The information contained in this catalog is a summary overview of
Cla-Val products. Visit www.cla-val.com to see the complete range
of products, new releases and the most up-to-date literature.
Table of Contents
Main Valve Technical Data
Company Overview ....................................................................................................6
The information contained in this catalog is a summary overview of
Cla-Val products. Visit www.cla-val.com to see the complete range of
products, new releases and the most up-to-date literature.
Table of Contents
Rate of Flow Control Valves
40-01/640-01 Rate of Flow Control Valves ................................................................60
43-01/643-01 Combination Rate of Flow Control and Solenoid Shut-Off Valves .........61
49-01/649-01 Combination Rate of Flow and Pressure Reducing Valves ...................62
136-01/636-01 Solenoid Control Valves (sizes 1/2”-6”) ..............................................86
136-03/636-03 Solenoid Control Valves with High Capacity Control System ..............87
139-01 Programmable Timer Control Valves ................................................................88
www.cla-val.com/waterworks.cfm
Pump Control Valves
60-08/660-08 Booster Pump Control Valves..............................................................90
60-11/660-011 Booster Pump Control Valves ............................................................91
60-31/660-031 Booster Pump Control Valves............................................................92
60-32/660-032 Combination Pump Control and Back Pressure Valves ......................93
61-02/661-02 Deep Well Pump Control Valves..........................................................94
www.cla-val.com/waterworks.cfm
3
Page 4
The information contained in this catalog is a summary overview of
Cla-Val products. Visit www.cla-val.com to see the complete range of
products, new releases and the most up-to-date literature.
The information contained in this catalog is a summary overview of
Cla-Val products. Visit www.cla-val.com to see the complete range of
products, new releases and the most up-to-date literature.
Table of Contents
Fire Protection Valves
100G/2100G/100GS/2100GS Fire Protection Deluge Valves ...................................131
50B-4KG1 Fire Protection Pressure Relief Valves ...................................................133
50B-5KG Pump Suction Control Valves ..................................................................134
Since 1936, Cla-Val has produced the world’s highest quality automatic control
valves for a diverse array of applications and market places. Our special blend of
engineering expertise, craftsmanship, quality materials and sophisticated
manufacturing processes has earned Cla-Val a reputation for excellence
throughout the United States and around the world.
Cla-Val’s Southern California facility serves as the worldwide headquarters
and features an on-site foundry as well as a manufacturing operation with
more than four-acres under roof. Other North American locations include
state-of-the-art machine shops, production facilities and a sales office/
manufacturing operation in Ontario, Canada. Cla-Val offices and production
facilities in Switzerland, France and the United Kingdom serve the European
and Middle Eastern markets. Cla-Val Pacific in New Zealand covers
Australasia and Asia.
All Cla-Val automatic control valves and associated products are made from
the highest quality materials and backed by the best warranty in the industry.
Cla-Val provides a broad range of valve patterns and sizes in over fifty
different varieties of metals and grades. To help ensure that our customers
receive the technical and product support they need, we conduct the
industry’s most comprehensive engineering and application seminars. We
also offer in-depth end-user training programs to help our customers derive
the maximum benefit from their product investment.
Engineering Capabilities
One of Cla-Val’s most unique characteristics is the strong focus we place on
continuous improvement in our products and manufacturing processes. This
focus is personified by our in-house Engineering Department. They work handin-hand with our customers to develop real-world solutions, such as the recently
developed KO Anti-Cavitation valve trim pictured below, to help them meet their
operational challenges. Cla-Val Engineers continue to create products that
ultimately become the industry standard.
With strategically located distribution centers and sales offices throughout the
world, Cla-Val is the ideal source for superior technical know-how, unparalleled
customer service and the finest quality fluid handling products.
Utilizing a wide array of the most advanced technical
software, including custom programs developed in-house,
our Engineers analyze product applications, and study our
customers’ fluid handling systems to characterize conditions
such as Cv, surge, flow, and the potential for valve
cavitation noise and damage. This expertise enables our
Engineers to take the data they gather and determine which
flow or pressure control products will best meet our
customers’ system requirements in the most operationally
efficient and cost effective manner.
Beyond analyzing and understanding our customers’ existing requirements, Cla-Val Engineering uses the latest in solid modeling
design software to develop new products to meet the ever-changing requirements of the industries we serve. To further enhance
the value we provide, our Manufacturing Engineers continually work to develop and implement the latest technologies in our
production and foundry facilities to ensure that all of our products are crafted with the highest possible quality, precision and
exceptional accuracy.
Cla-Val product innovations --
destined to become tomorrow’s standards.
6
Page 7
P
1
P
2
P
BASIC MAIN VALVE
Most CLA-VAL valves consist of a main valve and pilot control system. The basic main valve is called a Hytrol Valve.
When no pressure is in the valve, the spring and the
weight of the diaphragm assembly hold the valve closed.
With the cover chamber vented to atmosphere, the valve
will open from line pressure under the disc.
If inlet pressure is connected into the cover chamber, the
valve closes tightly. In this example, the 400 pound difference is the force which pushes the disc against the seat
and causes the valve to seal drip-tight.
NON-MODULATING CONTROLS
A simple control which either opens the valve wide or
closes it tightly is a three-way valve. The type of operation
this control gives is called “non-modulating” because the
valve cannot pause in a partially open position.
To open...
Control is turned to
exhaust cover
chamber pressure.
Ordinary three-way valves usually
are not satisfactory because they
require so much force to operate.
An easy-turning control which can
be operated in a variety of ways is
usually used. Several examples of
controls and their operation are
shown at right.
With a solenoid
Once the control is turned to either position, operating
fluid flow into or out of the cover chamber until the valve is
open or closed. For example...
To close...
Control is turned to
apply pressure to
cover chamber.
By hand
C
L
N
O
E
S
P
E
O
D
By pressure
By a difference in
two pressures
By a float
7
Page 8
MODULATING CONTROLS
The Cla-Val Automatic Control Valve modulates if the cover pressure is held between the inlet and outlet pressure. To
achieve modulating operation, a slightly different type of control system is utilized.
Valve Open
When the throttling control opens to a point where more
pressure is relieved from the cover chamber than the
restriction can supply, cover pressure is reduced and
the valve opens.
Valve Throttling
The main valve modulates to any degree of opening in
response to changes in the throttling control. At an equilibrium point, the main valve opening and closing forces
hold the valve in balance. This balance holds the valve
partially open, but immediately responds and readjusts
its position to compensate for any change in the controlled condition.
Valve Closed
When the modulating control closes sufficiently to direct a
great enough pressure into the cover chamber to overcome
opening forces of line pressure, the main valve closes.
AUTOMATIC CONTROLS
The following examples illustrate several different types of operation utilizing automatic controls.
Pressure Reduction
Outlet pressure on control
diaphragm causes the main valve
to hold a steady outlet pressure.
Pressure Relief
Inlet pressure on control
diaphragm causes the
main valve to hold a
steady inlet pressure.
Liquid Level Controller
Slight changes in flow through
the float control causes main
valve to counteract changes in
reservoir level so liquid level is
held constant.
Rate of Flow Controller
Limits the maximum flow rate by
changes to the main valve counteract any slight changes in differential
pressure across an orifice plate
located in the main line.
8
Page 9
Q
A
&
Q
A
&
KO ANTI-CAVITATION OPERATION
First Stage Pressure Reduction
• Flow enters through the seat
Second Stage Pressure Reduction
• Flow impinges upon itself within the seat and disc
guide assembly to dissipate cavitation and further
reduce pressure
Third Stage Pressure Reduction
• Flow exits through the disc guide for final
KO Anti-Cavitation
Internal Trim
pressure reduction
• Diagonal disc guide slots direct flow away
from surfaces.
Which way should fluid flow through a CLA-VAL Valve?
Q
Just as with any globe valve, the usual way is “under–the–disc” as shown.
A
The main exception to the “under-the-disc” rule of thumb is the check valve.
“Under-the-Disc”
What purpose does the
Q
internal spring in the
Hytrol valve serve?
To provide enough force
to close the valve when
A
no difference exists
between inlet, cover and
outlet pressures. When
the inlet pressure is
greater than outlet pressure (even by a small
amount) the hydraulic
forces, -- NOT THE
SPRING hold the valve
tightly closed.
Can the opening and closing speed of a CLA-VAL Valve be
controlled?
Q
Yes. It is a matter of controlling the rate at which operating fluid
flows into or out of the cover chamber.
A
Here is a typical valve equipped with both opening and closing
speed controls. A simple needle valve can be used for these
controls.
Normal so valve closes against the pressure
Can pressure other than line pressure be used to operate CLA-VAL Valves?
Q
Yes. Frequently, when line fluid is too dirty or otherwise unsuitable, a separate
source of pressure is desired. Clean water, air (with some limitations), or oil
A
are suitable. The important point is to make sure the operating pressure is
equal or greater than inlet pressure AT ALL TIMES.
What should be done if line pressure is very low? (Below 10 psi)
Q
Usually a separate source of operating pressure is required. A spring to open
A
the valve may be necessary. Consult the factory for recommendations.
Standard Flow
“Over-the-Disc”
Reverse Flow
Acceptable only under specific conditions
B-48 (R-3/2011)
CLA-VAL
PO Box 1325 Newport Beach CA 92659-0325
800-942-6326 Fax: 949-548-5441 Web Site: cla-val.com E-mail: claval@cla-val.com
Dainton House, Goods Station Road
Tunbridge Wells
Kent TN1 2 DH England
Phone: 44-1892-514-400
Fax: 44-1892-543-423
E-mail: info@cla-val.co.uk
CLA-VAL FRANCE
Porte du Grand Lyon 1
ZAC du Champ du Périer
France - 01700 Neyron
Phone: 33-4-72-25-92-93
Fax: 33-4-72-25-04-17
E-mail: cla-val@cla-val.fr
9
Page 10
Value Added Upgrades...
Cla-Valʼs flexible design allows for a wide
range of upgrades to further enhance
system performance.
Model X144 e-FlowMeter
patent pending
Inserts directly into an inlet
tapping of a control valve
X143 Series Power Generators
Model X143MP
Micro Turbine
Power Generator
Model X143IP
Intermediate
Power Generator
Model X143HP Hydro Power Generator
uses the hydraulic energy
of the distribution system to
produce power for site equipment
Model X101 Valve
Position Indicator
10
Page 11
...Go Beyond Standard
X117 Series
Valve Position Indicator
X117D
Accurately monitor valve
position, IP-68 submersible
X105 Limit Switch
Assembly
X117E
X140-01 Locking
Security Cap
Electronic Pilot Controls
33 Series
33 Series:
Remote electronic control
CPC Series:
Position control
CTC
Series
CTC:
Timer-based control
CPC Series
Prevents
tampering of pilot
controls
Model X141
Pressure Gauge
Factory mounted on
valve inlet and outlet
Dura-Kleen® Stem
Delrin® Sleeved Stems
Helps to extend valve life
in applications with harsh
or corrosive fluids
Model X43H-Style Strainer
Ductile Iron, fusion-
bonded epoxy
coating and
Stainless Steel
strainer mesh for
longer service life
11
Page 12
U
n
d
e
r
g
r
o
u
n
d
S
o
u
r
c
e
R
a
w
W
a
t
e
r
f
r
o
m
12
Page 13
Page 14
100-01
(Full Internal Port)
MODEL
(Sizes 3/8"-36")
Hytrol Valve
• Drip-Tight, Positive Seating
• Service Without Removal From Line
• Threaded, Flanged or Grooved Ends
• Globe or Angle Pattern
• 100% Factory Tested
The Cla-Val Model 100-01 Hytrol Valve is a hydraulically
operated, diaphragm actuated, globe or angle pattern
valve. It consists of three major components: body,
diaphragm assembly, and cover. The diaphragm assembly
is the only moving part.
The diaphragm assembly is guided top and bottom by a
precision machined stem. It utilizes a non-wicking
diaphragm of nylon fabric bonded with synthetic rubber. A
resilient synthetic rubber disc retained on three and one half
sides by a disc retainer forms a drip-tight seal with the renewable
seat when pressure is applied above the diaphragm.
The Model 100-01 is the basic valve used in nearly all
Cla-Val Automatic Control Valves. It is the valve of choice
for system applications requiring remote control, pressure
regulation, solenoid operation, rate of flow control, liquid
level control or check valve operation. The rugged simplicity of design and packless construction assure a long life of
dependable, trouble-free operation. It is available in various
materials and in a full range of sizes, with either threaded,
flanged or grooved ends. Its applications are unlimited.
Principle of Operation
On-Off Control
Full Open Operation
When pressure in the
is relieved to a zone of lower pressure, the line pressure at the valve
inlet opens the valve, allowing full
flow.
14
cover chamber
On-Off Control
Tight Closing Operation
When pressure from the valve inlet
is applied to the cover chamber, the
valve closes drip-tight.
Modulating
Control
Modulating Action
The valve holds any intermediate
position when operating pressures
are equal above and below the
diaphragm. A Cla-Val “Modulating”
Pilot Control will allow the valve to
automatically compensate for line
pressure changes.
Page 15
Specifications Model 100-01
Available Sizes
PatternThreadedFlangedGrooved End
Globe
Angle1" - 3"11⁄2" - 16" & 24"2" - 3" - 4"
Pressure Ratings
ASTM A536Ductile Iron B16.42250400400400
ASTM A216-WCB Cast Steel B16.5285400400400
ASTM B62BronzeB16.24225400400400
Note: * ANSI standards are for flange dimensions only.
Valves for higher pressure are available; consult factory for details
For material options not listed, consult factory.
Cla-Val manufactures valves in more than 50 different alloys.
Cast IronCast SteelBronze
Bronze is Standard
Stainless Steel is optional
Fluids
-40°to 180°F
KO Anti-Cavitation
Trim Option
KO
DISC GUIDE
KO
SEAT
COVER
Cover Bolt
6" and Smaller
*
DIAPHRAGM
*
DISC GUIDE
BODY
(Globe
or
Angle)
SPRING
DISC
SEAT
PIPE PLUG
COVER BEARING
STEM NUT
DIAPHRAGM WASHER
DISC RETAINER
*
SPACER WASHERS
STEM
Seat Screw
8" and Larger
SEAT O-RING
*
Repair Parts
HEX NUT
8" and Larger
PIPE PLUG
STUD
8" and Larger
PIPE PLUG
Viton®Rubber Parts- suffix KB
Optional diaphragm, disc and o-ring fabricated with Viton
®
synthetic rubber. Viton®is
well suited for use with mineral acids, salt
solutions, chlorinated hydrocarbons, and
petroleum oils; and is primarily used in high
temperature applications up to 250° F.
not use with epoxy coatings above
175° F.
Epoxy Coating - suffix KC
This option NSF 61 Listed and FDA
approved, fusion bonded epoxy coating is
for use with cast iron, ductile iron or steel
valves. This coating is resistant to various
water conditions, certain acids, chemicals,
solvents and alkalies.
Epoxy coatings are
applied in accordance with AWWA coating
specifications C116-03.
Do not use with temperatures above
175° F.
Dura-Kleen® Stem - suffix KD
This stem is designed for applications
where water supplies containing dissolved
minerals create deposits that build-up on a
standard stem and hamper valve operation. A patented, self-cleaning design on
Do
the stem allows all valve sizes to operate
freely in the harshest conditions.
®
Delrin
The Delrin
Sleeved Stem- suffix KG
®
sleeved stem is designed for
applications where water supplies contain
dissolved minerals which can form
deposits that build up on the valve stem
and hamper valve operation. Scale buildup will not adhere to the Delrin
stem. Delrin
®
sleeved stems are not recommended for valves in continuous operation where differential pressures are in
®
sleeve
-
Anti-Cavitation Trim
suffix KO
Anti-Cavitation Trim components consist of
a stainless steel radial slotted disc guide
and seat. This system is used when high
differentials are present across the valve.
-
Water Treatment Clearance
suffix KW
This additional clearance is beneficial in
applications where water treatment compounds can interfere with the closing of the
valve. The smaller outside diameter disc
guide provides more clearance between
the disc guide and the valve seat. This
option is best suited for valves used in onoff (non-modulating) service.
excess of 80 psi (2" and larger Hytrol valves).
For assistance in selecting appropriate valve options or valves manufactured with special design requirements, please contact
our Regional Sales Office or Factory.
A Threaded
AA 150 ANSI
AAA 300 ANSI
AAAA Grooved End
B Dia.
C Max.
CC Max. Grooved End
D Threaded
DD 150 ANSI
DDD 300 ANSI
DDDD Grooved End
E
EE Grooved End
F 150 ANSI
FF 300 ANSI
G Threaded
GG 150 ANSI
GGG 300 ANSI
GGGG Grooved End
H NPT Body Tapping
J NPT Cover Center Plug
K NPT Cover Tapping
A Threaded
AA 150 ANSI
AAA 300 ANSI
AAAA Grooved End
B Dia.
C Max.
CC Max. Grooved End
D Threaded
DD 150 ANSI
DDD 300 ANSI
DDDD Grooved End
E
EE Grooved End
F 150 ANSI
FF 300 ANSI
G Threaded
GG 150 ANSI
GGG 300 ANSI
GGGG Grooved End
H NPT Body Tapping
J NPT Cover Center Plug
K NPT Cover Tapping
Valve Stem Internal
Thread UNF
Stem Travel
Approx. Ship Wt. Kgs.
Cla-Val Control Valves operate with maximum efficiency when mounted in horizontal piping with the main valve cover UP, however, other positions are acceptable. Due to
component size and weight of 8 inch and larger valves, installation with cover UP is advisable. We recommend isolation valves be installed on inlet and outlet for maintenance.
Adequate space above and around the valve for service personnel should be considered essential. A regular maintenance program should be established based on the specific
application data. However, we recommend a thorough inspection be done at least once a year. Consult factory for specific recommendations.
The Cla-Val Model 100-02 is a hydraulically operated, diaphragm
actuated, globe, or angle pattern valve. It consists of four major
components: body, intermediate chamber, diaphragm assembly,
and cover. The diaphragm assembly is the only moving part.
The diaphragm assembly which is guided top and center by a precision machined stem, utilizes a non-wicking diaphragm of nylon
fabric bonded with synthetic rubber. The diaphragm forms a seal
between the cover chamber and intermediate chamber. A synthetic rubber disc retained on three and one half sides forms a
drip-tight seal with the renewable seat when pressure is applied
above the diaphragm. As pressure above the diaphragm is
relieved and pressure is applied below the diaphragm, the valve
opens wide for full flow. The rate of closing or opening can be controlled by modulating flow into or out of the diaphragm chambers.
The Model 100-02 is recommended where independent operating
pressure is desired. Available in various materials and in a full
range of sizes, with either threaded or flanged ends, its applications are many and varied.
Principle of Operation
Four-Way Control
Full Open Operation
When operating pressure below the
diaphragm is applied and operating,
pressure is relieved from the cover
chamber and, the valve is held
open, allowing full flow.
18
Four-Way Control
Tight Closing Operation
When pressure below the diaphragm
is relieved and operating pressure is
applied to the cover chamber, the
valve closes drip-tight.
Four-Way Control with Lock
Modulating Action
The valve holds any intermediate
position when operating pressure is
equal above and below the
diaphragm. A Cla-Val four-way pilot
control with "lock" position can maintain this balance by stopping flow in the pilot control system.
Note: * ANSI standards are for flange dimensions only.
Flanged valves are available faced but not drilled.
‡ End Details machined to ANSI B2.1 specifications.
† Consult factory when Maximum Operating Pressure
Differential (MOPD) is greater than 400 PSID
“Valves for higher pressure are available; consult factory for details”
For material options not listed, consult factory.
Cla-Val manufactures valves in more than 50 different alloys.
Cast IronCast SteelBronze
Bronze is Standard
Stainless Steel is Optional
LOWER DIAPHRAGM
WASHER
POWERUNIT BODY
O-RING
POWERUNIT BEARING
DISC RETAINER
WASHER SPACER
LOCK WASHER
STUD/BOLT
BODY
DIAPHRAGM
RETAINING RING
SEAL GASKET
O-RING
STEM
DISC
DISC GUIDE
LOWER STEM NUT
SEAT
SEAT-O-RING
OUTLET
PIPE PLUG
INLET
Options
Epoxy Coating - suffix KC
This option NSF 61 Listed and FDA approved,
fusion bonded epoxy coating is for use with cast
iron, ductile iron or steel valves. This coating is
resistant to various water conditions, certain
acids, chemicals, solvents and alkalies.
Epoxy
coatings are applied in accordance with AWWA
coating specifications C116-03.
Do not use with temperatures above
175° F
For assistance in selecting appropriate valve
options or valves manufactured with special
design requirements, please contact our
-
Viton® Rubber Parts
Optional diaphragm, disc and o-ring fabricated
with Viton
®
synthetic rubber. Viton®is well suited
suffix KB
Regional Sales Office or Factory.
for use with mineral acids, salt solutions, chlorinated hydrocarbons, and petroleum oils; and is
primarily used in high temperature applications
up to 250° F. Do not use with epoxy coating
above 175°F.
For assistance in selecting appropriate valve options or valves manufactured with special design requirements, please contact
our Regional Sales Office or Factory.
Valve Size (Inches)
A Threaded
AA 150 ANSI
AAA 300 ANSI
AAAA Grooved End
B Dia.
C Max.
CC Max. Grooved End
D Threaded
DD 150 ANSI
DDD 300 ANSI
DDDD Grooved End
E
EE Grooved End
F 150 ANSI
FF 300 ANSI
G Threaded
GG 150 ANSI
GGG 300 ANSI
GGGG Grooved End
H NPT Body Tapping
J NPT Cover Center Plug
K NPT Cover Tapping
Note: The top two flange holes on valve size 36 are threaded to 1 1/2"-6 UNC.
100-02
Grooved
End
(MAX)
Valve Size (mm)101520253240506580100 150 200 250 300 350 400 450 500 600 750
A Threaded
AA 150 ANSI
AAA 300 ANSI
AAAA Grooved End
B Dia.
C Max.
CC Max. Grooved End
D Threaded
DD 150 ANSI
DDD 300 ANSI
DDDD Grooved End
E
EE Grooved End
F 150 ANSI
FF 300 ANSI
G Threaded
GG 150 ANSI
GGG 300 ANSI
GGGG Grooved End
H NPT Body Tapping
J NPT Cover Center Plug
K NPT Cover Tapping
Valve Stem Internal
Thread UNF
Stem Travel
Approx. Ship Wt. Kgs.
Cla-Val Control Valves operate with maximum efficiency when mounted in horizontal piping with the main valve cover UP, however, other positions are acceptable. Due to
component size and weight of 8 inch and larger valves, installation with cover UP is advisable. We recommend isolation valves be installed on inlet and outlet for maintenance.
Adequate space above and around the valve for service personnel should be considered essential. A regular maintenance program should be established based on the specific
application data. However, we recommend a thorough inspection be done at least once a year. Consult factory for specific recommendations.
The Cla-Val Model 100-03 Powercheck Valve is a hydraulically operated diaphragm valve with a built-in check feature to
prevent return flow. Available in globe or angle pattern, it consists of four major components: body, intermediate chamber,
diaphragm assembly, and cover. The diaphragm assembly is
the only moving part.
The diaphragm assembly is guided top and center by a precision machined stem and utilizes a non-wicking diaphragm
of nylon fabric bonded with synthetic rubber. A synthetic rubber disc retained on three and one half sides forms a driptight seal with the renewable seat when pressure is applied
above the diaphragm. When pressure above the diaphragm
is relieved, the valve opens wide. The rate of closing or opening can be controlled by modulating flow into or out of the
diaphragm chambers.
