Installation and operation manual
a3P419248-1-KA
The English text is the original instruction. Other languages are translations of the original instructions.
Refer to http://www.daikineurope.com/support-and-manuals/ product-information/ for more detailed user reference guides.
Installation: see page 2.
OPERATION
1.General safety precautions
Also see operation manual attached to the outdoor and indoor unit.
Please read these "1. General safety precautions" carefully before installing air conditioning equipment and be sure to install it correctly.
Failure to follow these instructions properly may result in property damage or personal injury, which may be serious depending on the circumstances.
WARNING
Do NOT play with the unit or its remote controller. Accidental operation by a child may result in impairment of bodily functions and harm health.
WARNING
Never disassemble the remote controller. Touching the interior parts may result in electric shocks or fire. Consult your Daikin dealer or authorized contactor for internal inspections and adjustments.
WARNING
To avoid electric shocks, do not operate with wet hands.
WARNING
Do NOT modify or repair the remote controller. This may result in electric shocks or fire. Consult your Daikin dealer.
Do NOT relocate or reinstall the remote controller by yourself. Improper installation may result in electric shocks or fire. Consult your Daikin dealer.
Do NOT use flammable materials (e.g. hairspray or insecticide) near the product. Do not clean the product with organic solvents such as paint thinner. The use of organic solvents may cause crack damage to the product, electric shocks, or fire.
2.Features and functions
The BRC1E53 is a state of the art remote controller that offers full control over your installation.
1 BASIC REMOTE CONTROLLER The basic remote controller functions are:
ON/OFF,
operation mode change-over,
temperature adjustment,
air volume adjustment,
airflow direction adjustment.
2 CLOCK FUNCTION The clock functions are:
12/24 hours real time clock,
automatic daylight saving time.
3 SCHEDULE FUNCTION The schedule timer functions are:
a maximum of 5 actions can be programmed for each day of the week,
3 independent schedules can be programmed,
schedule can be enabled/disabled at any time,
linked to a cool temperature and/or heat temperature or an OFF operation (with or without a setback temperature),
"last command" overrules previous command until next scheduled command.
4 SETBACK
The setback function maintains the room temperature in a specific range when the occupants are out for a longer period and the airconditioning is switched OFF.
5 PROHIBIT BUTTON/FUNCTION
Buttons, functions and/or modes can be locked to limit the user action.
6 DETAILED DISPLAY POSSIBILITY
Additionally possible to display the outdoor temperature or room temperature.
7 Duty rotation
Auto backup unit and auto rotation to maximize your airconditioners' life.
8 Demand control
Make up an energy reduction schedule.
9 Quiet mode
Schedule a quiet mode for your outdoor unit(s).
10 INTERLOCK WITH 2 EXTERNAL SIGNALS
(Only available when the BRP7A51 Digital Input Adapter is connected)
Connect up to two switch contacts (contact B1 and B2).
Typical application: hotel interlock with field supplied window contact B1 and key card B2.
Installation and operation manual 1
3.Name and function of switches
9 4
5
1 |
|
|
|
|
|
7 |
|
|
|
|
|
|
|
3 |
|
|
|
|
6 |
|
|
|
|
|
|||
|
|
|
|
|
||
2 |
|
|
|
|
8 |
|
|
|
|
|
1 OPERATION MODE SELECTOR BUTTON To select the operation mode of your preference.
2 FAN SPEED/AIRFLOW DIRECTION SETTING BUTTON To enter the fan speed/airflow direction setting screen.
3 MENU/ENTER BUTTON
To enter the main menu or the selected setting item.
4 UP/DOWN BUTTON
To raise/lower the set temperature, to highlight the next item on the upper/lower side or to change the selected item.
5 RIGHT/LEFT BUTTON
To highlight the next item on the right/left-hand side.
6 ON/OFF BUTTON
To start or stop the system.
INFORMATION
This is the only button that works when the backlight is not lit.
7 OPERATION LAMP
Lights up during operation or blinks if a malfunction occurs.
