Daikin BRC1E53A, BRC1E53B, BRC1E53C User manual

4.5 (4)
Daikin BRC1E53A, BRC1E53B, BRC1E53C User manual

Installation and operation manual

a3P419248-1-KA

The English text is the original instruction. Other languages are translations of the original instructions.

Refer to http://www.daikineurope.com/support-and-manuals/ product-information/ for more detailed user reference guides.

Installation: see page 2.

OPERATION

1.General safety precautions

Also see operation manual attached to the outdoor and indoor unit.

Please read these "1. General safety precautions" carefully before installing air conditioning equipment and be sure to install it correctly.

Failure to follow these instructions properly may result in property damage or personal injury, which may be serious depending on the circumstances.

WARNING

Do NOT play with the unit or its remote controller. Accidental operation by a child may result in impairment of bodily functions and harm health.

WARNING

Never disassemble the remote controller. Touching the interior parts may result in electric shocks or fire. Consult your Daikin dealer or authorized contactor for internal inspections and adjustments.

WARNING

To avoid electric shocks, do not operate with wet hands.

WARNING

Do NOT modify or repair the remote controller. This may result in electric shocks or fire. Consult your Daikin dealer.

Do NOT relocate or reinstall the remote controller by yourself. Improper installation may result in electric shocks or fire. Consult your Daikin dealer.

Do NOT use flammable materials (e.g. hairspray or insecticide) near the product. Do not clean the product with organic solvents such as paint thinner. The use of organic solvents may cause crack damage to the product, electric shocks, or fire.

2.Features and functions

The BRC1E53 is a state of the art remote controller that offers full control over your installation.

1 BASIC REMOTE CONTROLLER The basic remote controller functions are:

ON/OFF,

operation mode change-over,

temperature adjustment,

air volume adjustment,

airflow direction adjustment.

2 CLOCK FUNCTION The clock functions are:

12/24 hours real time clock,

automatic daylight saving time.

3 SCHEDULE FUNCTION The schedule timer functions are:

a maximum of 5 actions can be programmed for each day of the week,

3 independent schedules can be programmed,

schedule can be enabled/disabled at any time,

linked to a cool temperature and/or heat temperature or an OFF operation (with or without a setback temperature),

"last command" overrules previous command until next scheduled command.

4 SETBACK

The setback function maintains the room temperature in a specific range when the occupants are out for a longer period and the airconditioning is switched OFF.

5 PROHIBIT BUTTON/FUNCTION

Buttons, functions and/or modes can be locked to limit the user action.

6 DETAILED DISPLAY POSSIBILITY

Additionally possible to display the outdoor temperature or room temperature.

7 Duty rotation

Auto backup unit and auto rotation to maximize your airconditioners' life.

8 Demand control

Make up an energy reduction schedule.

9 Quiet mode

Schedule a quiet mode for your outdoor unit(s).

10 INTERLOCK WITH 2 EXTERNAL SIGNALS

(Only available when the BRP7A51 Digital Input Adapter is connected)

Connect up to two switch contacts (contact B1 and B2).

Typical application: hotel interlock with field supplied window contact B1 and key card B2.

Installation and operation manual 1

3.Name and function of switches

9 4

5

1

 

 

 

 

 

7

 

 

 

 

 

 

3

 

 

 

 

6

 

 

 

 

 

 

 

 

 

2

 

 

 

 

8

 

 

 

 

1 OPERATION MODE SELECTOR BUTTON To select the operation mode of your preference.

2 FAN SPEED/AIRFLOW DIRECTION SETTING BUTTON To enter the fan speed/airflow direction setting screen.

3 MENU/ENTER BUTTON

To enter the main menu or the selected setting item.

4 UP/DOWN BUTTON

To raise/lower the set temperature, to highlight the next item on the upper/lower side or to change the selected item.

5 RIGHT/LEFT BUTTON

To highlight the next item on the right/left-hand side.

6 ON/OFF BUTTON

To start or stop the system.

INFORMATION

This is the only button that works when the backlight is not lit.

7 OPERATION LAMP

Lights up during operation or blinks if a malfunction occurs.

8 CANCEL BUTTON

To return to the previous screen.

9 LCD (with backlight)

When pushing any operation button, the backlight will be lit for approximately 30 seconds. When 1 indoor unit is controlled by 2 remote controllers, the backlight of the remote controller operated earlier than the other one will be lit.

4.Name and function of icons

To change between the standard display and the detailed display refer to "17.4 To select the display mode".

