Danfoss H62L-EZU Data sheet

Data Sheet
Micro Plate Heat Exchanger Type H62L-EZU
For more ecient Heat Pumps
21% lower hold-up volume enables signicant reduction in refrigerant charge.
The H62L-EZU is an evaporator optimized for R410A for use in high-eciency heat pumps with capacities of 5-40 kW.
The Z-pattern channel plate technology pushes the performance of heat exchangers to the limits by fully mixing the liquid and gas refrigerant through a “zigzag” ow, which increases the heat transfer coecient. At the same time, inheriting from dimple plate pattern of the previous generation of MPHE, H62L-EZU reduces the water side pressure drop and the amount of material used. In the reversible mode of the heat pump as a condenser, H62L­EZU also has outstanding performance.
To meet demands for higher seasonal
eciency, the H62L-EZU is designed to work eciently and increase comfort in modern
residential and commercial buildings without increasing the carbon footprint. Helping heat pumps perform more eciently, it reduces both energy costs and environmental impact. The low hold-up volume reduces the system refrigerant charge and oers valuable savings.
Thanks to the mixing chamber, the innovative refrigerant distribution device, the H62(L)-EZ is applicable with all refrigerant types.
AI358755407840en-000101
a
Applications C: chiller D: universal H: heat pump HDW: heat pump double wall
d Specic duty
E= evaporator C= condenser Plate design
Omit
L: L-type M: M-type H: H-type W: W-type X: Asymmetric Z: Z ow
Conguration
Omit: single
D: Dual circuit U: Mixing chamber
e
Distributor version
Omit
B F Plate stacking sequence
Omit: a-b-a… R: b-a-b…
b Platform* 22,30,55,62,118… *heat exchanging surface per plate 1/1000 m²
c
Pressure Service
Omit: 30bar L: 45/49bar
f
Number of plates**
**Rule:
-Single: even number
-Dual: even number not multiple of 4
Micro plate heat exchanger, type H62L-EZU
Features
• Improved heat transfer - equals higher eciency heat pumps
• Reduced water side pressure drop – equals higher eciency heat pumps
• Minimal hold-up volume - equals less refrigerant charge
• Smaller footprint - enables more compact heat pumps
• High heat transfer and minimal refrigerant charge - equals a reduced CO footprint
Portfolio overview
H62L-EZU: Evaporator optimized for R410A, R32, R452B and R454B H62-EZU: Evaporator for low/medium density refrigerants PS: 30bar
Application
The H62(L)-EZU is single circuit evaporators specically designed for highly ecient heat pump systems. The evaporator is design to operate also in reversable systems in condenser mode, in co or counter current ow
conguration.
Thanks to the mixing chamber, the innovative refrigerant distribution device, the H62(L)-EZ is applicable with all refrigerants types.
Table 1: Designation
Media
Refrigerants
R410A, R32, R452B, R454B, R454C, R134a, R290 For other refrigerants please contact your Danfoss Sales representative.
© Danfoss | Climate Solutions | 2021.02 AI358755407840en-000101 | 2
Q4 Q1
Q3 Q2
525 [20.7”]
63 [2.5”]
470 [18.5 “]
118 [4.6”]
11+1.64*NoP [0.43+0.065*NoP]
H4H1
H2 H3
Item
Material
Specication
Cover plates
Stainless steel
AISI 304L
Plates
Stainless steel
AISI 316L
Connections
Stainless steel
AISI 304L
Brazing
ller
Pure copper
Cu
Micro plate heat exchanger, type H62L-EZU
Product specication
Dimensions
Figure 1: Dimensions
Operating conditions
Preconditions:
N = number of plates Max number of plates: 120
Pressure and temperature data*:
Min. working temperature: -196 °C (-320 °F) Max. working temperature: 200 °C (390 °F) Max. working pressure: 45 bar (635psi) refrigerant side** / 30 bar (435psi) water side *For details, refer to the topic.Third party approvals **A lower pressure version (30bar) also available
Weight
H62L-EZU: 3.2 + 0.145 x N [kg] // 7.05 + 0.32 x N [lb] H62-EZU: 2.7 + 0.145 x N [kg] // 5.95 + 0.32 x N [lb] N:Number of Plate
Material specication
Table 2: Standard materials
Other material combinations are available on request. Please contact your Danfoss sales representative for more information.
© Danfoss | Climate Solutions | 2021.02 AI358755407840en-000101 | 3
H1
H4
H3H2
Q2
Q1
Q4
Q3
Model
Connections
Stud bolt
Pack format
Code
Q1&Q2 [in.]
Q3 (ref,in)[in.]
Q4 (ref,out)[in.]