When a pressure reversal occurs, the valve will immediately
close, preventing reverse flow thru the valve. The split stem
will allow the disc retainer assembly to check closed regardless of the position of the diaphragm.
Principle of Operation
Four-Way Control
Full Open Operation
When operating pressure below the
diaphragm is applied and pressure is
relieved from the cover chamber, the
valve is held open allowing full flow.
Note: For optimum operation of built-in check feature, installation with stem vertically up is recommended.
22
Tight Closing Operation
When pressure below the
diaphragm is relieved and operating
pressure is applied to the cover
chamber, the valve closes drip-tight.
Four-Way Control
When a static condition or pressure
reversal occurs, the split stem
design allows the valve to instantly
check closed. Return flow is prevented regardless of the
diaphragm's position.
Four - Way Control
Check Action
Page 23
Specifications
Model 100-03
Available Sizes
PatternThreadedFlanged
Globe2
Angle 2
Pressure Ratings
Valve Body & Cover
GradeMaterial
1
⁄2" - 3"2 1⁄2" - 16"
1
⁄2" - 3"2 1⁄2" - 16"
(Recommended Maximum Pressure - psi)
ANSI
Standards*
Operating Temp. Range
Fluids
-40° to 180° F
Pressure Class
FlangedGrooved Threaded
150
Class
300
Class
300
Class
End‡
Details
ASTM A536Ductile Iron B16.42250400400400
ASTM A216-WCB Cast Steel B16.5285400400400
ASTM B62BronzeB16.24225400400400
Note: * ANSI standards are for flange dimensions only.
Flanged valves are available faced but not drilled.
‡ End Details machined to ANSI B2.1 specifications.
Valves for higher pressure are available; consult factory for details
For material options not listed, consult factory.
Cla-Val manufactures valves in more than 50 different alloys.
Cast IronCast SteelBronze
Bronze is Standard
Stainless Steel is Optional
PIPE PLUG
HEX NUT
BEARING COVER
UPPER DIAPHRAGM WASHER
LOWER DIAPHRAGM WASHER
POWERUNIT BODY
O-RING
POWERUNIT BEARING
UPPER STEM
SPRING
DISC RETAINER
WASHER SPACER
LOCK WASHER
SEAT
STUD/BOLT
BODY
PIPE PLUG
COVER
UPPER STEM NUT
DIAPHRAGM
RETAINING RING
SEAL GASKET
O-RING
LOWER STEM
DISC
DISC GUIDE
LOWER STEM NUT
SEAT-O-RING
OUTLET
Options
Epoxy Coating - suffix KC
This option NSF 61 Listed and FDA
approved, fusion bonded epoxy coating is
for use with cast iron, ductile iron or steel
valves. This coating is resistant to various
water conditions, certain acids, chemicals, solvents and alkalies.
ings are applied in accordance with
AWWA coating specifications C116-03.
Do not use with temperatures above
Viton® Rubber Parts
Optional diaphragm, disc and o-ring fabricated with Viton® synthetic rubber. Viton®
is well suited for use with mineral acids,
salt solutions, chlorinated hydrocarbons,
and petroleum oils; and is primarily used
in high temperature applications up to
250° F.
above
Do not use with epoxy coating
175° F.
-
suffix KB
Epoxy coat-
175° F
PIPE PLUG
INLET
For assistance in selecting appropriate
valve options or valves manufactured
with special design requirements,
please contact our Regional Sales
Office or Factory.
inside pipe diameter of Schedule 40 Steel Pipe (inches)
d
friction factor for clean, new Schedule 40 pipe
=
f
(dimensionless) (from Cameron Hydraulic Data,
18th Edition, P 3-119)
Resistance Coefficient (calculated)
=
K
=
Equivalent Length of Pipe (feet)
L
=
Flow Rate in U.S. (gpm) or (l/s)
Q
=
Fluid Velocity (feet per second) or (meters per second)
V
=
Pressure Drop in (psi) or (bar)
P
or
Model 100-03 Flow Chart (Based on normal flow through a wide open valve)
24
Page 25
Dimensions
100-03
Threaded &
Flanged
H
B
(Diameter)
J
K
C
(MAX)
Model 100-03
Inlet
G
GG
GGG
A
AA
AAA
Inlet
D
DD
DDD
E
Outlet
F
FF
Valve Size (Inches)2 1⁄2346810121416
A Threaded
AA 150 ANSI
AAA 300 ANSI
B Dia.
C Max.
D Threaded
DD 150 ANSI
DDD 300 ANSI
E
F 150 ANSI
FF 300 ANSI
G Threaded
GG 150 ANSI
GGG 300 ANSI
H NPT Body Tapping
J NPT Cover Center Plug
K NPT Cover Tapping
Valve Size (mm)6580100150200250300350400
A Threaded
AA 150 ANSI
AAA 300 ANSI
B Dia.
C Max.
D Threaded
DD 150 ANSI
DDD 300 ANSI
E
F 150 ANSI
FF 300 ANSI
G Threaded
GG 150 ANSI
GGG 300 ANSI
H NPT Body Tapping
J NPT Cover Center Plug
K NPT Cover Tapping
Note: Various Flange Drilling to a Foreign and intranational Standards and Specifications are Available on Request.
Cla-Val Control Valves operate with maximum efficiency when mounted in horizontal piping with the main valve cover UP, however, other positions
are acceptable. Due to component size and weight of 8 inch and larger valves, installation with cover UP is advisable. We recommend isolation
valves be installed on inlet and outlet for maintenance. Adequate space above and around the valve for service personnel should be considered
essential. A regular maintenance program should be established based on the specific application data. However, we recommend a thorough
inspection be done at least once a year. Consult factory for specific recommendations.
Copyright Cla-Val 2012 Printed in USA Specifications subject to change without notice.
E-100-03 (R-8/2011)
P.O. Box 1325 • Newport Beach, CA 92659-0325 • Phone: 949-722-4800 • Fax: 949-548-5441 • E-mail: claval@cla-val.com • Website cla-val.com
25
Page 26
100-20
(Reduced Internal Port)
MODEL
600 Series
Hytrol Valve
• Reduced Cavitation Design
• Drip-Tight, Positive Seating Action
• Service Without Removal From Line
• Globe or Angle Pattern
• Every Valve Factory Tested
The Cla-Val Model 100-20 Hytrol Valve is a hydraulically operated,
diaphragm actuated, globe or angle pattern valve. It consists of three
major components: body, diaphragm assembly and cover. The
diaphragm assembly is the only moving part.
The diaphragm assembly is guided top and bottom by a precision
machined stem which utilizes a non-wicking diaphragm of nylon fabric
bonded with synthetic rubber. A resilient synthetic rubber disc, retained
on three and one-half sides by a disc retainer, forms a drip-tight seal
with the renewable seat when pressure is applied above the
diaphragm.
The reduced cavitation characteristics of the 100-20 Hytrol Valve is the
basis for the Cla-Val 600 Series. The rugged simplicity of design and
packless construction assure a long life of dependable, trouble-free
operation. It's smooth flow passages and fully guided disc and
diaphragm assembly assure optimum control when used in piping systems requiring remote control, pressure regulation, solenoid operation,
rate of flow control or check valve operation.
Available in various materials and in a wide range of sizes. It's applications are unlimited.
Principle of Operation
On-Off Control
Full Open Operation
When pressure in the
is relieved to a zone of lower pressure, the line pressure at the valve
inlet opens the valve, allowing full
flow.
26
cover chamber
On-Off Control
Tight Closing Operation
When pressure from the valve inlet
is applied to the cover chamber, the
valve closes drip-tight.
Modulating
Control
Modulating Action
The valve holds any intermediate
position when operating pressure is
equal above and below the
diaphragm. Using a Cla-Val
“Modulating” Control will allow the
valve to automatically compensate
for line pressure changes.
For material options not listed consult factory.
Cla-Val manufactures valves in more than 50 different alloys.
Options
Viton®Rubber Parts- suffix KB
Optional diaphragm, disc and o-ring fabricated with Viton
®
synthetic rubber. Viton®is
well suited for use with mineral acids, salt
solutions, chlorinated hydrocarbons, and
petroleum oils; and is primarily used in high
temperature applications up to 250° F.
not use with epoxy coatings above
175° F.
Epoxy Coating - suffix KC
This option NSF 61 Listed and FDA
approved, fusion bonded epoxy coating is
for use with cast iron, ductile iron or steel
valves. This coating is resistant to various
water conditions, certain acids, chemicals,
solvents and alkalies.
Epoxy coatings are
applied in accordance with AWWA coating
specifications C116-03.
Do not use with temperatures above
175° F.
Dura-Kleen® Stem - suffix KD
This stem is designed for applications
where water supplies containing dissolved
minerals create deposits that build-up on a
standard stem and hamper valve operation. A patented, self-cleaning design on
Do
the stem allows all valve sizes to operate
freely in the harshest conditions.
®
Delrin
The Delrin
Sleeved Stem- suffix KG
®
sleeved stem is designed for
applications where water supplies contain
dissolved minerals which can form
deposits that build up on the valve stem
and hamper valve operation. Scale buildup will not adhere to the Delrin
stem. Delrin
®
sleeved stems are not recommended for valves in continuous operation where differential pressures are in
excess of 80 psi (2" and larger Hytrol valves).
Operating Temp. Range
Fluids
-40° to 180° F
KO Anti-Cavitation
Trim Option
KO
DISC GUIDE
KO
SEAT
®
sleeve
COVER
Cover Bolt
6" and Smaller
SPRING
*
DIAPHRAGM
*
DISC
DISC GUIDE
SEAT
BODY
(Globe
or
Angle)
Anti-Cavitation Trim
PIPE PLUG
COVER BEARING
STEM NUT
DIAPHRAGM WASHER
*
SPACER WASHERS
STEM
SEAT O-RING
-
suffix KO
HEX NUT
10" and Larger
PIPE PLUG
DISC RETAINER
Seat Screw
10" annd Larger
10" and Larger
PIPE PLUG
*
Repair Parts
Anti-Cavitation Trim components consist of
a stainless steel radial slotted disc guide
and seat. This system is used when high
differentials are present across the valve.
-
Water Treatment Clearance
suffix KW
This additional clearance is beneficial in
applications where water treatment compounds can interfere with the closing of the
valve. The smaller outside diameter disc
guide provides more clearance between
the disc guide and the valve seat. This
option is best suited for valves used in onoff (non-modulating) service.
STUD
27
Page 28
K =
894d
4
C
2
v
L =
K
12 f
K Factor (Resistance Coefficient)
The Value of K is calculated from the formula:
(U.S. system units)
Equivalent Length of Pipe
Equivalent lengths of pipe (L) are determined from the formula:
(U.S. system units)
Fluid Velocity
Fluid velocity can be calculated from the following formula:
(U.S. system units)
d
V =
.4085 Q
2
d
C
V
Factor
Formulas for computing C Factor, Flow (Q) and Pressure Drop
V
( P):
C
V
=
Q
P
C
V
=
Q
P
C
V
=
Q
P
2
V
Where:
U.S. (gpm) @ 1 psi differential at 60 F water
(l/s) @ 1 bar (14.5 PSIG) differential
or
at 15 C water
inside pipe diameter of Schedule 40 Steel Pipe (inches)
friction factor for clean, new Schedule 40 pipe
(dimensionless) (from Cameron Hydraulic Data,
18th Edition, P 3-119)
Resistance Coefficient (calculated)
Equivalent Length of Pipe (feet)
Flow Rate in U.S. (gpm) or (l/s)
Fluid Velocity (feet per second) or (meters per second)
For assistance in selecting appropriate valve options or valves manufactured with special design requirements, please contact our Regional Sales Office or Factory.
Note: Various Flange Drilling to a Foreign and intranational Standards and Specifications are Available on Request.
Service and Installation
Cla-Val Control Valves operate with maximum efficiency when mounted in horizontal piping with the main valve cover UP, however, other positions
are acceptable. Due to component size and weight of 10 inch and larger valves, installation with cover UP is advisable. We recommend isolation
valves be installed on inlet and outlet for maintenance. Adequate space above and around the valve for service personnel should be considered
essential. A regular maintenance program should be established based on the specific application data. However, we recommend a thorough
inspection be done at least once a year. Consult factory for specific recommendations.
CLA-VAL
P.O. Box 1325 • Newport Beach, CA 92659-0325 • Phone: 949-722-4800 • Fax: 949-548-5441 • E-mail: claval@cla-val.com • Website cla-val.com
Copyright Cla-Val 2012 Printed in USA Specifications subject to change without notice.
E-100-20 (R-11/2012)
29
Page 30
PILOT
CONTROL
VALVE
RESTRICTOR
SEATING AREA
CONTROL CHAMBER
INLET
Pilot
Control
Valve
RESTRICTOR
SEATING AREA
CONTROL CHAMBER
INLET
100-42
700 SERIES
ROLL SEAL
MODEL
• Compact Design, Proven Reliable
• Light Weight Materials
• High Pressure Rating Availability
• Easy Installation and Maintenance
The Cla-Val Model 100-42 Roll Seal valve is a hydraulically operated valve used
to control liquid flow by means of a flexible control element: the liner.
The basic valve consists of only two parts: a one piece, investment cast body
and an elastomeric liner. The valve body is constructed with internal ribs and
slots forming a grillwork which surrounds the liner to provide support. A normally
closed type valve is formed by the installed liner which covers the grillwork and
seats against the raised seating surface in the valve body.
Upstream pressure actuates the valve to produce valve opening by rolling the
liner off the seating surface and the slotted grillwork.
The valve is actuated by upstream pressure as the loading pressure (pressure
supplied to the control chamber) is varied by an external pilot control system.
A typical pilot control system used to operate the Model 100-42 valve consists
of a restriction and a suitable pilot connected to the valve.
Principle of Operation
Model 100-42 Valve
in Closed Position
Upstream pressure is introduced to the
control chamber (the chamber formed
behind the liner) of the Cla-Val Model
100-42 Roll Seal valve through the control piping and restrictor. When the pilot
is closed, full inlet pressure is supplied
to the control chamber, thus balancing
the force developed by inlet pressure
acting on the upstream face on the
liner. Under these conditions, the liner
remains in the fully closed position.
Since the operating pressure in the
control chamber is greater than the outlet pressure, an additional closing force
is developed across the liner, pressing
the liner against the surrounding slotted
grillwork area and seating surface.
30
PILOT
CONTROL
VALVE
RESTRICTOR
SEATING AREA
INLET
CONTROL CHAMBER
Model 100-42 Valve
in Partially Open Position
As loading pressure is lowered slightly
below inlet pressure, the central portion
of the liner is forced to invert and come
to rest against the tip of the control
chamber cavity. Reducing the loading
pressure further (but still higher than
outlet pressure) causes the liner to
drape over the cone shaped portion of
the control chamber cavity. This action
causes the outer section of the liner to
roll off the seating surface and a portion
of the grillwork to partially open the
valve.
Model 100-42 Valve
in Fully Open Position
The valve is fully opened when loading
pressure is sufficiently reduced to allow
the liner to roll back completely and
expose the full slot area. Restoring
loading pressure reverses the liner
rolling action to return the liner to the
fully closed position.
1. Catalog No. 750-01 2. Valve Size 3. Fluid Being Handled 4. Fluid Temperature Range 5. Inlet Pressure Range
6. Outlet Pressure Range 7. Maximum Differential Pressure 8. Minimum Differential Pressure 9. Maximum Flow Rate
10. Pilot Set Point
E-100-42 (R-3/2011)
Represented By:
31
Page 32
100-44
(Reduced Internal Port)
MODEL
316SS Hytrol Valve
• All 316 Stainless Steel
• Reduced Cavitation Design
• Drip-Tight, Positive Sealing Action
•Service Without Removal From Line
•Every Valve Factory Tested
•Three-Year Warranty
The Cla-Val Model 100-44 Hytrol 316SS Valve is a hydraulically operated,
diaphragm actuated, globe pattern valve with all 316 Stainless Steel metal
parts. Specially designed 316 Stainless Steel removable slip-on flanges
provide 150 or 300 ANSI class flange connections that meet ANSI and ISO
standards. This valve is ideal for control valve applications where fluid
compatibility is often a problem. The standard Electropolish finish on the
316 Stainless Steel parts offers extreme corrosion resistance to many
industrial fluids such as seawater, high alkyl or high acid concentrations
or other aggressive or corrosive fluids.
The Model 100-44 Hytrol consists of these major components: body,
flanges, diaphragm assembly and cover. The diaphragm assembly is the
only moving part and is guided top and bottom by a precision-machined
stem. A non-wicking diaphragm of nylon fabric reinforced, synthetic rubber
creates the control chamber for the valve. A resilient, synthetic rubber disc
forms a drip-tight seal, with the renewable seat, when pressure is applied
to the control chamber. The rugged simplicity of design and packless construction assures a long life of dependable, trouble-free operation. Smooth
flow passages and fully guided diaphragm assembly assure optimum control, when used in piping systems requiring remote control, pressure regulation, solenoid operation, rate of flow control or check valve operation.
Principle of Operation
On-Off Control
Full Open Operation
When pressure in the
ber is relieved to a zone of lower
pressure, the line pressure at the
valve inlet opens the valve, allowing full flow.
32
cover cham-
On-Off Control
Tight Closing Operation
When pressure from the valve inlet
is applied to the cover chamber, the
valve closes drip-tight.
Modulating
Control
Modulating Action
The valve holds any intermediate
position when operating pressure
is equal above and below the
diaphragm. Using a Cla-Val
“Modulating” Control will
allow the valve to automatically compensate for line
pressure changes.
Page 33
PO Box 1325 Newport Beach CA 92659-0325 Phone: 949-722-4800
Fax: 949-548-5441 Web Site: cla-val.com E-mail: claval@cla-val.com
*Cv = gpm flow at 1 psi drop
**Cv = l/s flow at 1 bar drop
B
Size (Inches)22 1⁄234681012
Size (mm)506580100150200250300
When Ordering Please
Specify:
1. Catalog No. 100-44
2. Valve Size
3. Fluid Being Handled
4. Fluid Temperature
5. Inlet Pressure Range
6. Outlet Pressure Range
7. Maximum and Minimum
Differential Pressure
8. Flow Rate Range
E-100-44 (R-10/2011)
Represented By:
33
Page 34
100-46
(Full Internal Port)
MODEL
316SS Hytrol Valve
• All 316 Stainless Steel
• Reduced Cavitation Design
• Drip-Tight, Positive Sealing Action
• Service Without Removal From Line
•Every Valve Factory Tested
•Three-Year Warranty
The Cla-Val Model 100-46 Hytrol 316SS Valve is a hydraulically operated,
diaphragm actuated, globe pattern valve with all 316 Stainless Steel metal
parts. Specially designed 316 Stainless Steel removable slip-on flanges
provide 150 or 300 ANSI class flange connections that meet ANSI and ISO
standards. This valve is ideal for control valve applications where fluid
compatibility is often a problem. The standard Electropolish finish on the
316 Stainless Steel parts offers extreme corrosion resistance to many
industrial fluids such as seawater, high alkyl or high acid concentrations
or other aggressive or corrosive fluids.
The Model 100-46 Hytrol consists of these major components: body,
flanges, diaphragm assembly and cover. The diaphragm assembly is the
only moving part and is guided top and bottom by a precision-machined
stem. A non-wicking diaphragm of nylon fabric reinforced, synthetic rubber
creates the control chamber for the valve. A resilient, synthetic rubber disc
forms a drip-tight seal, with the renewable seat, when pressure is applied
to the control chamber. The rugged simplicity of design and packless construction assures a long life of dependable, trouble-free operation. Smooth
flow passages and fully guided diaphragm assembly assure optimum control, when used in piping systems requiring remote control, pressure regulation, solenoid operation, rate of flow control or check valve operation.
Principle of Operation
On-Off Control
Full Open Operation
When pressure in the
ber is relieved to a zone of lower
pressure, the line pressure at the
valve inlet opens the valve, allowing full flow.
34
cover cham-
On-Off Control
Tight Closing Operation
When pressure from the valve inlet
is applied to the cover chamber, the
valve closes drip-tight.
Modulating
Control
Modulating Action
The valve holds any intermediate
position when operating pressure
is equal above and below the
diaphragm. Using a Cla-Val
“Modulating” Control will
allow the valve to automatically compensate for line
pressure changes.
Page 35
PO Box 1325 Newport Beach CA 92659-0325 Phone: 949-722-4800
Fax: 949-548-5441 Web Site: cla-val.com E-mail: claval@cla-val.com
A 150 ANSI7.879.3811.0012.0015.0020.00
AA 300 ANSI7.879.3811.0012.0015.0020.00
B5.626.618.009.1311.5015.75
C.56.62.69.75.941.00
CC 300 ANSI.81.881.001.121.251.44
D5.906.257.258.2010.2113.32
E2.563.053.543.754.535.61
EE 300 ANSI3.053.253.744.135.026.30
F.62.75.75.75.75.88
FF 300 ANSI.88.75.88.88.88.88
G3.884.755.506.007.509.50
GG 300 ANSI4.505.005.886.627.8810.62
When Ordering Please
Specify:
1. Catalog No. 100-46
2. Valve Size
3. Fluid Being Handled
4. Fluid Temperature
5. Inlet Pressure Range
6. Outlet Pressure Range
7. Maximum and Minimum
Differential Pressure
8. Flow Rate Range
E-100-46 (R-10/2011)
Represented By:
35
Page 36
Flange Dimensions and End Details
All flanged Cla-Val valves are furnished faced and drilled unless otherwise specified. The dimensions and drilling of end flanges
conform to standards of the American National Standards Institute.
The ANSI tables are provided here for your convenience. When ANSI standards call for 1/16" raised face, this face is included in the dimensions for the thickness of flange. All dimensions are shown in inches.
Ductile Iron Valves* Class 150 and 300 (ANSI B16.42 — 1987)
Cla-Val’s KO anti-cavitation trim represents a dramatic departure from the standard approaches usually employed to
fight cavitation in valves that are required to undergo extreme pressure differentials and high velocity flow conditions.
Constructed of 316 Stainless Steel, the seat and disc guide feature dual interlocked sleeves containing cast radial slots
that deflect internal flow to impinge upon itself, harmlessly dissipating potential noise and cavitation damage. The cast
radial slots create a larger flow path than is possible with the standard drilled holes typically employed by other anticavitation valves currently available in the market place. The uniquely designed radial slots in the seat and disc guides
also lessen the possibility of fouling if small particles are present in the water.
Seat with Radial Slots
Slotted Disc Guide
Typical Applications
• Pressure Reducing Valve Stations
• Tank Fill Valve Applications
• Noise Reduction in High-Rise
Building Valve Stations
• Reservoir Level Control Valve
Applications
• Booster Pump Bypass Stations
• Offshore Fire Pump Relief Valve
Protection
• Applications with discharge to
atmosphere
• Any application where valves are
patented
subjected to extreme pressure
differentials or high velocity
flow conditions
Cla-Val KO Anti-Cavitation Valve Principals of Operation
First Stage Pressure Reduction
• Flow enters through seat slots and reduces
pressure
Second Stage Pressure Reduction
• Flow impinges upon itself within the seat and
disc guide assembly to dissipate cavitation
and further reduce pressure
Third Stage Pressure Reduction
• Flow exits through disc guide for final
pressure reduction
• Diagonal disc guide slots direct flow away
from surfaces
37
Page 38
The dark shaded portion of the chart illustrates the region where cavitation damage may occur. The lighter shaded portion is where significant cavitation noise and vibration may occur. Operating conditions
inside the dark shaded area is permissible for infrequent periods of
short duration. The guide is for modulating service valves. For on/off
valves, consult factory.
