Crestron DIN-8SW8 User Manual

4.5 (2)

Crestron Green Light™

DIN-8SW8

DIN Rail High-Voltage Switch

Operations & Installation Guide

This document was prepared and written by the Technical Documentation department at:

Crestron Electronics, Inc.

15 Volvo Drive

Rockleigh, NJ 07647

1-888-CRESTRON

Regulatory Compliance

This product is Listed to applicable UL Standards and requirements by Underwriters Laboratories Inc.

As of the date of manufacture, the DIN-8SW8 has been tested and found to comply with specifications for CE marking and standards per EMC and Radiocommunications Compliance Labelling.

Federal Communications Commission (FCC) Compliance Statement

This device complies with part 15 of the FCC Rules. Operation is subject to the following conditions:

(1) This device may not cause harmful interference and (2) this device must accept any interference received, including interference that may cause undesired operation.

CAUTION: Changes or modifications not expressly approved by the manufacturer responsible for compliance could void the user’s authority to operate the equipment.

NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

Reorient or relocate the receiving antenna

Increase the separation between the equipment and receiver

Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio/TV technician for help

Industry Canada (IC) Compliance Statement

This Class B digital apparatus complies with Canadian ICES-003.

Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada.

All brand names, product names and trademarks are the property of their respective owners. ©2010 Crestron Electronics, Inc.

Crestron DIN-8SW8

DIN Rail High-Voltage Switch

Contents

DIN Rail High-Voltage Switch: DIN-8SW8

1

Introduction ...............................................................................................................................

1

Features and Functions ................................................................................................

1

Applications.................................................................................................................

3

Specifications ..............................................................................................................

4

Physical Description....................................................................................................

6

Setup ..........................................................................................................................................

9

Network Wiring...........................................................................................................

9

Identity Code ...............................................................................................................

9

Installation.................................................................................................................

10

Hardware Hookup .....................................................................................................

12

Programming Software............................................................................................................

14

Earliest Version Software Requirements for the PC .................................................

14

Programming with Crestron SystemBuilder..............................................................

14

Programming with D3 Pro.........................................................................................

15

Programming with SIMPL Windows ........................................................................

15

Example Program ......................................................................................................

17

Uploading and Upgrading........................................................................................................

18

Establishing Communication.....................................................................................

18

Programs and Firmware ............................................................................................

19

Program Checks ........................................................................................................

19

Operation .................................................................................................................................

20

Problem Solving ......................................................................................................................

22

Troubleshooting.........................................................................................................

22

Check Network Wiring..............................................................................................

23

Reference Documents................................................................................................

24

Further Inquiries ........................................................................................................

24

Future Updates ..........................................................................................................

25

Return and Warranty Policies ..................................................................................................

26

Merchandise Returns / Repair Service ......................................................................

26

CRESTRON Limited Warranty.................................................................................

26

Operations & Installation Guide – DOC. 6666B

Contents i

Crestron DIN-8SW8

DIN Rail High-Voltage Switch

DIN Rail High-Voltage Switch:

DIN-8SW8

Introduction

The DIN-8SW8 is an eight channel lighting control module designed to support switching of non-dimmable lighting and fans. A single model supports both 120 and 220-240 Volt applications. Each channel handles incandescent loads up to 10 Amps, fluorescent loads up to 5 Amps, and also 1/2 HP motors.*

Features and Functions

Eight channels of power switching

Supports 120 to 240 Volt 50/60 Hz

Override input

Cresnet® communications

Setup via front panel or software

Programmable functionality via DIN-AP2

9M wide DIN rail mounting

*May not be compatible with some high inrush current loads.

Operations & Installation Guide – DOC. 6666B DIN Rail High-Voltage Switch: DIN-8SW8 1

DIN Rail High-Voltage Switch

Crestron DIN-8SW8

Override Input

An override input is provided to allow an external contact closure to momentarily override the control system program and set each channel output to its override preset state. States can be set and saved locally from the front panel or remotely via software.

DIN Rail Installation

The DIN-8SW8 is designed to snap onto a standard DIN rail for installation in a wall mount enclosure. Wiring connections are made using screw terminals positioned along the top and bottom, clearly accessible from the front for easy installation and servicing. All setup controls and indicators are positioned on the center front panel. When installed in an enclosure utilizing 45 mm cutouts, the DIN-8SW8’s front panel stays accessible while the connections are concealed.

