Danfoss MCD 201, MCD 202, MCD 500 Installation guide

ENGINEERING TOMORROW
Installation Guide
Modbus TCP Module
VLT® Compact Starter MCD 201/MCD 202 VLT® Soft Starter MCD 500
vlt-drives.danfoss.com
Contents Installation Guide
1 Introduction
1.1 Purpose of the Manual
1.2 Additional Resources
1.3 Product Overview
1.4 Approvals and Certications
1.5 Disposal
1.6 Symbols, Abbreviations, and Conventions
2 Safety
2.1 Qualied Personnel
2.2 General Warnings
3 Installation
3.1 Installation Procedure
4 Connection
4.1 Soft Starter Connection
4.2 Network Connection
3
3
3
3
3
3
3
4
4
4
6
6
7
7
8
4.2.1 Ethernet Ports 8
4.2.2 Cables 8
4.2.3 EMC Precautions 8
4.2.4 Network Establishment 8
4.3 Addressing
5 Device Conguration
5.1 Conguration Overview
5.2 On-board Web Server
5.3 Ethernet Device Conguration Tool
6 Operation
6.1 Device Classication
6.2 Conguration
6.3 LEDs
7 Modbus Registers
7.1 Compatibility
8
9
9
9
9
11
11
11
11
12
12
7.2 Ensuring Safe and Successful Control
7.3 Conguring Soft Starter Parameters
7.4 Standard Mode
7.4.1 PLC Conguration 12
7.4.2 Command and Conguration Registers (Read/Write) 13
MG17N102 Danfoss A/S © 10/2017 All rights reserved. 1
12
12
12
Contents Modbus TCP Module
7.4.3 Status Reporting Registers (Read Only) 13
7.4.4 Examples 14
7.5 Legacy Mode
7.5.1 PLC Conguration 15
7.5.2 Registers 15
7.5.3 Examples 16
7.6 Trip Codes
7.6.1 Internal Fault X 17
8 Network Design
8.1 Star Topology
8.2 Line Topology
8.3 Ring Topology
8.4 Combined Topologies
9 Specications
Index
15
17
18
18
18
18
19
20
21
2 Danfoss A/S © 10/2017 All rights reserved. MG17N102
Introduction Installation Guide
1 Introduction
1.1 Purpose of the Manual
This installation guide provides information for the instal-
lation of the Modbus TCP module for VLT® Compact Starter
MCD 201/MCD 202 and VLT® Soft Starter MCD 500. The installation guide is intended for use by qualied personnel.
Users are assumed to be familiar with:
VLT® soft starters.
Ethernet protocols.
PC or PLC that is used as a master in the system.
Read the instructions before installation and ensure that the instructions for safe installation are observed.
VLT® is a registered trademark.
1.2 Additional Resources
Resources available for the soft starter and optional equipment:
The VLT® Compact Starter MCD 200 Operating
Instructions provide the necessary information for getting the soft starter up and running.
®
The VLT
provides the necessary information for getting the soft starter up and running.
Supplementary publications and manuals are available from Danfoss. See drives.danfoss.com/knowledge-center/ technical-documentation/ for listings.
Product Overview
1.3
1.3.1 Intended Use
This installation guide relates to Modbus TCP Module for
VLT® soft starters, ordering number 175G9904.
Soft Starter MCD 500 Operating Guide
1 1
Familiarity with Ethernet protocols and networks is required to operate the device successfully. If there are diculties when using this device with third-party products, including PLCs, scanners, and commissioning tools, contact the relevant supplier.
1.4 Approvals and Certications
More approvals and certications are available. For more information, contact a local Danfoss partner.
1.5 Disposal
Do not dispose of equipment containing
electrical components together with
domestic waste.
Collect it separately in accordance with
local and currently valid legislation.
1.6 Symbols, Abbreviations, and Conventions
Abbreviation Denition
DHCP Dynamic host conguration protocol
EMC Electromagnetic compatibility
IP Internet protocol
LCP Local control panel
LED Light-emitting diode
LOP Local operation panel
PC Personal computer
PLC Programmable logic controller
Table 1.1 Symbols and Abbreviations
The Modbus TCP Module is intended for use with:
VLT® Compact Starter MCD 201/MCD 202,
24 V AC/V DC and 110/240 V AC control voltage.
VLT® Soft Starter MCD 500, all models.
