Notes and Warnings
NOTE: A NOTE indicates important information that helps you make better use of your software.
CAUTION: A CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or
moderate injury or in property damage incidents.
WARNING: A WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or
injury.
DANGER: A DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or
serious injury.
DANGER: Observe the following instruction to help prevent an imminently hazardous situation which, if not
avoided, will result in death or serious injury:
S This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by
AUTHORIZED SERVICE PERSONNEL ONLY.ThereareNO USER SERVICEABLE PARTS
inside the UPS.
Information in this document is subject to change without notice. E 2009 Dell Inc. All rights reserved.
Reproduction in any manner whatsoever without the written permission of Dell Inc. is strictly forbidden.
Trademarks used in this text: Dell and the DELL logo are trademarks of Dell Inc.; Phillips is a registered trademark of Phillips Screw Company.
Other trademarks and trade names may be used in this document to refer to either the entities claiming the marks and names or their products. Dell Inc. disclaims any proprietary interest in trademarks and trade names other than its own.
July 2009
System Features
Providing outstanding performance and reliability, the UPS's unique benefits include:
S Buck and Boost voltage regulation that ensures regulated voltage to your load by correcting voltage
fluctuations.
S Start-on-battery capability for powering up the UPS even if utility power is not available. S Extended runtime with an optional External Battery Module (EBM) for 1500–2700W UPS
models.
S 2700/2300W 3U UPS models only. Two-in-one form factor using the UPS in a rackmount
configuration or as a standalone cabinet.
S Emergency shutdown control through the Remote Emergency Power-off (REPO) ports. S Two standard communication ports (USB and DB-9 serial port). S Optional Dell Network Management Card with enhanced communication capabilities for
increased power protection and control.
S Advanced power management with the Dell UPS Management Software for graceful shutdowns
and power monitoring.
S Sequential shutdown and load management through separate receptacle groups called load
segments.
S Firmware that is easily upgradable without a service call. S Backed by worldwide agency approvals.
Getting Started With Your System
|
1
Finding Information
CAUTION: The Safety, Environmental, and Regulatory Information document provides important safety and
regulatory information.
What are You Looking For?
S The user's guide for my UPS S The user's guide for the Dell Network Management
Card
S Dell UPS Management Software
Find It Here
Dell UPS Disc
NOTE: Documentation and software updates can be
found at
S Specifications S How to configure UPS settings S How troubleshoot and solve problems S How to install REPO control S Safety instructions S Regulatory information S Recycling information
S Warranty information S Terms and Conditions (U.S. only) S End User License Agreement
S Support information Dell Support Website — support.dell.com
Dell UPS User's Guide
The user's guide is available on the Dell UPS disc and on support.dell.com.
Safety, Environmental, and Regulatory Information
Dell Warranty and Support Information
support.dell.com.
NOTE: Select your region or business segment to view
the appropriate support site.
|
2
Getting Started With Your System
Installation and Startup
CAUTION: Before performing the procedures in this document, read and follow the safety instructions and
important regulatory information in your Safety, Environmental, and Regulatory Information document.
This section describes the steps to set up your system for the first time.
Unpacking the System
1 Open the outer carton and remove the accessories packaged with the cabinet.
Getting Started With Your System
|
3
Lifting the Cabinet
CAUTION: The cabinet is heavy [1000W: 19.0 kg (41.8 lb); 1920/1500W: 31.0 kg (68.34 lb); 2700/2300W: 41.0 kg
(90.38 lb)]. Lifting the cabinets into the rack requires a minimum of two people.
1 Withonepersononeachside,carefullyliftthecabinet out of the outer carton using the handles
on the cardboard and set it on a flat, stable surface.
2 Discard or recycle the packaging in a responsible manner, or store it for future use.
|
4
Getting Started With Your System
Identifying the UPS
This section shows a front and rear panel of the Dell Line-Interactive Rack UPS. Refer to the Dell Line-Interactive Rack UPS 1000W, 1920/1500W, and 2700/2300W User's Guide for all rear panel details.
On/Off Button
Scroll Button (Up or Back)
LCD Panel
Scroll Button (Down or Forward)
Select Button
Figure 1. The Dell Line-Interactive Rack UPS Front Panel
REPO Ports
Ground Screw
UPS Communication Bay
USB Port
EBM Connector Cover/Strain Relief Bracket
Six 5-20 and Two IEC 320-C19 Receptacles
(Load Segment 1)
IEC-C14 Input
Connector
RS-232 Port
Two IEC 320-C13 Receptacles (Load Segment 2)
Figure 2. UPS Rear Panel (1920W/120V, 1500W/120V Shown)
Setting Up the UPS
If you are installing the UPS in a rack, continue to the following section, “Rackmount Setup.” To install the 2700W UPS as a standalone cabinet, continue to “Tower Setup” on page 12.