Cresnet

The DIN-8SW8 communicates with a DIN-AP2 2-Series Automation Processor, or other Crestron® 2-Series control system, via the Cresnet control network. A pair of Cresnet ports is provided on the DIN-8SW8 allowing for easy daisy chaining of several DIN Rail Series automation control modules.

2 DIN Rail High-Voltage Switch: DIN-8SW8 Operations & Installation Guide – DOC. 6666B

Crestron DIN-8SW8

DIN Rail High-Voltage Switch

Applications

The following diagram shows a DIN-8SW8 in a typical application.

DIN-8SW8 in a Typical Application

Operations & Installation Guide – DOC. 6666B DIN Rail High-Voltage Switch: DIN-8SW8 3

DIN Rail High-Voltage Switch

Crestron DIN-8SW8

Specifications

Specifications for the DIN-8SW8 are listed in the following table.

DIN-8SW8 Specifications

SPECIFICATION

 

DETAILS

Load Ratings

 

 

Switch Channels

8

 

Maximum Per Channel

10

Amps incandescent,

 

5 Amps fluorescent,

 

0.5 HP @ 120 to 240 Volts AC,

 

50/60 Hz;

 

5 Amps @ 30 Volts DC;

 

16

Amps Resistive

Module Total

80

Amps incandescent,

 

40

Amps fluorescent, @ 120-240

 

Volts AC, 50/60 Hz

Load Types1

Incandescent,

 

magnetic low-voltage,

 

electronic low-voltage,

 

neon/cold cathode,

 

fluorescent, motors

Power Requirements

 

 

Cresnet Power Usage

5.4 Watts

 

(0.23 Amps @ 24 Volts DC)

Default Net ID

89

 

Minimum 2-Series

Version 4.000.0226 or later

Control System Update

 

 

File2, 3

 

 

Environmental

 

 

Temperature

0º to 40º C (32º to 104º F)

Humidity

10% to 90% RH (non-condensing)

Heat Dissipation

18

BTU/Hr

(Continued on following page)

4 DIN Rail High-Voltage Switch: DIN-8SW8 Operations & Installation Guide – DOC. 6666B

Crestron DIN-8SW8

DIN Rail High-Voltage Switch

DIN-8SW8 Specifications (Continued)

 

 

 

 

 

SPECIFICATION

DETAILS

 

 

Enclosure

Light gray polycarbonate housing

 

 

 

with polycarbonate label overlay,

 

 

 

UL94 V-0 rated, 35 mm DIN EN

 

 

 

60715 rail mount, DIN 43880

 

 

 

form factor for enclosures with

 

 

 

45 mm front panel cutout,

 

 

 

occupies 9 DIN module spaces

 

 

 

(162 mm)

 

 

Dimensions

 

 

 

Height

95 mm (3.71 in)

 

 

Width

159 mm (6.26 in)

 

 

Depth

60 mm (2.35 in)

 

 

Weight

369 g (13 oz)

 

 

Available Accessories

 

 

 

DIN-BLOCK

DIN Rail Cresnet Distribution

 

 

 

Block

 

 

DIN-HUB

DIN Rail Cresnet Distribution Hub

 

 

DIN-PWS50

DIN Rail 50 Watt Cresnet Power

 

 

 

Supply

 

1.May not be compatible with some high inrush current loads.

2.The latest software versions can be obtained from the Crestron website. Refer to the NOTE following these footnotes.

3.Crestron 2-Series control systems include the DIN-AP2, AV2 and PRO2. Consult the latest Crestron Product Catalog for a complete list of 2-Series control systems.

NOTE: Crestron software and any files on the website are for authorized Crestron dealers and Crestron Authorized Independent Programmers (CAIP) only. New users may be required to register to obtain access to certain areas of the site (including the FTP site).

Operations & Installation Guide – DOC. 6666B DIN Rail High-Voltage Switch: DIN-8SW8 5

Crestron DIN-8SW8 User Manual

DIN Rail High-Voltage Switch

Crestron DIN-8SW8

Physical Description

This section provides information on the connections, controls and indicators available on your DIN-8SW8.

DIN-8SW8 Physical View

DIN-8SW8 Overall Dimensions

6 DIN Rail High-Voltage Switch: DIN-8SW8 Operations & Installation Guide – DOC. 6666B

Loading...