Standard display

With icons

With icons and text (default)

 

 

10

 

11

10

 

 

11

9

 

8

9

 

 

8

1

 

 

1

Heat

Set to

7

28°C

 

 

2

3

2

 

28°C

3

6

 

4

6

 

 

4

5

 

 

5

Error: Push Menu button

 

Detailed display

 

With icons

 

 

With icons and text

 

15

 

 

 

15

 

 

 

 

13

16

Fri

11:03

13

16

 

Fri

11:03

7

12

12

Heat

 

 

 

 

3

Set

to

Room

3

 

 

 

14

 

 

 

 

 

14

Error: Push Menu button

1 OPERATION MODE

Operation mode

cool

Heat

Vent

Air Clean

 

 

 

 

Fan

Dry

Auto (Cool)

Auto(Heat)

 

 

 

 

 

 

 

 

2 FAN SPEED

Indicates the fan speed that is set for the air conditioner. If the air conditioner does not have fan speed control function, the fan speed will not be displayed.

3 SET/SETBACK TEMPERATURE DISPLAY

When the unit is turned on, Set to indicates the temperatures that are set for the air conditioner.

When the unit is turned off, Setback indicates the temperatures that are set for the setback function.

4 DEFROST/HOT START

Indicates that the defrost/hot start mode is active.

5

MESSAGE

 

 

 

 

 

 

 

 

 

 

When the unit is turned on, Set to indicates the

 

7

SCHEDULE4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14.3 To use the holidays

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Messages can be displayed.

 

 

 

 

 

 

 

 

temperatures that are set for the air conditioner.

 

 

To set the startup time and operation stop time for any day of the

 

The schedule timer will be disabled for the days that have been set

 

 

 

 

 

 

 

When the unit is turned off, Setback indicates the

 

 

 

6

VENTILATION/CLEANING

 

 

 

 

 

 

 

 

week. It is possible to set up to 5 actions per day. Both operation

 

as holiday.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

c

 

temperatures that are set for the setback function.

 

 

modes (normal

and setback)

can be

selected. Additionally the

1

Display

the

Holidays

screen (14.3) (Refer to

"22. Main

menu

Ventilation mode icons

 

 

 

indicate the current

 

 

Fan speed/Airflow direction

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

holiday settings and schedule nr can be set.

 

 

 

 

 

 

structure" and "Appendix").

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ventilation mode (HRV only) (AUTOMATIC, ENERGY RECLAIM VENT.,

1

Push

 

several times until the desired operation mode Cool,

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

MAINTENANCE INFORMATION

 

 

 

 

 

Use

to select the desired day. Push

to display

 

to

 

BYPASS).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air Cleaning unit icon

 

indicates that the air cleaning unit

 

 

Heat, Vent, Fan, Dry, or Auto is selected.

 

 

 

 

 

 

Is used to display the service contact and model info.

 

 

 

 

 

set the holiday.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(option) is operational.

 

 

 

 

2

Push

 

. The operation lamp will light and the system starts

 

9

CONFIGURATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Schedule

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

DISPLAY

 

 

 

 

 

 

 

 

 

operating.

 

 

 

 

 

 

 

 

 

To set the LCD contrast. You can also switch between standard

 

 

 

 

 

 

 

Holidays

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indicates that the key lock is set or the menu button is prohibited.

 

 

 

 

 

 

 

 

 

 

 

and detailed display. When detailed display is selected, the detailed

 

 

 

 

 

 

 

Multiple Selection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

Use

 

to set the temperature.

 

 

 

 

 

 

display settings can be changed. You can also set Quiet mode and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sun

Mon

Tue

Wed

Thu

 

Fri

 

Sat

 

 

 

 

 

 

 

 

 

8

DISPLAY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Draft prevention.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INFORMATION

 

 

 

 

 

 

 

 

 

10 CURRENT SETTINGS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indicates that schedule timer or OFF timer is enabled.

 

 

When in Dry or Vent mode, the fan speed can not be set.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Return

 

Setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This shows a list of the current settings for the available items.

3

Push

to display the confirmation screen.

 

 

 

 

 

 

 

 

DISPLAY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

Push

 

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11 CLOCK & CALENDAR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indicates

that the clock needs

 

to be set. The schedule timer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

Use

to select Yes and push

.

 

 

 

 

 

 

 

 

 

 

 

 

5

Use

 

to select airflow Level or Direction setting.