Getting Started With Your System
|
5
Rackmount Setup
CAUTION: The cabinet is heavy (1000W: 19.0 kg/41.9 lb; 1920/1500W: 30 kg/66.1 lb; 2700W: 42 kg/92.6 lb): 1) Dell
strongly recommends to remove the battery tray from the UPS before lifting. 2) Lifting the cabinets into the rack requires a minimum of two people.
CAUTION: Removing the batteries should be performed or supervised by personnel knowledgeable about
batteries and the required precautions. Keep unauthorized personnel away from batteries.
Opening the Battery Cover
1 Loosen the thumbscrew on the metal battery cover, slide the cover to the right, and open.
|
6
Getting Started With Your System
Removing the Battery Tray
2 Unclip the right battery connector and move the connector out of the way. 3 Pull the battery tray out using the plastic tabs and remove the battery tray.
Getting Started With Your System
|
7
Installing the Rails
NOTE: The instructions are the same for square-hole racks and unthreaded, round-hole racks. The rails fit both
rack styles. The square-hole rack is shown in the illustrations.
4 Select the proper holes in the rail for positioningtheUPSinthedesiredlocationintherack.
The rails should be located at the bottom of the 2U (or 3U for 2700/2300W UPS models) space allocated for the UPS or EBM.
5 Position the end of the left and right rails labeled FRONT facing inward.
|
8
Getting Started With Your System
6 Attach the rails to the rack:
Engage the back end of the rail until it fully seats on the vertical rack flange and the hook latch locks i n place.
Pull the rail toward the front.
Push the front end of the rail until it fully seats on the vertical rack flange and the hook latch locks in place.
Installing the Cabinet
7 Slide the cabinet into the rack. Repeat for any additional cabinets.
Getting Started With Your System
|
9
Securing the Cabinet
8 Secure the front of the cabinet to the rack using the thumbscrews on the mounting brackets.
Tighten by hand; do not use power tools. Repeat for any additional cabinets.
Installing the Battery Tray
NOTE: A small amount of arcing may occur when connecting the batteries. This is normal and does not damage
the unit or present any safety concern.
9 Connect the internal battery connector and reclip the right battery connector.
|
10
Getting Started With Your System
10 Close the metal battery cover.
Adjust the battery connector so that the door closes properly. Push the door slightly to the right and then to left.
11 Tighten the thumbscrew.
Torque the screw to 0.7 Nm (6.2 lb in).
Installing the UPS Front Cover
12 Install the UPS front cover. 13 Continue to “Connecting the Equipment” on page 15.
Getting Started With Your System
|
11
Tower Setup (2700W UPS models only)
CAUTION: The cabinet is heavy (2700W: 42 kg/92.6 lb). Lifting the cabinets into the pedestals requires a
minimum of two people.
Removing the Mounting Brackets and Rear Hold-Down Brackets
1 Remove the mounting brackets and the rear hold-down brackets from the UPS using a Phillips
#2 screwdriver
Connecting the Internal Battery Connector
2 Loosen the thumbscrew on the metal battery cover, slide the cover to the right, and open.
|
12
Getting Started With Your System
®
3 Connect the internal battery connector.
Rotating the UPS Control Panel Orientation
4 Rotate the control panel 90° counterclockwise. 5 Close the metal battery cover and tighten the thumbscrew.
Torque the screw to 0.7 Nm (6.2 lb in).
Getting Started With Your System
|
13
Installing the UPS Front Cover
6 Rotate the Dell logo 90° counterclockwise and install the UPS front cover.
Installing the Pedestals
NOTE: Dell recommends a minimum of 63.5 mm (2.5) free space behind the UPS rear panel, and a minimum of
127 mm (5”) between cabinets
7 Align the pedestals with the holes on the end of the cabinet. Push the pedestals in place.
|
14
Getting Started With Your System
8 Carefully position the cabinet upright.
Connecting the Equipment
1
If you plan to use Dell UPS Management Software, connect your computer to the USB port using the supplied cable.
2 If your rack has conductors for grounding or bonding of ungrounded metal parts, connect the
ground cable (not supplied) to the ground bonding screw.
3 If an emergency power-off (disconnect) switch is required by local codes, see “Installing Remote
Emergency Power-off” (REPO) in the Dell Line-Interactive Rack UPS 1000W, 1920/1500W, and 2700/2300W User's Guide.
4 Plug the equipment to be protected into the UPS output receptacles, but do not turn on the
protected equipment.
Verify that the total equipment ratings do not exceed the UPS capacity to prevent an overload alarm.
