

 

 

Output Type

 

Relay-R

Current Specifications

 

1.5A / 1 Point (5A/COM)

Voltage Specifications

 

250VAC, below 30VDC

Maximum Loading

 

75VA (Inductive)

 

90 W (Resistive)

 

 

Response Time

 

Approx. 10 ms

Mechanical Life

 

2 × 107 times (without load)

Electrical Life

 

100,000 times (3A 250VAC/30VDC)

 

6,000 times (5A 250VAC/30VDC)

 

 

[ Installation & Wiring

4.1 Wiring

2

1.Please use the 28-16 AWG (1.5mm ) single-core bare wire (Solid type) or the multi-core wire (Stranded type) for the I/O wiring. The stripped length of

 

 

 

22-16AWG

the wire should be 6-7mm, and the torque specification of the screw for the

 

 

 

 

 

 

 

 

terminal is 4.5lb-in. Please refer to the specifications of the terminal shown

 

 

 

 

in the figure on the left.

< 1.5mm

 

 

 

 

 

2.DO NOT place the I/O signal wires and power supply wire in the same wiring duct.

4.2 Caution

Environment

1.DO NOT install the Extension Digital I/O Module in a place subjected to corrosive or flammable gases, liquids, or airborne dust or metallic particles.

2.DO NOT install the Extension Digital I/O Module in a location high temperature and high humidity (where temperature and humidity will exceed specification).

3.DO NOT install the Extension Digital I/O Module in a location where vibration and shock will exceed specification.

Wiring Note

1.Please avoid any conductive debris and tiny metal materials enter the Extension Digital I/O Module when screwing and wiring.

2.Allow a minimum space of 50mm between the Extension Digital I/O Module and other control devices, and keep the Extension Digital I/O Module away from the high-voltage lines or any power equipment.

4.3 Terminal Identification

4.4Wiring

There are two types of DC inputs, SINK and SOURCE, and they are defined as follows:

Sink = (common port for current input S/S)

 

Source = (common port for current output S/S)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input Point Wiring (S/S shown in the wiring diagrams indicates SS1 or SS2 contact)

DC Signal IN

Input point loop equivalent circuit

 

 

 

Wiring loop

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SINK mode

DC Signal IN

 

 

 

 

 

Input point loop equivalent circuit

Wiring loop

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SOURCE mode

Output Point Wiring

Be careful with the connection of the common terminals

when wiring outputs. For example, when wiring

DOP-EXIO14RAE (DOP-EXIO28RAE), output terminal

Y0

(Y10) uses C0 (C10), Y1 (Y11) uses C1 (C11), Y2 ~

Y3

(Y12 ~ Y13) uses C3 (C13), Y4 ~ Y5 (Y14 ~ Y15)

uses C5 (C15), as shown below:

NOTE