 

 

This allows you to set the date and time. Time can be displayed in

 

 

 

 

 

 

 

 

 

 

 

function will not work until the clock is set.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

either 12 hour or 24 hour time format.

 

 

 

 

 

 

14.4 To change the schedule settings of the selected schedule nr

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

EXTERNAL CONTROL ICON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12 LANGUAGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Airflow level/direction

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The schedule timer will be disabled for the days that have been set

Indicates that another controller with higher priority is controlling or

 

 

 

 

 

Level

 

 

Direction

 

 

 

 

 

 

This allows you to set the displayed language.

 

 

 

 

 

 

 

 

 

 

 

Low

 

 

 

Position 0

 

 

 

 

 

 

 

 

 

 

as holiday.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

disabling your remote controller.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8.

 

 

Lock

 

 

 

 

 

 

 

 

 

 

 

 

 

1

Display

the

Settings

screen (14.4) (Refer to

"22. Main

menu

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10 CHANGEOVER UNDER CENTRALISED CONTROL ICON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

structure" and "Appendix").

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 Display the main menu.

 

 

 

 

 

 

 

2

Use

to select the desired day (1).

 

 

 

 

 

 

 

Indicates that the changeover of the installation is under

 

 

 

 

 

Returneturn

 

Settingetti

 

 

 

 

 

2

Press the

button for 4 seconds.

 

 

 

 

 

 

 

 

 

 

 

 

6

With fan speed setting selected, use

 

to select the desired

 

 

 

 

 

 

3

Use

to highlight the Operation start Time and

 

 

 

to set

centralised control assigned to another indoor unit or optional cool/

 

 

3

Use

to select the Lock item and press

.

 

 

 

 

 

the desired Operation start Time (2).

 

 

 

 

 

 

 

 

 

 

 

 

heat selector connected to the outdoor unit (= master remote

 

 

fan speed.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

controller).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4 Use the submenu's to prohibit buttons, functions or modes.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INFORMATION

 

 

 

 

 

 

 

 

 

 

 

 

 

(2)

 

 

Schedule nr 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

Time

Act

 

Cool

 

Heat

 

 

 

 

 

 

 

 

11 SETBACK ICON

 

 

 

 

 

 

 

 

 

 

When in Dry or Vent mode, the fan speed can not be set.

 

 

For more information refer to the detailed user reference guide .

 

 

 

 

(1)

 

 

Mon

6

:00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flashes when the unit is turned on under the setback control.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9.

 

 

Rotation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

With airflow direction setting selected, use

to change the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12 AIRFLOW DIRECTION

 

 

 

 

 

 

 

setting to Swing, Pos. 0, Pos. 1, Pos. 2, Pos. 3, and Pos. 4.

 

 

1 Display the main menu.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is displayed when the airflow direction and swing are set.

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

Push the

button for 4 seconds.

 

 

 

 

 

4

 

 

 

 

 

 

Return

Setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

4

 

 

 

 

 

 

 

 

Use

to highlight the action and

 

 

 

to select the desired

13 CLOCK (12/24 Hours real time clock)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

3

Use

to select the Rotation function and press

.

 

 

 

 

Is displayed when the clock is set. If the clock is not set, - : - is

 

 

 

 

2 3 4

 

 

 

 

 

 

1

2

3

 

 

 

 

 

 

Act.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

displayed.

 

 

 

 

 

 

 

8

Push

 

to display the basic screen.

 

 

 

 

 

4

Use the submenu to Enable or Disable Rotation and to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

configure the rotation cycle.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

14 DETAILED SELECTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For

more

information refer to the detailed

installer

reference

 

 

 

 

 

 

 

Schedule nr 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is displayed when the detailed display items are selected.

9

Push

 

. The operation lamp will turn off and the system stops

 

 

 

 

 

 

 

 

 

 

 

 

Time

Act

Cool

Heat

 

 

 

 

 

 

 

 

 

 

 

guide3.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mon

6 :00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

operating.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

:

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

1

 

 

15 ROTATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10.

Airflow direction1/Individual air direction

 

 

 

 

 

 

 

 

 

 

:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Additional features of the controller: KEY LOCK

 

 

 

 

 

 

 

 

 

 

 

:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indicates one unit is set as back-up and rotation mode is enabled.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

Push

 

for 4 seconds to enable the key lock mode. The key

 

 

For more information refer to the detailed user reference guide3.

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting

 

 

 

 

 

 

 

 

 

 

OFF

2

 

 

16 QUIET MODE

 

 

 

 

 

 

 

 

 

 

 

 

 

Quick start (SkyAir only)1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

lock icon is displayed.

