Inductive sensor NCB2-V3-N0
Technical Data
General specifications
Switching function Normally closed (NC)
Output type NAMUR
Rated operating distance sn2 mm
Installation flush
Assured operating distance sa0 ... 1.62 mm
0102
Model Number
NCB2-V3-N0
Features
•2 mm flush
• Usable up to SIL 2 acc. to IEC 61508
Reduction factor r
Reduction factor rCu 0.2
Reduction factor r
Output type 2-wire
Nominal ratings
Nominal voltage Uo8.2 V (Ri approx. 1 kΩ)
Switching frequency f 0 ... 2000 Hz
Hysteresis H typ. 3 %
Current consumption
Measuring plate not detected
Measuring plate detected
Switching state indicator LED, yellow
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
MTTF
2180 a
d
Mission Time (TM) 20 a
Diagnostic Coverage (DC) 0 %
Ambient conditions
Ambient temperature -25 ... 100 °C (-13 ... 212 °F)
Mechanical specifications
Connection type cable PVC , 130 mm
Core cross-section 0.14 mm
Housing material PBT
Sensing face PBT
Degree of protection IP67
Cable
Bending radius
General information
Use in the hazardous area see instruction manuals
Compliance with standards and
directives
Standard conformity
NAMUR
Electromagnetic compatibility
Standards
Approvals and certificates
EAC conformity TR CU 012/2011
FM approval
Control drawing
UL approval cULus Listed, General Purpose
CSA approval cCSAus Listed, General Purpose
CCC approval CCC approval / marking not required for products rated ≤36 V
0.3
Al
0.7
304
≥ 3 mA
≤ 1 mA
2
> 10 x cable diameter
EN 60947-5-6:2000
IEC 60947-5-6:1999
NE 21:2007
EN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012
116-0165
Release date: 2018-04-19 08:12 Date of issue: 2018-04-19 087119_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
1

Inductive sensor NCB2-V3-N0
Dimensions
3
16
10.3
22.2
27.8
26.1
10
5
LED
22.7
Electrical Connection
BN
BU
L+
L-
Release date: 2018-04-19 08:12 Date of issue: 2018-04-19 087119_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
2

Inductive sensor NCB2-V3-N0
Data for application in connection with hazardous
areas
Equipment protection level Ga , Gb , Da , Mb
Equipment protection level Ga
Type of protection intrinsic safety
CE marking 0102
Certificates
Appropriate type
ATEX certificate
ATEX marking
Standards
IECEx certificate
IECEx marking
Standards
Effective internal inductivity C
Effective internal inductance L
i
i
Maximum permissible ambient temperature T
for ATEX
for IECEx
NCB2-V3-N0...
PTB 00 ATEX 2032 X
¬ II 1G Ex ia IIC T6...T1 Ga
EN 60079-0:2012 +A11:2013, EN 60079-11:2012
IECEx PTB 11.0021X
Ex ia IIC T6 Ga
IEC 60079-0:2004 , IEC 60079-11:2006 , IEC 60079-26:2006
≤ 100 nF
≤ 100 µH
Also observe the maximum permissible ambient temperature stated in the general technical data.
amb
Keep to the lower of the two values.
= 16 V , Ii = 25 mA , Pi = 34 mW ,
at U
i
T6 : 56 °C (132.8 °F)
T5 : 68 °C (154.4 °F)
T4 : 96 °C (204.8 °F)
T3 : 96 °C (204.8 °F)
T2 : 96 °C (204.8 °F)
T1 : 96 °C (204.8 °F)
at U
= 16 V , Ii = 25 mA , Pi = 64 mW ,
i
T6 : 49 °C (120.2 °F)
T5 : 61 °C (141.8 °F)
T4 : 89 °C (192.2 °F)
T3 : 89 °C (192.2 °F)
T2 : 89 °C (192.2 °F)
T1 : 89 °C (192.2 °F)
at U
= 16 V , Ii = 52 mA , Pi = 169 mW ,
i
T6 : 28 °C (82.4 °F)
T5 : 40 °C (104 °F)
T4 : 68 °C (154.4 °F)
T3 : 68 °C (154.4 °F)
T2 : 68 °C (154.4 °F)
T1 : 68 °C (154.4 °F)
at U
= 16 V , Ii = 76 mA , Pi = 242 mW ,
i
T6 : 13 °C (55.4 °F)
T5 : 25 °C (77 °F)
T4 : 53 °C (127.4 °F)
T3 : 53 °C (127.4 °F)
T2 : 53 °C (127.4 °F)
T1 : 53 °C (127.4 °F)
at Ui = 16 V , Ii = 25 mA , Pi = 34 mW ,
T6 : 56 °C (132.8 °F)
T5 : 68 °C (154.4 °F)
T4 : 96 °C (204.8 °F)
T3 : 96 °C (204.8 °F)
T2 : 96 °C (204.8 °F)
T1 : 96 °C (204.8 °F)
at U
= 16 V , Ii = 25 mA , Pi = 64 mW ,
i
T6 : 49 °C (120.2 °F)
T5 : 61 °C (141.8 °F)
T4 : 89 °C (192.2 °F)
T3 : 89 °C (192.2 °F)
T2 : 89 °C (192.2 °F)
T1 : 89 °C (192.2 °F)
at U
= 16 V , Ii = 52 mA , Pi = 169 mW ,
i
T6 : 28 °C (82.4 °F)
T5 : 40 °C (104 °F)
T4 : 68 °C (154.4 °F)
T3 : 68 °C (154.4 °F)
T2 : 68 °C (154.4 °F)
T1 : 68 °C (154.4 °F)
at U
= 16 V , Ii = 76 mA , Pi = 242 mW ,
i
T6 : 13 °C (55.4 °F)
T5 : 25 °C (77 °F)
T4 : 53 °C (127.4 °F)
T3 : 53 °C (127.4 °F)
T2 : 53 °C (127.4 °F)
T1 : 53 °C (127.4 °F)
Release date: 2018-04-19 08:12 Date of issue: 2018-04-19 087119_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
3

