Cla-Val Automatic Control Valve Solutions User Manual

Page 1
Valve Solutions
Serving worldwide markets:
• Municipal Waterworks
• Pressure Management
• Reclaimed Water
• Industrial
• Irrigation
• HVAC
• Fire Protection
Page 2
The information contained in this catalog is a summary overview of Cla-Val products. Visit www.cla-val.com to see the complete range of products, new releases and the most up-to-date literature.
Table of Contents
Main Valve Technical Data
Company Overview ....................................................................................................6
Product Overview .......................................................................................................7
Cla-Val Value Adder Upgrades ..................................................................................10
Cla-Val Solution City - Water Treatment Systems Solutions.......................................12
100-01 Hytrol Valve ..................................................................................................14
100-02 Powertrol Valve.............................................................................................18
100-03 Powercheck Valve ........................................................................................22
100-20 Series 600 Reduced Port Hytrol Valve ..........................................................26
100-42 700 Series Roll Seal Valves ..........................................................................30
100-44 Hytrol 316SS Reduced Port Valves ...............................................................32
100-46 Hytrol 316 SS Full Port Valves ......................................................................34
Flange Dimensions and End Details .........................................................................36
www.cla-val.com/waterworks.cfm
Anti-Cavitation Valves
Anti-Cavitation Trim: Principles of Operation .............................................................37
Valve Cavitation Guide .............................................................................................38
CLA-CAV Overview ..................................................................................................38
100-01KO Anti-Cavitation Hytrol Valve ......................................................................39
100-20KO Anti-Cavitation Hytrol Valve ......................................................................40
www.cla-val.com/waterworks.cfm
Pressure Relief Valves
50-01/650-01 Pressure Relief and Pressure Sustaining Valves..................................41
50-01KO Anti-Cavitation Pressure Relief and Pressure Sustaining Valves .................43
52-03/652-03 Pressure Relief and Surge Anticipator Valves ......................................44
58-01/658-01 Combination Back Pressure and Solenoid Shutoff Valves ....................45
750-01 Pressure Relief, Sustaining and Back Pressure Valves..................................46
250-01/605-01 Differential Pressure Relief Valves.....................................................47
www.cla-val.com/waterworks.cfm
Pressure Reducing Valves
90-01/690-01 Pressure Reducing Valves ..................................................................48
90-01KO Anti-Cavitation Pressure Reducing Valves ..................................................50
90-48/690-48 Pressure Reducing Valves with Low Flow Bypass ...............................51
92-01/692-02 Combination Pressure Reducing and Pressure Sustaining Valves........52
93-01/693-01 Pressure Reducing and Solenoid Shut-Off Valves ...............................53
94-01/694-01 Combination Pressure Reducing and Surge Control Valves .................54
990 Balance Direct Acting Pressure Reducing Valves ...............................................55
790-01 Pressure Reducing Valves ................................................................................56
www.cla-val.com/waterworks.cfm
Pressure Management Products
98-06 Hydraulic Pressure Management Control Valve with Dual Setpoints ................57
Pressure Reducing Valve with Two Stage Solenoid Selected Pressure ............58
90-11
97-20 Dual Stage Pressure Reducing Valve with Programmable Timer Control .........59
For Metering Option see 133VF. ...............................................................................79
For Electronic Pressure Management Control Valve see 390-02/690-02....................84
For Pressure Management Control see CRD-33 .......................................................85
X144 e-Flow Meter......................................................................................................130
www.cla-val.com/waterworks.cfm
2
Page 3
The information contained in this catalog is a summary overview of Cla-Val products. Visit www.cla-val.com to see the complete range of products, new releases and the most up-to-date literature.
