Danfoss KPU Series Installation Manual

Installation guide
Pressure switch
KPU
060R9767
060R9767
© Danfoss | DCS (jmn) | 2016.11
DKRCC.PI.CD0.F4.22 | 520H11543 | 1
KPU pressure switches are for use on commercial refrigeration and air conditioning systems to give protection against excessively low suction pressure or excessively high discharge pressure.
They are also used for starting and stopping refrigeration compressors and fans on air-cooled condensers. KPU pressure switches are tted with the Single-Pole Single­Throw (SPST) or Single-Pole Double-Throw (SPDT) switches, suitable for direct as well as indirect (with a contactor) control.
KPU pressure switches are available in several pressure ranges and are compatible with refrigerants listed below. KPU 6W and KPU 6B are fail safe switches for high pressure refrigerants. Standard enclosure is ~NEMA 1.
Product Specication
Application Typ e
Code number
Reset
Contact system
Regulating
range
[inHg] [psi g]
Dierential
∆p
[psi]
Max. working pressure
[psig]
Max.
testing
pressure
[psig]
Ambient
temp.
[°F]
¼ in
male are
36 in. cap. tube w. ¼
in are nu t
Typ e
Switch action
Low Pressure Switch Cut O ut on pressure fall
KPU 1 06 0-5231 060 -5233 Auto. SPDT 6 in. – 108 10 – 60 250 290
-40 – 122
(175 for
max.
2 hours)
KPU 1 060- 5236 Auto. SPST(NO) close High op en Low 6 in. – 108 10 – 60 250 290
KPU 2 060 -5237 060-52 35 Auto. SPST(NO) close High open Low 6 in. – 73 6 – 30 250 290
KPU 2 060- 5239 060-524 0 Auto. SPDT 6 in. – 73 6 – 30 250 290
KPU1B 060 -5232 060-523 4 Man (Min.) SPDT 28 in. – 100 10 x ed 250 290
Fan switch K PU 5 06 0-5241 060 -5242 Auto. SPST(N O) close High op en Low 100 – 465 25 – 85 510 530
High Pressure Switch Cut Out on pressure rise
KPU 6W
060 -5243 06 0-5245 Auto. SPDT 100 – 600 58 – 145 675 / 610* 725
KPU 6B
060 -5244 06 0-5246 Man. (Max.) SPDT 100 – 60 0 60 xed 675 / 610* 725
* 610psig - MWP for produc ts used according to 97/23/EG PED directive.
Refrigerants:
R22, R134a, R404A, R407A, R407C, R407F, R410A*), R422B, R422D, R438A, R448A, R449A, R450A, R452A, R507A, R513A
For complete list of approved refrigerants, go to http://products.danfoss.com/all-products/
*) R410A only for KPU 6W and KPU 6B
Installation
Select an accessible location, where the switch and pressure connection line will not be subject to damage.
IMPORTANT:
Mount the pressure switch in a position that will allow drainage of liquids away from switch bellows. Pressure connection of the switch must always be located on the top side of the refrigerant line. This reduces the possibility of oil, liquids, or sediment collecting in the bellows, which could cause the switch malfunction.
IMPORTANT:
Ensure the ambient temperature for the pressure switch is higher than the refrigeration line as that will prevent liquid migration and accumulation in the bellows.
© Danfoss | DCS (jmn) | 2016.11
2 | 520H11543 | DKRCC.PI.CD0.F4.22
Recommendations for capillary tube and are connections:
1. Ensure self-draining of the capillary tube to minimize
clogging.
2. Coil excess capillary tube into smooth, circular coils (approx. 3 inch diameter). The coiled tube should be securely fastened in order to prevent possible damage due to vibration.
3. Leave a little slack in the capillary tube as it helps to damp mechanical vibrations.
4. Avoid sharp bends as well as re-bending of the capillary tube on the same point as it weakens the material, increasing the risk of crack.
5. Never allow for contact between the capillary tube and sharp or abrasive objects as during vibrations the tube could be damaged due to friction.
6. Purge the piping before connecting pressure switches.
7. Always use two wrenches
tightening the are nut on the pressure switch. One wrench should support the connector while the second wrench isused to tighten the nut.
8. Do not over tighten are nuts as it may damage the threads causing leaks.
9. Protect the capillary tube from damage caused by vibrations from compressor:
when the switch unit is mounted directly on the compressor, the capillary must be secured to the compressor so that everything vibrates as a whole.
– when the switch is mounted remote from the compressor,
make the pressure connections away from thecompressor.
– when the switch is mounted remote from the compressor
and the pressure connections have to be on the compressor, then damping coils must be used between the compressor and the pressure switch.
NOTE:
After installing the pressure switch, evacuate theplant in accordance with applicable EPA and other regulations, to remove air, moisture, and other contaminants.
Screws for bracket mounting
Mounting holes for at surfaces
120 V AC 24 FLA, 144 LRA – make only
240 V AC 24 FLA, 144 LRA – make only
240 V DC 12 W pilot duty
Wiring
Electrical ratings according to UL regulations
European electrical ratings according to EN 60947
AC1 AC3 AC15 LR DC13
16 A 16 A 10 A 112 A 12 W
400 V 220 V
CAUTION:
Disconnect power supply before wiring connections are made or service to avoid possible electrical shock or damage to equipment. Do never touch live parts with your ngers or with anytool.