Inductive sensor NCB2-V3-N0
Equipment protection level Gb
Type of protection intrinsic safety
CE marking 0102
Certificates
Appropriate type
ATEX certificate
ATEX marking
Standards
IECEx certificate
IECEx marking
Standards
Effective internal inductivity C
Effective internal inductance L
i
i
Maximum permissible ambient temperature T
Equipment protection level Da
Type of protection intrinsic safety
CE marking 0102
NCB2-V3-N0...
PTB 00 ATEX 2032 X
¬ II 1G Ex ia IIC T6…T1 Ga
EN 60079-0:2012+A11:2013 , EN 60079-11:2012
IECEx PTB 11.0021X
Ex ia IIC T6 Ga
IEC 60079-0:2004 , IEC 60079-11:2006
≤ 100 nF
≤ 100 µH
Also observe the maximum permissible ambient temperature stated in the general technical data.
amb
Keep to the lower of the two values.
at U
= 16 V , Ii = 25 mA , Pi = 34 mW ,
i
T6 : 73 °C (163.4 °F)
T5 : 88 °C (190.4 °F)
T4 : 100 °C (212 °F)
T3 : 100 °C (212 °F)
T2 : 100 °C (212 °F)
T1 : 100 °C (212 °F)
at U
= 16 V , Ii = 25 mA , Pi = 64 mW ,
i
T6 : 66 °C (150.8 °F)
T5 : 81 °C (177.8 °F)
T4 : 100 °C (212 °F)
T3 : 100 °C (212 °F)
T2 : 100 °C (212 °F)
T1 : 100 °C (212 °F)
at U
= 16 V , Ii = 52 mA , Pi = 169 mW ,
i
T6 : 45 °C (113 °F)
T5 : 60 °C (140 °F)
T4 : 89 °C (192.2 °F)
T3 : 89 °C (192.2 °F)
T2 : 89 °C (192.2 °F)
T1 : 89 °C (192.2 °F)
at U
= 16 V , Ii = 76 mA , Pi = 242 mW ,
i
T6 : 30 °C (86 °F)
T5 : 45 °C (113 °F)
T4 : 74 °C (165.2 °F)
T3 : 74 °C (165.2 °F)
T2 : 74 °C (165.2 °F)
T1 : 74 °C (165.2 °F)
Certificates
Appropriate type
ATEX certificate
ATEX marking
Standards
Effective internal inductivity C
Effective internal inductance L
i
i
Maximum permissible ambient temperature T
NCB2-V3-N0...
PTB 00 ATEX 2032 X
¬ II 1D Ex ia IIIC T135°C Da
EN 60079-0:2012+A11:2013 , EN 60079-11:2012
≤ 100 nF
≤ 100 µH
Also observe the maximum permissible ambient temperature stated in the general technical data.
amb
Keep to the lower of the two values.
at U
= 16 V , Ii = 25 mA , Pi = 34 mW : 100 °C (212 °F)
i
at U
= 16 V , Ii = 25 mA , Pi = 64 mW : 100 °C (212 °F)
i
at U
= 16 V , Ii = 52 mA , Pi = 169 mW : 89 °C (192.2 °F)
i
at U
= 16 V , Ii = 76 mA , Pi = 242 mW : 74 °C (165.2 °F)
i
Equipment protection level Mb
Type of protection intrinsic safety
Certificates
Appropriate type
IECEx certificate
IECEx marking
Standards
Effective internal inductivity C
Effective internal inductance L
i
i
Maximum permissible ambient temperature T
NCB2-V3-N0...
IECEx PTB 11.0021X
Ex ia I
IEC 60079-0:2004 , IEC 60079-11:2006
≤ 100 nF
≤ 100 µH
Also observe the maximum permissible ambient temperature stated in the general technical data.
amb
Keep to the lower of the two values.
at U
= 16 V , Ii = 25 mA , Pi = 34 mW : 100 °C (212 °F)
i
at U
= 16 V , Ii = 25 mA , Pi = 64 mW : 100 °C (212 °F)
i
at U
= 16 V , Ii = 52 mA , Pi = 169 mW : 89 °C (192.2 °F)
i
at U
= 16 V , Ii = 76 mA , Pi = 242 mW : 74 °C (165.2 °F)
i
Release date: 2018-04-19 08:12 Date of issue: 2018-04-19 087119_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
4