Table of Contents
Rate of Flow Control Valves
40-01/640-01 Rate of Flow Control Valves ................................................................60
43-01/643-01 Combination Rate of Flow Control and Solenoid Shut-Off Valves .........61
49-01/649-01 Combination Rate of Flow and Pressure Reducing Valves ...................62
X52E Orifice Plate Assembly .................................................................................122
X144 e-Flow Meter......................................................................................................130
www.cla-val.com/waterworks.cfm
Level Control Valves
124-01/624-01 Float Valves - Non-Modulating Type (sizes 1/2”-6”)............................63
129-01/629-01 Modulating Float Valves ....................................................................64
428-01/628-01 Modulating Float Valves ....................................................................65
210-01/610-01 Altitude Valves for One-Way Flow......................................................66
210-09/610-09 Combination Altitude and Back Pressure Valve..................................67
210-16/610-16 Altitude Valves for Two-Way Flow......................................................68
210-17/610-17 Altitude and Solenoid Shut-Off Valve .................................................69
www.cla-val.com/waterworks.cfm
Electronic Control Valves
131/631 Electronic Control Valves ............................................................................70
131VC Series Controllers .........................................................................................73
133-01/633-01 Modulating Metering Valves...............................................................75
Advanced Cla-Val Electronic Backwash Valve with Metering .....................................76
138-01 Electronic Actuated Positioning Control Valves ................................................77
133VF Valve Flow Measurement System ..................................................................79
340-02/3640-02 Electronic Actuated Rate of Flow Valves ..........................................80
350-02/3650-02 Electronic Actuated Pressure Relief and Pressure Sustaining Valve .82
390-02/3690-02 Electronic Actuated Pressure Reducing Valves ................................84
www.cla-val.com/waterworks.cfm
Solenoid Control Valves
136-01/636-01 Solenoid Control Valves (sizes 1/2”-6”) ..............................................86
136-03/636-03 Solenoid Control Valves with High Capacity Control System ..............87
139-01 Programmable Timer Control Valves ................................................................88
www.cla-val.com/waterworks.cfm
Pump Control Valves
60-08/660-08 Booster Pump Control Valves..............................................................90
60-11/660-011 Booster Pump Control Valves ............................................................91
60-31/660-031 Booster Pump Control Valves............................................................92
60-32/660-032 Combination Pump Control and Back Pressure Valves ......................93
61-02/661-02 Deep Well Pump Control Valves..........................................................94
www.cla-val.com/waterworks.cfm
3
Page 4
The information contained in this catalog is a summary overview of Cla-Val products. Visit www.cla-val.com to see the complete range of products, new releases and the most up-to-date literature.
Table of Contents
Check Valves
81-01/681-01 Hydraulic Non-Slam Check Valves ......................................................95
81-02/681-02 Hydraulic Non-Slam Check Valves with Dual Speed Controls ..............96
81-12/681-12 Hydraulic Non-Slam Check Valves ......................................................97
501A Wafer Swing Check Valves ..............................................................................98
580 Silent Wafer Check Valves .................................................................................99
581 Silent Globe Check Valves...............................................................................100
582 Two-Door Wafer Check Valves.........................................................................101
584 Flex-Check™ Valves ............................................................................................102
Duckbill Check Valves ............................................................................................103
www.cla-val.com/industrial.cfm
Waterworks Air Valves
33A Series Air Release and Vacuum Breaker Valves ..............................................104
34 Series Air Release Valves ..................................................................................106
35 Series Air and Vacuum Valves ...........................................................................107
36 Series Combination Air Release and Vacuum Breaker Valves ............................108
37 Series Well Service Valves ................................................................................109
38VB/AR Series Vacuum Breaker / Air Release Valves for Water & Wastewater......110
www.cla-val.com/waterworks.cfm
Wastewater Air Valves
34WW Series Waste Water Air Release Valves .......................................................111
35WW Series Waste Water Air and Vacuum Valves ................................................112
36WW Series Waste Water Combination Air Release and Vacuum Breaker Valves..113
www.cla-val.com/industrial.cfm
Controls & Accessories
55F Pressure Relief Valve Pilots .............................................................................117
CDHS-33 Electronic Actuated Rate of Flow Pilot Control.............................................81
CDS6A Altitude Pilot Control.. .....................................................................................114
CF1-C1 Float Control Valves for Open Tanks ..........................................................115
CPC Electronic
CRA Remote Sensing Type Pressure Reducing Pilot Control ....................................11 6
CRA-33 Electronic Actuated Pressure Reducing Pilot Control .....................................85
CRD Pressure Reducing Pilot Control ........................................................................116
CRD-33 Electronic Actuated Pressure Reducing Pilot Control.....................................85
CRL Pressure Relief Pilot Control ...............................................................................117
CRL-33 Electronic Actuated Pressure Sustaining Pilot Control....................................83
CTC Electronic Timer Control .......................................................................................89
CV/CVS-1 Flow Control ..............................................................................................120
Pilot System Strainers and Restriction Assemblies.....................................................118
X43H H-Style Strainers ...............................................................................................121
X52E Orifice Plate Assembly .................................................................................122
X101 Valve Position Indicator .....................................................................................123
X105L/X105L2 Limit Switch Assemblies.....................................................................124
X117D Valve Position Transmitter...............................................................................125
X117E Valve Position Transmitter ...............................................................................126
X140-1
X141 Gauges ..............................................................................................................128
X143HP Hydro-Powered Generator............................................................................129
X143IP Turbine-Powered Generator...........................................................................129
X143MP Micro Turbine-Powered Generator ...............................................................129
X144 e-Flow Meter......................................................................................................130
www.cla-val.com/waterworks.cfm
Locking Security Cap
Actuator Positioning Control
......................................................................................127
...................................................................78
4
Page 5
The information contained in this catalog is a summary overview of Cla-Val products. Visit www.cla-val.com to see the complete range of products, new releases and the most up-to-date literature.
