Crestron Green Light™
DIN-8SW8
DIN Rail High-Voltage Switch
Operations & Installation Guide
This document was prepared and written by the Technical Documentation department at:
Crestron Electronics, Inc.
15 Volvo Drive
Rockleigh, NJ 07647
1-888-CRESTRON
Regulatory Compliance
This product is Listed to applicable UL Standards and requirements by Underwriters Laboratories Inc.
As of the date of manufacture, the DIN-8SW8 has been tested and found to comply with specifications for CE marking and standards per EMC and Radiocommunications Compliance Labelling.
Federal Communications Commission (FCC) Compliance Statement
This device complies with part 15 of the FCC Rules. Operation is subject to the following conditions:
(1) This device may not cause harmful interference and (2) this device must accept any interference received, including interference that may cause undesired operation.
CAUTION: Changes or modifications not expressly approved by the manufacturer responsible for compliance could void the user’s authority to operate the equipment.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna
Increase the separation between the equipment and receiver
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio/TV technician for help
Industry Canada (IC) Compliance Statement
This Class B digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada.
All brand names, product names and trademarks are the property of their respective owners. ©2010 Crestron Electronics, Inc.
Crestron DIN-8SW8 |
DIN Rail High-Voltage Switch |
Contents
DIN Rail High-Voltage Switch: DIN-8SW8 |
1 |
Introduction ............................................................................................................................... |
1 |
Features and Functions ................................................................................................ |
1 |
Applications................................................................................................................. |
3 |
Specifications .............................................................................................................. |
4 |
Physical Description.................................................................................................... |
6 |
Setup .......................................................................................................................................... |
9 |
Network Wiring........................................................................................................... |
9 |
Identity Code ............................................................................................................... |
9 |
Installation................................................................................................................. |
10 |
Hardware Hookup ..................................................................................................... |
12 |
Programming Software............................................................................................................ |
14 |
Earliest Version Software Requirements for the PC ................................................. |
14 |
Programming with Crestron SystemBuilder.............................................................. |
14 |
Programming with D3 Pro......................................................................................... |
15 |
Programming with SIMPL Windows ........................................................................ |
15 |
Example Program ...................................................................................................... |
17 |
Uploading and Upgrading........................................................................................................ |
18 |
Establishing Communication..................................................................................... |
18 |
Programs and Firmware ............................................................................................ |
19 |
Program Checks ........................................................................................................ |
19 |
Operation ................................................................................................................................. |
20 |
Problem Solving ...................................................................................................................... |
22 |
Troubleshooting......................................................................................................... |
22 |
Check Network Wiring.............................................................................................. |
23 |
Reference Documents................................................................................................ |
24 |
Further Inquiries ........................................................................................................ |
24 |
Future Updates .......................................................................................................... |
25 |
Return and Warranty Policies .................................................................................................. |
26 |
Merchandise Returns / Repair Service ...................................................................... |
26 |
CRESTRON Limited Warranty................................................................................. |
26 |
Operations & Installation Guide – DOC. 6666B |
Contents • i |
Crestron DIN-8SW8 |
DIN Rail High-Voltage Switch |
DIN Rail High-Voltage Switch:
DIN-8SW8
The DIN-8SW8 is an eight channel lighting control module designed to support switching of non-dimmable lighting and fans. A single model supports both 120 and 220-240 Volt applications. Each channel handles incandescent loads up to 10 Amps, fluorescent loads up to 5 Amps, and also 1/2 HP motors.*
•Eight channels of power switching
•Supports 120 to 240 Volt 50/60 Hz
•Override input
•Cresnet® communications
•Setup via front panel or software
•Programmable functionality via DIN-AP2
•9M wide DIN rail mounting
*May not be compatible with some high inrush current loads.
Operations & Installation Guide – DOC. 6666B DIN Rail High-Voltage Switch: DIN-8SW8 • 1
DIN Rail High-Voltage Switch |
Crestron DIN-8SW8 |
Override Input
An override input is provided to allow an external contact closure to momentarily override the control system program and set each channel output to its override preset state. States can be set and saved locally from the front panel or remotely via software.
DIN Rail Installation
The DIN-8SW8 is designed to snap onto a standard DIN rail for installation in a wall mount enclosure. Wiring connections are made using screw terminals positioned along the top and bottom, clearly accessible from the front for easy installation and servicing. All setup controls and indicators are positioned on the center front panel. When installed in an enclosure utilizing 45 mm cutouts, the DIN-8SW8’s front panel stays accessible while the connections are concealed.