The chart is based on cavitation index (sigma) values as defined by
Utah State University Water Research Laboratory.
2 — Pv
)
(P
=where
1 — P2
(P
)
1
= cavitation index, P
v
(psi), P
= water vapor pressure (psia).
= inlet pressure (psi), P2 = outlet pressure
The dark shaded portion is below of 0.5 and the lighter shaded
area is below of 0.8. The chart is to be used for typical valve operating conditions below 40% open at standard water temperature and
elevation below 1000 feet.
More accurate cavitation conditions are determined from the Cla-CAV
analysis program including static and dynamic inlet and outlet pressures, flow range, elevation, water temperature, and service conditions. If operation is inside the shaded areas, the Cla-CAV analysis
can be used to determine whether added backpressure from an orifice
plate, a second valve in series, or adding KO Anti-Cavitation trim (see
100-01KO data sheet). is necessary.
CAVITATION GUIDE
CLA-CAV DETAILED ANALYSIS CHART
For a more detailed cavitation analysis or if operation will be outside
of the above chart, request a Cla-CAV computer analysis. Cla-CAV
can evaluate what options best solve any potential cavitation problem. In the example shown, a 6 inch 100-01 modulating service valve
requires an orifice plate downstream to prevent damaging cavitation.
For wider flow range service, either an extra valve in series or the
addition of KO Anti-Cavitation trim to the valve may be necessary
(see 100-01KO data sheet). Consult factory for a free analysis for
wide open or modulating service valves.
Cavitiation Characteristics
1.4
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.0
0
200 400 600 800
Valve 1
Flow (gpm)
Orifice 1
1000
38
If the lines go above 1.0 there will be cavitiation damage.
Page 39
MODEL
100-01KO
(Full Internal Port)
Anti-Cavitation Hytrol Valve
• Virtually Cavitation Free Operation
100G-01KO ANTI-CAVITATION VALVE CURVES
1 1/2"
2 1/2"
2"
100
3"
4"
6"
1000
FLOW RATE (gpm)
8"
10"
14"
12"
16"
18"
10000
20"
24"
30"
36"
400
300
100
PRESSURE DROP (psi)
SOLID LINE IS FULL OPEN FLOW CURVES FOR 18 FT/SEC CONTINUOUS DUTY APPLICATIONS
DASHED LINE IS FULL OPEN FLOW CURVE FOR 25 FT/SEC INTERMITTENT DUTY APPLICATIONS
10
1
10
1 1/4"
1"
Notes: On Operating Differential
1. For atmospheric discharge, the maximum inlet pressure
cannot exceed 150 psi.
2. For pressure differentials greater than 300 psi the maximum
flow velocity should not exceed 18 ft/sec.
• Severe Service Design - High Pressure
Differentials
• Reduced Noise and Vibration
• 316 Stainless Steel Disc Guide and Seat
Standard
• Drip-Tight, Positive Sealing
• Service Without Removal From Line
• Retrofit to Standard Hytrol Valves
The Cla-Val Model 100-01KO Anti-Cavitation Hytrol Valve is
designed for applications where there is a high potential for
damage from cavitation. Specify this valve series for a wide
variety of control valve applications having pressure differen-
100000
tials up to 300 psid or for relief valves having atmospheric
discharge up to 150 psid.
The 100-01KO Hytrol main valve provides optimum internal
pressure control through a unique anti-cavitation trim design.
Constructed of 316 Stainless Steel, the seat and disc guide
trim components feature dual interlocked sleeves containing
radial slots that deflect internal flow to impinge upon itself in
the center of the flow path, harmlessly dissipating the potential cavitation damage. This unique design also lessens the
possibility of fouling if large particles in the water are present
due to the large flow path of the radial slots.
3. Flow velocities greater than 25 ft/sec are not recommended.
4. Recommended minimum flow velocity is 1 ft/sec.
The 100-01KO Hytrol is the basic valve used in Cla-Val
Automatic Control Valves for high differential applications
requiring remote control, pressure regulation, solenoid operation, rate of flow control, or liquid level control.
5. Consult factory for conditions exceeding these recommenda-
tions.
Functional Data
Valve Size
C
Pattern
V
Factor
Pattern
Equivalent
Length of
Pipe
K Factor
Liquid Displaced from
Cover Chamber When
For assistance in selecting appropriate valve options or valves manufactured with special design requirements, please contact our Regional Sales Office or Factory.
The Anti-Cavitation Trim components can be retrofitted to
existing valves if the application indicates an appropriate
need. Please consult factory for details.
39
Page 40
100-20KO
(Reduced Internal Port)
MODEL
Anti-Cavitation Hytrol Valve
• Virtually Cavitation Free Operation
SOLID LINE IS FULL OPEN FLOW CURVES AT 18 FT/SEC FOR CONTINUOUS DUTY APPLICATIONS
DASHED LINE IS FULL OPEN FLOW CURVE AT 25 FT/SEC FOR INTERMITTENT DUTY APPLICATIONS
400
300
100
10
PRESSURE DROP (psi)
1
10
100G-20KO ANTI-CAVITATION VALVE CURVES
3"
100
6"
4"
FLOW RATE (gpm)
8"
1000
10"
12"
16"
14"
20"
24"
18"
30"
10000
Notes: On Operating Differential
The 100-20KO Series is the reduced internal port size version
*
of the 100-01KO Series.
1. For atmospheric discharge, the maximum inlet pressure
cannot exceed 150 psi.
2. For pressure differentials greater than 300 psi the maximum
flow velocity should not exceed 18 ft/sec.
3. Flow velocities greater than 25 ft/sec are not recommended.
4. Recommended minimum flow velocity is 1 ft/sec.
• Severe Service Design - High Pressure
*
Differentials
*
• Reduced Noise and Vibration
• 316 Stainless Steel Disc Guide and Seat
Standard
• Drip-Tight, Positive Sealing
• Serviced Without Removal From Line
• Retrofit to Standard Hytrol Valves
The Cla-Val Model 100-20KO Anti-Cavitation Hytrol Valve is
designed for applications where there is a high potential for
damage from cavitation. Specify this valve series for a wide
variety of control valve applications having pressure differentials up to 350 psid or for relief valves having atmospheric
discharge up to 150 psid.
The 100-20KO Hytrol main valve provides optimum internal
pressure control through a unique anti-cavitation trim design.
Constructed of 316 Stainless Steel, the seat and disc guide
trim components feature dual interlocked sleeves containing
radial slots that deflect internal flow to impinge upon itself in
the center of the flow path, harmlessly dissipating the potential cavitation damage. This unique design also lessens the
possibility of fouling if large particles in the water are present
due to the large flow path of the radial slots.
The 100-20KO Hytrol is the basic valve used in Cla-Val
Automatic Control Valves for high differential applications
requiring remote control, pressure regulation, solenoid operation, rate of flow control, or liquid level control.
5. Consult factory for conditions exceeding these recommenda-
tions.
Functional Data
Valve Size
K
V
Opens
Pattern
Pattern
Pattern
Pattern
C
Factor
Equivalent
Length
of Pipe
Factor
Liquid Displaced from Cover
Chamber When Valve
For assistance in selecting appropriate valve options or valves manufactured with special design requirements, please contact our Regional Sales Office or Factory.
Inches
mm.
Gal./Min. (gpm.)
Globe
Litres/Sec. (l/s.)
Gal./Min. (gpm.)
Angle
Litres/Sec. (l/s.)
Feet (ft.)
Globe
Meters (m.)
Feet (ft.)
Angle
Meters (m.)
Globe Pattern
Angle Pattern
U.S. Gal..03.08.17.531.262.54.04.09.69.69.629.0
Litres.12.30.642.04.89.515.115.136.236.236.2110
The Anti-Cavitation Trim components can be retrofitted to
existing valves if the application indicates an appropriate
need. Please consult factory for details.
Model 100-20KO
40
Page 41
50-01
(Full Internal Port)
MODEL
650-01
(Reduced Internal Port)
Pressure Relief
& Pressure Sustaining Valve
• Accurate Pressure Control
• Optional Check Feature
• Fast Opening to Maintain Line Pressure
• Slow Closing to Prevents Surges
• Completely Automatic Operation
The Cla-Val Model 50-01/650-01 Pressure Relief Valve is a hydraulically
operated, pilot-controlled, modulating valve designed to maintain constant
upstream pressure within close limits. This valve can be used for pressure
relief, pressure sustaining, back pressure, or unloading functions in a
by-pass system.
In operation, the valve is actuated by line pressure through a pilot control
system, opening fast to maintain steady line pressure but closing gradually
to prevent surges. Operation is completely automatic and pressure
settings may be easily changed.
If a check feature is added, and a pressure reversal occurs, the downstream pressure is admitted into the main valve cover chamber, closing the
valve to prevent return flow.
B CK2 (Isolation Valve)
D Check Valves with Isolation Valve
F Remote Pilot Sensing
H Drain to Atmosphere
P X141 Pressure Gauge
S CV Speed Control (Opening)
V X101 Valve Position Indicator
Typical Applications
Supply
CLA-VAL 60-73
Booster Pump
Control Valve
Pump
CLA-VAL
50-01/650-01
Pressure Sustaining
Valve
Isolation Valve
Service
Upper Zone
Isolation Valve
CLA-VAL
50-01/650-01
Pressure Relief
Pressure Sustaining
Valve
Area Of Heavy Demand
Pressure Relief Service
This fast opening, slow closing relief valve provides system protection
against high pressure surges on pump start up and pump shut down
by dissipating the excess pressure to a safe location.
Pressure Sustaining Service
When installed in a line between an upper zone and a
lower area of heavy demand, the valve acts to maintain desired
upstream pressure to prevent "robbing" of the upper
zone. Water in excess of pressure setting is allowed to
flow to an area of heavy demand, control is smooth,
and pressure regulation is positive.
41
Page 42
CLA-VAL
Copyright Cla-Val 2014 Printed in USA Specifications subject to change without notice.
P.O. Box 1325 • Newport Beach, CA 92659-0325 • Phone: 949-722-4800 • Fax: 949-548-5441 • E-mail: claval@cla-val.com • Website cla-val.com
For the 50-01 Main Valve (100-01) dimensions, see pages 17.
For the 650-01 Main Valve (100-20) dimensions, see pages 29.
Pilot System Specifications
Adjustment Ranges
0 to75 psi Max.
20 to105 psi
20 to200 psi *
100 to300 psi
*Supplied unless otherwise specified.
Other ranges available, please consult factory.
Temperature Range
Water: to 180°F
Materials
Standard Pilot System Materials
Pilot Control: Bronze ASTM B62
Trim:Stainless Steel Type 303
Rubber:Buna-N
®
Synthetic Rubber
Tubing & Fitting:Copper and Bronze
Optional Pilot System Materials
Pilot Systems are available with
optional Aluminum, Stainless Steel or
Monel materials at additional cost.
When Ordering, Please Specify
1. Catalog No. 50-01 or No. 650-01
2. Valve Size
3. Pattern - Globe or Angle
4. Pressure Class
5. Threaded or Flanged
6. Trim Material
7. Adjustment Range
8. Desired Options
9. When Vertically Installed
42
E-50-01/650-01 (R-3/2014)
Page 43
Schematic Diagram
Item Description
1Hytrol (100-01KO Main Valve)
2X42N-2 Strainer & Needle Valve
3CRL Pressure Relief Control
MODEL
50-01KO
(Full Internal Port)
Anti-Cavitation Pressure Relief and
Pressure Sustaining Valve
• Virtually Cavitation Free Operation
•
Sensitive and Accurate Pressure Control
•
Easy Adjustment and Maintenance
•
Tamper Resistant
•
Optional Check Feature
•
Fully Supported Frictionless Diaphragm
The Cla-Val Model 50-01KO Anti-Cavitation Pressure Relief Valve is a
hydraulically operated, pilot-controlled, modulating valve designed to maintain constant upstream pressure within close limits. This valve can be used
for pressure relief, pressure sustaining, back pressure, or unloading
functions in a by-pass system.
In operation, the valve is actuated by line pressure through a pilot control
system, opening fast to maintain steady line pressure but closing gradually
to prevent surges. Operation is completely automatic and pressure
settings may be easily changed.
If a check feature is added, and a pressure reversal occurs, the downstream pressure is admitted into the main valve cover chamber, closing the
valve to prevent return flow.
Optional Features
Item Description
BCK2 (Isolation Valve)
DCheck Valves with Isolation Valve
FRemote Pilot Sensing
HDrain to Atmosphere
PX141 Pressure Gauge
SCV Speed Control (Opening)
VX101 Valve Position Indicator
Product Dimensions Data:
For the 50-01KO Main Valve (100-01) dimensions, see pages 17.
Typical Applications
Supply
CLA-VAL 60-73
Booster Pump
Control Valve
Pump
CLA-VAL Model 50-01KO
Pressure Relief
Pressure Sustaining
Valve
Isolation Valve
Service
Upper Zone
Isolation Valve
CLA-VAL Model 50-01KO
Pressure Relief
Pressure Sustaining
Val ve
Area Of Heavy Demand
Pressure Relief Service
This fast opening, slow closing relief valve provides system protection
against high pressure surges on pump start up and pump shut down
by dissipating the excess pressure to a safe location.
Pressure Sustaining Service
When installed in a line between an upper zone and a
lower area of heavy demand, the valve acts to maintain desired
upstream pressure to prevent "robbing" of the upper zone. Water
in excess of pressure setting is allowed to flow to an area of heavy
demand, control is smooth, and pressure regulation is positive.
43
Page 44
Pump
Discharge To
Atmosphere
Isolation
Valve
Pressure Sensing Line
Discharge To System
Discharge To
Atmosphere
CLA-VAL
52-03/652-03
Surge Anticipator Valve
CLA-VAL
81-02/681-02
Check Valve
CLA-VAL
61-02/661-02
Pump Control Valve
52-03
(Full Internal Port)
MODEL
652-03
(Reduced Internal Port)
Pressure Relief & Surge Anticipator Valve
• System Saver
• Protects Against Water Hammer Surges
• Opens on Initial Low Pressure Wave
• Closes Slowly to Prevent Subsequent Surges
• Adjustable Over a Wide Range of Settings
The Cla-Val Model 52-03/652-03 Surge Anticipator Valve is indispensable
for protecting pumps, pumping equipment and all applicable pipelines
from dangerous pressure surges caused by rapid changes of flow velocity within a pipeline.
When pumping systems are started and stopped gradually, harmful
surges do not occur. Should a power failure take place, however the
abrupt stopping of the pump can cause dangerous surges in the system
which could result in severe equipment damage.
Power failure to a pump will usually result in a down surge in pressure, followed by an up surge in pressure. The surge control valve opens on the
initial low pressure wave, diverting the returning high pressure wave from
Schematic Diagram
Item Description
1Hytrol (Main Valve)
2X102F Flow Limiter
3X101 Valve Position Indicator *
4CK2 Isolation Valve
5100-01 Hytrol (Reverse Flow)
6CRL Pressure Relief Control
7CRA Pressure Reducing Control
8X58B Restriction Tube Assembly
*Note: X101 or X105L Accessories not available in 4" and smaller sizes.
the system.*In effect, the valve has anticipated the returning high pressure
wave and is open to dissipate the damage causing surge. The valve will
then close slowly without generating any further pressure surges.
* An adjustable hydraulic flow control limits the valve opening for a controlled initial surge relief.
Product Dimensions Data:
For the 52-03 Main Valve (100-01) dimensions, see pages 17.
For the 652-03 Main Valve (100-20) dimensions, see pages 29.
44
Typical Application
The 52-03/652-03 discharges to atmosphere from a
tee in the pump discharge header. The valve anticipates surges caused by power failure as well as acting
as a standard overpressure relief valve.
Note: The remote pressure sensing line should
Note: We recommend protecting tubing
and valve from freezing temperatures.
3
⁄4
" minimum I.D. installed with a 2° slope
be
from the valve to the pipeline to avoid air
pockets.
Page 45
Schematic Diagram
Item Description
1Hytrol (Main Valve)
2X42N-3 Strainer & Needle Valve
3CRL Pressure Relief Control
4CS3 Solenoid Control
5100-01 Hytrol (Reverse Flow)
58-01
(Full Internal Port)
MODEL
658-01
(Reduced Internal Port)
Combination Back Pressure
& Solenoid Shut-Off Valve
• Accurate Pressure Control
• Wide Adjustment Ranges
• Optional Check Feature Available
• Quick Acting Solenoid Shut-Off
• Easy Installation and Maintenance
The Cla-Val Model 58-01/658-01 valve performs two separate functions. It
maintains a constant back pressure by discharging excess pressure downstream and when the solenoid is activated the valve closes drip-tight.
In operation, the valve is actuated by hydraulic line pressure through
the pilot control system. When inlet pressure is greater than the control
setting, the valve opens. When inlet pressure is equal to the control setting, the pilot modulates the valve, maintaining the preselected back
pressure. When inlet pressure is less than the control setting, the pilot
system closes the valve drip tight. Changing the pressure setting simply involves turning an adjusting screw on the pilot control.
The solenoid control is available in energize to open or de-energize
to open models.
Optional Features
Item Description
BShutoff Isolation Valve - Isolates Pilot System
DCheck Valves with Isolation Valve
FRemote Pilot Sensing
HDrain to Atmosphere
PX141 Pressure Gauge
SCV Speed Control (Opening)
VX101 Valve Position Indicator
Product Dimensions Data:
For the 58-01 Main Valve (100-01) dimensions, see pages 17.
For the 658-01 Main Valve (100-20) dimensions, see pages 29.
Typical Applications
Electrode
Supply System
Gound
Storage
Tan k
CLA-VAL
58-01/658-01
Combination Back
Pressure and Solenoid
Shut-Off Valve
Back Pressure Maintenance Service
A frequent application of this valve is to maintain minimum
back pressure in the system while supplying water to
a reservoir. The electrode in the storage tank activates
the solenoid shutoff feature when the tank reaches a
preset level.
Pump
The "D" feature on a vertically installed 6" and larger valve
Electronic Control Service
Using a timer connected to the solenoid control of
the valve, flow from the high pressure system to the
low pressure system can be controlled at certain
times during the day.
must be horizontally oriented.
High Pressure System
CLA-VAL
58-01/658-01
Combination Back
Pressure and Solenoid
Shut-Off Valve
Time
Clock
Low Pressure
System
45
Page 46
750-01
MODEL
Pressure Relief,
Sustaining & Back Pressure Valve
Description
The Cla-Val Model 750-01 is a hydraulically operated pilot actuated
automatic control valve for pressure sustaining, relief and/or back
pressure service. The main valve consists of only two parts, a stainless
steel body and an elastomeric liner or control element.
The main valve will open when inlet pressure begins to exceed a preset
pressure and will allow enough flow to maintain that inlet pressure. In
pressure sustaining service, Model 750-01 will conserve pressure in
an upper system during periods of high demand in a system below. In
pressure relief service, the Model 750-01 will modulate to exhaust line
pressure to keep it below a set point maximum. On a pump bypass
system, the valve will allow flow back to the pump suction when pump
discharge pressure exceeds the set point.
Cla-Val Model 750-01 will control from no flow to full open flow without
any chattering or slamming under low flow conditions. For this reason,
on by-pass, relief, and pressure sustaining service, there is never a
Performance Specification
Capacity: See Technical Data Sheet
CfFactor:0.9
Cavitation:See Technical Data Sheet
Rangeability:500:1
Bearing Friction:No friction from slip-type
bearings
Design Specification
Sizes:2, 3, and 6 inch wafer style
6, 8, 10, and 12 inch flanged
6, 8, 10, 12, inch Victaulic® Ends
End Detail Wafer:Fits ANSI B16.5 class 125,150,
250, and 300 flanges
End Detail Flanged:ANSI B16.5 class 150
(fits class 125) or
ANSI B16.5 class 300
®
End Detail Victaulic
Operating Pressure: 720 psi maximum
Maximum Differential: 150 psid continuous,
Reverse Pressure
Temperature Range: 32 to 160 degrees F*
Flange Operating Pressure: Class 125-175 psi maximum
Victaulic
*Standard natural rubber 65 durometer in water service. Temperature range
depends on liner material. Higher differential pressure ratings available.
For other than standard ANSI flanges consult factory
DIN drilling available on all sizes
®
Ends Rating: 300 psi maximum
:Fits standard steel pipe
: 125 psid maximum
(fits class 250)
®
Victaulic
225 psid intermittent*
Class 150-275 psi maximum
Class 250-300 psi maximum
Class 300-720 psi maximum
Ends - 300 psi max.
Product Dimensions Data:
For the 750-01 Main Valve (100-42) dimensions, see pages 31.
region of control instability. There is no slip-type friction because the
valve has no bearings. Cla-Val Model 750-01 valves have excellent
resistance to cavitation with a Cf factor of 0.9.
These valves can be supplied as combination control valve with
check. Pilot controls, options, and accessories are fully piped at the
factory and the Cla-Val Model 750-01 is shipped ready for installation.
Purchase Specification
Valve and control system shall maintain inlet pressure at a predetermined
set point; shall open as pressure starts to increase above the set
point, and close as pressure falls below the set point. Control valve
shall be constructed of two parts: a stainless steel body and an
elastomeric liner or control element. Minimum rangeability shall be
500:1 based on capacity at flowing pressure conditions. Cf shall be
greater than or equal to 0.9. Valve and control system shall be similar
in all respects to Cla-Val Model 750-01 as manufactured by Cla-Val,
Newport Beach, California.
The Cla-Val Model 250-01/605-01 Differential Pressure Relief Valve is
a hydraulically operated, pilot-controlled, modulating valve. It is
designed to maintain a constant pressure differential between any two
pressure points in a system where the closing of the valve directly causes the differential pressure to increase. The valve tends to open on an
increase in differential pressure and close on a decrease in differential
pressure.
In operation, the valve is actuated by line pressure through a pilot control system sensing from two points across which a differential is to be
maintained. Operation is completely automatic and pressure settings
may be easily changed.
Optional Features
Item Description
BCK2 (Isolation Valve)
DCheck Valves with Isolation Valve
FRemote Pilot Sensing (H.P.)
PX141 Pressure Gauge
SCV Speed Control (Opening)
VX101 Valve Position Indicator
Product Dimensions Data:
For the 250-01 Main Valve (100-01) dimensions, see pages 17.
For the 605-01 Main Valve (100-20) dimensions, see pages 29.
Typical Applications
PUMP SUCTION LOW PRESSURE SENSING
CONNECTED TO DIFFERENTIAL CONTROL
VARIABLE
VARIABLE
PRESSURE
MAIN
PUMP
CLA-VAL 250-01/605-01
DIFFERENTIAL RELIEF
& CHECK VALVE
The Model 250-01/605-01 Differential Pressure Relief Valve maintains a constant differential across centrifugal pump regardless of
variable upstream pressures or downstream demand.
By maintaining a constant differential pressure across a centrifugal
pump operating at a known capacity, the maximum flow rate is controlled.
DEMAND
Supply to
Cirulating
Loop
Chilled Water
Supply
CLA-VAL
250-01/605-01
Differential Pressure
Relief Valve
Return
From Loop
On a chilled water circulating loop system the 250-01/605-01
Differential Pressure Relief Valve is installed between loop supply
and return lines to maintain a constant differential
across the loop. The loop differential pressure remains
constant regardless of the loop demand change thereby increasing cooling system efficiency.