Table of Contents
Fire Protection Valves
100G/2100G/100GS/2100GS Fire Protection Deluge Valves ...................................131
50B-4KG1 Fire Protection Pressure Relief Valves ...................................................133
50B-5KG Pump Suction Control Valves ..................................................................134
85-09-1 Automatic Breach Containment Valve.........................................................135
90-21UL UL Listed Fire Protection Pressure Reducing Valves. ................................136
134-05
403 Series
582SWS Two-Door Wafer Check Valves.................................................................141
834-05 Fire Deluge Valve .......................................................................................139
850B-4 Fire Relief Valve .........................................................................................140
55L Fire Protection Pressure Relief Valves .............................................................142
X43HL H-Style Strainers.........................................................................................143
www.cla-val.com/fire-protection.cfm
Solenoid Operated Deluge Valve
Pneumatically Operated Remote Control Valve
Warranties and Certifications
................................................................137
s
...................................138
Cla-Val Three-Year Warranty ..................................................................................144
Cla-Val One-Year Warranty - 700 Series Products ..................................................145
Cla-Val Certifications ..............................................................................................146
Visit www.cla-val.com for extended coverage of our product line
Take a Factory Tour...............................................................................About Us Section
Statement of Qualifications....................................................................About Us Section
Cla-Val Sales Representatives ...........................................................Contact Us Section
Field Service Capabilities and Providers.........................................Field Service Section
Valve Animations..........................................................................See individual products
M-Sheets (Cla-Val Applications Flyers)........................................See individual products
Waterworks Catalog and Brochure....................................................Waterworks Section
Electronic Products .............................................................................Electronics Section
Fire Protection Products ...............................................................Fire Protection Section
Aviation / Ground Fueling Products.............................................Ground Fueling Section
Marine Products...........................................................................Marine Product Section
Wastewater Products.............................................................................Industrial Section
Training Seminars & Product Education .............................Technical Assistance Section
System Troubleshooting......................................................Technical Assistance Section
Software & Drivers Library ..................................................Technical Assistance Section
Service Training Manual .................................................Engineering Resources Section
Waterworks Solution City................................................Engineering Resources Section
Fire Products Solution City .............................................Engineering Resources Section
Improving System Efficiency...........................................Engineering Resources Section
Water Saving Calculator .................................................Engineering Resources Section
Pressure Drop Calculator................................................Engineering Resources Section
How To Order Products...................................................Engineering Resources Section
Cavitation Guide .............................................................Engineering Resources Section
AutoCad Drawings ..........................................................Engineering Resources Section
CLA-VAL WARRANTY
Cla-Val quality products
Page 6
Company Overview
Since 1936, Cla-Val has produced the world’s highest quality automatic control valves for a diverse array of applications and market places. Our special blend of engineering expertise, craftsmanship, quality materials and sophisticated manufacturing processes has earned Cla-Val a reputation for excellence throughout the United States and around the world.
Cla-Val’s Southern California facility serves as the worldwide headquarters and features an on-site foundry as well as a manufacturing operation with more than four-acres under roof. Other North American locations include state-of-the-art machine shops, production facilities and a sales office/ manufacturing operation in Ontario, Canada. Cla-Val offices and production facilities in Switzerland, France and the United Kingdom serve the European and Middle Eastern markets. Cla-Val Pacific in New Zealand covers Australasia and Asia.
All Cla-Val automatic control valves and associated products are made from the highest quality materials and backed by the best warranty in the industry. Cla-Val provides a broad range of valve patterns and sizes in over fifty different varieties of metals and grades. To help ensure that our customers receive the technical and product support they need, we conduct the industry’s most comprehensive engineering and application seminars. We also offer in-depth end-user training programs to help our customers derive the maximum benefit from their product investment.
Engineering Capabilities
One of Cla-Val’s most unique characteristics is the strong focus we place on continuous improvement in our products and manufacturing processes. This focus is personified by our in-house Engineering Department. They work hand­in-hand with our customers to develop real-world solutions, such as the recently developed KO Anti-Cavitation valve trim pictured below, to help them meet their operational challenges. Cla-Val Engineers continue to create products that ultimately become the industry standard.