8 CANCEL BUTTON
To return to the previous screen.
9 LCD (with backlight)
When pushing any operation button, the backlight will be lit for approximately 30 seconds. When 1 indoor unit is controlled by 2 remote controllers, the backlight of the remote controller operated earlier than the other one will be lit.
4.Name and function of icons
To change between the standard display and the detailed display refer to "17.4 To select the display mode".
Standard display
With icons |
With icons and text (default) |
|
|
10 |
|
11 |
10 |
|
|
11 |
9 |
|
8 |
9 |
|
|
8 |
1 |
|
|
1 |
Heat |
Set to |
7 |
28°C |
|
|
||||
2 |
3 |
2 |
|
28°C |
3 |
|
6 |
|
4 |
6 |
|
|
4 |
5 |
|
|
5 |
Error: Push Menu button |
|
Detailed display
|
With icons |
|
|
With icons and text |
|
|||||
15 |
|
|
|
15 |
|
|
|
|
13 |
|
16 |
Fri |
11:03 |
13 |
16 |
|
Fri |
11:03 |
7 |
||
12 |
12 |
Heat |
||||||||
|
|
|||||||||
|
|
3 |
Set |
to |
Room |
3 |
||||
|
|
|
14 |
|
|
|
|
|
14 |
Error: Push Menu button
1 OPERATION MODE
Operation mode
cool |
Heat |
Vent |
Air Clean |
|
|
|
|
|
|
Fan |
Dry |
Auto (Cool) |
Auto(Heat) |
|
|
|
|
|
|
|
|
|
|
2 FAN SPEED
Indicates the fan speed that is set for the air conditioner. If the air conditioner does not have fan speed control function, the fan speed will not be displayed.
3 SET/SETBACK TEMPERATURE DISPLAY
When the unit is turned on, Set to indicates the temperatures that are set for the air conditioner.
When the unit is turned off, Setback indicates the temperatures that are set for the setback function.
4 DEFROST/HOT START
Indicates that the defrost/hot start mode is active.
5 |
MESSAGE |
|
|
|
|
|
|
|
|
|
|
• When the unit is turned on, Set to indicates the |
|
7 |
SCHEDULE4 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
14.3 To use the holidays |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||
Messages can be displayed. |
|
|
|
|
|
|
|
|
temperatures that are set for the air conditioner. |
|
|
To set the startup time and operation stop time for any day of the |
|
The schedule timer will be disabled for the days that have been set |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
• When the unit is turned off, Setback indicates the |
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
6 |
VENTILATION/CLEANING |
|
|
|
|
|
|
|
|
week. It is possible to set up to 5 actions per day. Both operation |
|
as holiday. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
c |
|
temperatures that are set for the setback function. |
|
|
modes (normal |
and setback) |
can be |
selected. Additionally the |
1 |
Display |
the |
Holidays |
screen (14.3) (Refer to |
"22. Main |
menu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
Ventilation mode icons |
|
|
|
indicate the current |
|
|
Fan speed/Airflow direction |
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
holiday settings and schedule nr can be set. |
|
|
|
|
|
|
structure" and "Appendix"). |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||
|
ventilation mode (HRV only) (AUTOMATIC, ENERGY RECLAIM VENT., |
1 |
Push |
|
several times until the desired operation mode Cool, |
|
|
|
|
|
|
2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
8 |
MAINTENANCE INFORMATION |
|
|
|
|
|
Use |
to select the desired day. Push |
to display |
|
to |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
BYPASS). |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
Air Cleaning unit icon |
|
indicates that the air cleaning unit |
|
|
Heat, Vent, Fan, Dry, or Auto is selected. |
|
|
|
|
|
|
Is used to display the service contact and model info. |
|
|
|
|
|
set the holiday. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||
|
(option) is operational. |
|
|
|
|
2 |
Push |
|
. The operation lamp will light and the system starts |
|
9 |
CONFIGURATION |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Schedule |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||
7 |
|
DISPLAY |
|
|
|
|
|
|
|
|
|
operating. |
|
|
|
|
|
|
|
|
|
To set the LCD contrast. You can also switch between standard |
|
|
|
|
|
|
|
Holidays |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||
Indicates that the key lock is set or the menu button is prohibited. |
|
|
|
|
|
|
|
|
|
|
|
and detailed display. When detailed display is selected, the detailed |
|
|
|
|
|
|
|
Multiple Selection |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||||||||
3 |
Use |
|
to set the temperature. |
|
|
|
|
|
|
display settings can be changed. You can also set Quiet mode and |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Sun |
Mon |
Tue |
Wed |
Thu |
|
Fri |
|
Sat |
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||
8 |
DISPLAY |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Draft prevention. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
INFORMATION |
|
|
|
|
|
|
|
|
|
10 CURRENT SETTINGS |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||
Indicates that schedule timer or OFF timer is enabled. |
|
|