47
Page 48
90-01
(Full Internal Port)
MODEL
690-01
(Reduced Internal Port)
Pressure Reducing Valve
• Sensitive and Accurate Pressure Control
• Easy Adjustment and Maintenance
• Tamper Resistant
• Optional Check Feature
• Fully Supported Frictionless Diaphragm
The Cla-Val Model 90-01/690-01 Pressure Reducing Valve automatically
reduces a higher inlet pressure to a steady lower downstream pressure,
regardless of changing flow rate and/or varying inlet pressure. This valve
is an accurate, pilot-operated regulator capable of holding downstream
pressure to a pre-determined limit. When downstream pressure exceeds
the pressure setting of the control pilot, the main valve and pilot valve close
drip-tight.
If a check feature is added, and a pressure reversal occurs, the downstream pressure is admitted in the main valve cover chamber, closing the
valve to prevent return flow.
Schematic Diagram
Item Description
1Hytrol (Main Valve)
2X58 Restriction Fitting
3CRD Pressure Reducing Control
Optional Features
Item Description
AX46A Flow Clean Strainer
BCK2 (Isolation Valve)
CCV Flow Control (Closing)*
DCheck Valves with Isolation Valve
PX141 Pressure Gauge
VX101 Valve Position Indicator
SCV Flow Control (Opening)
Y X43 "Y" Strainer
The closing speed control (optional) on this valve should
*
always be open at least three (3) turns off its seat.
Typical Applications
Typical applications include pressure reducing valve station
using Model 90-01BY/690-01BY and Model 90-01AS/690-01AS
in parallel to handle wide range of flow rates. Larger Model 9001BY/690-01BY valve meets requirements of peak loads and
smaller Model 90-01AS/690-01AS handles low flows.
High Pressure
CLA-VAL 90-01BY/690-01BY
Pressure Reducing Valve
Isolation Valve
Gauge
CLA-VAL 90-01AS/690-01AS
Pressure Reducing Valve
Constant
Downstream
Pressure
48
Cla-Val Model
Anti-Cavitation Trim provides for optimum downstream pressure
control while reducing noise and eliminating damage associated
with cavitation.
See Cavitation Guide to determine if the valve is a candidate for
the KO Anti-Cavitation Trim.
High Pressure
90-01KO/690-01KO
CLA-VAL Model
90-01KO
Anti-Cavitation Trim
for Excess Pressure Drop
Consult Cavitation Chart
Pressure Reducing Valve with
Isolation Valve
Gauge
Constant
Downstream
Pressure
Page 49
CLA-VAL
Copyright Cla-Val 2014 Printed in USA Specifications subject to change without notice.
P.O. Box 1325 • Newport Beach, CA 92659-0325 • Phone: 949-722-4800 • Fax: 949-548-5441 • E-mail: claval@cla-val.com • Website cla-val.com
Many factors should be considered in sizing pressure reducing valves including inlet pressure,
outlet pressure and flow rates.
For sizing questions or cavitation analysis, consult Cla-Val with system details.
When Ordering, Please
Materials
Standard Pilot System Materials
Pilot Control: Bronze ASTM B62
Trim: Stainless Steel Type 303
Rubber: Buna-N
®
Synthetic Rubber
Optional Pilot System Materials
Pilot Systems are available with optional
Aluminum, Stainless Steel or Monel materials
at additional cost.
Note: Available with remote sensing control.
Specify
1. Catalog No. 90-01 or No. 690-01
2. Valve Size
3. Pattern - Globe or Angle
4. Pressure Class
5. Threaded, Flanged or Grooved
6. Trim Material
7. Adjustment Range
8. Desired Options
9. When Vertically Installed
10. Product Enhancements
E-90-01/690-01 (R-3/2014)
49
Page 50
90-01KO
(Full Internal Port)
MODEL
Anti-Cavitation
Pressure Reducing Valve
• Virtually Cavitation Free Operation
•
Sensitive and Accurate Pressure Control
•
Easy Adjustment and Maintenance
•
Tamper Resistant
•
Optional Check Feature
•
Fully Supported Frictionless Diaphragm
Schematic Diagram
Item Description
1Hytrol (100-01KO Main Valve)
2X58 Restriction Fitting
3CRD Pressure Reducing Control
Optional Features
Item Description
AX46A Flow Clean Strainer
BCK2 (Isolation Valve)
CCV Flow Control (Closing)*
DCheck Valves with Isolation Valve
PX141 Pressure Gauge
CV Speed Control (Opening)
S
X101 Valve Position Indicator
V
Y X43 "Y" Strainer
*The closing speed control (optional) on this valve should
always be open at least three (3) turns off its seat.
Product Dimensions Data:
For the 90-01KO Main Valve (100-01) dimensions, see pages 17.
The Cla-Val Model 90-01KO
Valve automatically reduces a higher inlet pressure to a steady lower
downstream pressure, regardless of changing flow rate and/or varying
inlet pressure. This valve is an accurate, pilot-operated regulator capable
of holding downstream pressure to a pre-determined limit. When downstream pressure exceeds the pressure setting of the control pilot, the main
valve and pilot valve close drip-tight.
If a check feature is added, and a pressure reversal occurs, the downstream pressure is admitted in the main valve cover chamber, closing the
valve to prevent return flow.
The "D" check feature on a vertically installed 6"
and larger valves must be horizontally installed.
Anti-Cavitation Hytrol
Pressure Reducing
Typical Applications
Typical applications include pressure reducing valve station
using Model 90-01BYKO and Model 90-01ASKO in parallel to
handle wide range of flow rates. Larger Model 90-01BYKO
valve meets requirements of peak loads and smaller Model
90-01ASKO handles low flows.
High Pressure
CLA-VAL 90-01BYKO
Pressure Reducing Valve
Isolation Valve
Gauge
CLA-VAL 90-01ASKO
Pressure Reducing Valve
Constant
Downstream
Pressure
50
Cla-Val Model
Cavitation Trim provides for optimum downstream pressure control while reducing noise and eliminating damage associated
with cavitation.
See Cavitation Guide to determine if the valve is a candidate for
the KO Anti-Cavitation Trim.
High Pressure
90-01KO
CLA-VAL Model
Anti-Cavitation Trim
for Excess Pressure Drop
Consult Cavitation Chart
Pressure Reducing Valve with Anti-
90-01KO
Isolation Valve
Gauge
Constant
Downstream
Pressure
Page 51
90-48
MODEL
(Full Internal Port)
690-48
(Reduced Internal Port)
Pressure Reducing Valve with
Low Flow By-Pass
• Modulating Control
• Maintains Constant Outlet Pressure Over a
Wide Range of Flows
• Durable Construction
• Convenient and Space Saving
The Cla-Val Model 90-48/690-48 Pressure Reducing Valve with
Low Flow By-Pass automatically reduces a higher inlet pressure to
a steady lower downstream pressure, regardless of changing flow
rate. The low flow by-pass capability is achieved by using the ClaVal Model CRD-40 Direct Acting Pressure Reducing Valve as an
integral part of the main valve. By doing this, space is saved and
installation and maintenance become much easier.
The pressure reducing valve is hydraulically operated and controlled by a Cla-Val CRD pilot control, which senses pressure at the
main valve outlet. An increase in outlet pressure forces the CRD
pilot control to close and a decrease in outlet pressure opens the
control. This causes the main valve cover pressure to vary, modulating the main valve, thereby, maintaining constant outlet pressure.
AX46A Flow Clean Strainer
BCK2 (Isolation Valve)
CCV Flow Control (Closing)*
DCheck Valves with Isolation Valve
PX141 Pressure Gauge
SCV Speed Control (Opening)
VX101 Valve Position Indicator
YX43 "Y" Strainer
*The optional closing speed control on this valve should
always be open at least three (3) turns off its seat.
*
Typical Applications
This valve has the flexibility to be installed in a distribution system where the demand varies over a wide range. This frequently occurs in industrial, residential, educational, high-rise buildings and other applications. Another important feature of the
valve is its space efficient configuration, allowing easy installation and maintenance.
The Model CRD-40 low flow pressure reducing by-pass is preset to
a higher pressure than the CRD pilot control. The CRD-40
responds to pressure changes at the main valve outlet. When the
CRD closes, the Model CRD-40 remains open, allowing low flow to
by-pass the main valve. The CRD-40 closes when the flow
decreases and the downstream pressure reaches its set-point .
The Cla-Val Model 90-48/690-48 is not a substitute for a low flow
bypass valve in all cases. This valve is commonly used in building
where 1-15 gpm low flows are common in off peak usage. The
bypass on this valve is limited to the body tapping size on the main
valve.
Product Dimensions Data:
For the 90-48 Main Valve (100-01) dimensions, see pages 17.
For the 690-48 Main Valve (100-20) dimensions, see pages 29.
The Cla-Val Model 92-01/692-01 Combination Pressure Reducing
and Pressure Sustaining Valve automatically performs two independent functions. It maintains a constant downstream pressure,
regardless of fluctuating demand and sustains the upstream pressure to a pre-determined minimum.
The pressure reducing control responds to slight variations in downstream pressure and immediately repositions the main valve to
maintain the desired downstream pressure. The pressure sustaining
control is normally held open by the upstream pressure, but modulates should the pressure drop to the control set point. This, in turn,
modulates the main valve to sustain the desired upstream pressure.
Schematic Diagram
Item Description
1Hytrol (Main Valve)
2X44A Strainer & Orifice
3CRD Pressure Reducing Control
4CRL Pressure Relief Control
5CV Flow Control (Opening)
If a check feature is added, and a pressure reversal occurs, the
downstream pressure is admitted into the main valve cover chamber and the valve closes to prevent return flow.
Optional Features
Item Description
BCK2 (Isolation Valve)
CCV Flow Control (Closing)*
DCheck Valves With Isolation Valve
FRemote Pilot Sensing
PX141 Pressure Gauge
VX101 Valve Position Indicator
* The (optional) closing speed control on this valve should
always be open at least three (3) turns off its seat.
Product Dimensions Data:
For the 92-01 Main Valve (100-01) dimensions, see pages 17.
For the 692-01 Main Valve (100-20) dimensions, see pages 29.
Isolation
Valve
High Pressure Main
CLA-VAL MODEL
Combination Pressure Reducing
92-01/692-01
& Pressure Sustaining Valve
Distribution
Typical Applications
A Combination Pressure Reducing and Pressure Sustaining
Valve is typical used to automatically reduce pressure for the
downstream distribution network and sustain a minimum
pressure in the high pressure main regardless of distribution
demand.
52
Page 53
Schematic Diagram
Item Description
1Hytrol (Main Valve)
2X58C Restriction Assembly
3CRD Pressure Reducing Control
4100-01 Hytrol (Reverse Flow)
5CS3 Solenoid Control
93-01
(Full Internal Port)
MODEL
693-01
(Reduced Internal Port)
Pressure Reducing &
Solenoid Shut-Off Valve
• Accurate Pressure Control
• Wide Adjustment Ranges
• Optional Check Feature Available
• Quick Acting Solenoid Shut-Off
• Easy Installation and Maintenance
The Cla-Val Model 93-01/693-01 Combination Pressure Reducing and
Solenoid Shut-Off Valve consists of a Cla-Val Hytrol main valve, a reducing control and a solenoid control connected to the main valve. This
valve automatically reduces higher inlet pressure to a steady lower
downstream pressure, regardless of changing flow rate and/or varying
inlet pressure.
The 93-01/693-01 is an accurate, pilot-operated regulator capable of
holding downstream pressure to a pre-determined delivery pressure.
When downstream pressure exceeds the pressure setting of the control
pilot, the pilot valve and main valve close drip-tight. A solenoid control is
provided to intercept the operation of the pressure reducing control and
close the main valve. This valve is furnished either normally open (deenergized to open), or normally closed (energized to open). Pressure
setting adjustment is made with a single adjusting screw.
Optional Features
Item Description
AX46A Flow Clean Strainer
BCK2 (Isolation Valve)
CCV Flow Control (Closing)*
DCheck Valves with Isolation Valve
HSolenoid Drain To Atmosphere
PX141 Pressure Gauge
SCV Speed Control (Opening)
VX101 Valve Position Indicator
Y X43 "Y" Strainer
The closing speed control (optional) on this valve should
*
always be open at least three (3) turns off its seat.
Product Dimensions Data:
For the 93-01 Main Valve (100-01) dimensions, see pages 17.
For the 693-01 Main Valve (100-20) dimensions, see pages 29.
Typical Applications
Electronic Control Service
A typical application for this valve is to reduce high transmission line
pressures to lower distribution system levels, while opening and
closing on command. The solenoid control feature can be activated
by an electrical signal from a timer or programmer.
Fire Service
The 93-01/693-01 can be installed in a distribution
line where there is a need to close the valve on the
starting of a fire pump. The solenoid control is activated on pump start-up and closes the valve.
53
Page 54
94-01
(Full Internal Port)
MODEL
694-01
(Reduced Internal Port)
Combination Pressure Reducing and
Surge Control Valve
• Sensitive and Accurate Pressure Control
• Easy Adjustment and Maintenance
• Tamper Resistant
• Optional Check Feature
• Fully Supported Frictionless Diaphragm
The Cla-Val Model 94-01/694-01 Combination Pressure Reducing and
Surge Control Valve automatically reduces a higher inlet pressure to a
steady lower downstream pressure, regardless of changing flow rate
and/or varying inlet pressure. This valve is an accurate, pilot-operated control valve capable of holding downstream pressure to a pre-determined
limit. When downstream pressure rapidly exceeds the pressure setting of
the pressure reducing control pilot, the surge pilot (CRL) will open quickly
to prevent a rapid pressure rise downstream.
Schematic Diagram
Item Description
1100-01 Hytrol (Main Valve)
2X58C Restriction Assembly
3CRD Pressure Reducing Control
4CRL Pressure Relief Control
If a check feature is added, and a pressure reversal occurs, the downstream pressure is admitted in the main valve cover chamber closing the
valve to prevent return flow.
Optional Features
Item Description
AX46A Flow Clean Strainer
BCK2 (Isolation Valve)
CCV Flow Control (Closing)*
DCheck Valves with Isolation Valve
FRemote Pilot Sensing
PX141 Pressure Gauge
SCV Speed Control (Opening)
VX101 Valve Position Indicator
Y X43 "Y" Strainer
*The closing speed control (optional) on this valve should
always be open at least three (3) turns off its seat.
Product Dimensions Data:
For the 94-01 Main Valve (100-01) dimensions, see pages 17.
For the 694-01 Main Valve (100-20) dimensions, see pages 29.
Typical Application
Should the downstream pressure suddenly increase above the setting of the pressure reducing control due to on-off operation of two or more downstream systems,
the Surge Control tracks rapidly enough to
prevent high pressure surges from entering any of the downstream systems, when
any one of the downstream systems is
rapidly closed off. The typical combination
pressure reducing and surge control valve
station uses Model 94-01BY/694-01BY to
control surges in downstream piping as
remote control valves change from one
downstream zone to another. Surge
Control is set approximately 10 psi above
Pressure Reducing Control to prevent
high pressure surge entering other downstream zones.
54
Page 55
MODEL
990
Balanced Direct Acting
Pressure Reducing Valve
• Balanced, Single Seat Design
• Operates in Any Position
• Easy Installation
• Stainless Steel Trim Standard
• Gauge Connections Standard
• All Bronze Body and Cover
The Cla-Val Model 990 Pressure Reducing Valve automatically
reduces a higher inlet pressure to a steady lower downstream pressure with our unique balanced design. This valve is an accurate regulator capable of holding downstream pressure to a predetermined
amount, regardless of upstream pressure fluctuations.
Periodic maintenance consist of regular cleaning of internal strainer
that is accessed by removing bottom plug. There are no user serviceable components.
Typical Applications
High rise buildings use 990 Pressure Reducing Valves
in various water systems (potable water, boiler feed
air conditioning, etc.) to control pressure fluctuations between
floors.
Industrial plants use 990 Pressure Reducing Valves between
a high pressure supply system and equipment requiring lower
pressure. Typically 990 Pressure Reducing Valves are used at
supply connections for water heaters, boiler feed water or
other process water systems.
Municipal water systems use 990 Pressure Reducing Valves
at service connections in a high pressure distribution zone.
Depending on flow requirements, 990's may be installed in
parallel. One 990 provides desired outlet pressure while the
second 990 handles low flow conditions. If necessary, additional 990s can be added for more flow capacity. The 990 is
also ideal for a low flow bypass around a larger Cla-Val 90
Series Pressure Reducing Valve.
Flow
Isolation
Valve
55
Page 56
790-01
SINGAPORE
PUB
MODEL
Pressure Reducing Valve
Description
The Cla-Val Model 790-01 is a hydraulically operated, pilot actuated
automatic control valve for pressure reducing service. The main
valve consists of only two parts: a stainless steel body, and an
elastomeric liner or control element.
Pressure reducing valves are used to lower pipeline pressure to a
predetermined set point. Cla-Val Model 790-01 automatically
controls downstream pressure, from no flow to full open flow, without
regard to changes in inlet pressure. Outlet pressure control is
smooth and precise since the friction and hysteresis of the valve
and pilot is negligible.
Because the valve will not chatter or slam under low flow conditions,
it is not necessary to parallel Cla-Val Model 790-01 with a second
smaller size control valve to obtain accurate pressure control at low
flow rates. In any size, Cla-Val Model 790-01 will control pressure
right down to shutoff.
Performance Specification
Capacity: See Technical Data Sheet
CfFactor:0.9
Cavitation:See Technical Data Sheet
Rangeability:500:1
Bearing Friction:No friction from slip-type
bearings
Design Specification
Sizes:2, 3, and 6 inch wafer style
6, 8, 10, and 12 inch flanged
6, 8, 10, 12 inch Victaulic
End Detail Wafer:Fits ANSI B16.5 class 125,150,
250, and 300 flanges
End Detail Flanged:ANSI B16.5 class 150
(fits class 125) or
ANSI B16.5 class 300
End Detail Victaulic
Operating Pressure: 720 psi maximum
Maximum Differential: 225 psid
Reverse Pressure
Approvals: PUB Listed.........Sizes 2" thru 6"
Temperature Range: 32 to 160 degrees F*
Flange Operating Pressure: Class 125-175 psi maximum
Victaulic
*Standard natural rubber 65 durometer in water service.
Temperature range depends on liner material. Higher differential pressure
ratings available.
For other than standard ANSI flanges consult factory
DIN drilling available on all sizes
56
®
Ends Rating: 300 psi maximum
®
:Fits standard steel pipe
: 125 psid maximum
(fits class 250)
Victaulic
For higher differential consult factory
Class 150-275 psi maximum
Class 250-300 psi maximum
Class 300-720 psi maximum
®
Ends - 300 psi max.
®
Ends
Pressure reducing valves can be supplied as a combination with
check valve. Control systems are fully piped at the factory and the
Cla-Val Model 790-01 is shipped ready for installation.
Purchase Specification
Valve and control system shall lower line pressure to a predetermined
set point and shall maintain that set point regardless of variations in
flow or inlet pressure. Control valve shall be constructed of two
parts: a stainless steel body, and an elastomeric liner or control element.
Minimum rangeability shall be 500:1 based on capacity at flowing
pressure conditions. C
and control system shall be similar in all respects to Cla-Val Model
790-01 as manufactured by Cla-Val, Newport Beach, California.
Shut-off Isolation Valve: Brass*
"Y" Strainer: Bronze*
Speed Controls: Brass*
Check Controls: Brass*
Control Piping: Copper*
Control Fittings: Brass*
316 stainless steel available
*
Product Dimensions Data:
For the 790-01 Main Valve (100-42) dimensions, see
pages 31.
Page 57
2
INLET
B
B
6A
P1
S
C
6B
3
7
1
5
9
ADJUSTMENT
HIGH PRESSURE
10
LOW
ADJUSTMENT
PRESSURE
11
4
B
8
ADJUSTMENT SCREW
P2
MODEL
98-06
(Full Internal Port)
698-06
(Reduced Internal Port)
(2"-10")
(3"-12")
Hydraulic
Pressure Management Control Valve
with Dual Setpoints
• 100% Hydraulic Control
• Two Adjustable Downstream Set Points for
High and Low Pressure
• Simple to Setup and Adjust
• Smooth Transition from High to Low Pressure
• Retrofits to Existing Valve Without Removal
From Pipeline
• Helps Prevent Pipe Breaks and Background Leaks
The Cla-Val Model 98-06/698-06 Pressure Management Control
Valve is a pressure reducing valve that allows for two downstream
set points. A high pressure set point is selected for high flow
demand and a low pressure set point is selected for low flow
demand. This dual set point arrangement allows for reduction in
water loss by not over pressurizing the system during times of low
demand, while providing adequate pressure during high or fire
demand. The design is 100% hydraulic and in addition to the dual
pressure set points the transition point at which the pressure
changes based on the flow is adjustable as well. The patent
pending design of the valve allows for smooth transition from one
BCK2 (Isolation Valve)
CCV Flow Control (Closing)
PX141 Gage Assembly
SCV Flow Control (Opening)
Typical Performance
A dual system pressure with reduced system pressure during
low demand periods is illustrated in the chart. At low flows a
minimum pressure is maintained and as flow increases to the
switch point delivery pressure increases to the maximum
pressure set point for switch. The point between low pressure
and high pressure setpoints is adjustable to fine tune valve to
system requirements.The “water saving zone” below
maximum pressure line represents valve effectiveness in
reducing water losses and pipeline breakage in a system.
set point to the other.
P1
Upstream
Pressure
Upstream
Pressure
(P1)
Go to www.cla-val.com for Purchase Specification
Water Saving Zone for reduced leakage
and fewer pipe breaks
Water Saving Zone
Pressure
Modulating Profile
flow
Low Demand
Flow
Downstream
Pressure
P2 (Q max.)
P2 (Q min.)
Q = Flow
High Demand
(Fire Flow,
Irrigation, etc.)
LP
Savings
Setpoint High
Downstream
Pressure (P2)
Setpoint Low
HP
57
Page 58
Y
CS3
2
1
3
5
4
3B
3A
H
SOLENOID
DRAIN TO
ATMOSPHERE
C
D2
D3
B
B
S
2
D1
B
A
1
INLETOUTLET
90-11
(Full Internal Port)
690-11
(Reduced Internal Port)
MODEL
790-11
Pressure Reducing Valve with
Two Stage - Solenoid Selected Pressure
• Two Adjustable Setpoints
• Sensitive and Accurate Pressure Control
• Ideal For Use with SCADA System
• Low Power Required
• Low Maintenance Cost
The Cla-Val Model 90-11 Two-Stage Pressure Reducing Control valve allows
selection between two different pressure-reducing set points. It has one pilot set at
a higher pressure setting; a second pilot set at a lower pressure setting and a solenoid control to select the active pilot control for the main valve. The valve smoothly changes setpoint and will control pressure regardless of inlet pressure fluctuations or downstream demand changes. Set point switching is achieved by energizing the solenoid control for the desired time that the low pressure is needed. The
two set points are easily changed in the field.
This valve is suitable for many pressure control applications where downstream
conditions change sufficiently to require a lowered pressure during part of the time.
A variety of electronic controls can be use with the 90-11 ranging from a simple battery powered timer to extensive SCADA systems. In leakage abatement applications, the 90-11 offers simplified two-pressure control of a distribution zone. For
times of high demand, the higher pressure control is used and for times of low
demand, the lower pressure control is selected.