Cresnet
The DIN-8SW8 communicates with a DIN-AP2 2-Series Automation Processor, or other Crestron® 2-Series control system, via the Cresnet control network. A pair of Cresnet ports is provided on the DIN-8SW8 allowing for easy daisy chaining of several DIN Rail Series automation control modules.
2 • DIN Rail High-Voltage Switch: DIN-8SW8 Operations & Installation Guide – DOC. 6666B
Crestron DIN-8SW8 |
DIN Rail High-Voltage Switch |
The following diagram shows a DIN-8SW8 in a typical application.
DIN-8SW8 in a Typical Application
Operations & Installation Guide – DOC. 6666B DIN Rail High-Voltage Switch: DIN-8SW8 • 3
DIN Rail High-Voltage Switch |
Crestron DIN-8SW8 |
Specifications for the DIN-8SW8 are listed in the following table.
DIN-8SW8 Specifications
SPECIFICATION |
|
DETAILS |
Load Ratings |
|
|
Switch Channels |
8 |
|
Maximum Per Channel |
10 |
Amps incandescent, |
|
5 Amps fluorescent, |
|
|
0.5 HP @ 120 to 240 Volts AC, |
|
|
50/60 Hz; |
|
|
5 Amps @ 30 Volts DC; |
|
|
16 |
Amps Resistive |
Module Total |
80 |
Amps incandescent, |
|
40 |
Amps fluorescent, @ 120-240 |
|
Volts AC, 50/60 Hz |
|
Load Types1 |
Incandescent, |
|
|
magnetic low-voltage, |
|
|
electronic low-voltage, |
|
|
neon/cold cathode, |
|
|
fluorescent, motors |
|
Power Requirements |
|
|
Cresnet Power Usage |
5.4 Watts |
|
|
(0.23 Amps @ 24 Volts DC) |
|
Default Net ID |
89 |
|
Minimum 2-Series |
Version 4.000.0226 or later |
|
Control System Update |
|
|
File2, 3 |
|
|
Environmental |
|
|
Temperature |
0º to 40º C (32º to 104º F) |
|
Humidity |
10% to 90% RH (non-condensing) |
|
Heat Dissipation |
18 |
BTU/Hr |
(Continued on following page)
4 • DIN Rail High-Voltage Switch: DIN-8SW8 Operations & Installation Guide – DOC. 6666B
Crestron DIN-8SW8 |
DIN Rail High-Voltage Switch |
||
DIN-8SW8 Specifications (Continued) |
|||
|
|
|
|
|
SPECIFICATION |
DETAILS |
|
|
Enclosure |
Light gray polycarbonate housing |
|
|
|
with polycarbonate label overlay, |
|
|
|
UL94 V-0 rated, 35 mm DIN EN |
|
|
|
60715 rail mount, DIN 43880 |
|
|
|
form factor for enclosures with |
|
|
|
45 mm front panel cutout, |
|
|
|
occupies 9 DIN module spaces |
|
|
|
(162 mm) |
|
|
Dimensions |
|
|
|
Height |
95 mm (3.71 in) |
|
|
Width |
159 mm (6.26 in) |
|
|
Depth |
60 mm (2.35 in) |
|
|
Weight |
369 g (13 oz) |
|
|
Available Accessories |
|
|
|
DIN-BLOCK |
DIN Rail Cresnet Distribution |
|
|
|
Block |
|
|
DIN-HUB |
DIN Rail Cresnet Distribution Hub |
|
|
DIN-PWS50 |
DIN Rail 50 Watt Cresnet Power |
|
|
|
Supply |
|
1.May not be compatible with some high inrush current loads.
2.The latest software versions can be obtained from the Crestron website. Refer to the NOTE following these footnotes.
3.Crestron 2-Series control systems include the DIN-AP2, AV2 and PRO2. Consult the latest Crestron Product Catalog for a complete list of 2-Series control systems.
NOTE: Crestron software and any files on the website are for authorized Crestron dealers and Crestron Authorized Independent Programmers (CAIP) only. New users may be required to register to obtain access to certain areas of the site (including the FTP site).
Operations & Installation Guide – DOC. 6666B DIN Rail High-Voltage Switch: DIN-8SW8 • 5
DIN Rail High-Voltage Switch |
Crestron DIN-8SW8 |
This section provides information on the connections, controls and indicators available on your DIN-8SW8.
DIN-8SW8 Physical View
DIN-8SW8 Overall Dimensions
6 • DIN Rail High-Voltage Switch: DIN-8SW8 Operations & Installation Guide – DOC. 6666B