When in Dry or Vent mode, the fan speed can not be set. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Return |
|
Setting |
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
This shows a list of the current settings for the available items. |
3 |
Push |
to display the confirmation screen. |
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
DISPLAY |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
4 |
Push |
|
. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
11 CLOCK & CALENDAR |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||||
Indicates |
that the clock needs |
|
to be set. The schedule timer |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
4 |
Use |
to select Yes and push |
. |
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||||
|
5 |
Use |
|
to select airflow Level or Direction setting. |
|
|
This allows you to set the date and time. Time can be displayed in |
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
function will not work until the clock is set. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
either 12 hour or 24 hour time format. |
|
|
|
|
|
|
14.4 To change the schedule settings of the selected schedule nr |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||||
9 |
EXTERNAL CONTROL ICON |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
12 LANGUAGE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
Airflow level/direction |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
The schedule timer will be disabled for the days that have been set |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Indicates that another controller with higher priority is controlling or |
|
|
|
|
|
Level |
|
|
Direction |
|
|
|
|
|
|
This allows you to set the displayed language. |
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
Low |
|
|
|
Position 0 |
|
|
|
|
|
|
|
|
|
|
as holiday. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||
disabling your remote controller. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
8. |
|
|
Lock |
|
|
|
|
|
|
|
|
|
|
|
|
|
1 |
Display |
the |
Settings |
screen (14.4) (Refer to |
"22. Main |
menu |
|||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||
10 CHANGEOVER UNDER CENTRALISED CONTROL ICON |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
structure" and "Appendix"). |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 Display the main menu. |
|
|
|
|
|
|
|
2 |
Use |
to select the desired day (1). |
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||
Indicates that the changeover of the installation is under |
|
|
|
|
|
Returneturn |
|
Settingetti |
|
|
|
|
|
2 |
Press the |
button for 4 seconds. |
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||
6 |
With fan speed setting selected, use |
|
to select the desired |
|
|
|
|
|
|
3 |
Use |
to highlight the Operation start Time and |
|
|
|
to set |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
centralised control assigned to another indoor unit or optional cool/ |
|
|
3 |
Use |
to select the Lock item and press |
. |
|
|
|
|
|
the desired Operation start Time (2). |
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
heat selector connected to the outdoor unit (= master remote |
|
|
fan speed. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||
controller). |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
4 Use the submenu's to prohibit buttons, functions or modes. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
INFORMATION |
|
|
|
|
|
|
|
|
|
|
|
|
|
(2) |
|
|
Schedule nr 1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3 |
|
|
|
|
|
|
|
|
|
|
Time |
Act |
|
Cool |
|
Heat |
|
|
|
|
|
|
|
|
||||||||||
11 SETBACK ICON |
|
|
|
|
|
|
|
|
|
|
When in Dry or Vent mode, the fan speed can not be set. |
|
|
For more information refer to the detailed user reference guide . |
|
|
|
|
(1) |
|
|
Mon |
– 6 |
:00 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||
Flashes when the unit is turned on under the setback control. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
9. |
|
|
Rotation |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||
7 |
With airflow direction setting selected, use |
to change the |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||
12 AIRFLOW DIRECTION |
|
|
|
|
|
|
|
setting to Swing, Pos. 0, Pos. 1, Pos. 2, Pos. 3, and Pos. 4. |
|
|
1 Display the main menu. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||
Is displayed when the airflow direction and swing are set. |
|
|
|
|
0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2 |
Push the |
button for 4 seconds. |
|
|
|
|
|
4 |
|
|
|
|
|
|
Return |
Setting |
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
0 |
|
4 |
|
|
|
|
|
|
|
|
Use |
to highlight the action and |
|
|
|
to select the desired |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
13 CLOCK (12/24 Hours real time clock) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
1 |
|
|
|
|
|
|
|
|
|
|
3 |
Use |