Schematic Diagram
Item Description
1Hytrol (Main Valve)
2X58 Restriction Fitting
3CRD Pressure Reducing Control
4100-01 Auxiliary Hytrol (Reverse Flow)
5CS3 Solenoid Control
Optional Features
Item Description
AX46A Flow Clean Strainer
BCK2 (Isolation Valve)
CCV Flow Control (Closing)
DCheck Valves with Isolation Valve
HSolenoid Drain to Atmosphere
SCV Flow Control (Opening)
Y X43 "Y" Strainer
Typical Application
The valve can be used to conserve water by lowering
the system pressure during low demand periods.The
valve is designed to be used with a SCADA system that
will select which setpoint to use.
provide a control system to determine when to shift the
solenoid so as to prevent holding the low pressure set
point during unforeseen high flow demands such as fire
flow.
Product Dimensions Data:
For the 90-11 Main Valve (100-01) dimensions, see pages 17.
For the 690-11 Main Valve (100-20) dimensions, see pages 29.
For the 790-11 Main Valve (100-42) dimensions, see pages 31.
58
The customer must
Page 59
CLA-VAL
Schematic Diagram
Item Description
1Hytrol (Main Valve)
2X58C Restriction Assembly
3CRD Pressure Reducing Control
4CTC Electronic Timer Control
5100-01 Auxiliary Hytrol
97-20
MODEL
(Full Internal Port)
697-20
(Reduced Internal Port)
Dual Stage Pressure Reducing Control Valve
with Programmable Timer Control
Precise Valve On-Off Control
•
Completely Self-contained
•
High Energy Efficiency
•
Battery Life Exceeds 3 Years
•
Direct Control of Valve Opening and Closing Four Times Daily
•
Combines with Pressure, Flow or Level Control
•
Ideal for Remote Valve Location Control
•
FLOW
The Cla-Val Model 97-20/690-20 Dual Stage Pressure Reducing Control
Valve with Programmable Timer Control allows selection between two different pressure-reducing set points. It has one pilot set at a higher pressure setting; a second pilot set at a lower pressure setting and a solenoid control to
select the active pilot control for the main valve. The valve smoothly changes
setpoint and will control pressure regardless of inlet pressure fluctuations or
downstream demand changes. Set point switching is achieved by energizing the solenoid control for the desired time that the low pressure is needed.
The two set points are easily changed in the field.
This valve is suitable for many pressure control applications where downstream conditions change sufficiently to require a lowered pressure during
part of the time. In leakage abatement applications, the 97-20 offers simplified two-pressure control of a distribution zone. For times of high demand,
the higher pressure control is used and for times of low demand, the lower
pressure control is selected.
Timer function and parameters are changed using downloadable software
from the Cla-Val website www.cla-val.com and special USB cable part
number 20519203A. Future software and firmware upgrades will be available from Cla-Val website. Powered by a long-life lithium battery, the CTC
control offers powerful valve control for remote locations and other valve
automation applications.
Optional Features
Item Description
AX46A Flow Clean Strainer
BCK2 (Isolation Valve)*
CCV Flow Control (Closing)
DCheck Valves with Isolation Valve
SCV Flow Control (Opening)
YX43 “Y” Strainer
*Standard on 1-1/4” and larger
Product Dimensions Data:
For the 97-20 Main Valve (100-01) dimensions, see pages 17.
For the 697-20 Main Valve (100-20) dimensions, see pages 29.
Typical Application
The valve can be used to conserve water by lowering
the system pressure during low demand periods.The
valve is designed to help prevent pipe breaks in the
system.
determine when to shift the solenoid so as to prevent
holding the low pressure set point during unforeseen high
flow demands such as fire flow.
The customer must provide a control system to
Upper Zone
CLA-VAL
Dual Stage Pressure Reducing Valve
97-20/697-20
with Programmable Timer Control
System Pressure
High Pressure-For high flow demand
Low Pressure-For low flow demand
Isolation Valve
59
Page 60
40-01
(Full Internal Port)
MODEL
640-01
(Reduced Internal Port)
Rate of Flow Control Valve
Accurately Limits Flow Rate
•
Completely Automatic Operation
•
Includes Orifice Plate with Holder
•
Optional Check Feature
•
Easily Adjusted
•
The Cla-Val Model 40-01/640-01 Rate of Flow Control Valve prevents
excessive flow by limiting flow to a preselected maximum rate, regardless of changing line pressure. It is a hydraulically operated, pilot controlled, diaphragm valve. The pilot control responds to the differential
pressure produced across an orifice plate installed downstream of the
valve. Accurate control is assured as very small changes in the controlling differential pressure produce immediate corrective action of the main
valve. Flow rate adjustments are made by turning an adjusting screw on
the pilot control.
AX46A Flow Clean Strainer
BCK2 (Isolation Valve)
CCV Flow Control (Closing)
DCheck Valves with Isolation Valve
PX141 Pressure Gauge
SCV Speed Control (Opening)
VX101 Valve Position Indicator
YX43 "Y" Strainer
Product Dimensions Data:
For the 40-01 Main Valve (100-01) dimensions, see pages 17.
For the 640-01 Main Valve (100-20) dimensions, see pages 29.
Typical Applications
The Model 40-01/640-01 includes an orifice plate with a holder that
should be installed one to five pipe diameters downstream of the valve.
If the check feature option is added and a pressure reversal occurs, the
downstream pressure is admitted into the main valve cover chamber and
the valve closes to prevent return flow. See X52E data sheet for sizing
selection.
The 40-01/640-01 is typically installed where water supply to a system
must be limited to a preset maximum flow rate. The valve is easily set to
maintain the maximum allowable flow rate.
60
The 40-01/640-01 is typically installed as a pressure type filter
effluent control valve where a constant flow rate is maintained
as head loss through the filter varies.
Page 61
Schematic Diagram
Item Description
1Hytrol (Main Valve)
2X58C Restriction Fitting
3100-01 Hytrol (Reverse Flow)
4CDHS18 Differential Control
5CS3 Solenoid Control
6X52E Orifice Plate Assembly
43-01
(Full Internal Port)
MODEL
643-01
(Reduced Internal Port)
Combination Rate of Flow Control
& Solenoid Shut-Off Valve
• Multi-functional Capability
• Includes Orifice Plate with Holder
• Optional Check Feature
• Easily Adjusted
• Every Valve Factory Tested
The Cla-Val Model 43-01/643-01 Combination Rate of Flow Control
and Solenoid Shut-Off Valve limits the maximum flow rate, regardless of changing line pressure. It is a hydraulically operated, pilot
controlled, diaphragm valve. The pilot control
is actuated by the differential pressure produced across an orifice
plate installed downstream of the valve. Accurate control is assured
as very small changes in the controlling differential pressure produce immediate corrective action of the main valve. A solenoid control is provided to intercept the operation of the differential control
and close the main valve.
The Model 43-01/643-01 includes a orifice plate with a holder that
should be installed one to five pipe diameters downstream of the
main valve. If the check feature option is added and a pressure
reversal occurs, the downstream pressure is admitted into
the main valve cover chamber and the valve closes to prevent return
flow.
Optional Features
Item Description
AX46A Flow Clean Strainer
BCK2 (Isolation Valve)
CCV Flow Control (Closing)
DCheck Valves with Isolation Valve
HSolenoid Drain to Atmosphere
PX141 Pressure Gauge
SCV Speed Control (Opening)
VX101 Valve Position Indicator
YX43 “Y” Strainer
Product Dimensions Data:
For the 43-01 Main Valve (100-01) dimensions, see pages 17.
For the 643-01 Main Valve (100-20) dimensions, see pages 29.
The 43-01/643-01 is typically installed where water supply to a system
must be limited to a pre-set maximum flow rate at certain times of day.
The valve is easily set to maintain the maximum allowable flow rate and
is to open or close on an electrical signal.
The "D" feature on a vertically installed 6" and
larger valves must be horizontally installed.
The 43-01/643-01 is typically installed as a pressure
type filter effluent control valve where a constant
flow rate is maintained as head loss through the filter varies. The valve opens or closes on an electrical signal.
61
Page 62
49-01
(Full Internal Port)
MODEL
649-01
(Reduced Internal Port)
Combination Rate of Flow
& Pressure Reducing Valve
• Multi-Functional Capability
• Accurate and Immediate Control
• Includes Orifice Plate with Holder
• Optional Check Feature
• Easily Adjustable Controls
The Cla-Val Model 49-01/649-01 Rate of Flow and Pressure Reducing
Valve automatically reduces a higher inlet pressure to a steady lower
downstream pressure regardless of changing flow rate and/or varying
inlet pressure, as long as the flow rate is below a preset maximum. It
also prevents excessive flow by limiting flow to a preselected maximum rate.
This valve is a hydraulically operated, pilot controlled diaphragm valve.
The pilot system includes a direct acting pressure reducing pilot and a
rate of flow differential control. The pressure reducing pilot is responsive to slight variations in downstream pressure and immediately controls the main valve to maintain the desired line pressure.
Schematic Diagram
Item Description
1Hytrol (Main Valve)
2X58A Restriction Fitting
3 CRA Pressure Reducing Control
4X52E Orifice Plate Assembly
5CDHS18 Differential Control
Optional Features
Item Description
AX46A Flow Clean Strainer
BCK2 (Isolation Valve)
CCV Flow Control (Closing)
DCheck Valves with Isolation Valve
PX141 Pressure Gauge
SCV Speed Control (Opening)
VX101 Valve Position Indicator
YX43 "Y" Strainer
Product Dimensions Data:
For the 49-01 Main Valve (100-01) dimensions, see pages 17.
For the 649-01 Main Valve (100-20) dimensions, see pages 29.
The rate of flow control responds to the differential pressure produced
across an orifice plate in the main line. Accurate control is assured as
very small changes in the controlling differential pressure produce
immediate corrective action by the main valve.
If the check feature option is added and a pressure reversal occurs,
the downstream pressure is admitted into the main valve cover chamber and the valve closes to prevent return flow.
62
Supply
Main
Meter
Cla-Val
49-01/649-01
Isolation
Valve
Flow
Typical Application
Installed where water supply to a
system must be limited to a preset
flow to prevent lowering the supply
pressure. Easily set to maintain the maximum allowable
flow rate.
Page 63
Schematic Diagram
Item Description
1Hytrol (Main Valve)
2CF1-C1 Float
Control
Optional Features
MODEL
(Sizes 1/2"- 6"Full Internal Port)
624-01
124-01
(Sizes 3"- 8"Reduced Internal Port)
Float Valve
• Accurate and Repeatable Level Control
• On-Off or Non-Modulating Action
• Fully Adjustable High and Low Level Settings
• Simple Design, Proven Reliable
• Easy Installation and Maintenance
The Cla-Val Model 124-01/624-01 Float Valve is a non-modulating valve that
accurately controls the liquid level in tanks. This valve is designed to open fully
when the liquid level reaches a pre-set low point and close drip-tight when the
level reaches a preset high point.
This is a hydraulically operated, diaphragm valve with the pilot control and float
mechanism mounted on the cover of the main valve. The float positions the pilot
control to close the valve when the float contacts the upper stop. The high and low
liquid levels are adjusted by positioning the stop collars on the float rod. The difference between high and low levels can be adjusted to as little as one inch, or to
as much as eighteen inches.
Level settings can be as much as eleven and one half feet below the valve. The
float mechanism may be located remotely from the main valve. See the technical
data sheet on Model CF1-C1 Float Control for additional information.
Note: For 8
" and Larger Float Valve Sizes use Model 124-02/624-02
SCV Speed Control (Opening)
VX101 Valve Position Indicator
Y X43 "Y" Strainer
CLA-VAL
124-01/624-01
Float Valve
Supply
Tank
Stilling Well
Product Dimensions Data:
For the 124-01 Main Valve (100-01)
dimensions, see pages 17.
For the 624-01 Main Valve (100-20)
dimensions, see pages 29.
Typical Applications
The Model 124-01/624-01 Float Valve is
commonly mounted above the high water
level in a tank. Globe pattern valves are
supplied standard with the float control
mounted on the cover as illustrated, with
a horizontal discharge. Angle valves are
configured to discharge downward.
Note:1. We recommend protecting
tubing and valve from freezing
temperatures.
2. Must be inspected
periodically
Installation
A stilling well (8" minimum diameter) must
be provided around the float. When the
valve is mounted on top of the tank roof, a
2" clearance hole should be provided for
side movement of the float rod where the
rod goes through the top of the tank.
A clear independent source of air or water
may be used to operate the valve (option
F). The pressure from this independent
source must at all times be equal to or
greater than pressure at the valve inlet.
If minimum flowing line pressure is less
than 10 psi, consult factory.
If the float control is remotely mounted
from the main valve, the control may be
installed at any elevation above the valve,
provided the flowing line pressure in psi is
greater than the vertical distance in feet
between the valve and the float control.
See the technical data sheet on Model
CF1-C1 for additional information.
63
Page 64
129-01
(Full Internal Port)
MODEL
629-01
(Reduced Internal Port)
Float Valve
Schematic Diagram
• Accurate and Repeatable Level Control
• Proportional Flow
• Reliable Hydraulic Operation
• Drip-Tight Positive Shut-Off
• Completely Automatic Operation
The Cla-Val Model 129-01/629-01 Float Valve maintains a relatively
constant level in storage tanks and reservoirs by admitting flow into the
tank in direct proportion to the flow out of the tank. It is a hydraulically
operated, pilot controlled, diaphragm valve. The rotary disc type float
operated pilot control is installed at the high liquid level in the reservoir
and is connected via tubing or pipe to the main valve. As the liquid level
changes, the float control proportionally opens or closes the main
valve, keeping the liquid level nearly constant. If the check feature
option "D" is added and a pressure reversal occurs, the downstream
pressure is admitted into the main valve cover chamber and the valve
closes to prevent return flow.
Item Description
1Hytrol (Main Valve)
2X47A Ejector
3Bell Reducer
4CFM2 Float Control
Optional Features
Item Description
AX46A Flow Cleaner Strainer
BCK2 (Isolation Valve)
CCV Flow Control (Closing)
DCheck Valves With Isolation Valve
F Independent Operating Pressure
PX141 Pressure Gauge
SCV Speed Control (Opening)
VX101 Valve Position Indicator
Typical Applications
Product Dimensions Data:
For the 129-01 Main Valve (100-01) dimensions, see pages 17.
For the 629-01 Main Valve (100-20) dimensions, see pages 29.
Piping and Tank Sizing
Install valve and control as shown in the diagram above. The float
control should be located in a still liquid surface. If it is necessary
to obtain this condition, a stilling well should be constructed.
Mount the float control on the connecting piping with the outlet
port at the desired high water level.
supply pressure (Option F) is used by the pilot control system, that
pressure must at all times be constant and equal to or greater than
the pressure at the valve inlet.
64
When a separate source of
Filter Liquid Level Control
Maintains constant level in rapid sand filter.
Usually requires the use of an independent
operating pressure as shown.
DO NOT USE FOR ON-OFF SERVICE.
Note: We recommend protecting tubing and
valve from freezing temperatures.
Page 65
Schematic Diagram
Isolation
Valve
Control Lines 3/4" Min. I.D.
Open Tank-"Air Gap" Valve
Closes on Rising Level
Balances Tank Effluent Rate
to Equal Influent Rate.
Stilling Well
Flow
CFM9
Water Level
Cla-Val 428-01/628-01
Modulating Float Valve
Item Description
1
Hytrol Main Valve
2CFM-9 Float Control
3 CK2 (Isolation Valve)
428-01
(Full Internal Port)
MODEL
628-01
(Reduced Internal Port)
Modulating Float Valve
• Accurate Level Control
• Completely Automatic Operation
• Simple Operation
• Drip-Tight Shut-Off
• Easy Installation and Maintenance
The Cla-Val Model 428-01/628-01 Float Valve modulates to maintain a
constant liquid level in a storage tank by compensating for variations in
supply or demand. It can be installed to control the flow into or out of the
tank by either closing on a rising level or opening on a rising level. This
valve is a hydraulically operated, pilot controlled diaphragm valve.
The pilot control system consists of an integral variable orifice in the main
valve cover and a remotely mounted float control. A slight change in liquid
level moves the float control. This action varies the pressure in the valve
cover, causing the main valve to seek a new position. The integral variable
orifice automatically regulates the flow into the cover chamber until the
valve reaches a position that is in direct relation to the position of the float
control.
Optional Features
Item Description
AX46A Flow Clean Strainer
D Check Valves with Isolation Valve
FIndependent Operating Pressure
PX141 Pressure Gauge
YX43 “Y” Strainer
Product Dimensions Data:
For the 428-01 Main Valve (100-32) dimensions, see pages 17.
For the 628-01 Main Valve (100-33) dimensions, see pages 29.
Installation Data
The valve may be installed in any position. The remote
float control may be mounted at any convenient location
above the liquid level. Float rods are available in
lengths from 2' to 12' in one-foot increments.
A stilling well (8" min. diameter) should be provided
around the float if the liquid surface is subject to turbulence, ripples or wind.
The float control may be installed at any elevation above
the valve providing that the amount of flowing line pressure (in psi) is equal to or greater than the vertical distance in feet between the valve and the float control.
When a separate source of supply pressure (Option F) is
used by the pilot control system, that pressure must at all
times be constant and equal to or greater than the pressure at the valve inlet.
DO NOT USE FOR ON-OFF SERVICE.
Note: We recommend protecting tubing and valve
from freezing temperatures.
Typical Applications
65
Page 66
210-01
(Full Internal Port)
MODEL
610-01
(Reduced Internal Port)
Altitude Valve For One-Way Flow
Accurate and Repeatable Level Control
•
• Drip-Tight, Positive Shut-Off
• Reliable Hydraulic Operation
• Easily Adjustable Control
• Completely Automatic Operation
The Cla-Val Model 210-01/610-01 Altitude Valve controls the high water
level in reservoirs without the need for floats or other devices. It is a nonthrottling valve that remains fully open until the shut-off point is reached.
This valve is designed for one-way flow only.
This valve is hydraulically operated and pilot controlled. The pilot control
operates on the differential in forces between a spring load and the water
level in the reservoir. The desired high water level is set by adjusting the
spring force. The pilot control measures the reservoir head through a
customer supplied sensing line* connected directly to the reservoir.
This valve can also be furnished with auxiliary controls to meet the need
for multiple functions, such as: pressure sustaining, pressure reduction,
Schematic Diagram
Item Description
1Hytrol (Main Valve)
2CDS6A Altitude Control
3X101 Valve Position Indicator
4Bell Reducer
5CV Flow Control (Closing)
rate of flow control, solenoid override, etc.
If the check feature option is added and a pressure reversal occurs, the
downstream pressure is admitted into the main valve cover chamber and
the valve closes to prevent return flow.
RReservoir Gauge with Tester
SCV Flow Control (Opening)
YX43 "Y" Strainer
Typical Applications
Used on reservoirs where the water is withdrawn
through a separate line or through a bypass equipped
with a check valve. The valve opens to refill the reservoir when the water lowers below the shut-off level. For
more information see data sheet E-CDS6A.
*Note: The reservoir pressure sensing line should be
3
⁄4
" minimum I.D. installed with a 2° slope from
the valve to the reservoir to avoid air pockets.
Note: We recommend protecting tubing and valve
from freezing temperatures.
Product Dimensions Data:
For the 210-01 Main Valve (100-01) dimensions, see pages 17.
For the 610-01 Main Valve (100-20) dimensions, see pages 29.
66
Note: When "D" check feature is ordered, the "H" feature is required.
Page 67
Schematic Diagram
Item Description
1Hytrol (Main Valve)
2CDS6A Altitude Control
3X101 Valve Position Indicator
4Bell Reducer
5CRL Pressure Relief Valve
6.100-01 Hytrol (Reverse Flow)
7X42N-3 Strainer
210-09
(Full Internal Port)
MODEL
610-09
(Reduced Internal Port)
Combination Altitude and
Back Pressure Valve
• Accurate and Repeatable Level Control
• Prevents Low Supply Pressure When Filling
• Drip Tight Positive Shut-Off
• Reliable Hydraulic Operation
• Easily Adjustable Controls
The Cla-Val Model 210-09/610-09 Combination Altitude and Back
Pressure Valve controls the high water level in reservoirs without the
need for floats or other devices. The valve modulates to maintain
upstream pressure within close limits to prevent over drawing system
supply while filling reservoir. When the shut-off point of the hydraulic pilot
control is reached, the valve closes smoothly without surges. This valve
is designed for one-way flow only.
The 210-09/610-09 Valve is hydraulically-operated and pilot-controlled
for optimum automatic level and pressure control. The level pilot control
operates on a differential in forces between spring load and reservoir
head level. When force of spring is overcome by force of reservoir head,
the pilot shifts and closes main valve. Desired high water level is set by
adjusting spring force. The level pilot control measures the reservoir
head through a customer supplied separate sensing line* connected
directly to reservoir. The pressure sustaining pilot control senses
upstream system pressure and modulates the main valve more open on
a rise in pressure to maintain a minimum inlet pressure when filling reservoir.
The valve can also be furnished with auxiliary controls to meet the need
for additional functions, such as: rate of flow control, pressure reduction,
solenoid override, etc. If the check feature option is added and a pressure reversal occurs, reservoir pressure is admitted into main valve cover
chamber and valve closes to prevent return flow.
Optional Features
Item Description
BCK2 (Isolation Valve)
DCheck Valve with Isolation Valve
F Remote Pilot Sensing
RReservoir Gauge with Tester
SCV Flow Control (Opening)
Product Dimensions Data:
For the 210-09 Main Valve (100-01) dimensions, see pages 17.
For the 610-09 Main Valve (100-20) dimensions, see pages 29.
Typical Applications
Used on reservoirs where water is withdrawn through a separate line or through a
bypass equipped with a check valve. Valve closes at the desired high water level
and reopens for filling when reservoir head lowers below the shut off level. Valve
controls minimum supply pressure to keep from overdrawing supply while filling
reservoir. Water in excess of system pressure flows to reservoir at controlled rate.
For more information see data sheet E-CDS6A.
3
⁄4
*Note: The reservoir pressure sensing line should be
a 2° slope from the valve to the reservoir to avoid air pockets.
Note: We recommend protecting tubing and valve from freezing temperatures.
" minimum I.D. installed with
67
Page 68
To Elevated
Storage
Shutoff Cock
Isolation Valve
Supply Source
Distribution
CLA-VAL
210-16/610-16
Alititude Valve
Sensing Line
(Customer Supplied)
210-16
R(Full Internal Port)
MODEL
610-16
(Reduced Internal Port)
Altitude Valve For Two-Way Flow
• Accurate and Repeatable Level Control
• Drip-Tight Positive Shut-Off
• Reliable Hydraulic Operation
• Easily Adjustable Control
• Completely Automatic Operation
The Cla-Val Model 210-16/610-16 Altitude Valve controls the high water
level in reservoirs without the need for floats or other devices. It is a nonthrottling valve that remains fully open until the shut off point is reached.
This valve closes at a high water level, and opens for return flow when
the pressure at the valve inlet is less than the reservoir pressure.
This valve is hydraulically operated and pilot controlled. The pilot control
operates on the differential in forces between a spring load and the water
level in the reservoir. When the force of the spring is overcome by the
force of the reservoir head, the pilot closes the main valve. The desired
high water level is set by adjusting the spring force. The pilot control
measures the reservoir head through a customer supplied sensing line*
Schematic Diagram
Item Description
1Hytrol (Main Valve)
2CDS6A Altitude Control
3X101 Valve Position Indicator
4Bell Reducer
5Check Valve
6CV Flow Control (Closing)
7CK2 Isolation Valve
connected directly to the reservoir.