NOTICE
The Modbus TCP Module is NOT suitable for use with the MCD 201/MCD 202 compact starters using 380/440 V AC control voltage.
The Modbus TCP Module allows a Danfoss soft starter to connect to an Ethernet network and be controlled or monitored using an Ethernet communication model.
MG17N102 Danfoss A/S © 10/2017 All rights reserved. 3
Conventions
Numbered lists indicate procedures. Bullet lists indicate other information and description of illustrations.
Italicized text indicates:
Cross-reference.
Link.
Parameter name.
Parameter group name.
Parameter option.
Safety Modbus TCP Module
2 Safety
22
The following symbols are used in this manual:
WARNING
Indicates a potentially hazardous situation that could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation that could result in minor or moderate injury. It can also be used to alert against unsafe practices.
NOTICE
Indicates important information, including situations that can result in damage to equipment or property.
2.1 Qualied Personnel
Correct and reliable transport, storage, installation, operation, and maintenance are required for the trouble­free and safe operation of the soft starter. Only qualied personnel are allowed to install or operate this equipment.
Qualied personnel are dened as trained sta, who are authorized to install, commission, and maintain equipment, systems, and circuits in accordance with pertinent laws and regulations. Also, the qualied personnel must be familiar with the instructions and safety measures described in this installation guide.
WARNING
PROPER GROUNDING
Disconnect the soft starter from mains voltage before carrying out repair work. It is the responsibility of the person installing the soft starter to provide proper grounding and branch circuit protection according to local electrical safety codes. Do not connect power factor correction capacitors to the
output of the VLT® Soft Starter MCD 500. If static power factor correction is employed, it must be connected to the supply side of the soft starter.
WARNING
IMMEDIATE START
In auto-on mode, the motor can be controlled remotely (via remote inputs) while the soft starter is connected to mains. MCD5-0021B ~ MCD5-0961B: Transportation, mechanical shock, or rough handling may cause the bypass contactor to latch into the On state.
To prevent the motor from starting immediately on rst commissioning or operation after transportation:
Always ensure that the control supply is applied
before the power.
Applying control supply before power ensures
that the contactor state is initialized.
General Warnings
2.2
WARNING
ELECTRICAL SHOCK HAZARD
VLT® Soft Starter MCD 500 contains dangerous voltages when connected to mains voltage. Only a qualied electrician should carry out the electrical installation. Improper installation of the motor or the soft starter can cause death, serious injury, or equipment failure. Follow the guidelines in this manual and local electrical safety codes. Models MCD5-0360C ~ MCD5-1600C: Treat the busbar and heat sink as live parts whenever the unit has mains voltage connected (including when the soft starter is tripped or waiting for a command).
WARNING
UNINTENDED START
When the soft starter is connected to AC mains, DC supply, or load sharing, the motor can start at any time. Unintended start during programming, service, or repair work can result in death, serious injury, or property damage. The motor can start with an external switch, a eldbus command, an input reference signal from the LCP or LOP, via remote operation using MCT 10 Set-up Software, or after a cleared fault condition.
To prevent unintended motor start:
Press [O]/[Reset] on the LCP before
programming parameters.
Disconnect the soft starter from mains.
Completely wire and assemble the soft starter,
motor, and any driven equipment before connecting the soft starter to AC mains, DC supply, or load sharing.
4 Danfoss A/S © 10/2017 All rights reserved. MG17N102
Safety Installation Guide
WARNING
SAFETY OF PERSONNEL
The soft starter is not a safety device and does not provide electrical isolation or disconnection from the supply.
If isolation is required, the soft starter must be
installed with a main contactor.
Do not rely on the start and stop functions for
safety of personnel. Faults occurring in the mains supply, the motor connection, or the electronics of the soft starter can cause unintended motor starts or stops.
If faults occur in the electronics of the soft
starter, a stopped motor may start. A temporary fault in the supply mains or loss of motor connection can also cause a stopped motor to start.
To provide safety of personnel and equipment, control the isolation device through an external safety system.
2 2
NOTICE
Before changing any parameter settings, save the current parameter to a le using MCD PC Software or the Save
User Set function.
NOTICE
Use the autostart feature with caution. Read all the notes related to autostart before operation.
The examples and diagrams in this manual are included solely for illustrative purposes. The information contained in this manual is subject to change at any time and without prior notice. Responsibility or liability is never accepted for direct, indirect, or consequential damage resulting from the use or application of this equipment.