NOTE:
|
Getting Started With Your System
15
Connecting the Power Cord
5 Verify that the power input to the UPS has adequate upstream overcurrent protection:
Table 1. Minimum Upstream Circuit Breaker Rating
UPS Output Power
1000W 15A 15A 1500W (at 100V) 1920W 2700W 30A 20A 16A
120V 208V 230V
20A 15A
6 For models with a detachable power cord. Plug the detachable UPS power cord into the input
connector on the UPS rear panel.
7 Plug the UPS power cord into a power outlet.
For 1920/1500W models. There are two power cords in the box, one with BSMI and PSE certified
NOTE:
markings that can be used in Taiwan and Japan, another cord is for regions other than Taiwan and Japan.
|
16
Getting Started With Your System
Starting the UPS
8 Press the button on the UPS front panel.
Completing the Startup
9 Verify that the Normal icon appears on the UPS status summary screen, indicating that the
UPS is operating normally and any loads are powered.
10 On the UPS status summary screen, press the button to check for active alarms or notices.
Resolve any active alarms before continuing. See “Troubleshooting” in the Dell Line-Interactive Rack UPS 1000W, 1920/1500W, and 2700/2300W User's Guide.
If there are no active alarms, a “No Active Alarms” message appears.
11 To change other factory-set defaults, see “Operation” in the Dell Line-Interactive Rack UPS
1000W, 1920/1500W, and 2700/2300W User's Guide.
Getting Started With Your System
|
17
18
|
Getting Started With Your System
Onduleur en baie Line-Interactive Dellt
1000 W, 1920/1500 W et 2700/2300 W
Démarrage
avec votre système
www.dell.com | support.dell.com
K792N, H928N, K802N, H945N, J727N
J735N, K811N, H919N, J718N
Getting Started With Your System
|
19
Remarques et avertissements
REMARQUE : Une REMARQUE indique des informations importantes qui vous aident à mieux utiliser votre logiciel.
DANGER : Un DANGER indique une situation dangereuse imminente qui, si elle n'est pas évitée, provoquera la
mort ou une blessure grave.
AVERTISSEMENT : Un AVERTISSEMENT indique une situation dangereuse potentielle qui, si elle n'est pas évitée,
pourrait provoquer la mort ou une blessure.
ATTENTION : L'ATTENTION indique une situation dangereuse potentielle qui, si elle n'est pas évitée, peut
provoquer une blessure mineure ou légère ou des dommages matériels.
DANGER : Respectez les instructions suivantes pour aider à empêcher une situation dangereuse imminente qui, si
elle n'est pas évitée, peut provoquer la mort ou des blessures graves :
S Cet onduleur contient des TENSIONS MORTELLES. Toutes les réparations et tous les entretiens
devront être effectués UNIQUEMENT PAR UN PERSONNEL D'ENTRETIEN AGRÉÉ. Aucune pièce à l'intérieur de cet onduleur NE PEUT ÊTRE ENTRETENUE PAR L'UTILISATEUR.
Les informations dans ce document sont soumises à modifications sans préavis. E 2009 Dell Inc. Tous droits réservés.
La reproduction de quelque manière que ce soit sans autorisation écrite de Dell Inc. est strictement interdite.
Marques commerciales utilisées dans ce texte : Dell et le logo DELL sont des marques commerciales de Dell Inc. ; Phillips est une marque déposée de Phillips Screw Company.
D’autres marques commerciales et noms commerciaux peuvent être utilisés dans ce document pour se référer à des entités revendiquant les marques et les noms ou leurs produits. Dell Inc. rejette tout intérêt propriétaire dans les marques commerciales et les noms commerciaux ne lui appartenant pas.
Julliet 2009
|
20
Getting Started With Your System
Caractéristiques du système
Offrant une fiabilité et des performances remarquables, les avantages uniques de l'onduleur comprennent :
S La régulation de tension Buck and Boost qui assure une tension régulée à votre charge en
corrigeant les fluctuations de tension.
S La capacité de démarrage-sur-batterie pour alimenter l'onduleur même si le courant du secteur
n'est pas disponible.
S Temps d'exécution prolongé avec un Module de batterie externe (EBM) en option pour modèles
d'onduleur 1500–2700W.
S Modèles d'onduleurs 2700/2300 W 3U uniquement. Facteur de forme deux-en-un pour utilisation de
l'onduleur en baie ou en unité autonome.
S Commande d'arrêt d'urgence par les ports d'arrêt d'urgence distants (REPO). S Deux ports de communication standards (port série DB-9 et USB). S Carte de gestion de réseau Dell optionnelle avec capacités de communication améliorées pour une
protection et un contrôle accrus de l'alimentation électrique.
S Gestion avancée de l'alimentation électrique avec le Logiciel de gestion d'onduleur Dell pour des
coupures progressives et une surveillance de l'alimentation.