This valve can also be furnished with auxiliary controls to meet the need
for multiple functions, such as: pressure sustaining, pressure reduction,
rate of flow control, solenoid override, etc.
RReservoir Gauge with Tester
SCV Flow Control (Opening)
Y X43 "Y" Strainer
Typical Applications
Used on reservoirs where water is withdrawn through the
Altitude Valve. The valve closes at the high water level and
opens for return flow when the pressure at the valve inlet
lowers below the reservoir pressure.
For more information see data sheet E-CDS6A
3
*Note: The reservoir pressure sensing line should be
We recommend protecting tubing and valve from freezing temperatures.
Product Dimensions Data:
For the 210-16 Main Valve (100-01) dimensions, see pages 17.
For the 610-16 Main Valve (100-20) dimensions, see pages 29.
68
minimum I.D. installed with a 2° slope from valve
to reservoir to avoid air pockets.
⁄4"
Page 69
Schematic Diagram
Item Description
1Hytrol (Main Valve)
2CDS6A Altitude Control
3X101 Valve Position Indicator
4Bell Reducer
5102C-3H Three-way Valve
6CS3 Solenoid Control
7CV Flow Control (Closing)
8Union
Optional Features
210-17
(Full Internal Port)
MODEL
610-17
(Reduced Internal Port)
Altitude and Solenoid Shut-Off Valve
• Accurate and Repeatable Level Control
• Easy Interface With Remote Control Systems
• Drip Tight Positive Shut Off
• Reliable Hydraulic Operation
• Easily Adjustable Control
The Cla-Val Model 210-17/610-17 Altitude Valve controls the high water
level in reservoirs with out the need for floats or other devices. It is a
non-throttling valve that remains fully open until the solenoid is activated or the shut-off point of the hydraulic pilot control is reached. The
valve closes at high water level and opens for return flow when the
pressure at the valve inlet is less than reservoir pressure.
This valve is hydraulically-operated and pilot-controlled. The level pilot
control operates on the differential in forces between a spring load and
reservoir head level. When force of the spring is overcome by the force
of reservoir head, the pilot shifts and closes main valve. Desired high
water level is set by adjusting the spring force. The pilot control measures the reservoir head through a customer supplied separate sensing
line* connected directly to the reservoir. A three-way solenoid control
and a high-capacity three-way pilot control valve provide override shutoff of valve from a remote location, such as a SCADA control system. It
is furnished either normally open (de-energize solenoid to open) or normally closed (energize solenoid to open).
The valve can also be furnished with auxiliary controls to meet the need
for additional functions, such as: pressure sustaining, rate of flow control, pressure reduction, etc.
FIndependent Operation Pressure
HDry Drain
RReservoir Gauge with Tester
PX141 Pressure Gauge
SCV Flow Control (Opening)
Y X43 "Y" Strainer
Product Dimensions Data:
For the 210-17 Main Valve (100-01) dimensions, see pages 17.
For the 610-17 Main Valve (100-20) dimensions, see pages 29.
Typical Applications
Used on reservoirs where water is supplied and withdrawn through the Altitude Valve.
Valve closes at the desired high water level controlled remotely via SCADA system
signal to solenoid or automatically with preset level control (usually set higher). Also,
valve automatically opens for return flow when the pressure at the valve inlet lowers
below the reservoir head pressure. For more information see data sheet E-CDS6A.
3
*Note: The reservoir pressure sensing line should be
2° slope from valve to reservoir to avoid air pockets.
Note: We recommend protecting tubing and valve from freezing temperatures.
⁄4” minimum I.D. installed with a
69
Page 70
131 Series
(Full Internal Port)
MODEL
631 Series
(Reduced Internal Port)
Electronic Control Valves
Model 131-01/631-01
• Simple Proven Design
• Quality Solenoid Pilot Controls
• Ideal For SCADA Systems
• Multi-Function Capability; Hydraulic Backup
• Security System to Prevents Unauthorized Changes
• Easy to Maintain
The Cla-Val Series 131/631 Electronic Control Valves are designed
specifically for applications where remote control of the valve is preferred.
It is a hydraulically operated, pilot controlled, diaphragm valve. The solenoid pilot controls are actuated by electrical signals from the optional
131VC-1 Electronic Valve Controller. The solenoid pilots either add or
relieve line pressure from the cover chamber of the valve, causing it to
open or close as directed by the electronic controller.
Series 131/631 Electronic Control valves can be configured to perform a
wide range of functions, such as; pressure reducing, pressure sustaining,
flow control, or level control. The electric controls can also be combined
with hydraulic controls to create dual function, or fail-safe capability.
Schematic Diagram
Item Description
1Hytrol (Main Valve)
2CS2 Solenoid Control
3CK2 (Solenoid By-Pass)
Optional Features
The basic 131-01/631-01 Electronic Control Valve (Schematic shown
below) includes the main valve and solenoid pilot controls. Optional features include the 131VC-1 Electronic Valve Controller and the X117D
Valve Position Transmitter. If the check feature option is added, and a
pressure reversal occurs, the downstream pressure is admitted into the
cover, closing the valve.
Item Description
AX46A Flow Clean Strainer
BCK2 (Isolation Valve)
CCV Flow Control (Closing)
DCheck Valves With Isolation Valve
For the 131 Series Main Valve dimensions, see pages 17.
For the 631 Series Main Valve dimensions, see pages 29.
Typical Applications
This brochure contains typical application that are modifications
to the basic 131-01/631-01 Electronic Control Valve shown here.
It is typical installed in a pipeline with a 131VC Series Controller
that receives a process variable signal that is compared to setpoint and adjusts the main valve's capacity until the signals
match. There are many different variations not shown in this
brochure. Contact us with your specific application and we will
provide a field proven solution.
A X46A Flow Clean Strainer
B CK2 Cock (Isolation Valve)
C CV Flow Control (Closing)
D Check Valves with Isolation Valve
E X117D/X117E Position Transmitter
F Independent Operating Pressure
H Atmospheric Drain
N Electronic Controller
P X141 Pressure Gauge
S CV Flow Control (Opening)
Y X43 "Y" Strainer
131-06/631-06
Combination Electronic
Control And High Level
Shut-Off Valve
This valve is used in reservoir applications where the filling or draining rate is
controlled and modulated by the electronic controller. Flow pressure and valve
position can also be controlled. Should
the liquid in the reservoir reach a high
level, the hydraulic altitude control automatically overrides the electronic control
and closes the valve. The altitude control
can be adjusted to close the valve over a
wide range of settings. The optional
check feature will close the valve if there
is a pressure reversal in the line.
131-09/631-09
Modulating Float Valve
With Solenoid Lockout
of Float Control
and Electronic Positioning
The electronic controller modulates the
flow through this valve to control liquid
level in a tank. If power failure should
occur, the third solenoid shifts, and the
float control will allow the valve to modulate using hydraulic line pressure. The
131VC Electronic Valve Controller and
X117D Valve Position Transmitter are
used in combination with an electronic
level sensing device to provide modulating flow control of
the valve.
3
CS3
2
4A
2
D1
Y
B
CS3
7A
3
6A
S
E
4B
B
Schematic Diagram
Item Description
1Hytrol (Main Valve)
2X74B-3 Stem Valve
3CFM-7 Float Pilot
4100-01 Hytrol (Reverse Flow)
5CS3 Solenoid Control
6CS2 Solenoid Control
7CK2 Solenoid By-Pass
Optional Features
Item Description
A X46A Flow Clean Strainer
B CK2 Cock (Isolation Valve)
E X117D/X117E Position Transmitter
F Independent Operating Pressure
N Electronic Controller
P X141 Pressure Gauge
Y X43 "Y" Strainer
Schematic Diagram
CS2
N
5
6B
Item Description
1
Hytrol (Main Valve)
2 X58C Restriction Assembly
3 CS3 Solenoid Control
4 100-01 Hytrol (Reverse Flow)
5 CRD Pressure Reducing Control
6 CK2 Solenoid Control
7 CK2 Solenoid Bypass
Optional Features
7B
D2
D3
OUTLET INLET
Item Description
B
A X46A Flow Clean Strainer
B CK2 Isolation Valve
C CV Flow Control ( Closing)
D Check Valves Isolation Valve
E X117D/X117E Position Transmitter
N Electronic Controller (Single)
P X141 Pressure Gauge
S CV Flow Control (Opening)
Y X43 "Y" Strainer
131-18/631-18
Electronic Control Valve
Equipped with Hydraulic
Pressure Reducing Solenoid
Selected
Flow, pressure, level or valve position is
normally controlled by the electronic controller that operates two solenoids to
modulate the valve to maintain the
process variable. Should a power failure
occur, a parallel hydraulically operated
pressure reducing pilot system takes
control of the valve maintaining a preset
outlet pressure. When power is restored,
the valve automatically reverts back to
the electronic mode. The optional check
feature automatically will close the valve
if a pressure reversal occurs in the
pipeline.
71
Page 72
131-22/631-22
Electronic Control Valve
(Power Fail Closed)
Flow, pressure, level or valve position
is normally controlled by the electronic controller that operates two solenoids to modulate the valve to maintain the process variable. Should a
power failure occur, the valve can be
configured to go open or closed. The
optional check feature automatically
will close the valve if a pressure
reversal occurs in the pipeline.
Schematic Diagram
Item Description
1100-01 Hytrol (Main Valve)
2CS2 Solenoid Control
3CK2 (Solenoid By-Pass)
Optional Features
Item Description
A X46A Flow Clean Strainer
B CK2 Isolation Valve
C CV Flow Control (Closing)
D Check Valves with Isolation valve
E X117D/X117E Position Transmitter
F Independent Operating Pressure
H Atmospheric Drain
N Electronic Controller
P X141 Pressure Gauge
S CV Flow Control (Opening)
Y X43 "Y" Strainer
N
N
131-EJ/631-EJ
Electronic Interface Control
with Pressure Sustaining
Feature, Hydraulically
Operated
Flow, pressure, level or valve position is
normally controlled by the electronic
controller that operates two solenoids to
modulate the valve to maintain the
process variable. Should a power failure
occur, a parallel hydraulically operated
pressure sustaining pilot system takes
control of the valve limiting the minimum
inlet pressure. When power is restored,
the valve automatically reverts back to
the electronic mode. The optional checkfeature automatically will close the valve
if a pressure reversal occurs in the
pipeline
Schematic Diagram
Item Description
1
Hytrol (Main Valve)
2 CS2 Solenoid Control
3 CK2 Solenoid By-Pass
4 CRL5 Pressure Relief Control
5 X58C Restriction Assembly
Optional Features
Item Description
A X46A Flow Clean Strainer
B CK2 Isolation Valve
C CV Flow Control ( Closing)
D Check Valves with Isolation Valve
E X117D/X117E Position Transmitter
F Independent Operating Pressure
N Electronic Controller (Single)
P X141 Pressure Gauge
S CV Flow Control (Opening)
Y X43 "Y" Strainer
Schematic Diagram
Item Description
1
Hytrol (Main Valve)
2 CS2 Solenoid Control
3 CK2 Solenoid By-Pass
4 CRA Pressure Reducing Control
5 X58C Restriction Assembly
Optional Features
Item Description
A X46A Flow Clean Strainer
B CK2 Isolation Valve
C CV Flow Control ( Closing)
D Check Valves with Isolation Valve
E X117D/X117E Position Transmitter
F Independent Operating Pressure
H Atmospheric Drain
N Electronic Controller (Single)
P X141 Pressure Gauge
S CV Flow Control (Opening)
Y X43 "Y" Strainer
131-CW/631-CW
Electronic Interface Control
with Pressure Reducing
Feature, Hydraulically
Operated
Flow, pressure, level or valve position is
normally controlled by the electronic
controller that operates two solenoids to
modulate the valve to maintain the
process variable. Should a power failure
occur, a parallel hydraulically operated
pressure reducing pilot system takes
control of the valve limiting the maximum
outlet pressure. When power is restored,
the valve automatically reverts back to
the electronic mode. The optional check
feature automatically will close the valve
if a pressure reversal occurs in the
pipeline
72
Page 73
Optional Remote Control
Modem
Modem
Computer
131-01
Control Valve
Signal Transmitter
4-20 mA
SERIES
131VC
Electronic Control Systems
• Electronic Control of Hydraulic
Cla-Val Valves
• Programmable Monitoring and
Control of Flow, Pressure, Delta P,
Level or Valve Position
• Accurate Control of Valve Speed and
Response
• Remote Set-Point Control
• Security System - Prevents
Unauthorized Changes
• Control Backup Systems in the
Event of an Emergency
Electronic Control of Hydraulic Valves
The 131VC-1 Electronic Control System is designed to work in
conjunction with Cla-Val 131 Series hydraulic control valves—
a combination that takes advantage of the simplicity of
hydraulic valve operation and the control possibilities available
with electronics.
The 131VC-1 Electronic Control System receives transmitted
signals and activates dual solenoid pilots on the hydraulic control valve. These pilots direct hydraulic pressure within the system to position and regulate the valve. By continuously comparing system conditions to the programmed set-point, the system is automatically maintained at the desired value.
Additional important control features, unique to this type of
valve control, are offered as standard. They are designed for
user friendly operation and system safety and are addressed in
this brochure.
The Cla-Val 131VC-1 Electronic Control System is
designed to achieve unprecedented valve control
accuracy and stability. Ideal for remote valve control,
the 131VC-1 Electronic Control System provides the
interface between SCADA system computers and
hydraulic control valves sites.
Key Advantages
• Proven reliable hydraulic control valve
• Low electric power requirement
• Solid state electronic components
• No motors, bearings, bushings or packings to
wear out or leak
We Not Only Sell Valves—
We Provide Solutions
73
Page 74
How it Works
131-01 Valve
Transmitter
Dead
Band
Set-Point Command
131-01 Valve
Transmitter
Transmitter
Feedback
Signal
Deviation
Transmitter
131-01 Valve
Devitation
Transmitte
Feedback
Signal
1. Set-Point Command
Set-point command is received from a
remote location or entered via the key
pad into the Electronic Valve Controller.
2. Feedback and Comparison
The Electronic Valve Controller compares
the feedback signal from the transmitter
to the set-point. If the deviation exceeds
the deadband, the valve control system is
activated.
3. Valve Actuation
The Electronic Valve Controller actuates the solenoid controls, causing the
valve to modulate as needed to regain
the set-point condition.
Keypad & Display
Display
The 131VC-1 has been engineered to be the industryʼs most
user friendly controller. With three digital displays areas (two
offering up to 9 characters of true alphanumeric), the 131VC-1
effectively eliminates cryptic messages, sub-routines and loops
that could confuse even the most experienced operator. The
bright, crisp display is vacuum fluorescent, and offers much
better readability than any other display technology. Additional
operator-friendly features include: custom programmable
alarm messages, illuminated keys, and an easy-to-use menu
system.
Status Indicators - Four status indicators show the controllerʼs
operating status at all times:
Manual Key Light: For manual control.
Set-point Key Light: For indication of remote control.
Output Indicator: “OUT” and indicator lights illuminate
when either output 1 or 2 are on.
Alarm Indicator: “ALM” and indicator lights illuminate
when either output 1 or 2 are on.
Keys Pads: All menu entry, configuration, tuning and set-point
controls is entered through rugged backlit rubber keys. A simple
menu system prompts the operator, step by step, through all
procedures. Security system prevents unauthorized changes to
all values.
The Cla-Val Model 133-01/633-01 Metering Valve is a completely
self contained valve and control system that accurately meters
and/or controls flow rate when used on valves with pressure differentials of less than 100 psid.
Using a 131VC-3T Cla-Val Microprocessor, data from valve mounted differential pressure and position transmitters are assimilated into a proprietary
algorithm program that is based on valve size and configuration to arrive
at a flow measurement. This information is used for retransmission
and/or compared with a local or remote set-point for valve flow control.
The 133-01 Control System can also be installed on new or existing
hydraulic pilot control valves such as: pressure reducing, pressure
sustaining, flow limiting and level control to transmit flow rate without
disturbing the valve's primary hydraulic function(s). Specify Kit 133-01
for these applications. Consult factory.
Prevents Unauthorized Changes
Optional Features
Item Description
AX46A Flow Clean Strainer
BCK2 Isolation Valve
CCV Flow Control (Closing)
DCheck Feature
FIndependent Operation Pressure
HAtmospheric Drain
P
SCV Flow Control (Opening)
YX43 "Y" Strainer
X141 Pressure Gauge
Typical Applications
The Model 133-01/633-01 Metering and Flow Rate Controller is typically installed in
a fluid delivery system where the flow rate is measured and changed from a remote
location such as a SCADA system.
Main Transmission
Line
Product Dimensions Data:
For the 133-01 Main Valve (100-01) dimensions, see pages 17.
For the 633-01 Main Valve (100-20) dimensions, see pages 29.
For all applications, specify voltage, minimum/maximum pressures and
flow rates, valve size, pressure class and optional features. Consult your
local representative or the Factory for engineering assistance and valve
selection.
Please refer to the 131VC “Electronic Control Systems”
brochure for specific information regarding valve theory of
operation, standard and optional features, control parameters
and electrical component specifications.
131VC-3T Electronic
133-01/633-01
Metering & Flow Rate Controller
Valve Controller
131VC-3T
To Optional Remote
Computer Control (Local)
Optional Remote Control
Optional Remote Control
Modem
Computer
Modem
Computer
75
Page 76
Improved Filter Backwashing
Advanced Cla-Val Electronic Backwash Valves with metering capability
All water treatment plant filters must be regularly backwashed to clear away impurities left by raw water and to ensure
optimum filtration results. Conventional systems, utilizing a combination of devices, often succumb to the ravages of
cavitation caused by high system pressure and pose space challenges because of the long runs of piping required
between components to guarantee proper function.
Cla-Val electronic metering valves equipped with KO anti-cavitation trim can handle the pressure and can perform the
backwashing function without external metering or control components, greatly reducing space requirements and
installation/maintenance costs.
This multi-functional control valve cost effectively meets the following operational requirements:
• Low-rate wash• High-rate wash
• Remote valve closure• Flow metering and totalizing
• Hydraulic pressure override• Can interface with SCADA systems
In addition to being available on new valves, any existing, installed Cla-Val Pressure Reducing Valve can be field retrofitted with the Model 133 electronic control and metering kit to perform backwashing at peak efficiency.
76
Conventional
Backwash System
Advanced Electronic
Backwash System
visit www.cla-val.com
and click the “Backwash” Quick Link
Page 77
138-01
(Sizes 3"- 12")
(Full Internal Port)
MODEL
638-01
(Sizes 4"- 16")
(Reduced Internal Port)
Electronic Actuated Positioning Control Valve
Product Features and Benefits
•
Precise Valve Position Control
•
Completely Self-contained
•
High Energy Efficiency with Low Operation Friction
•
Direct Control of Valve Opening and Closing
•
Combines with Pressure, Flow or Level Control
•
Ideal for SCADA Control
• Easy adjustment and maintenance
• Fully Supported Frictionless Diaphragm for troublefree service and low maintenance
Product Enhancements
Get more from your valve by adding any of the
following optional features.
• KO Anti-Cavitation Trim
• Epoxy Coating
• X141 Pressure Gauge
• Stainless Steel Tubing and Fittings
• X43H-Style Strainer
• Stem Upgrade to Delrin® or Dura-Kleen®
Schematic Diagram
Item Description
1Hytrol (Main Valve)
2X58A Restriction Fitting
3CS3 Solenoid Control
4100-01 Auxiliary Hytrol (Reverse Flow)
5CPC Electronic Actuator Positioning Control
The Cla-Val Model 138-01/638-01 Electronic Actuated Positioning
Control Valve regulates flow or pressure or other system parameter
by changing valve position from full open to shut-off. Exact valve
position for large-scale waterworks or industrial applications is
achieved with CPC pilot control that consists of electronic actuator
and hydraulic pilot sub-assembly. The CPC controls valve position
by limiting valve opening using hydraulically-assisted technology.
The pilot sub-assembly has two calibrated orifices that are positioned proportional to valve position to vary main valve control
chamber operating pressure. The CPC actuator creates slight
changes in orifice position and in turn operating pressure hydraulically changes valve position. The pilot sub-assembly requires very
little torque and is virtually frictionless for long service life. The actuator features high repeatable-accuracy brush-less motor technology and low energy consumption. Precision, no-contact hall-effect
internal position sensor assures accuracy and durability. The CPC
has factory pre-configured parameters of full valve stroke, preset
rotation speed, and default setting on loss of set point. Actuator
parameters can be changed using free downloadable software and
special USB cable. Valve fully-closed position is assured by signaling solenoid to lock control pressure in main valve operating chamber when valve is very close to seat (adjustable). Operating on 24
VDC and with customer supplied battery backup, the 138-01/63801 valve can eliminate downtime due to power failures.
77
Page 78
Model 138-01 Electronic Position Process Control Valve
RTU
CPC
MODEL
Electronic Actuated Positioning
Pilot Control
Precise Valve Position Control
•
Completely Self-contained
•
High Energy Efficiency with Low Operation Friction
•
Direct Control of Valve Opening and Closing
•
Combines with Pressure, Flow or Level Control
•
Ideal for SCADA Control
•
Optional 133VF Valve-Mounted Flow Monitoring
•
The Cla-Val CPC Electronic Actuated Positioning Control regulates
flow through Cla-Val Main Valves by changing valve position from full
open to shut-off. The CPC consists of electronic actuator and
hydraulic pilot sub-assembly. The CPC controls valve position by
hydraulically limiting valve opening with hydraulically-assisted pilot
modulating main valve. The pilot sub-assembly has two calibrated orifices that are positioned proportional to valve position to vary Cla-Val
basic valve control chamber operating pressure. The CPC actuator
creates slight changes in orifice position and in turn operating pressure
hydraulically changes valve position. The pilot sub-assembly requires
very little torque and is virtually frictionless for long service life. The
actuator features high repeatable-accuracy brush-less motor technology and low energy consumption. Precision, no-contact hall-effect
internal position sensor assures durability. The CPC is factory preconfigured to full stroke, preset rotation speed, and default setting on
loss of set point. Actuator parameters can be changed using free
downloadable software and special USB cable. Valve fully-closed
position is assured by signaling solenoid to lock control pressure in
main valve operating chamber when valve is very close to seat
(adjustable). Operating on 24 VDC and with customer supplied battery
backup, the CPC can eliminate downtime due to power failures.
Typical Applications
78
Note: When retrofitting an existing valve, high capacity cover bearing
must be installed. This requires removing the valve cover. Consult
factory for details.
The CPC Electronic Actuated Positioning Control is used with
138 Series Electronic Actuated Control Valves in high rise
building chill water circulating system applications. Building
SCADA control systems often use multiple circulating system
parameters to control valve position for optimizing water circulating system. Also, 138 Series valves are used in large water
transmission systems where several system parameters must
be controlled by one valve. SCADA system monitors various
water distribution system parameters, such as downstream
pressure, upstream pressure, tank level, time of day, flow rates
in several zones, etc., and then remotely changes 138 Series
valve position to meet several system requirements as all
parameters continue changing.
Cla-Val 138 Series valves can have optional 133VF
Flow Metering System installed for flow rate moni-
toring. Consult factory for details.