 

 

 

 

 

 

 

 

11.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indicates the HVAC system runs in quiet mode or under demand

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INFORMATION (Act column)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 Display the Main Menu and proceed step (9) to display the basic

 

 

 

There are 3 types of operations:

 

 

 

 

 

 

 

 

 

 

 

 

control.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.

Description of the operation modes

 

 

 

 

 

Cool

Set to

 

 

 

 

 

2

screen (Refer to "22. Main menu structure" and "Appendix").

 

 

 

1.

The temperature setpoints can be configured.

 

 

 

 

 

 

 

 

 

 

 

 

Quick Start will appear on the basic screen when the Quick Start

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.

The setback temperature setpoints can be configured.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cool

 

 

 

 

 

 

 

function is turned ON.

 

 

 

 

 

 

 

 

 

 

1

FAN ONLY OPERATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3. The temperature and setback temperature setpoints

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

In this mode, air only circulates without heating or cooling.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INFORMATION

 

 

 

 

 

 

 

 

 

 

 

are disabled.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

DRY OPERATION

 

 

 

 

 

 

 

 

 

 

 

 

Return

 

Setting

 

 

 

 

 

 

 

 

 

Repeat this procedure to turn Quick Start function off.

 

5

Use

to highlight the temperature and

 

to select the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

In this mode, the air humidity will be lowered with a minimal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

desired value.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

To cancel the key lock mode, push

for 4 seconds. The key

 

12.

Ventilation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

temperature decrease.

 

 

 

 

 

 

 

 

 

lock icon disappears.

 

 

 

 

 

 

 

 

 

Only in case an HRV is connected. Refer to the HRV manuals for

 

 

 

INFORMATION (Cool and Heat column)

 

 

 

 

 

 

 

The temperature and fan speed are controlled automatically and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

__: Indicates that the temperature setpoint for

cool/heat

7.

Description of the items in the main menu

 

 

more information.

 

 

 

 

 

 

 

 

 

 

cannot be controlled by the remote controller.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and setback temperature setpoint for this time period is not

 

13.

Energy saving options

 

 

 

 

 

 

 

 

Dry operation will not function if the room temperature is too low.

1

LOCK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

specified. The last active setpoint will be utilized.

 

 

 

 

 

3

AUTOMATIC OPERATION

 

 

 

 

To prohibit buttons, functions or modes.

 

 

 

 

 

 

For more information refer to the detailed user reference guide3.

 

 

 

- -: Indicates that the setback function is disabled for this

In this mode, the controller will automatically switch between

2

ROTATION

 

 

 

 

 

 

 

 

14.

Schedule

 

 

 

 

 

 

 

 

 

 

time period with action OFF.

 

 

 

 

 

 

 

 

 

 

 

 

heating and cooling as required by the setpoint.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

To set a different day of the week, use

 

 

 

 

to highlight the day.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

COOLING OPERATION

 

 

 

 

 

To enable the duty rotation functionality.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Use

to change the day.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Only available with indoor units that support duty rotation)

 

 

14.1 To enable/disable the schedule

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

In this mode, cooling will be activated as required by the setpoint or

3

AIRFLOW DIRECTION1/INDIVIDUAL AIR DIRECTION

 

 

1 Display the Enable/Disable setting screen (14.1) (Refer to "22. Main

7

To copy all actions of the day previously set, push

.

 

 

limit operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

HEATING OPERATION

 

 

 

 

 

 

(only if the individual airflow function is installed)

 

 

 

menu structure" and "Appendix").

 

 

 

 

 

8

When the entire schedule settings are completed, push

 

to

 

 

 

 

 

 

 

2

Use

to change the setting to Enable or Disable.

 

 

 

 

 

 

 

 

 

To set the airflow direction for each 4 flaps individually.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

display the confirmation screen.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

In this mode, heating will be activated as required by the setpoint or

 

 

QUICK START1 (SkyAir only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

setback operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

Use

to select Yes and push

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Schedule

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

VENTILATION (HRV only)

 

 

 

 

 

To quickly set the room temperature to a comfortable temperature.

 

 

 

 

 

 

 

 

Enable/Disable

 

 

 

 

 

 

 

15.

Filter auto clean

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

VENTILATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The ventilation mode operates the HRV; refer to the HRV manual

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Disable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This function is available only on the model whose panel has

for more details.