H62L-EZU-20
ISO G1
1
4 - 1 1⁄8
3⁄87
8
YES
Single -1pcs
111B2112
H62L-EZU-26
ISO G1
1
4 - 1 1⁄8
3⁄87
8
YES
Single -1pcs
111B2113
H62L-EZU-30
ISO G1
1
4 - 1 1⁄8
3⁄87
8
YES
Single -1pcs
111B2114
H62L-EZU-36
ISO G1
1
4 - 1 1⁄8
3⁄87
8
YES
Single -1pcs
111B2115
H62L-EZU-40
ISO G1
1
4 - 1 1⁄8
3⁄87
8
YES
Single -1pcs
111B2116
H62L-EZU-46
ISO G1
1
4 - 1 1⁄8
1⁄27
8
YES
Single -1pcs
111B2117
H62L-EZU-50
ISO G1
1
4 - 1 1⁄8
1
2
1
1
8
YES
Single -1pcs
111B2118
H62L-EZU-60
ISO G1
1
4 - 1 1⁄8
1
2
1
1
8
YES
Single -1pcs
111B2119
H62L-EZU-70
ISO G1
1
4 - 1 1⁄8
1
2
1
1
8
YES
Single -1pcs
111B2120
H62L-EZU-80
ISO G1
1
4 - 1 1⁄8
1
2
1
1
8
YES
Single -1pcs
111B2121
H62L-EZU-90
ISO G1
1
4 - 1 1⁄8
5
8
1
3
8
YES
Single -1pcs
111B2122
H62L-EZU-100
ISO G1
1
4 - 1 1⁄8
5
8
1
3
8
YES
Single -1pcs
111B2123
H62L-EZU-110
ISO G1
1
4 - 1 1⁄8
5
8
1
3
8
YES
Single -1pcs
111B2124
H62L-EZU-120
ISO G1
1
4 - 1 1⁄8
5
8
1
3
8
YES
Single -1pcs
111B2125
Micro plate heat exchanger, type H62L-EZU
Conguration ow
Figure 2: Conguration ow
Parallel ow: Q1 - Q2 [H1 - H2]: brine/secondary side Q3 - Q4 [H3 - H4]: refrigerant/primary side
Hold up volume
Q1 - Q2 (l): 0.089 x N/2 Q3 - Q4 (l): 0.062 x (N-2)/2 N: Number of Plate
Ordering
Global or local standard code numbers can be accessed via Store.Danfoss.com on local subsites, with full set of technical data as well as relevant assets such as documentation and drawings. Since the portfolio may contain dierent types depending on country, this document contains only a summarized list of standard code numbers with a few data relevant for the product selection.
Table 3: Ordering
Conguring and calculating products
The H62(L)-EZU can be easily customized based on the application needs; model size can be evaluated using Hexact software.
For details, product conguration and code creation please contact your Danfoss Sales representative.
© Danfoss | Climate Solutions | 2021.02 AI358755407840en-000101 | 4
Circuits
Connection type options
Connection size option [in.]
Q1 - Q2 (water-brine side)
BSP Gas male
½, ¾, 1, 1 ¼, 1 ½
BSP Gas female
½, ¾, 1
DIN R male
1, 1 ¼, 1 ½
NPT
¾, 1, 1 ¼
Victaulic
1 ½
Q3 (Refrigerant inlet)
Soldering
3
8, ½,5⁄8
Q4 (Refrigerant outlet)
Soldering
5
8, ¾, 7⁄8, 1 1⁄8, 1 3⁄8
Stud bolt position
Bolt sizes
80 mm, middle
M8x20mm M8x25mm M8x30mm
Pressure Equipment Directive (PED)
Underwriters Laboratory Inc (UL)
Micro plate heat exchanger, type H62L-EZU
Mechanical connections
Table 4: Mechanical connections
Accessories and spare parts
MPHE products are not serviceable, i.e. cannot be taken apart and repaired, and there are no spare parts program. As for accessories, stud bolts, feet on front and/or back cover plates for mounting support and handling are available upon request.
Table 5: Stud bolts:
Contact your Danfoss sales representative for further information.
Certicates, declarations, and approvals
The list contains all certicates, declarations, and approvals for this product type. Individual code number may have some or all of these approvals, and certain local approvals may not appear on the list.
Some approvals may change over time. You can check the most current status at danfoss.com or contact your local Danfoss representative if you have any questions.
Third party approvals
All MPHE and BPHE are certied to European Pressure Equipment Directive (PED) and are approved by Underwriters Laboratories (UL).
© Danfoss | Climate Solutions | 2021.02 AI358755407840en-000101 | 5
Online support
Danfoss oers a wide range of support along with our products, including digital product information, software, mobile apps, and expert guidance. See the possibilities below.
The Danfoss Product Store
The Danfoss Product Store is your one-stop shop for everything product related—no matter where you are in the world or what area of the cooling industry you work in. Get quick access to essential information like product specs, code numbers, technical documentation, certications, accessories, and more. Start browsing at store.danfoss.com.
Find technical documentation
Find the technical documentation you need to get your project up and running. Get direct access to our ocial collection of data sheets, certicates and declarations, manuals and guides, 3D models and drawings, case stories, brochures, and much more.
Start searching now at www.danfoss.com/en/service-and-support/documentation.
Danfoss Learning
Danfoss Learning is a free online learning platform. It features courses and materials specically designed to help engineers, installers, service technicians, and wholesalers better understand the products, applications, industry topics, and trends that will help you do your job better.
Create your Danfoss Learning account for free at www.danfoss.com/en/service-and-support/learning.
Get local information and support
Local Danfoss websites are the main sources for help and information about our company and products. Find product availability, get the latest regional news, or connect with a nearby expert—all in your own language.
Find your local Danfoss website here: www.danfoss.com/en/choose-region.
Coolselector®2 - nd the best components for you HVAC/R system
Coolselector®2 makes it easy for engineers, consultants, and designers to nd and order the best components for refrigeration and air conditioning systems. Run calculations based on your operating conditions and then choose the best setup for your system design.
Download Coolselector®2 for free at coolselector.danfoss.com.
Hexact for heat exchangers
Hexact for heat exchangers helps you identify the best heat exchanger for your chiller, heat pump, or other application based on operating conditions. Works for innovative MPHE and traditional BPHE brazed heat exchangers.
Download Hexact for free at hexact.danfoss.com
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.