MG17N102 Danfoss A/S © 10/2017 All rights reserved. 5
177HA528.13
A
B
C
177HA378.12
A
Installation Modbus TCP Module
3 Installation
3.1 Installation Procedure
33
CAUTION
EQUIPMENT DAMAGE
If mains and control voltage are applied when installing or removing options/accessories, it may damage the equipment.
To avoid damage:
Remove mains and control voltage from the
soft starter before attaching or removing options/accessories.
Installing the Modbus TCP Module:
1. Remove control power and mains supply from the soft starter.
2. Fully pull out the top and bottom retaining clips on the module (A).
3. Line up the module with the communication port slot (B).
4. Push in the top and bottom retaining clips to secure the module to the soft starter (C).
5. Connect Ethernet port 1 or port 2 on the Modbus TCP Module to the network.
6. Apply control power to the soft starter.
Remove the module from the soft starter:
1. Remove control power and mains supply from the soft starter.
2. Disconnect all external wiring from the module.
3. Fully pull out the top and bottom retaining clips on the module (A).
4. Pull the module away from the soft starter.
Illustration 3.2 Removing the Modbus TCP Module
Illustration 3.1 Installing the Modbus TCP Module
6 Danfoss A/S © 10/2017 All rights reserved. MG17N102
N2
177HA620.12
1
2
3
A1
17
18
25
177HA621.11
1
2
3
Connection Installation Guide
4 Connection
4.1 Soft Starter Connection
The device is powered from the soft starter.
VLT® Compact Starter MCD 201/MCD 202
For the Modbus TCP Module to accept eldbus commands, t a link across terminals A1–N2 on the soft starter.
VLT® Soft Starter MCD 500
If the MCD 500 has to be operated in auto-on mode, input links are required across terminals 17 and 25 to terminal
18. In hand-on mode, links are not required.
Modbus TCP Module connections
MCD 201/202 MCD 500
NOTICE
FOR MCD 500 ONLY
Control via the eldbus communication network is always enabled in local control mode and can be enabled or disabled in auto-on mode (parameter 3-2
Comms in Remote). See the VLT® Soft Starter MCD 500 Operating Guide for parameter details.
4 4
1 A1, N2: Stop input 1 (Auto-on mode)
17, 18: Stop input
25, 18: Reset input
2 Modbus TCP Module 2 Modbus TCP Module
3 RJ45 Ethernet ports 3 RJ45 Ethernet ports
Table 4.1 Connection Diagrams
MG17N102 Danfoss A/S © 10/2017 All rights reserved. 7
1
2
≥ 200 mm
90°
177HA653.10
ProfiNet MAC: 00-02-A2-25-DC-B3
1 2
TX/RX 2
TX/RX 1
Link 2
Link 1
Error
Status
Power
177HA622.10
Connection Modbus TCP Module
4.2 Network Connection
4.2.1 Ethernet Ports
4.2.4 Network Establishment
The controller must establish communication directly with each device before the device can participate in the
The device has 2 Ethernet ports. If only 1 connection is required, either port can be used.
4.2.2 Cables
44
Suitable cables for EtherNet/IP Module connection:
Category 5
Category 5e
Category 6
Category 6e
network.
4.3 Addressing
Each device in a network is addressed using a MAC address and an IP address and can be assigned a symbolic name associated with the MAC address.
The device can be assigned a static IP address
during conguration or can be congured to accept a dynamic IP address (via DHCP).
The symbolic name is optional and must be
congured within the device.
4.2.3 EMC Precautions
To minimize electromagnetic interference, Ethernet cables
The MAC address is xed within the device and is
printed on a label on the front of the module.
should be separated from motor and mains cables by 200 mm (7.9 in).
The Ethernet cable must cross the motor and mains cables at an angle of 90°.
1 3-phase supply
2 Ethernet cable
Illustration 4.1 Correct Running of Ethernet Cables
Illustration 4.2 MAC ID Location
8 Danfoss A/S © 10/2017 All rights reserved. MG17N102
e77ha639.10
Device Conguration Installation Guide
5 Device Conguration
5.1 Conguration Overview
NOTICE
The error LED ashes whenever the device is receiving power but is not connected to a network. The error LED ashes throughout the conguration process.
5.2 On-board Web Server
Ethernet attributes can be using the on-board web server.
congured directly in the device
NOTICE
The web server only accepts connections from within the same subnet domain.