 

 

 

 

 

 

 

 

To set the ventilation rate and the ventilation mode (HRV only).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

ENERGY SAVING OPTIONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

automatic

cleaning function of filter. Needs to be set when

7

SETBACK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Return

Setting

 

 

 

 

 

 

operation is OFF.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SETBACK is a feature that enables to keep the room temperature

 

This allows you to restrict the setting temperature range and

 

3

Push

to display the confirmation screen.

 

 

 

16.

Maintenance information

 

 

 

 

 

 

 

 

display the energy consumption.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

in

a specific range

when

 

the occupants are out and the

 

Setpoint Range Setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

Display the Maintenance Information screen (16) (Refer to "22. Main

airconditioning is switched OFF.

 

 

 

 

 

 

 

 

 

 

 

 

4

Use

to select Yes and push

.

 

 

 

 

 

 

 

 

Energy saving list

 

 

 

 

 

 

 

 

 

 

 

 

For example:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

menu structure" and "Appendix").

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setback condition

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14.2 To select the schedule number

 

 

 

 

 

2

The phone number for the Contact info will appear at the top of the

If the room temperature drops below 10°C, heating is started

 

Sensing sensor (Low)1, 2 (Only if sensing sensor is installed)

 

 

 

 

 

 

 

 

automatically. As soon as 12°C is reached, the controller

 

Sensing sensor (Stop)1, 2 (Only if sensing sensor is installed)

 

1

Display the Select Schedule screen (14.2) (Refer to "22. Main

 

 

screen. The model info of the Indoor unit and Outdoor unit of your

 

returns to its original status.

 

 

 

 

Setpoint Auto Reset

 

 

 

 

 

 

 

 

 

 

menu structure" and "Appendix").

 

 

 

 

 

 

 

product will appear on the bottom of the screen.

 

 

 

 

 

If the room temperature goes above 35°C, cooling is started

 

OFF Timer

 

 

 

 

 

 

 

 

2

Use

to change the setting to Schedule nr 1, Schedule nr 2,

3

Push

to return to the Main Menu.

 

 

 

 

 

 

 

 

 

 

 

 

 

automatically. As

soon

as

33°C is reached, the controller

 

Auto display OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

or Schedule nr 3.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

returns to its original status.

 

 

 

 

 

For more information refer to the detailed user reference

 

 

 

 

 

 

 

 

 

 

17.

Configuration

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The differential can be adjusted in the Setback configuration menu.

 

 

guide3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Schedule

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The setback temperature can be set during the unit is turned off on

 

Energy Consumption1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Select Schedule

 

 

 

 

 

 

17.1 To select quiet mode enable/disable

 

 

 

 

 

 

 

basic screen or set in the schedule.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6.

Basic operation method

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Schedule nr 1

 

 

 

 

 

1

Display the Quiet Operation Mode settings screen.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 Display the Enable/Disable screen (17.1) (Refer to "22. Main

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

menu structure" and "Appendix").

 

 

 

 

 

 

 

 

 

 

 

 

 

 

a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

Return

Setting

 

 

 

 

 

3

Use

to select Enable or Disable.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Push

to display the confirmation screen.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cool

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set to

 

 

 

1.

 

This function is not compatible with SkyAir

 

 

 

 

4

Push

to display the confirmation screen.

 

 

 

 

 

 

 

 

 

c

 

 

 

 

 

 

 

Cool

 

 

 

 

 

RR+RQ units.

 

 

 

 

 

 

 

 

4

Use

to select Yes and push

.

 

 

 

 

5

Use

to select Yes and push

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b

 

 

2.

In case of a simultaneous operation system, the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

system is controlled by the sensing sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

17.2 To select quiet mode settings

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Return

 

Setting

 

 

 

 

 

mounted in the master indoor unit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

a

Operation mode

 

 

 

 

 

 

3.

The detailed user reference guide and installer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 Display the Quiet Operation Mode settings screen.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.

The schedule will not be available when a

 

 

 

 

 

 

 

 

 

b

Temperature:

 

 

 

 

 

 

 

 

 

 

 

reference guide are available on http://

 

 

 

 

 

 

 

 

 

2 Display the Settings screen (17.2).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

www.daikineurope.com/support-and-manuals/

 

 

 

 

 

 

centralised controller or the BRP7A51 Digital

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

Use

to select the start or End time.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

product-information/ .

 

 

 

 

 

 

 

 

 

 

Input Adapter is connected.

 

 

 

 

 

 

 

 

 

 

 

 

BRC1E53 3P419248-1-KA – 2015.09