S Arrêt séquentiel et gestion de charge par des groupes de prises séparés appelés « segments de
charge ».
S Micrologiciel qui peut être facilement mis à niveau sans appeler le service technique. S Soutenu par des approbations d'organismes dans le monde entier.
Caractéristiques du système
|
21
Trouver des informations
ATTENTION! Le document Informations sur la sécurité, l'environnement et la réglementation fournit des
informations importantes sur la sécurité et la réglementation.
Que recherchez-vous ?
S Le guide d'utilisation de mon onduleur S Le guide d'utilisation de ma Carte de gestion de
réseau Dell
S Logiciel de gestion d'onduleur Dell
Trouvez-le ici
Disque de l'onduleur Dell
REMARQUE : Les mises à jour des documents et des
logiciels se trouvent sur
S Spécifications S Comment configurer les paramètres de l'onduleur S Comment identifier et résoudre les problèmes S Comment installer un contrôle REPO S Instructions sur la sécurit S Informations sur la réglementation S Informations sur le recyclage
S Informations sur la garantie S Termes et conditions (États-Unis uniquement) S Contrat de licence de l'utilisateur final
S Informations sur l'assistance Site Internet d'assistance Dell — support.dell.com
Guide d'utilisation de l'onduleur Dell
Le guide d'utilisation est disponible sur le disque de l'onduleur Dell et sur support.dell.com.
Informations sur la sécurité, l'environnement et la régle mentation
Informations sur l'assistance et la garantie Dell
support.dell.com.
REMARQUE : Sélectionnez votre région ou votre seg
ment commercial pour voir le site d'assistance approprié.
22
|
Trouver des informations
Installation et démarrage
ATTENTION! Avant de réaliser les procédures de ce document, lisez et suivez les instructions de sécurité et
les informations importantes sur la réglementation qui figurent dans votre document Informations sur la sécurité, l'environnement et la réglementation.
Cette section décrit les étapes de configuration de votre système pour la première fois.
Déballage du système
1 Ouvrez le carton extérieur et retirez les accessoires emballés avec le module.
Installation et démarrage
|
23
Levage du module
ATTENTION! Le module est lourd [1000 W : 19,0 kg (41,8 lb) ; 1920/1500 W : 31,0 kg (68,34 lb) ; 2700/2300 W :
41,0 kg (90,38 lb)]. Le levage des modules dans la baie exige deux personnes au minimum.
2 Avec une personne de chaque côté, levez soigneusement le module hors du carton extérieur en
utilisant les poignées du carton et posez-le sur une surface plane et stable.
3 Jetez ou recyclez l'emballage d'une façon responsable, ou conservez-le pour une utilisation
ultérieure.
24
|
Installation et démarrage
Identification de l'onduleur
Cette section montre un panneau avant et arrièredel'onduleurBaieLine-InteractiveDell. Reportez-vous au Guide d'utilisation de l'onduleur en baie Line-Interactive Dell 1000 W, 1920/1500 W et 2700/2300 W pour tous les détails sur le panneau arrière.
Bouton Marche/Arrêt
Bouton de défilement (haut ou arrière)
Panneau LCD
Bouton de défilement (bas ou avant)
Bouton de sélection
Figure 3. Panneau avant de l'onduleur Baie Line-Interactive Dell
Baie de
Ports REPO
Visdemiseàla
terre
communication de l'onduleur
Port USB
Serre-câble/Couvercle du connecteur EBM
Six prises 5-20 et deux prises CEI 320-C19
(Segment de charge 1)
Connecteur
d'entrée CEI-C14
Port RS-232
Deux prises CEI 320-C13 (Segment de charge 2)
Figure 4. Panneau arrière de l'onduleur (1920 W/120 V, 1500 W/120 V représenté)
Installation et démarrage
|
25
Configuration de l'onduleur
Si vous installez l'onduleur en baie, continuez à la section suivante, « Configuration en baie ». Pour installer l'onduleur 2700 W comme un module autonome, continuez à « Configuration en tour »,
àlapage32.
Configuration en baie
ATTENTION! Le module est lourd (1000 W : 19,0 kg/41,9 lb ; 1920/1500 W : 30 kg/66,1 lb ; 2700 W :
42 kg/92,6 lb) : 1) Dell recommande fortement de retirer le plateau de batteries de l'onduleur avant le levage.
2) Soulever les modules dans la baie exige deux personnes au minimum.
ATTENTION! Le retrait des batteries doit être réalisé ou supervisé par un personnel connaissant les batteries
et les précautions requises. Maintenez le personnel non autorisé éloigné des batteries.
Ouverture du couvercle des batteries
1 Desserrez la vis à oreilles sur le couvercle métallique des batteries, faites glisser le couvercle vers la
droite et ouvrez.
|
26
Installation et démarrage