To congure the device using the on-board web server:
1. Attach the module to a soft starter.
2. Connect Ethernet port 1 or port 2 on the Modbus TCP Module to the network.
3. Apply control power to the soft starter.
4. Start a browser on the PC and enter the device address, followed by /ipcong. The default address for a new Modbus TCP Module is
192.168.1.2.
8a Username: danfoss
8b Password: danfoss
NOTICE
If an IP address is changed and its record is lost, use the Ethernet Device Conguration Tool to scan the network and identify the module.
NOTICE
If changing the subnet mask, the server is unable to communicate with the module after the new settings are saved.
5.3 Ethernet Device Conguration Tool
If the IP address is unknown, or if the subnet mask of the web server does not match, use the Ethernet Device Conguration Tool to connect to the Modbus TCP Module.
Changes made via the Ethernet Device Conguration Tool cannot be stored permanently in the module and are lost when control power is cycled. Use the Ethernet Device Conguration Tool to change the IP address settings temporarily. After that, use the new address to connect to the module using the on-board web server to save the settings permanently.
5 5
Illustration 5.1 Entering Network Settings
5. Edit the settings as required.
6. Click Submit to save the new settings.
7. Tick Static to store the settings permanently in the device.
8. If prompted, enter username and password.
Download the Ethernet Device install the software, administrator privileges are required on the PC.
Downloading the tool:
1. Go to drives.danfoss.com/downloads/pc-tools/ to nd the tool.
2. Make sure to have administrator privileges on the PC before starting the installation.
3. Accept the End-User License Agreement.
4. Click Yes on the User account control dialog box.
Conguration Tool. To
NOTICE
If the PC has a rewall enabled, add the tool to the list of authorized programs.
MG17N102 Danfoss A/S © 10/2017 All rights reserved. 9
177HA623.10
177HA641.10
177HA642.10
Device Conguration Modbus TCP Module
Conguring the device using the Ethernet Device Conguration Tool:
1. Attach the module to a soft starter.
2. Connect Ethernet port 1 or port 2 on the module to the network.
3. Apply control power to the soft starter.
4. Start the Ethernet Device Conguration Tool.
6. To set a static IP address, click Congure and select Set IP Address.
55
Illustration 5.4 Setting a Static IP Address
Illustration 5.2 Starting the Tool
5. Click Search Devices.
5a The software searches for connected
devices.
Illustration 5.3 The Tool Shows the Connected Devices
10 Danfoss A/S © 10/2017 All rights reserved. MG17N102
1 2
TX/RX 2
TX/RX 1
Link 2
Link 1
Error
Status
Power
177HA627.10
Operation Installation Guide
6 Operation
The Modbus TCP Module must be controlled by a Modbus client (such as a PLC) which complies with the Modbus Protocol Specication. For successful operation, the client must also support all functions and interfaces described in this manual.
6.2 Conguration
Congure the device directly in the PLC. No additional les are required.
6.1 Device Classication
The Modbus TPC Module is a Modbus server managed by a Modbus client over Ethernet.
6.3 LEDs
LED name LED status Description
Power
Error
Status
Link x
TX/RX x Flashing Establishing connection.
O The module is not powered up.
On The module receives power.
O No error.
Flashing System error.
On Communication error.
O Not ready.
Slow ash Ready, but not congured.
Fast ash Congured and waiting for communication.
On Communication has been established.
O No network connection.
On Connected to a network.
On Normal operation.
6
6
Table 6.1 Feedback LEDs
MG17N102 Danfoss A/S © 10/2017 All rights reserved. 11
e77ha632.10
Modbus Registers Modbus TCP Module
7 Modbus Registers
NOTICE
All references to registers mean the registers within the module unless otherwise stated.
Conguring Soft Starter Parameters
7.3
Parameter management is always multiple write of the entire parameter block.
7.1 Compatibility
The Modbus TCP Module supports 2 modes of operation:
In standard mode, the module uses registers
dened in the Modbus Protocol Specication.
In legacy mode, the module uses the same
registers as the Modbus Module from Danfoss. Some registers dier from those specied in the Modbus Protocol Specication.
77
The values of bit 15 in register 40001 determine the operating mode.
Standard mode: Set bit 15 = 1. Bits 0–7 of register
40001 are used for command.
Legacy mode: Set bit 15 = 0. The remaining bits
of register 40001 are reserved.
Examples
10000000 00000001 = Start the motor (standard mode).
