LonWorks Communication Module (CME-LW01) Instruction Sheet

Lonworks is a registered trademark of Echelon Corporation.

Please thoroughly read and understand the following contents to ensure correct use before operation.

The content of this instruction sheet may be revised without prior notice. Please consult our distributors or download the most updated version at http://www.delta.com.tw/industrialautomation

A.Introduction

Device CME-LW01 is used for communication interface between Modbus and LonTalk. CME-LW01 needs be configured via LonWorks network tool first, so that it can perform the function on LonWorks network. No need to set CME-LW01 address.

This manual provides instructions for the installation and setup for CME-LW01 that is used to communicate with Delta VFD-E (firmware version of VFD-E should conform with CME-LW01 according to the table below) via LonWorks Network. The content of this instruction sheet may be revised without prior notice. Please consult our distributors or download the most updated version at http://www.delta.com.tw/industrialautomation.

 

 

Delta AC Drive

 

 

 

 

 

Series

Firmware Version

 

VFD-E

 

Version 2.02 or higher

 

Terminal definition for LonTalk system

 

Terminal

 

 

 

 

 

Function

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

These are twisted pair cables

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

to connect to LonTalk system.

 

 

 

 

 

 

 

 

Terminals 1 and 2 should be

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

used as one group, and the

 

 

 

 

 

 

 

 

same for terminals 3 and 4.

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E.LEDs Indications

There are three LEDs in front panel of CME-LW01. If the communication is normal, power LED, SP LED should be green (red LED means abnormal communication) and service LED should be OFF. If LEDs display do not match, refer to user manual for details.

B.Dimensions

72.2[2.84]

[2.35]59.7

[0.37]9.5

[2.26]57.3

 

 

SP

 

 

CME-LW 01

34.8 [1.37]

 

 

 

 

 

 

 

 

 

3.5 [0.14]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C.Specification

 

Power supply

 

16-30VDC, 750mW

 

Communication

 

Modbus in ASCII format, protocol: 9600, 7, N, 2

 

 

 

LonTalk

 

free topology with FTT-10A 78 Kbps

 

LonTalk terminal

 

4-pin terminal, wire gauge: 28-12 AWG, wire strip

 

 

length: 7-8mm

 

 

 

 

RS-485 port

 

8 pins with RJ-45

 

 

D.Wiring

Service LED

Service Pin

Power LED SP LED

 

 

 

 

 

 

 

 

 

 

 

 

 

1: Reserved

5: SG+

 

 

 

 

 

2: EV

6: Reserved

 

 

 

 

 

3: GND

7: Reserved

 

 

 

 

SP

4: SG-

8: Reserved

 

 

 

 

 

 

 

 

 

 

CME-LW01

 

1

2

3

4

 

 

 

LonTalk

LonTalk

Power LED

 

State

Description

 

Corrective Actions

 

 

Green LED

Power is on and

 

 

 

 

CME-LW01 works

 

 

 

 

 

 

 

 

 

 

Power on or program is

1.

Check if power is 24V or

 

 

LED is OFF

 

plug is loose.

 

 

abnormal

2.

Check if flash memory IC is

 

 

 

 

 

 

 

 

well-inserted to the socket.

 

SP LED

 

State

Description

 

Corrective Actions

 

Green LED

It communicates to AC

 

 

 

drive

 

 

 

 

 

 

 

Blinked Green

CME-LW01 reads default

 

 

 

LED

setting from AC drive

 

 

 

 

 

1.

Check if cable is loose.

 

Red LED

Disconnect or time-out

2.

Check if the communication

 

 

 

 

protocol is properly set.

Service LED

 

State

Description

Corrective Actions

 

 

LED blinks at

This is the normal

 

 

 

1/2 Hz rate

situation for an

 

 

 

un-configured device

 

 

 

 

 

 

 

LED is OFF

Bad hardware device

Check if anything wrong with

 

 

power supply, clock or

 

 

 

 

Neuron chip.

 

 

LED is ON

 

1. Check if anything wrong

 

 

continuously,

 

with power supply, clock or

 

 

even when

Bad hardware device

Neuron chip.

 

 

power is first

2. Check if there is a short

 

 

 

 

 

applied to the

 

circuit between pin 17 and

 

 

device.

 

18.

 

 

LED blinks at

 

If the device is not an

 

 

 

application-less, then it could

 

 

power-up,

This is the normal

 

 

be memory problems or

 

 

goes OFF,

situation for an

 

 

application code errors. A

 

 

then ON

application-less device.

 

 

self-test failure can also turn

 

 

solid.

 

 

 

 

the LED ON solid.

 

 

 

 

 

NOTE

Please download the XIF file and user manual at http://www.delta.com.tw/industrialautomation/