to select the Rotation function and press |
. |
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Is displayed when the clock is set. If the clock is not set, - : - is |
|
|
|
|
2 3 4 |
|
|
|
|
|
|
1 |
2 |
3 |
|
|
|
|
|
|
Act. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||
displayed. |
|
|
|
|
|
|
|
8 |
Push |
|
to display the basic screen. |
|
|
|
|
|
4 |
Use the submenu to Enable or Disable Rotation and to |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
configure the rotation cycle. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3 |
|
|
||||||||||
14 DETAILED SELECTION |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
For |
more |
information refer to the detailed |
installer |
reference |
|
|
|
|
|
|
|
Schedule nr 1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||
Is displayed when the detailed display items are selected. |
9 |
Push |
|
. The operation lamp will turn off and the system stops |
|
|
|
|
|
|
|
|
|
|
|
|
Time |
Act |
Cool |
Heat |
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
guide3. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Mon |
– 6 :00 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
operating. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
: |
|
|
|
|
|
|
|
|
|
|
|
|
|
ON |
1 |
|
|
|||||||||||||||||||
15 ROTATION |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
10. |
Airflow direction1/Individual air direction |
|
|
|
|
|
|
|
|
|
|
: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
Additional features of the controller: KEY LOCK |
|
|
|
|
|
|
|
|
|
|
|
: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||
Indicates one unit is set as back-up and rotation mode is enabled. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||
1 |
Push |
|
for 4 seconds to enable the key lock mode. The key |
|
|
For more information refer to the detailed user reference guide3. |
|
|
|
|
|
|
|
|
|
|
|
|
|
Setting |
|
|
|
|
|
|
|
|
|
|
OFF |
2 |
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||
16 QUIET MODE |
|
|
|
|
|
|
|
|
|
|
|
|
|
Quick start (SkyAir only)1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
lock icon is displayed. |
|
|
|
|
|
|
|
|
11. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||
Indicates the HVAC system runs in quiet mode or under demand |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
INFORMATION (Act column) |
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 Display the Main Menu and proceed step (9) to display the basic |
|
|
|
There are 3 types of operations: |
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||
control. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||
5. |
Description of the operation modes |
|
|
|
|
|
Cool |
Set to |
|
|
|
|
|
2 |
screen (Refer to "22. Main menu structure" and "Appendix"). |
|
|
|
1. |
The temperature setpoints can be configured. |
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
Quick Start will appear on the basic screen when the Quick Start |
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
2. |
The setback temperature setpoints can be configured. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Cool |
|
|
|
|
|
|
|
function is turned ON. |
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||
1 |
FAN ONLY OPERATION |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3. The temperature and setback temperature setpoints |
||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||
In this mode, air only circulates without heating or cooling. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
INFORMATION |
|
|
|
|
|
|
|
|
|
|
|
are disabled. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||
2 |
DRY OPERATION |
|
|
|
|
|
|
|
|
|
|
|
|
Return |
|
Setting |
|
|
|
|
|
|
|
|
|
Repeat this procedure to turn Quick Start function off. |
|
5 |
Use |
to highlight the temperature and |
|
to select the |
|||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||
In this mode, the air humidity will be lowered with a minimal |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
desired value. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||
2 |
To cancel the key lock mode, push |
for 4 seconds. The key |
|
12. |
Ventilation |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||||||
temperature decrease. |
|
|
|
|
|
|
|
|
|
lock icon disappears. |
|
|
|
|
|
|
|
|
|
Only in case an HRV is connected. Refer to the HRV manuals for |
|
|
|
INFORMATION (Cool and Heat column) |
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||
The temperature and fan speed are controlled automatically and |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
__: Indicates that the temperature setpoint for |
cool/heat |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
7. |
Description of the items in the main menu |
|
|
more information. |
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
cannot be controlled by the remote controller. |
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
