Installation Instructions for MD6xT6, MD6xT4, MD6CPxT6 and MD6CPxT4

Commercial Recessed Housings

Risk Of Electrical Shock

Disconnect power at fuse or circuit breaker before installing or servicing.

Risk Of Fire

Supply conductors (power wires) connecting the fixture must be rated minimum 90°C. If uncertain, consult an electrician.

Risk Of Fire.

Do not install insulation within 3 inches (76 mm) of any part of the fixture or in a way that may entrap heat.

CAUTION: To avoid possible electrical shock, be sure that power supply is turned off before installing or servicing this fixture.

CAUTION: Metal halide lamps have arc tubes that operate at extremely high temperatures and may shatter unexpectedly as a result of misapplication, system failure or internal factors. This violent failure could cause extremely hot glass and lamp parts to discharge into the surrounding environment, creating a risk of personal injury, fire or property damage. Therefore, it is incumbent on the user to use common sense and good judgment in anticipation of these potential violent failures. Never use or operate this fixture without safety glass or lens properly installed and secured in place.

Reduction of Risk

The potential of violent failure can be significantly reduced by relamping at or before the rated end of life. In applications where the lamps burn continuously, the lamps should be turned off for a period of 15 minutes at least once per week which will cause lamps nearing their end of life to fail passively upon relighting. Careful adherence to the above precautions may not eliminate all possible risks associated with the use of Metal Halide lamps, but it will reduce the likelihood of personal injury or property damage.

Rough-In Mounting

This fixture should be supported by main runners or other structure that is capable of supporting fixture weight of 17lbs.

The junction box will accept both ½” and ¾” trade size metal conduit.

Review fixture labeling to make sure it is rated for the voltage installation being used.

The housing is designed for installation where it will not come in contact with insulation. Thermal insulation must be kept a minimum of three inches (3”) away from the housing sides, top and junction box.

This housing/trim is designed to be used with T6/T4.5 Ceramic Metal Halide lamps for the specified wattages only. These lamps can cause serious skin burn and

eye inflammation from shortwave ultraviolet radiation if the envelope of the lamp is broken or punctured.

704530 Rev. A

- 1 -

Customer First Center · 1121 Highway 74 South · Peachtree City, GA 30269

Portfolio®

Step 1. Install fixture into ceiling cavity using ½” electrical conduit, ¾” channel, 1½” channel or “ x ½” bar stock as mounting rails (furnished by others) by inserting them into hanger brackets at both ends of the fixture as shown.

Step 2. Secure mounting rails to support structures.

Step 3. Adjust fixture so bottom of plaster ring is flush with finished ceiling line, using screws securing hanger brackets. Hanger bracket is reversible for a total adjustment of 5”.

Electrical Connection

CAUTION: Make certain no bare wires are exposed outside of wire nut connectors.

Step 4. Provide electrical service according to the “National Electrical Code” or your local electrical code to the junction box (located on the plaster frame). Supply wire insulation must be rated for at least 90° C. The junction box is also rated for a maximum of 12 No. 12 AWG Branch Circuit conductors suitable for at least 90°C.

Step 5. Remove junction box cover.

Step 6. Remove appropriate round pryout and connect conduit to junction box with proper connector (not included).

Step 7. Connect supply lead wires to junction box lead wires (line, neutral and ground) in fixture using properly sized wire nuts (not included). Be careful not to leave any bare conductors outside of the wire nut connectors.

Step 8. 120V or 277V AC Supply: Connect white to white, black to black and green (from electrical service) to the bare copper wire in the junction box. See the appropriate wiring diagram for more detail.

Place all connections and excess wiring into the junction box and replace cover.

704530 Rev. A

- 2 -

Customer First Center · 1121 Highway 74 South · Peachtree City, GA 30269

Cooper Lighting MD6CPxT4, MD6CPxT6, MD6xT4, MD6xT6 User Manual

Portfolio®

Distribution Selection & Trim Installation

Step 1. Install the proper lamp type and wattage into the socket. Make sure the new lamp does not have any fingerprints, dust, lint, etc.

NOTE: The lamp-socket assembly is installed onto the trim in one of three possible positions. These are labeled Narrow, Medium and Wide. The selected position determines the light distribution from the fixture.

Step 2. As shown in figure at right, the trim assembly includes six plastic lockout inserts. Remove and discard the two lockouts from the desired distribution positions. For example, if a Medium distribution is desired, remove the two lockouts closest to the “Medium” labels.

NOTE: It is intended that the remaining plastic lockouts remain in place. This will help avoid any inadvertent distribution changes during re-lamping in the future.

Step 3. Secure the lamp-socket assembly in the desired distribution position with the two thumbscrews.

Step 4. Install the trim into the housing. The trim’s torsion springs pass through slots in torsion spring receivers inside the housing.

704530 Rev. A

- 3 -

Customer First Center · 1121 Highway 74 South · Peachtree City, GA 30269

Portfolio®

Lamping Information

The electronic ballast has a very important shutdown timing feature that turns off the ballast output after time periods ranging from 2 minutes up to 30 minutes if a lamp does not start or operate properly or if the fixture wiring is improper. For proper system diagnosis and at lamp replacement time, the INPUT POWER TO THE BALLAST MUST BE RESET (turn power off, wait 10 seconds, turn power back on) to start a new lamp.

Take proper care in handling and disposing of the old lamp. Do not touch glass bulb with bare hands.

Lamp contains Mercury. Manage in accordance with disposal laws. See www.lamprecycle.org or 1-866-666- 6850.

Main Lamp

Ceramic Metal Halide Lamp

MD6xT6G12 Housings

G12 socket for one 20W, 39W, 70W or 150W lamp. Generic lamp designations (lamp by others):

M156/E (20W)

M130/E (39W) M98/E, M139/E (70W)

M102/E, M142/E (150W)

MD6xT4G85 Housings

G8.5 socket for one 20W, 39W, or 70W lamp. Generic lamp designations (lamp by others):

M156/E (20W)

M130/E (39W) M98/E, M139/E (70W)

MD6xT4G65 Housings

GU6.5 socket for one 20W or 39W lamp. Generic lamp designations (lamp by others):

M156/E (20W)

M130/E (39W)

Quartz Lamp

Quartz Restrike Lamp

The Quartz lamp is a 100W, 120V, T4 Bulb with a “DC Bayonet” base.

This housing may be re-lamped either from below or above the ceiling.

Allow sufficient time for the lamp to cool.

704530 Rev. A

- 4 -

Customer First Center · 1121 Highway 74 South · Peachtree City, GA 30269