10000000 00000000 = Stop the motor (standard mode).
00000000 xxxxxxxx = Switch to legacy mode. The module ignores the remaining bits in register 40001 and checks the value in register 40002.
Ensuring Safe and Successful Control
7.2
conguring parameters in the soft starter, the PLC
When must be programmed with the correct values for all parameters. The card updates every parameter in the soft starter to match the values in the PLC.
CAUTION
UNPREDICATABLE BEHAVIOR
Do not change the default values of parameter group 20- ** Factory Parameters. Changing these values may cause unpredictable behavior in the soft starter.
7.4 Standard Mode
7.4.1 PLC Conguration
The PLC must be congured to map registers within the module to addresses within the PLC.
Data written to the Modbus TCP Module remains in its registers until the data is overwritten or the module is reinitialized. The Modbus TCP Module does not transfer successive duplicate commands to the soft starter.
If the soft starter is started via eldbus communi-
cations but stopped via the LCP or a remote input, an identical start command cannot be used to restart the soft starter.
If the soft starter may also be controlled via the
LCP or the remote inputs (and via eldbus communications), a control command should be immediately followed by a status query to conrm that the command has been actioned.
Illustration 7.1 Example Mapping of PLC Registers to Registers
within the Modbus TCP Module (Target)
12 Danfoss A/S © 10/2017 All rights reserved. MG17N102
Modbus Registers Installation Guide
7.4.2 Command and Conguration Registers (Read/Write)
Register Description Bits Details
40001 Command (single
write)
40002 Reserved
40003 Reserved
40004 Reserved
40005 Reserved
40006 Reserved
40007 Reserved
40008 Reserved
400092)–
40200
Table 7.1 Command and Conguration Registers
1) Ensure that the programmable input is not set to Motor Set Select
before using this function.
2) See the relevant soft starter manuals for a complete parameter list.
The rst product parameter is always allocated to register 40009. The
last product parameter is allocated to register 40XXX, where XXX =
008 plus total number of available parameters in the product. The
Modbus TCP Module can read or write a maximum of 125 registers in
1 operation. These registers support multiple write (Modbus function
code 16). Attempting to write a single register returns a fault code 01
(illegal function code).
Parameter
management
(single/multiple
read or multiple
write)
0–7 To send a command to the
soft starter, write the
required value:
00000000 = Stop
00000001 = Start
00000010 = Reset
00000100 = Quick stop
(coast to stop)
00001000 = Forces
communication trip
00010000 = Start using
Parameter Set 1
00100000 = Start using
Parameter Set 2
01000000 = Reserved
10000000 = Reserved
8–14 Reserved
15 Must = 1
0–15 Manage soft starter
programmable parameters
1)
1)
7.4.3 Status Reporting Registers (Read Only)
NOTICE
For models MCD5-0053B and smaller (soft starter model ID 1–4), the current reported via communication registers is 10 times greater than the actual value.
NOTICE
The following functions are only available with MCD 500 soft starters:
Parameter management
Dual motor control
Digital inputs
Jog
Current measurement in amperes
Power information
Warnings
MCD 201 open-loop soft starters do not support motor current and motor temperature information.