and setback temperature setpoint for this time period is not |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
13. |
Energy saving options |
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Dry operation will not function if the room temperature is too low. |
1 |
LOCK |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
specified. The last active setpoint will be utilized. |
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||
3 |
AUTOMATIC OPERATION |
|
|
|
|
To prohibit buttons, functions or modes. |
|
|
|
|
|
|
For more information refer to the detailed user reference guide3. |
|
|
|
- -: Indicates that the setback function is disabled for this |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
In this mode, the controller will automatically switch between |
2 |
ROTATION |
|
|
|
|
|
|
|
|
14. |
Schedule |
|
|
|
|
|
|
|
|
|
|
time period with action OFF. |
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||||||||||
heating and cooling as required by the setpoint. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
6 |
To set a different day of the week, use |
|
|
|
|
to highlight the day. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||
4 |
COOLING OPERATION |
|
|
|
|
|
To enable the duty rotation functionality. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Use |
to change the day. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||
|
|
|
|
|
(Only available with indoor units that support duty rotation) |
|
|
14.1 To enable/disable the schedule |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||
In this mode, cooling will be activated as required by the setpoint or |
3 |
AIRFLOW DIRECTION1/INDIVIDUAL AIR DIRECTION |
|
|
1 Display the Enable/Disable setting screen (14.1) (Refer to "22. Main |
7 |
To copy all actions of the day previously set, push |
. |
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
limit operation. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||||
5 |
HEATING OPERATION |
|
|
|
|
|
|
(only if the individual airflow function is installed) |
|
|
|
menu structure" and "Appendix"). |
|
|
|
|
|
8 |
When the entire schedule settings are completed, push |
|
to |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
2 |
Use |
to change the setting to Enable or Disable. |
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
To set the airflow direction for each 4 flaps individually. |
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
display the confirmation screen. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||
In this mode, heating will be activated as required by the setpoint or |
|
|
QUICK START1 (SkyAir only) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||
4 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||
setback operation. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
9 |
Use |
to select Yes and push |
. |
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Schedule |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||||||||||||
6 |
VENTILATION (HRV only) |
|
|
|
|
|
To quickly set the room temperature to a comfortable temperature. |
|
|
|
|
|
|
|
|
Enable/Disable |
|
|
|
|
|
|
|
15. |
Filter auto clean |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||
|
|
|
|
5 |
VENTILATION |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||
The ventilation mode operates the HRV; refer to the HRV manual |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Disable |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
This function is available only on the model whose panel has |
||||||||||||||||||||||||||||||||||||||||||||||||
for more details. |
|
|
|
|
|
|
|
|
To set the ventilation rate and the ventilation mode (HRV only). |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
6 |
ENERGY SAVING OPTIONS |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
automatic |
cleaning function of filter. Needs to be set when |
|||||||||||||||||||||||||||||||||||||||||
7 |
SETBACK |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Return |
Setting |
|
|
|
|
|
|
operation is OFF. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||
SETBACK is a feature that enables to keep the room temperature |
|
This allows you to restrict the setting temperature range and |
|
3 |
Push |
to display the confirmation screen. |
|
|
|
16. |
Maintenance information |
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
display the energy consumption. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
in |
a specific range |
when |
|
the occupants are out and the |
|
|
Setpoint Range Setting |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 |
Display the Maintenance Information screen (16) (Refer to "22. Main |
|||||||||||||||||||||||||||||||||||||||||||||||||
airconditioning is switched OFF. |
|
|
|
|
|
|
|
|
|
|
|
|
4 |
Use |
to select Yes and push |
. |
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
Energy saving list |
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