Page 79
MODEL
Q = C
v DP / SG
133VF
Valve Flow Measurement
133VF Retrofittable Metering
Kit Option
131VF Flow Module
X117 Series
X117E
Position
Transmitter
X117D
DP Differential
Pressure Transmitter
The 131VF flow module accepts 4-20 mA analog signals of
valve differential pressure and valve position to determine the
flow rate.
The partially-open valve Cv is derived from valve position then
used to calculate flow rate with formula shown below:
Where:
Q = flow (gpm)
DP = differential pressure (psi)
SG = specific gravity of fluid (water = 1.0)
Automatic Control Valve
with Metering Kit
Installed
• System accurately measures flow rate
• No external meter is required
• For new installations and retrofitting
existing valves
• Completely self-contained, requiring
12 to 24 VDC power
• Simple integration
The Cla-Val 133VF Flow Metering System is an effective
means of obtaining real-time flow data from a Cla-Val
control valve regardless of valve function and without an
external flow device. Now all Cla-Val control valves in a
water distribution system can be economically integrated
into SCADA control or pressure and flow management
strategies.
The 133VF System is completely self-contained and when
factory installed on new Cla-Val automatic control valves
or field installed on existing valves, accurately measures
flow rate and transmits it as a 4 - 20 mA analog signal. It
can be used on virtually all valve sizes from two through
twenty-four inch and is typically used at pressure reducing, back pressure, flow limiting, and level control valve
stations.
The system features the “heart” of the 133-01 Flow
Metering Control Valve technology and adapts it for single-valve flow monitoring-only applications. The 133VF
System major components are an X117D valve position
transmitter, a differential or inlet and outlet pressure
transmitters and a 131VF flow calculating module. All
components are 24 VDC powered and weather protected to IP-68 submersible rating. The 131VF module, with
standard DIN rail mounting, contains powerful mini-computer technology for calculating valve flow based on
inputs from the sensors and using the appropriate flow
curve for a particular Cla-Val valve. For increased accuracy the 131VF module uses third-party certified flow
curves tested for this particular metering application.
Valve differential pressure measurement can be located
either at the valve inlet and outlet bosses or on pipe
adjacent to the valve providing installation versatility in
all applications and operating conditions.
For applications requiring flow measurement and remote set point
control, see 133-01 Metering Valve catalog data sheet.
BCK2 (Isolation Valve)
CCV Flow Control (Closing)
DCheck Valves with Isolation Valve
PX141 Pressure Gauge
SCV Flow Control (Opening)
VX101 Valve Position Indicator
Y X43 "Y" Strainer
Simplified Remote Valve Set-Point Control
•
12 to 24 VDC Input Power
•
Isolated Input
•
Reverse Polarity Protection
•
Reliable Hydraulic Operation
•
IP-68 (Submersible)
•
The Cla-Val Model 340-02/3640-02 Electronic Actuated Rate of Flow Control
Valve combines the precise control of field proven Cla-Val hydraulic pilots and
simple remote valve control. The Model 340-02/3640-02 valve controls flow by
limiting flow to a preselected maximum rate (within a four to one ratio), regardless
of changing line pressure. It is a hydraulically operated, pilot controlled,
diaphragm actuated control valve. The valve uses a CDHS-33 actuated pilot control, consisting of a hydraulic pilot and integral controller that accepts a remote setpoint command input and makes set-point adjustments to the pilot.
The recommended control method is simple remote set point change from an
RTU (Remote Telemetry Unit) to the CDHS-33 where the 4-20 mA command
signal is ranged to specific flow range of orifice plate and hydraulic pilot control
components. Very accurate control can be achieved when span does not
exceed 4:1 turndown. Since the CDHS-33 is pre-ranged to full spring range,
some on-site calibration may be necessary when this control method is used.
Free downloadable software is available from Cla-Val website for this purpose.
The CDHS-33 can also accommodate control systems where the RTU compares flow rate transmitter signal to the remote set point command signal. The
RTU adjusts the CDHS-33 with 4-20 mA command signal containing an adequate deadband to prevent actuator dithering after the two signals agree.
Internal continuous electronic monitoring of actuator position results in virtually
instantaneous position change with no backlash or dithering when control signal is changed. In the event of a power or control input failure, the CDHS-33
pilot remains in hydraulic control virtually assuring system stability under changing conditions. If check feature (“D”) is added, and pressure reversal occurs,
the valve closes to prevent return flow.
Typical Applications
The valve is designed to be used with supervisor control systems (SCADA),
having an isolated remote analog set-point output and a process variable
flow transmitter input. It is also an effective solution for lowering costs associated with “confined space” requirements by eliminating the need for entry
into valve structure for set-point adjustments and system information.
Additional pilot controls, hydraulic and/or electronic, can be easily added to
perform multiple control functions to fit exact system requirements.
Product Dimensions Data:
For the 340-02 Main Valve (100-01) dimensions, see pages 17.
For the 3640-02 Main Valve (100-20) dimensions, see pages 29.
80
Page 81
MODELS
CDHS-33
Electronic Actuated
Rate of Flow Pilot Control
Simplified Remote Valve Set-Point Control
•
12-24VDC Input Power
•
Isolated Input
•
Reverse Polarity Protection
•
Reliable Hydraulic Operation
•
IP-68 Submersible
•
The Cla-Val Model CDHS-33 Electronic Actuated Differential Pressure
Pilot Control provides remote set-point adjustment and accurate differential pressure control for rate of flow control on Cla-Val 340 Series
Control Valves. Remote set-point command signals can be from any
SCADA-type control system using analog 4-20 mA signal or by contact closure for cc/ccw rotation. A precision orifice plate installed with
valve creates differential pressure used for rate of flow control by the
CDHS-33. Operating on 12 to 24 VDC and consuming very little
power, it is an ideal control system for remote valve sites that may
even be solar powered. Existing manually-set Cla-Val 40 Series
Rate-of-Flow control valves can be retrofitted with CDHS-33 to add
remote set-point control. Verification of differential pressure and corresponding flow rate may be sent to SCADA system from customer
supplied differential pressure sensor attached to orifice plate.
The CDHS-33 consists of a hydraulic pilot and integral controller that
accepts a 4-20 mA remote set-point and positions the pilot to maintain
a maximum pressure differential at orifice plate and corresponding
flow rate within preset limits. Pressure differential settings are linear
between these settings. Special USB connector cable and free downloadable software can be used to change built-in electronic range limits for differential pressure and corresponding flow rate. Continuous
internal monitoring of actuator position results in smooth transitions
between pilot set-points with no backlash or dithering. When power
or control input fail, the CDHS-33 pilot remains in automatic hydraulic
control assuring system stability under all conditions.
Typical Applications
The CDHS-33 Is installed on Cla-Val 340 Series valves that
maintain flow rate and require this flow to be changed from a
remote location. It is also an effective solution for lowering costs
associated with "confined space" requirements by eliminating
the need for entry in valve structure for set-point adjustment.
Additional pilot controls, hydraulic and/or electronic, are also
available to perform multiple functions to fit exact system
requirements.
81
Page 82
350-02
(Full Internal Port)
MODEL
3650-02
(Reduced Internal Port)
Electronic Actuated
Pressure Sustaining Control Valve
Simplified Remote Valve Set-Point Control
•
12 to 24 VDC Input Power
•
Isolated Input
•
Reverse Polarity Protection
•
Reliable Hydraulic Operation
•
IP-68 (Submersible)
•
The Cla-Val Model 350-02/3650-02 Electronic Actuated Pressure
Sustaining Control Valve combines precise control of field proven Cla-Val
hydraulic pilots and simple, remote valve control. The Model 35002/3650-02 is a hydraulically operated, pilot controlled, modulating valve
designed to maintain constant upstream pressure within close limits. This
valve can be used for pressure sustaining, back pressure or unloading
functions in a by-pass system. The valve uses a CRL-33 pilot control,
consisting of a hydraulic pilot and integral controller, that accepts a remote
set-point command input and makes set-point adjustments to the pilot.
BCK2 (Isolation Valve)
DCheck Valves with Isolation Valve
FRemote Pilot Sensing
H Drain to Atmosphere
PX141 Pressure Gauge
SCV Flow Control (Opening)
VX101 Valve Position Indicator
The recommended control method is simple remote set point change from
an RTU (Remote Telemetry Unit) to the CRL-33 where the 4-20 mA command signal is ranged to specific pressure range. Very accurate control
can be achieved when span does not exceed 100 psi. Since the CRL-33
is pre-ranged to the full spring range, some on-site calibration may be necessary when this control method is used. Free downloadable software is
available from the Cla-Val website for this purpose. The CRL-33 can also
accommodate control systems where the RTU compares pressure transmitter signal to the remote set point command signal. The RTU adjusts
the CRL-33 with 4-20 mA command signal containing an adequate deadband to prevent actuator dithering after the two signals agree.
Internal continuous electronic monitoring of actuator position results in virtually instantaneous position change with no backlash or dithering when
control signal is changed. In the event of a power or control input failure,
the CRL-33 pilot remains in hydraulic control virtually assuring system stability under changing conditions. If check feature ("D") is added, and pressure reversal occurs, the valve closes to prevent return flow.
Product Dimensions Data:
For the 350-02 Main Valve (100-01) dimensions, see pages 17.
For the 3560-02 Main Valve (100-20) dimensions, see pages 29.
82
Typical Applications
The valve is designed to be used with supervisory control systems (SCADA),
having remote analog set-point output and process variable upstream pressure
input. It is also an effective solution for lowering costs associated with “confined
space” requirements by eliminating need for entry into valve structure for setpoint adjustment.
Additional pilot controls, hydraulic and/or electronic, can be easily added to perform multiple control functions to fit exact system requirements.
Page 83
MODELS
CRL-33
Electronic Actuated
Pressure Sustaining Pilot Control
Simplified Remote Valve Set-Point Control
•
12-24VDC Input Power
•
Isolated Input
•
Reverse Polarity Protection
•
Reliable Hydraulic Operation
•
IP-68 Submersible
•
The Cla-Val Model CRL-33 Electronic Actuated Pressure Sustaining Pilot
Control provides remote set-point adjustment and accurate pressure sustaining control on Cla-Val 350 Series Control Valves. Remote set-point
command signals can be from any SCADA-type control system using an
analog 4-20 mA signal or by contact closure for cc/ccw rotation.
The CRL-33 senses upstream pressure with a remote hydraulic connection. Operating on 12 to 24 VDC and consuming very little power, it is an
ideal control system for remote valve sites that may even be solar powered. Existing manually-set Cla-Val 50 Series Pressure Sustaining control
valves can be retrofitted with CRL-33 to add remote set-point control of
minimum inlet pressure. Verification of inlet pressure may be sent to
SCADA system from customer supplied pressure sensor attached
upstream of valve.
The CRL-33 consists of a hydraulic pilot and integral controller that
accepts a 4-20 mA remote set-point and positions the pilot to maintain a
minimum pressure at valve inlet within preset limits. Pressure settings are
linear between these settings. Pressure settings are calibrated to the specific spring range of the control. Special USB connector cable and free
downloadable software can be used to change this range if needed.
Continuous internal monitoring of actuator position results in smooth transitions between pilot set-points with no backlash or dithering. Should
power or control input fail, the CRL-33 pilot remains in automatic hydraulic
control assuring system stability under all conditions.
Typical Applications
The CRL-33 is installed on Cla-Val 350 Series valves that maintain minimum upstream pressure by relieving excess pressure
to lower zone and require this pressure setting to be changed
from a remote location. It is also an effective solution for lowering costs associated with "confined space" requirements by
eliminating the need for entry in valve structure for set point
adjustment. Flow information can also be provided from the main
valve, see E-133VF. Additional pilot controls, hydraulic and/or
electronic, are also available to perform multiple functions to fit
exact system requirements.
DCheck Valves with Isolation Valve
PX141 Pressure Gauge
S CV Flow Control (Opening)
VX101 Valve Position Indicator
• Simplified Remote Valve Set-Point Control
• Isolated Input
• Ideal for Pressure Management
• 12-24VDC Input Power
• Reverse Polarity Protection
• IP-68 (Submersible)
The Cla-Val Model 390-02/3690-02 Electronic Actuated Pressure Reducing
Control Valve combines precise control of field proven Cla-Val hydraulic pilots
and simple, remote valve control. The Cla-Val Model 390-02/3690-02
Pressure Reducing Valve automatically reduces a higher inlet pressure to a
steady lower downstream pressure regardless of changing flow rate and/or
varying inlet pressure. This valve is an accurate, pilot-operated regulator capable of holding downstream pressure to a pre-determined limit. The valve uses
a CRD-33 pilot control, consisting of a hydraulic pilot and integral controller,
that accepts a remote set-point command input and makes set-point adjustments to the pilot.
The recommended control method is simple remote set-point change from an
RTU (Remote Telemetry Unit) to the CRD-33 where the 4-20 mA command
signal is ranged to specific pressure range. Very accurate control can be
achieved when span does not exceed 100 psi. Since the CRD-33 is preranged to the full spring range, some on-site calibration may be necessary
when this control method is used. Free downloadable software is available
from Cla-Val website for this purpose. The CRD-33 can also accommodate
control systems where the RTU compares pressure transmitter signal to the
remote set point command signal. The RTU adjusts the CRD-33 with 4-20 mA
command signal containing an adequate deadband to prevent actuator dithering after the two signals agree.
Typical Applications
The Cla-Val 390 Series valves that maintain downstream pressure
and require this pressure to be changed from a remote location. It
can be an effective solution for lowering costs associated with "confined space" requirements by eliminating the need for entry in valve
structure for set-point adjustment. It is also ideal for pressure management, and can be programmed to minimum night time and optimum daytime pressures. Optional profiler can be used to create custom correlation between pressure and flow information.
Flow information can also be provided from the main valve, see 133VF.
Additional pilot controls, hydraulic and/or electronic, are also available to perform multiple functions to fit exact system requirements.
84
Internal continuous electronic monitoring of actuator position results in virtually instantaneous position change with no backlash or dithering when control
signal is changed. In the event of a power or control input failure, the CRD-33
pilot remains in hydraulic control virtually assuring system stability under
changing conditions. If check feature ("D") is added, and pressure reversal
occurs, the valve closes to prevent return flow.
Product Dimensions Data:
For the 390-02 Main Valve (100-01) dimensions, see pages 17.
For the 3690-02 Main Valve (100-20) dimensions, see pages 29.
Page 85
MODEL
CRD-33 and CRA-33
Electronic Actuated
Pressure Reducing Pilot Control
• Ideal for Pressure Management
• Simplified Remote Valve Set-Point Control
• Isolated Input
• 12-24VDC Input Power
• Reverse Polarity Protection
• IP-68 Submersible
The Cla-Val Model CRD-33 and CRA-33 Electronic Actuated Pressure
Reducing Pilot Controls provide remote set-point adjustment and accurate
downstream pressure control on Cla-Val 390 Series Control Valves.
Remote set-point command signals can be from any SCADA-type control
system using an analog 4-20 mA signal or by contact closure for cc/ccw
rotation.
The CRD-33 senses valve outlet pressure directly and the CRA-33 senses downstream pressure with remote hydraulic connection. Operating on
12 to 24 VDC and consuming very little power, they are an ideal control
system for remote valve sites that may even be solar powered. Existing
manually-set Cla-Val 90 Series Pressure Reducing control valves can be
retrofitted with CRD-33 or CRA-33 to add remote set-point control of delivery pressure. Verification of downstream pressure may be sent to SCADA
system from customer supplied pressure sensor attached to valve outlet.
The CRD-33 and CRA-33 consists of a hydraulic pilot and integral controller that accepts a 4-20 mA remote set-point and positions the pilot to
maintain a pressure at valve outlet within preset limits. Pressure settings
are linear between these settings. Pressure settings are calibrated to the
specific spring range of the control. Special USB connector cable and free
downloadable software can be used to change this range if needed.
Continuous internal monitoring of actuator position results in smooth transitions between pilot set-points with no backlash or dithering. Should
power or control input fail, the CRD-33 or CRA-33 pilot remains in automatic hydraulic control assuring system stability under all conditions.
Typical Applications
The CRD-33 and CRA-33 are installed on Cla-Val 390 Series valves
that maintain downstream pressure and require this pressure to be
changed from a remote location. It can be an effective solution for lowering costs associated with "confined space" requirements by eliminating the need for entry in valve structure for set-point adjustment. It is
also ideal for pressure management, and can be programmed to minimum night time and optimum daytime pressures. Optional profiler can be
used to create custom correlation between pressure and flow information.
Flow information can also be provided from the main valve, see E-133VF.
Additional pilot controls, hydraulic and/or electronic, are also available
to perform multiple functions to fit exact system requirements.
85
Page 86
136-01
(Full Internal Port)
(Sizes 1/2"-4")
MODEL
636-01
(Reduced Internal Port)
(Sizes 3"-6")
Solenoid Control Valve
• Fast Acting Solenoid Control
• Reliable, Drip-Tight Shut-Off
• Simple Design, Proven Reliable
• Optional Check Feature
• Easy Installation and Maintenance
The Cla-Val Model 136-01/636-01 Solenoid Control Valve is an
on-off control valve that either opens or closes upon receiving
an electrical signal to the solenoid pilot control. This valve consists
of a Hytrol main valve and a three-way solenoid valve that alternately
applies pressure to or relieves pressure from the diaphragm chamber of
the main valve. It is furnished either normally open (de-energized solenoid to open) or normally closed (energized solenoid to open).
If the check feature option is added and a pressure reversal occurs, the
Schematic Diagram
Item Description
1Hytrol (Main Valve)
2CS3 Solenoid Control
downstream pressure is admitted into the main valve cover chamber and
the valve closes to prevent return flow.
Optional Features
Item Description
AX46A Flow Clean Strainer
BCK2 (Isolation Valve)
CCNA Closing Speed Control
DCheck Valves with Isolation Valve
PX141 Pressure Gauge
SCNA Needle Valve (Opening)
VX101 Valve Position Indicator
YX43 "Y" Strainer
Product Dimensions Data:
For the 136-01 Main Valve (100-01) dimensions, see pages 17.
For the 636-01 Main Valve (100-20) dimensions, see pages 29.
Typical Applications
Industrial uses for the solenoid control valve are many and
include accurate control of process water for batching, mixing,
washing, blending or other on-off type uses.
86
Liquid level control can be provided by using a float
switch or electrode probe which sends an electrical
signal to open or close the valve as needed.
Page 87
Schematic Diagram
136-03
(Sizes 4"and Larger)
(Full Internal Port)
MODEL
636-03
(Sizes 6"and Larger)
(Reduced Internal Port)
Solenoid Control Valve
• Fast Acting Solenoid Control
• Drip Tight Shut-Off
• Simple Design, Proven Reliable
• Optional Check Feature
• Easy Installation & Maintenance
The Cla-Val Model 136-03/636-03 Solenoid Control Valve is an on-off
control valve which either opens fully or closes drip-tight upon receiving an electrical signal to the solenoid pilot control. This valve consists
of a Hytrol main valve, a three way solenoid and a high capacity threeway pilot valve. The solenoid control operates the three-way valve
which alternately applies pressure to or relieves pressure from the
diaphragm chamber of the main valve. It is furnished either normally
open (de-energize solenoid to open) or normally closed (energize solenoid to open).
If the check feature option is added and a pressure reversal occurs, the
downstream pressure is admitted into the main valve cover chamber
and the valve closes to prevent return flow.
For the 136-03 Main Valve (100-01) dimensions, see pages 17.
For the 636-03 Main Valve (100-20) dimensions, see pages 29.
Industrial uses for the solenoid control valve are many
and include accurate control of process water for batching,
mixing, washing, blending or other on-off type uses.
Liquid level control can be provided by using a float
switch or electrode probe which sends an electrical
signal to open or close the valve as needed.
87
Page 88
139-01
(Full Internal Port)
MODEL
639-01
(Reduced Internal Port)
Programmable Timer Control Valve
Precise Valve On-Off Control
•
Completely Self-contained
•
High Energy Efficiency
•
Battery Life Exceeds 3 Years
•
Direct Control of Valve Opening and Closing Four Times Daily
•
Combines with Pressure, Flow or Level Control
•
Ideal for Remote Valve Location Control
•
The Cla-Val Model 139-01/639-01 Programmable Timer Control Valve
is an on-off control valve for applications using a programmable time
schedule. Using the CTC Electronic Timer Control up to four opening
and closing times per day can be set for a weekly schedule.
Timer function and parameters are changed using downloadable soft-
www.cla-val.com and special USB
Schematic Diagram
Item Description
1Hytrol (Main Valve)
2CTC Electronic Timer Control
3X58C Restriction Assembly
ware from the Cla-Val website
cable part number 20519203A. Future software and firmware
upgrades will be available from Cla-Val website. Powered by a longlife lithium battery, the CTC control offers powerful valve control for
remote locations and other valve automation applications.
Model 139-01 Programmable Timer
Control Valve is ideal for automating distribution system flushing applications.
The valve is installed in distribution system locations that require a regular flushing schedule to maintain system water
quality within disinfection and health
standard limits. The valve vents a small
quantity of water for a short time on a
regular schedule to create desired water
turnover.
Other Model 139-01 applications requiring remote, stand alone valve opening
and closing on a predetermined schedule include night-time tank filling, service
line limiting time of use, automatic line
strainer flushing, etc.
Product Dimensions Data:
For the 139-01 Main Valve (100-01) dimensions, see pages 17.
For the 639-01 Main Valve (100-20) dimensions, see pages 29.
88
Page 89
CLA-VAL
FLOW
to drain
CLA-VAL
MODEL
CTC
Electronic Timer Control
Precise Valve On-Off Control
•
Completely Self-contained
•
High Energy Efficiency
•
Battery Life Exceeds 3 Years
•
Direct Control of Valve Opening and Closing 4 Times Daily
•
Combines with Pressure, Flow or Level Control
•
Ideal for Remote Valve Location Control
•
The Cla-Val CTC Electronic Timer Control is a battery powered, programmable on-off control used for opening and closing Cla-Val main
valves according to time schedule. Up to four opening and closing
times per day can be set for a weekly schedule.
Timer function and parameters are changed using downloadable software from the Cla-Val website
cable part number 20519203A. Future software and firmware
upgrades will also be available from Cla-Val website. Powered by a
long-life lithium battery, the CTC offers powerful valve control for
remote locations and valve automation applications.
www.cla-val.com and special USB
CTC Electronic Timer Control Specifications
Pressure Connection: 1/4"NPT
Operating Pressure:Maximum 145 psi (10 bar)
°
Temperature Range:14
Enclosure Protection: IP-68 (submersible)
Battery Type:Lithium 9V/PP3
F to 176°F (-10°C to + 80°C)
Typical Application
The CTC Electronic Timer Control is used for pressure management applications in water distribution systems where
SCADA control is not available. A Cla-Val Pressure Control
Valve is programmed with CTC to change pressure during high
flow and low flow demand times according to pre-engineered
schedule reducing leaks and pipe burst frequency.
CLA-VAL
P.O. Box 1325 • Newport Beach, CA 92659-0325 • Phone: 949-722-4800 • Fax: 949-548-5441 • E-mail: claval@cla-val.com • Website cla-val.com
Copyright Cla-Val 2012 Printed in USA Specifications subject to change without notice.
Fluids:Water, others compatible with materials
Materials:Enclosure: PVC
Valve Body: Glass-Fiber Nylon Body
Seals: Buna-N®
Programming Interface: Custom USB cable (1 m, supplied standard); Windows NT, 2000, XP, Vista
Programming Software is free download from Cla-Val website.