Register Description Bits Details
30240 Soft starter state 0–3 1 = Ready
2 = Starting
3 = Running
4 = Stopping (including
braking)
5 = Restart delay (including
temperature check)
6 = Tripped
7 = Programming mode
8 = Jog forward
9 = Jog reverse
4 1 = Positive phase sequence
(only valid if bit 6 = 1)
5 1 = Current exceeds FLC
6 0 = Uninitialized
1 = Initialized
7–15 Reserved
30241 Trip code 0–7 See chapter 7.6 Trip Codes
8–15 Reserved
30242 Motor current 0–7 Average 3-phase motor
current [A]
8–15 Reserved
30243 Motor
temperature
30244–
30249
Reserved
0–7 Motor thermal model (%)
8–15 Reserved
7 7
MG17N102 Danfoss A/S © 10/2017 All rights reserved. 13
e77ha633.10
Modbus Registers Modbus TCP Module
Register Description Bits Details
30250 Version 0–5 Reserved
6–8 Product parameter list
version
9–15 Product type code:
4 = MCD 200
7 = MCD 500
30251 Model number 0–7 Reserved
8–15 Soft starter model ID
30252 Reserved
30253 Reserved
30254 Soft starter state 0–4 0 = Reserved
1 = Ready
2 = Starting
3 = Running
4 = Stopping
5 = Not ready (restart delay,
77
30255 Current 0–13 Average rms current across
30256 Current 0–9 Current (% of motor FLC)
30257 Motor
temperature
1)
30258
30259 % power factor 0–7 100% = power factor of 1
30260 Reserved
30261 Current 0–13 Phase 2 current (rms)
30262 Current 0–13 Phase 2 current (rms)
30263 Current 0–13 Phase 3 current (rms)
30264 Reserved
30265 Reserved
30266 Reserved
Power 0–11 Power
restart temperature check)
6 = Tripped
7 = Programming mode
8 = Jog forward
9 = Jog reverse
5 1 = Warning
6 0 = Uninitialized
1 = Initialized
7 0 = Local control
1 = Remote control
8 Reserved
9 0 = Negative phase
sequence
1 = Positive phase sequence
10–15 See chapter 7.6 Trip Codes
all 3 phases
14–15 Reserved
10–15 Reserved
0–7 Motor thermal model (%)
8–15 Reserved
12–13 Power scale
14–15 Reserved
8–15 Reserved
14–15 Reserved
14–15 Reserved
14–15 Reserved
Register Description Bits Details
30267 Parameter list
version number
30268 Digital input
state
30269–
30281
Table 7.2 Status Reporting Registers
1) Power scale functions as follows:
0 = Multiply power by 10 to get W.
1 = Multiply power by 100 to get W.
2 = Power (kW ).
3 = Multiply power by 10 to get kW.
Reserved
0–7 Parameter list minor version
8–15 Parameter list major version
0–15 For all inputs, 0 = open, 1 =
closed (short-circuited)
0 = Start
1 = Stop
2 = Reset
3 = Input A
4–15 = Reserved
7.4.4 Examples
Illustration 7.2 Send Start Command (Register 40001)
14 Danfoss A/S © 10/2017 All rights reserved. MG17N102
e77ha634.10
e77ha635.10
e77ha636.10
Modbus Registers Installation Guide
Illustration 7.3 Get Status (Starting at Address 30240)
Illustration 7.4 Get Parameter Values (Starting Register 40009)
7.5 Legacy Mode
7.5.1 PLC Conguration
The PLC must be congured to map registers within the module to addresses within the PLC.
Illustration 7.5 Example Mapping of PLC Registers to Registers
within the Modbus TCP Module (Target)
7.5.2 Registers
NOTICE
For models MCD5-0053B and smaller (soft starter model ID 1–4), the current reported via communications registers is 10 times greater than the actual value.
NOTICE
Some soft starters do not support some functions.
Register Description Bits Details
40001 Reserved 0–14 Reserved
15 Must be 0.
40002 Command
(single write)
40003 Soft starter state 0–3 1 = Ready
40004 Trip code 0–7 See chapter 7.6 Trip Codes
40005 Motor current 0–7 Average 3-phase motor
40006 Motor
temperature
40007 Reserved
40008 Reserved
0–2 To send a command to the
soft starter, write the
required value:
1 = Start
2 = Stop
3 = Reset
4 = Quick stop (coast to
stop)
5 = Forced communication
trip
6 = Start using Parameter
Set 1
7 = Start using Parameter
Set 2
3–15 Reserved
2 = Starting
3 = Running
4 = Stopping (including
braking)
5 = Tripped
6 = Programming mode
7 = Jog forward
8 = Jog reverse
4 1 = Positive phase
sequence (only valid if bit 6
= 1)
5 1 = Current exceeds FLC
6 0 = Uninitialized
1 = Initialized
7–15 Reserved
8–15 Reserved
current [A]
8–15 Reserved
0–7 Motor thermal model (%)
8–15 Reserved
7 7
MG17N102 Danfoss A/S © 10/2017 All rights reserved. 15
e77ha637.10
Modbus Registers Modbus TCP Module
Register Description Bits Details
400091)–
40200
40600 Version 0–5 Binary protocol version
40601 Reserved
40602 Reserved
40603 Reserved
40604 Soft starter state 0–4 0 = Reserved
Parameter
management
(single/multiple
read or multiple
write)
77
40605 Current 0–13 Average rms current across
40606 Current 0–9 Current (% motor FLC)
40607 Motor
temperature
2)
40608
40609 % power factor 0–7 100% = power factor of 1
Power 0–11 Power
0–15 Manage soft starter
programmable parameters
6–8 Parameter list version
number
9–15 Product type code:
4 = MCD 200
7 = MCD 500
1 = Ready
2 = Starting
3 = Running
4 = Stopping
5 = Not ready (restart
delay, restart temperature
check)
6 = Tripped
7 = Programming mode
8 = Jog forward
9 = Jog reverse
5 1 = Warning
6 0 = Uninitialized
1 = Initialized
7 0 = Hand on
1 = Auto on
8 Reserved
9 0 = Negative phase
sequence
1 = Positive phase
sequence
10–15 Reserved
all 3 phases
14–15 Reserved
10–15 Reserved
0–7 Motor thermal model (%)
8–15 Reserved
12–13 Power scale
14–15 Reserved
8–15 Reserved
Register Description Bits Details
40612 Current 0–13 Phase 2 current (rms)
14–15 Reserved
40613 Current 0–13 Phase 3 current (rms)
14–15 Reserved
40614 Reserved
40615 Reserved
40616 Reserved
40617 Parameter list
version number
40618 Digital input
state
40619–
40631
Table 7.3 Legacy Mode Registers
1) See the relevant soft starter manual for a complete parameter list.