NOTE:
All wiring should conform to the National Electrical Code and local regulations. Use copper wire only. Use terminal screws furnished in the contact block. Do not exceed tightening torque 20 lb. in (2.3 Nm). Do not exceed electrical ratings for the switch.
The terminal block as well as grounding screw are accessible after dismounting of the front cover.
Mount the KPU pressure switch on a bracket or on a completely at surface. Mounting to an uneven surface might cause improper switch operation. For bracket mounting use only the 10-32x3/16 screws provided with the switch. If other screws are used function of the pressure switch might be disturbed (they may not protrude into the switch more than 1/8 in.).
Use only the mounting holes provided; no other holes are to be added to the switch.
IMPORTANT:
Pressure pulsations in the refrigeration system reduce life time of the bellows and might disturb switch function. Pressure pulsations should always be eectively damped e.g. by connection the pressure switches to the refrigeration system through a capillary tube.
Load ~Line
B
C
A
D
C
D
A
B
© Danfoss | DCS (jmn) | 2016.11
DKRCC.PI.CD0.F4.22 | 520H11543 | 3
Contact function test (Manual trip)
When the electrical leads are connected the contact function can be manually tested regardless of pressure condition in the system. The manual trip lever is located in the left side of the KPU. It must be operated with ngers only. Do not use screwdriver as it will damage the switch.
NOTE:
While operating the manual trip on KPU switches with manual reset it is necessary to push the reset knob.
NOTE:
Adjust the pressure switch with settings specied by the manufacturer of the controlled quipment. Do not exceed the pressure ratings of the controlled equipment or any of its components when checking pressure switch operation or operating the controlled equipment. Do not adjust pointers beyond the highest or lowest indicator marks on the scale plate, as this may cause inaccurate switch operation.
A: Manual trip. Press the lever up. USE FINGERS ONLY! B: Manual reset button
(available only for contols with manual reset function)
C: Terminal block D: Grounding screw
A: Dierential adjusting screw B: Locking plate C: Range adjusting screw D: Cover screw
Adjustment
Before adjustment, loosen the locking plate. For setting use the Universal Refrigeration Wrench.
Wire dimensions: 10 AWG max. Cable entry: 7/8 in. cable entry for ½ in. male pipe thread connection (conduit boss) or similar (Pg13.5 or Pg16) screwed cable entry.
Wiring Option A:
– Low Pressure Switch Cut Out on pressure fall – Condenser Fan Cycling
Wiring Option B:
– High Pressure Switch Cut Out on pressure rise
Load ~Line
1
2
1 2
1
© Danfoss | DCS (jmn) | 2016.11
4 | 520H11543 | DKRCC.PI.CD0.F4.22
Adjustment: Low Pressure Switch
Cut out on pressure fall with automatic reset.
Scale plate directly indicates the Cut In and the Dierential set points.
1. Set Cut In by adjusting range screw. Turn the screw clockwise to lower the set point.
2. Then set Dierential by adjusting dierential screw. Turn the screw clockwise to increase the Dierential.
3. The Cut Out setting equals the Cut In less the Dierential: CUT OUT = CUT IN - DIFFERENTIAL
Adjustment: Condenser Fan Cycling
Scale plate directly indicates the Cut In and the Dierential set points.
1. Set Cut In by adjusting range screw. Turn the screw clockwise to lower the set point.
2. Then set Dierential by adjusting dierential screw. Turn the screw clockwise to increase the Dierential.
3.The Cut Out setting equals the Cut In less the Dierential: CUT OUT = CUT IN - DIFFERENTIAL
Adjustment: Low Pressure Switch
Cut out on pressure fall with manual reset.
Scale plate directly indicates the Cut Out set point. There is no pointer for the Dierential. The Dierential pressure value is xed and printed on the scale plate.
Adjustment: High Pressure Switch
Cut Out on pressure rise with automatic reset.
Scale plate directly indicates the Cut Out and the Dierential set points.
1. Set Cut Out by adjusting range screw. Turn the screw clockwise to lower the set point.
2. Then set Dierential by adjusting dierential screw. Turn the screw clockwise to decrease the Dierential.
3. The Cut In setting equals the Cut Out less the Dierential: CUT IN = CUT OUT - DIFFERENTIAL
Adjustment: High Pressure Switch
Cut Out on pressure rise with manual reset.
Scale plate directly indicates the Cut Out set point. There is no pointer for the Dierential. The Dierential pressure value is xed and printed on the scale plate.
1. Set Cut Out by adjusting range screw. Turn the screw clockwise to lower the set point.
2. The Cut In setting equals the Cut Out less the Dierential: CUT IN = CUT OUT - 60 psi
1. Set Cut Out by adjusting range screw. Turn the screw clockwise to lower the set point.
2. The Cut In setting equals the Cut Out plus the Dierential: CUT IN = CUT OUT + 10 psi
NOTE:
Cut Out set point must be above absolute vacuum! If the Dierential is set too high then the switch will not stop the compressor.
IMPORTANT:
The scale plate is only for reference and for more precise setting a pressure gauge should be used.
IMPORTANT:
After installing and adjusting pressure switch run the controlled equipment several times (at least three cycles) at normal operating conditions.
1 2
1
Loading...