The CTC Electronic Timer Control is used in 139 Series
Programmable Control Valves to automate circulating water
requirements in distribution system applications. Valve opening and closing time of day and duration are programmed for
convenient system flushing and circulating during times of low
flow to optimize water quality.
E-CTC (R-9/2011)
89
Page 90
60-08
(Full Internal Port)
MODEL
660-08
(Reduced Internal Port)
Booster Pump Control Valve
with High Capacity Pilot System
Schematic Diagram
• Designed for Larger Sized Pump Stations
• Low Head Loss
• Built-in Check Valve
• Opening and Closing Rates Separately Adjusted
• Proven Reliable Design
The Cla-Val Model 60-08/660-08 Pump Control Valve is a pilotoperated valve designed for installation on the discharge of
booster pumps to eliminate pipeline surges caused by the starting and stopping of the pump.
The pump starts against a closed valve. When the pump is started, the solenoid control is energized and the valve begins to
open slowly, gradually increasing line pressure to full pumping
head. When the pump is signaled to shut-off, the solenoid control is de-energized and the valve begins to close slowly, gradually reducing flow while the pump continues to run. When the
valve is closed, a limit switch assembly, which serves as an electrical interlock between the valve and the pump, releases the
pump starter and the pump stops.
Should a power failure occur, a built-in, lift-type check valve closes
the moment flow stops, preventing reverse flow regardless of
solenoid or diaphragm assembly position.
Item Description
1Powercheck (Main Valve)
2CV Flow Control
3CS4SM 4-Way Solenoid Control
4X105LCW Switch Assembly
5CVS-1 Shuttle Valve
For the 60-08 Main Valve (100-03) dimensions, see pages 25.
For the 660-08 Main Valve (100-22) dimensions, www.cla-val.com
Typical Installation
Install Model 60-08/660-08 valve as shown. Flexible
conduit should be used for electrical connections to
the solenoid control and the limit switch. A Model
52-02/652-03 Surge Anticipator Valve is recommended for power failure protection.
Note: For optimum operation of built-in check feature,
installation must be with valve stem vertically up.
The Model 60-08/660-08 is for 10" and larger
valves or when the pressure is above 300 psi.
90
Page 91
Pump
CLA-VAL 60-11/660-11
Booster Pump
Control Valve
CLA-VAL
52-03/652-03
Surge Anticipator
Valve
Discharge to
Atmosphere
Isolation Valve
Discharge To
System
60-11
MODEL
(Full Internal Port)
660-11
(Reduced Internal Port)
Booster Pump Control Valve
Built-in Check Valve
•
Valve Uses Line Pressure for Operation
•
Opening and Closing Rates Adjusted Separately
•
Solenoid Control Can Be Operated Manually
•
The Cla-Val Model 60-11/660-11 Booster Pump Control Valve is a
pilot-operated valve designed for installation on the discharge of
booster pumps to eliminate pipeline surges caused by the starting
and stopping of the pump.
The pump starts against a closed valve. When the pump is started, the solenoid control is energized and the valve begins to open
slowly, gradually increasing line pressure to full pumping head.
When the pump is signaled to shut-off, the solenoid control is deenergized and the valve begins to close slowly, gradually reducing
flow while the pump continues to run. When the valve is closed, a
limit switch assembly, which serves as an electrical interlock
between the valve and the pump, releases the pump starter and
the pump stops.
Schematic Diagram
Item Description
1Powercheck (Main Valve)
2CV Flow Control
3CSM11-A2-2 Solenoid Control
4X105LCW Switch Assembly
5CVS-1 Shuttle Valve
For the 60-11 Main Valve (100-03) dimensions, see pages 25.
For the 660-11 Main Valve (100-22) dimensions, www.cla-val.com
Typical Installation
Install Model 60-11/660-11 valve as shown. Flexible
conduit should be used for electrical connections to
the solenoid control and the limit switch. A Cla-Val
Model 52-03/652-03 Surge Anticipator Valve is recommended for power failure protection.
Note: Installation with valve stem vertical up is
recommended. For horizontal stem installation use
Cla-Val Model 60-73/660-73.
Should a power failure occur, a built-in lift-type check valve closes
the moment flow stops, preventing reverse flow regardless of solenoid or diaphragm assembly position.
91
Page 92
60-31
(Full Internal Port)
MODEL
660-31
(Reduced Internal Port)
Booster Pump Control Valve
• Simple Hydraulic Operation
• Low Head Loss
• Built-in Check Valve
• Proven Reliable Design
The Cla-Val Model 60-31/660-31 Booster Pump Control valve is a
pilot-operated valve designed for installation on the discharge of
booster pumps to eliminate pipeline surges caused by the starting and stopping of the pump.
The pump starts against a closed valve. When the pump is started, the solenoid control is energized and the valve begins to open
slowly, gradually increasing line pressure to full pumping head.
When the pump is signaled to shut-off, the solenoid control is deenergized and the valve begins to close slowly, gradually reducing flow while the pump continues to run. When the valve is
closed, a limit switch assembly, which serves as an electrical
interlock between the valve and the pump, releases the pump
starter and the pump stops.
Schematic Diagram
Item Description
1Hycheck (Main Valve)
2102C-3H Three Way Hytrol
3CS3SM Solenoid Control
4X105LCW Switch Assembly
5CDC Disk Check Valve
6CDC/CSC Check Valve
7CNA Angle Valve
8CK2 Cock (Isolation Valve)
For the 60-31 Main Valve (100-04) dimensions, see www.cla-val.com
For the 660-31 Main Valve (100-23) dimensions, www.cla-val.com
Typical Application
Install Model 60-31/660-31 valve as shown in multiple pump
applications. Flexible conduit should be used for electrical
connections to the solenoid control and the limit switch. A
Model 52-03/652-03 Surge
mended for power failure
Anticipator Valve is recom-
protection.
The Model 60-31/660-31 is an automatic valve of a modified
globe-type design with a built-in, lift type, check feature. It is
hydraulically operated and diaphragm-actuated. A three-way
solenoid valve controls the valve operation. Flow control valves
located in the pilot control system provide regulation of both the
opening and closing rate. Pilot system strainer insures that the
pilot control supply is clean.
8CV Flow Control (Opening and Closing Speed)
9CDC/CSC Check Valve
Pressure Valve
(4" and Larger)
• Built-in Check Valve
• Accurate Pressure Control
• Low Head Loss
• Smooth Control of Pump Surges
• Easy Maintenance Design
The Cla-Val Model 60-32/660-32 Combination Pump Control and
Back Pressure Valve is a pilot-operated control valve designed for
booster pump discharge installation to eliminate pipeline surges
caused by starting and stopping of pump and to provide
adjustable back pressure on pump while it is running. The valve
features a modified globe-design with diaphragm-actuation, and
hydraulic operation for smooth, reliable automatic operation during pump starting and stopping. A built-in lift-type check feature
automatically closes valve on electric power failure or any time
pressure reversal occurs to protect pump from back spinning.
In operation, when pump is off, the pump control valve is closed
by downstream system pressure. When pump is started, the
solenoid control is energized and valve opens slowly to gradually
increase pump flow and line pressure to desired back pressure
setting for pumping conditions. When pump is signaled to shutoff, the solenoid control is de-energized and the valve begins to
slowly close, gradually reducing flow while pump continues to run.
When valve is closed, the included limit switch assembly turns off
pump. Adjustable flow controls are included to easily regulate
valve opening and closing speed to prevent surges.
Using Cla-Val wiring diagram (see page 4) ensures safe electrical
interlock control of pump and valve.
Install Model 60-32/660-32 valve as shown in multiple pump
applications. Flexible water-tight conduit should be used for
electrical connections to the solenoid control and the limit
switch. A Model 52-03/652-03 Surge
recommended for power failure
Anticipator Valve is
protection.
Product Dimensions Data:
For the 60-32 Main Valve (100-04) dimensions, see www.cla-val.com
For the 660-32 Main Valve (100-23) dimensions, www.cla-val.com
93
Page 94
61-02
(Full Internal Port)
MODEL
661-02
(Reduced Internal Port)
Deep Well Pump Control Valve
• Prevent Surges in Pipelines
• Simple Hydraulic Operation
• Adjustable Opening and Closing Speeds
• Solenoid Control Can Be Operated Manually
• Proven Reliable Design
The Cla-Val Model 61-02/661-02 Deep Well Pump Control Valve
is designed to protect pipelines from surges caused by the starting and stopping of deep well pumps. This is a hydraulically
operated diaphragm valve which is controlled by a solenoid pilot
valve. Separate adjustable flow control valves in the pilot system
regulate the opening and closing rates. A limit switch on the
valve stem serves as an electrical interlock between the valve
and the pump motor.
The operation of the valve is completely automatic and controlled by the solenoid valve. With the pump off, the valve is wide
open. When the pump is started, the solenoid is energized and
the valve begins to close slowly, discharging air and the initial
rush of sand and water from the pump column to atmosphere. As
the valve closes the pump output is gradually diverted into the
main line, preventing the development of a starting surge.
Schematic Diagram
Item Description
1Powertrol (Main Valve)
2CSM11-A2-2 Solenoid Control
3CV Flow Control
4X105LOW Switch Assembly
5CK (Isolation Valve)
6X43 "Y" Strainer
7Union
Item Description
PX141 Pressure Gauge
Note: For main valve option descriptions, refer to 100-02 (61-02) or 10021 (661-02) Technical Data Sheets.
Product Dimensions Data:
For the 61-02 Main Valve (100-02) dimensions, see pages 21.
For the 661-02 Main Valve (100-21) dimensions, www.cla-val.com
Typical Installation
Install Model 61-02/661-02 valve as shown. Use a minimum
of 1/2" tubing to connect operating pressure connection of the
valve to the system side of check valve. Flexible conduit
should be used for electrical connections to the solenoid control and the limit switch assembly. A Model 52-02/652-03
Surge Anticipator is recommended for power failure and
surge protection.
When it is time to shut-off the pump, the solenoid is de-energized. The pump continues to run while the pump control valve
opens slowly, diverting pump output to atmosphere. As pump
pressure gradually decreases, the main line check valve closes
slowly, preventing shock or slam during the pump stopping
cycle. When the pump control valve is wide open, the limit switch
assembly releases the pump starter and the pump stops.
94
Page 95
81-01
MODEL
(Full Internal Port)
681-01
(Reduced Internal Port)
Check Valve
• Simple Proven Design
• No-Slam Operation
• Drip-Tight Shut-Off
• No Packing Glands or Stuffing Boxes
• Easy to Install & Maintain
The Cla-Val Model 81-01/681-01 Check Valve is a hydraulically
operated No-Slam Check Valve. This valve opens when the pressure at the inlet exceeds the discharge pressure. A gradual rate of
opening prevents sudden opening surges. When a pressure reversal occurs the higher downstream pressure is applied to the cover
chamber through the control tube lines, and the valve closes drip
tight.
This valve is ideally suited for use where a positive shutoff is
required. The rubber disc assures tight sealing even if the fluid contains grit or other small-size particles. The simple packless design
insures reliable operation and freedom from leaks.
Schematic Diagram
Item Description
1Hytrol (Reverse Flow Main Valve)
Product Dimensions Data:
For the 81-01 Main Valve (100-01) dimensions, see pages 17.
For the 681-01 Main Valve (100-20) dimensions, see pages 29.
Note: The effectiveness of this valve is related to pipeline velocity.
We recommend a maximum flow based on pipeline velocity of 6 feet
per second. If pipeline velocities exceed 6 feet per second, consideration should be given to adding a Cla-Val Model 50-01 Pressure
Relief Valve or a Cla-Val Model 52 Series Surge Control Valve to the
system.
InletOutlet
M
1
Typical Applications
Smaller sizes of this valve are used in pilot control systems in Cla-Val Automatic Control valves. This valve
can also be used in any piping system where one-way
flow is desired.
Install on the discharge of booster pumps to prevent
return flow into tank when pump is off. Relief valve as
shown is good practice to minimize surges when pump
stops.
For valve sizes larger than 3", use Model 81-02.
95
Page 96
81-02
(Full Internal Port)
MODEL
681-02
(Reduced Internal Port)
Check Valve
• Simple Proven Design
• No-Slam Operation
• Drip-Tight Shut-Off
• Dual Speed Control
• No Packing Glands or Stuffing Boxes
• Available in a Variety of Materials
The Cla-Val Model 81-02/681-02 Check Valve is a hydraulically operated
No-Slam Check Valve with dual speed controls. This valve opens when
the pressure at the inlet exceeds the discharge pressure. A gradual rate of
opening prevents sudden opening surges. When a pressure reversal
occurs, the higher downstream pressure is applied to the cover chamber
through the control tube lines, and the valve closes drip tight.
This valve is ideally suited for use where a positive shutoff is required. The
rubber disc assures tight sealing even if the fluid contains grit or other
small-size particles. The simple packless design insures reliable operation
and freedom from leaks.
PX141 Pressure Gauge
VX101 Valve Position Indicator
Product Dimensions Data:
For the 81-02 Main Valve (100-01) dimensions, see pages 17.
For the 681-02 Main Valve (100-20) dimensions, see pages 29.
Typical Applications
Note: The effectiveness of this valve is related to pipeline velocity. We recommend a maximum flow based on pipeline velocity of 6 feet per second.
If pipeline velocities exceed 6 feet per second, consideration should be
given to adding a Cla-Val Model 50-01 Pressure Relief Valve or a Cla-Val
Model 52 Series Surge Control Valve to the system.
Deep Well Pump
This valve should be an integral part of any well designed pumping system. It is used to prevent damaging and sometimes expensive flow reversal.
96
Booster Pump
Install on the discharge of booster pumps to prevent return flow into
tank when pump is off. Relief valve as shown is good practice to minimize
surges when pump stops.
Page 97
81-12
MODEL
(Full Internal Port)
681-12
(Reduced Internal Port)
Check Valve
• Simple Proven Design
• No-Slam Operation
• Drip-Tight Shut-Off
• Recommended for Variable Speed Pumps
• No Packing Glands or Stuffing Boxes
• Easy to Install & Maintain
The Cla-Val Model 81-12 Check Valve is a hydraulically operated
No-Slam Check Valve. This valve opens when the pressure at the
inlet exceeds the discharge pressure. A gradual rate of opening prevents sudden opening surges. When a pressure reversal occurs the
higher downstream pressure is applied to the cover chamber
through the control tube lines, and the valve closes drip tight.
This valve is ideally suited for use where a positive shutoff is
required. The rubber disc assures tight sealing even if the fluid contains grit or other small-size particles. The simple packless design
insures reliable operation and freedom from leaks.
Schematic Diagram
Item Description
1Hytrol (Main Valve)
Product Dimensions Data:
For the 81-12 Main Valve (100-01) dimensions, see pages 17.
Typical Applications
Install on the discharge of booster pumps to prevent
return flow when pump is off. Relief valve as shown is
good practice to minimize surges when pump stops.
For valve sizes 3" and larger consult factory
97
Page 98
Series 501A
Wafer Swing Check Valve
Standard Style
2”-12”
SPECIFICATIONS
The wafer swing check valve shall have torsional a
spring-assisted fast closure to minimize possibility of
water hammer. The valve shall be constructed of
either cast iron or steel body.
The body shall have a machined dovetail groove to
®
retain a field replaceable Nitrile (Buna-N
provides water-tite shut-off at low/high pressure
) Seal that
•Low Head Loss
•Watertight Nitrile Seat
•Spring Assisted, Fast Closure
•Extremely Light Weight
DESCRIPTION
Cla-Val Series 501A Wafer Swing Check Valve has a quick,
spring-assisted closure that minimizes the possibility of
water hammer. The swing check design offers low head loss
and a full-flow passageway making it ideal for water or wastewater applications. The short lay length of the valve allows
for a space-saving design. It is available in sizes 2” to 30”,
with either a 125 lb. or 150 lb. pressure class rating.
Available in a variety of materials, including all 316 stainless steel, the Cla-Val Wafer Swing Check Valve uses a
standard soft seat to ensure a drip-tight seal. For ease of
installation, valves 6” and larger are supplied with a tapped
hole to mount an eye bolt for lifting. All materials conform
to ASTM specifications, ensuring performance reliability.
Typical Applications with
Correct Valve Location
Avoid These Applications
with Incorrect Valve
Location
The valve disc/arm assembly shall be one piece
design utilizing an integral disc arm for connection to
the shalt for positive shut-off and no disc flutter.
For corrosion resistance the valve shall be
Electroless Nickel Plated
All materials conform to ASTM specifications, The valve
shall be a Cla-Val Series 501A Wafer Swing Check Valve,
Newport Beach, CA 92659-0325
Note: Allow minimum
(2) pipe diameters
clearance downstream
of check valve with
disc open to promote
smooth flow
Recommendations for Installation Position
1. Install the valve in horizontal or upward flow for proper valve closure.
Caution: Do not use with reciprocating compressors, or in other pulsating services.
98
Page 99
Silent Wafer Check Valve
SPECIFICATIONS
The silent wafer check valve shall consist of a heavy
cast iron body, bronze seat, bronze disc, and stainless steel spring. The valve disc shall be center
guided at both ends with an integral shaft and shall
be spring loaded for silent operation. The spring shall
be helical or conical and stone tumbled to achieve a
micro-finish to resist mineral deposits. For ease of
maintenance, the seat and disc shall be replaceable
in the field.
Check valve shall be capable of silent operation
when installed in vertical or horizontal positions with
either flow up or flow down. The flow area through
the body shall be equal to or greater than the crosssection area of the equivalent pipe size. The valve
shall be a Cla-Val Series 580 Silent Wafer Check
Valve.
All materials of construction shall conform to
ASTM specifications as follows:
Valve Body: Wafer Style Cast Iron ASTM A126
Class B
Disc & Seat: Bronze ASTM B584
Spring:Stainless Steel ASTM A313.5
Stone Tumbled
Sizes:2" to 10"
Series 580
• Short Lay Length
•Watertight Seating
•Field Replaceable Parts
•Factory Mutual Approved
•Optional Resilient Seat
The Cla-Val Series 580 Silent Wafer Check Valve has a springloaded poppet that allows the valve to close before flow reversal
occurs, resulting in a silent, non-slam closure. It is a truly silent
check valve. For ease of installation, the valve can be installed
in vertical or horizontal positions with flow up or flow down. The
short lay length of the valve allows for a space-saving design.
Silent Wafer Check Valves are available in sizes 2” to 10”, with
either a 125 lb. or 250 lb. pressure class rating.
Constructed of a cast iron body with bronze trim, the Cla-Val
Silent Wafer Check Valve offers watertight shutoff with metal-tometal seating. For special applications, stainless steel trim and Buna-N
resilient seats are available as options. All materials conform to
ASTM specifications, ensuring long lasting reliable performance.
As a confirmation of Cla-Valʼs commitment to quality, all Series 580
125 lb. class valves are Factory Mutual approved.
Series 580 Pressure Loss Curve
3
2
1
Pressure Loss PSI
12
WAFER AND GLOBE STYLE SILENT CHECK VALVES
TEMP
DEG F.
0 -150º
200º
250º
TEST
PRES.
* Ductile Iron Recommended For Hot Water Service Above 200º F.
GRAY IRON
125 LB. CLASS
2” - 12”
200
190
*
300
3
PRESSURE / TEMPERATURE RATINGS
MAXIMUM NON-SHOCK WATER SERVICE PRESSURE
14” - 42”
150
135
*
230
(Typical)
45678910 11 12
Fluid Velocity / FPS
DUCTILE IRON
150 LB. CLASS
2” - 12”
300
280
270
450
14” - 42”
250
230
220
375
GRAY IRON
250 LB. CLASS
2” - 12”
400
370
*
600
14” - 42”
300
280
450
2” - 12”
*
DUCTILE IRON
300 LB. CLASS
500
460
440
750
7
6
5
4
3
2
1
14” - 42”
®
Pressure Loss Ft. of Water
400
370
355
600
99
Page 100
12
3
45678910 11 12
Series 581 Pressure Loss Curve
3
2
1
7
6
5
4
3
2
1
Pressure Loss PSI
Pressure Loss Ft. of Water
Fluid Velocity / FPS
(Typical)
Series 581
Silent Globe Check Valve
•Operates Horizontally or Vertically
• Watertight Seating
•Field Replaceable Parts
• Factory Mutual Approved – Various Sizes
•Optional Resilient Seat
The Cla-Val Series 581 Silent Globe Check Valve has a springloaded poppet that allows the valve to close before flow reversal
occurs, resulting in a silent, non-slam closure. It is a truly silent
check valve. For ease of installation, the valve can be installed
in vertical or horizontal positions with flow up or flow down. Silent
Globe Check Valves are available in 2 1/2” to 42” sizes, with
either a 125 lb. or 250 lb. pressure class rating. Silent Globe
Check Valves in 3” to 10” sizes have enough outlet clearance to
allow them to be bolted directly to wafer style butterfly valves.
SPECIFICATIONS
The silent globe check valve shall consist of a heavy
cast iron body, bronze seat, bronze disc, and stainless steel spring. The valve disc shall be center
guided at both ends with an integral shaft and shall
be spring loaded for silent operation. The spring shall
be helical or conical and stone tumbled to achieve a
micro-finish to resist mineral deposits. For ease of
maintenance, the seat and disc shall be replaceable
in the field.
Constructed of a cast iron body with bronze trim, the Cla-Val
Silent Globe Check Valve offers watertight shutoff with metal-tometal seating. For special applications, stainless steel trim and
®
Buna-N
resilient seats are available as options. All materials
conform to ASTM specifications, ensuring long lasting reliable
performance. As a confirmation of Cla-Valʼs commitment to quality,
2 1/2” to 12” 125 lb. class Series 581 valves are Factory Mutual
approved.
Check valve shall be capable of silent operation
when installed in vertical or horizontal positions with
either flow up or flow down. The flow area through
the body shall be equal to or greater than the crosssection area of the equivalent pipe size. Sizes 2 1/2”
to 10” shall allow bolting a wafer style butterfly valve
directly to the outlet flange without a spool piece.
All materials of construction shall conform to ASTM
specifications as follows:
Valve Body:
Disc & Seat:
Spring:
Sizes:
Cast Iron ASTM A126 Class B
Bronze ASTM B584
Stainless Steel ASTM A313.5
Stone Tumbled & Stress Relieved.
3" thru 10" shall accept a direct connected Butterfly Valve for isolation
use and space saving in the pump
station.
The valve shall be a Cla-Val Series 581 Silent Globe
Check Valve.
Cla-Val Series 581 Silent Globe Check Valve avaliable in all 316 Stainless Steel Material.
Note:
PRESSURE / TEMPERATURE RATINGS
WAFER AND GLOBE STYLE SILENT CHECK VALVES
TEMP
DEG F.
º
0 -150
200º
250º
TEST
PRES.
* Ductile Iron Recommended For Hot Water Service Above 200º F.
MAXIMUM NON-SHOCK WATER SERVICE PRESSURE
GRAY IRON
125 LB. CLASS
2” - 12”
14” - 42”
200
190
*
300
150
135
*
230
DUCTILE IRON
150 LB. CLASS
2” - 12”
300
280
270
450
14” - 42”
250
230
220
375
GRAY IRON
250 LB. CLASS
2” - 12”
400
370
600
14” - 42”
300
280
*
450
2” - 12”
*
DUCTILE IRON
300 LB. CLASS
14” - 42”
500
460
440
750
400
370
355
600
100