The rst product parameter is always allocated to register 40009. The
last product parameter is allocated to register 40XXX, where XXX =
008 plus total number of available parameters in the product. The
Modbus TCP Module can read or write a maximum of 125 registers in
1 operation. These registers support multiple write (Modbus function
code 16). Attempting to write to a single register returns a fault code
01 (illegal function code).
2) Power scale functions as follows:
0 = Multiply power by 10 to get W.
1 = Multiply power by 100 to get W.
2 = Power (kW ).
3 = Multiply power by 10 to get kW.
Reserved
0–7 Parameter list minor version
8–15 Parameter list major version
0–15 For all inputs, 0 = open, 1
= closed (short-circuited)
0 = Start
1 = Stop
2 = Reset
3 = Input A
7.5.3 Examples
40610 Reserved
40611 Current 0–13 Phase 1 current (rms)
14–15 Reserved
16 Danfoss A/S © 10/2017 All rights reserved. MG17N102
Illustration 7.6 Send Start Command (Register 40002)
e77ha638.10
e77ha635.10
Modbus Registers Installation Guide
Illustration 7.7 Get Status (Starting at Register 40003)
Trip
code
9 Undercurrent
10 Heat sink overtemperature
11 Motor connection
12 Input A trip
13 FLC too high
14 Unsupported option
15 Soft starter communication
16 Network communication
17 Internal fault x (where x is
23 Parameter out of range
25 Bypass fail (bypass
26 L1 phase loss
27 L2 phase loss
28 L3 phase loss
29 L1-T1 short-circuited
30 L2-T2 short-circuited
31 L3-T3 short-circuited
33
35 Battery/clock
36 Thermistor circuit
Description MCD
(function not available in
inside delta)
(between device and soft
starter)
(between device and soft
starter)
the fault code detailed in
Table 7.5)
contactor)
1)
Time-overcurrent (bypass
overload)
201
MCD
202
MCD
500
7 7
Illustration 7.8 Get Parameter Values (Starting at Register
40009)
7.6 Trip Codes
Trip codes are reported in registers 30241 and 30254 (standard mode) and register 40604 (legacy mode).
Trip
code
0 No trip
1 Excess start time
2 Motor overload
3 Motor thermistor
4 Current imbalance
5 Frequency
6 Phase sequence
7 Instantaneous overcurrent
8 Power loss
Description MCD
201
MCD
202
MCD
500
Table 7.4 Trip Codes
1) For MCD 500, time-overcurrent protection is only available on
internally bypassed models.
7.6.1 Internal Fault X
Internal fault Message shown on the LCP
70–72 Current Read Err Lx
73 ATTENTION! Remove Mains Volts
74–76 Motor Connection Tx
77–79 Firing Fail Px
80–82 VZC Fail Px
83 Low Control Volts
84–98 Internal fault x
Contact the local supplier with the fault code (X).
Table 7.5 Internal Fault Code Associated with Trip Code 17
MG17N102 Danfoss A/S © 10/2017 All rights reserved. 17
177HA628.10
177HA629.10
177HA630.10
Network Design Modbus TCP Module
8 Network Design
The device supports star, line, and ring topologies.
8.1 Star Topology
In a star network, all controllers and devices connect to a central network switch.