For example: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
menu structure" and "Appendix"). |
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
Setback condition |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
14.2 To select the schedule number |
|
|
|
|
|
2 |
The phone number for the Contact info will appear at the top of the |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
If the room temperature drops below 10°C, heating is started |
|
|
Sensing sensor (Low)1, 2 (Only if sensing sensor is installed) |
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
automatically. As soon as 12°C is reached, the controller |
|
|
Sensing sensor (Stop)1, 2 (Only if sensing sensor is installed) |
|
1 |
Display the Select Schedule screen (14.2) (Refer to "22. Main |
|
|
screen. The model info of the Indoor unit and Outdoor unit of your |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
returns to its original status. |
|
|
|
|
|
Setpoint Auto Reset |
|
|
|
|
|
|
|
|
|
|
menu structure" and "Appendix"). |
|
|
|
|
|
|
|
product will appear on the bottom of the screen. |
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||
If the room temperature goes above 35°C, cooling is started |
|
|
OFF Timer |
|
|
|
|
|
|
|
|
2 |
Use |
to change the setting to Schedule nr 1, Schedule nr 2, |
3 |
Push |
to return to the Main Menu. |
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
automatically. As |
soon |
as |
33°C is reached, the controller |
|
|
Auto display OFF |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
or Schedule nr 3. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||
|
returns to its original status. |
|
|
|
|
|
For more information refer to the detailed user reference |
|
|
|
|
|
|
|
|
|
|
17. |
Configuration |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||
The differential can be adjusted in the Setback configuration menu. |
|
|
guide3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Schedule |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||
The setback temperature can be set during the unit is turned off on |
|
|
Energy Consumption1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Select Schedule |
|
|
|
|
|
|
17.1 To select quiet mode enable/disable |
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||||||||||||
basic screen or set in the schedule. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||
6. |
Basic operation method |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Schedule nr 1 |
|
|
|
|
|
1 |
Display the Quiet Operation Mode settings screen. |
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2 Display the Enable/Disable screen (17.1) (Refer to "22. Main |
||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
menu structure" and "Appendix"). |
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||
|
|
a |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3 |
|
|
|
|
|
|
|
Return |
Setting |
|
|
|
|
|
3 |
Use |
to select Enable or Disable. |
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Push |
to display the confirmation screen. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
Cool |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
Set to |
|
|
|
1. |
|
This function is not compatible with SkyAir |
|
|
|
|
4 |
Push |
to display the confirmation screen. |
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
c |
|
|
|
|
|
|
|
Cool |
|
|
|
|
|
RR+RQ units. |
|
|
|
|
|
|
|
|
4 |
Use |
to select Yes and push |
. |
|
|
|
|
5 |
Use |
to select Yes and push |
. |
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
b |
|
|
2. |
In case of a simultaneous operation system, the |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
system is controlled by the sensing sensor |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
17.2 To select quiet mode settings |
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
Return |
|
Setting |
|
|
|
|
|
mounted in the master indoor unit. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||
|
a |
Operation mode |
|
|
|
|
|
|
3. |
The detailed user reference guide and installer |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 Display the Quiet Operation Mode settings screen. |
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
4. |
The schedule will not be available when a |
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
b |
Temperature: |
|
|
|
|
|
|
|
|
|
|
|
reference guide are available on http:// |
|
|
|
|
|
|
|
|
|
2 Display the Settings screen (17.2). |
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
www.daikineurope.com/support-and-manuals/ |
|
|
|
|
|
|
centralised controller or the BRP7A51 Digital |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3 |
Use |
to select the start or End time. |
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
product-information/ . |
|
|
|
|
|
|
|
|
|
|
Input Adapter is connected. |
|
|
|
|
|
|
|
|
|
|
|
|
BRC1E53 3P419248-1-KA – 2015.09