NOTICE
The device has an integrated switch to allow data to pass through in line topology. The device must be receiving control power from the soft starter for the switch to operate.
NOTICE
If the connection between 2 devices is interrupted, the controller cannot communicate with devices after the interruption point.
NOTICE
Each connection adds a delay to communication with the next device. The maximum number of devices in a line network is 32. Exceeding this number may reduce the reliability of the network.
88
8.3 Ring Topology
In a ring topology network, the controller connects to the
Illustration 8.1 Star Network Topology
8.2 Line Topology
In a line network, the controller connects directly to 1 port of the 1st module. The 2nd Ethernet port connects to another module, which in turn connects to another device until all devices are connected.
1st module via a network switch. The 2nd Ethernet port of the module connects to another device, which in turn connects to another device until all devices are connected. The nal device connects back to the switch.
The device supports beacon-based ring node congu-
ration.
Illustration 8.3 Ring Network Topology
Illustration 8.2 Line Network Topology
18 Danfoss A/S © 10/2017 All rights reserved. MG17N102
NOTICE
The network switch must support loss of line detection.
177HA631.10
Network Design Installation Guide
8.4 Combined Topologies
A single network can include both star and line components.
Illustration 8.4 Combined Star/Line Network Topology
8 8
MG17N102 Danfoss A/S © 10/2017 All rights reserved. 19
Specications Modbus TCP Module
9 Specications
Enclosure Dimensions, W x H x D [mm (in)] 40 x 166 x 90 (1.6 x 6.5 x 3.5) Weight 250 g (8.8 Oz) Protection IP20
Mounting Spring-action plastic mounting clips 2
Connections Soft starter 6-way pin assembly Contacts Gold ash Networks RJ45
Settings IP address Automatically assigned, congurable Device name Automatically assigned, congurable
Network Link speed 10 Mbps, 100 Mbps (auto-detect) Full duplex Auto crossover
99
Power Consumption (steady state, maximum) 35 mA at 24 V DC Reverse polarity protected Galvanically isolated
Certication
CE IEC 60947-4-2
20 Danfoss A/S © 10/2017 All rights reserved. MG17N102
Index Installation Guide
Index
A
Abbreviations........................................................................................... 3
Additional resources.............................................................................. 3
Approvals................................................................................................... 3
Auto-on mode.......................................................................................... 4
B
Busbar......................................................................................................... 4
C
Cable
category................................................................................................. 8
Ethernet cable..................................................................................... 8
Capacitors
Power factor correction capacitor................................................ 4
Certications............................................................................................. 3
Connections........................................................................................... 20
Contactors
Bypass contactor................................................................................ 4
Main contactor.................................................................................... 5
Conventions.............................................................................................. 3
D
Dimensions............................................................................................. 20
M
MAC address............................................................................................. 8
Motor
connection............................................................................................ 5
N
Network
Auto crossover.................................................................................. 20
Full duplex.......................................................................................... 20
Line........................................................................................................ 18
Link speed........................................................................................... 20
Ring....................................................................................................... 18
Star........................................................................................................ 18
O
Operating mode................................................................................... 12
P
Parameter management.................................................................... 12
Q
Qualied personnel........................................................................... 3, 4
R
Removing the Modbus TCP Module................................................ 6
Reset mode............................................................................................... 7
E
Electromagnetic interference............................................................. 8
Ethernet attribute................................................................................... 9
H
Heat sink..................................................................................................... 4
I
Inputs
Remote................................................................................................... 4
Installing the Modbus TCP module.................................................. 6
Intended use............................................................................................. 3
Internal fault code................................................................................ 17
IP address....................................................................................... 8, 9, 20
L
LED
Description......................................................................................... 11
LED........................................................................................................... 3
Name.................................................................................................... 11
Status.................................................................................................... 11
Legacy mode.......................................................................................... 12
S
Standard mode...................................................................................... 12
Subnet mask............................................................................................. 9
Supply..................................................................................................... 4, 5
Symbols...................................................................................................... 3
T
Terminals
A1............................................................................................................. 7
N2............................................................................................................. 7
U
Unintended start..................................................................................... 4
W
Weight...................................................................................................... 20
MG17N102 Danfoss A/S © 10/2017 All rights reserved. 21
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Danfoss A/S Ulsnaes 1 DK-6300 Graasten vlt-drives.danfoss.com
175R1139 MG17N102 10/2017
*MG17N102*
Loading...