With strategically located distribution centers and sales offices throughout the world, Cla-Val is the ideal source for superior technical know-how, unparalleled customer service and the finest quality fluid handling products.
Utilizing a wide array of the most advanced technical software, including custom programs developed in-house, our Engineers analyze product applications, and study our customers’ fluid handling systems to characterize conditions such as Cv, surge, flow, and the potential for valve cavitation noise and damage. This expertise enables our Engineers to take the data they gather and determine which flow or pressure control products will best meet our customers’ system requirements in the most operationally efficient and cost effective manner.
Beyond analyzing and understanding our customers’ existing requirements, Cla-Val Engineering uses the latest in solid modeling design software to develop new products to meet the ever-changing requirements of the industries we serve. To further enhance the value we provide, our Manufacturing Engineers continually work to develop and implement the latest technologies in our production and foundry facilities to ensure that all of our products are crafted with the highest possible quality, precision and exceptional accuracy.
Cla-Val product innovations --
destined to become tomorrow’s standards.
6
Page 7
P
1
P
2
P
BASIC MAIN VALVE
Most CLA-VAL valves consist of a main valve and pilot control system. The basic main valve is called a Hytrol Valve.
When no pressure is in the valve, the spring and the weight of the diaphragm assembly hold the valve closed.
With the cover chamber vented to atmosphere, the valve will open from line pressure under the disc.
If inlet pressure is connected into the cover chamber, the valve closes tightly. In this example, the 400 pound differ­ence is the force which pushes the disc against the seat and causes the valve to seal drip-tight.
NON-MODULATING CONTROLS
A simple control which either opens the valve wide or closes it tightly is a three-way valve. The type of operation this control gives is called “non-modulating” because the valve cannot pause in a partially open position.
To open...
Control is turned to exhaust cover chamber pressure.
Ordinary three-way valves usually are not satisfactory because they require so much force to operate. An easy-turning control which can be operated in a variety of ways is usually used. Several examples of controls and their operation are shown at right.
With a solenoid
Once the control is turned to either position, operating fluid flow into or out of the cover chamber until the valve is open or closed. For example...
To close...
Control is turned to apply pressure to cover chamber.
By hand
C
L
N
O
E
S
P
E
O
D
By pressure
By a difference in
two pressures
By a float
7
Page 8
MODULATING CONTROLS
The Cla-Val Automatic Control Valve modulates if the cover pressure is held between the inlet and outlet pressure. To achieve modulating operation, a slightly different type of control system is utilized.
Valve Open
When the throttling control opens to a point where more pressure is relieved from the cover chamber than the restriction can supply, cover pressure is reduced and the valve opens.
Valve Throttling
The main valve modulates to any degree of opening in response to changes in the throttling control. At an equi­librium point, the main valve opening and closing forces hold the valve in balance. This balance holds the valve partially open, but immediately responds and readjusts its position to compensate for any change in the con­trolled condition.
Valve Closed
When the modulating control closes sufficiently to direct a great enough pressure into the cover chamber to overcome opening forces of line pressure, the main valve closes.
AUTOMATIC CONTROLS
The following examples illustrate several different types of operation utilizing automatic controls.
Pressure Reduction
Outlet pressure on control diaphragm causes the main valve to hold a steady outlet pressure.
Pressure Relief
Inlet pressure on control diaphragm causes the main valve to hold a steady inlet pressure.
Liquid Level Controller
Slight changes in flow through the float control causes main valve to counteract changes in reservoir level so liquid level is held constant.
Rate of Flow Controller
Limits the maximum flow rate by changes to the main valve counter­act any slight changes in differential pressure across an orifice plate located in the main line.
8
Page 9
Q
A
&
Q
A
&
KO ANTI-CAVITATION OPERATION
First Stage Pressure Reduction
• Flow enters through the seat
Second Stage Pressure Reduction
• Flow impinges upon itself within the seat and disc guide assembly to dissipate cavitation and further reduce pressure
Third Stage Pressure Reduction
• Flow exits through the disc guide for final
KO Anti-Cavitation
Internal Trim
pressure reduction
• Diagonal disc guide slots direct flow away from surfaces.
Which way should fluid flow through a CLA-VAL Valve?
Q
Just as with any globe valve, the usual way is “under–the–disc” as shown.
A
The main exception to the “under-the-disc” rule of thumb is the check valve.
“Under-the-Disc”
What purpose does the
Q
internal spring in the Hytrol valve serve?
To provide enough force to close the valve when
A
no difference exists between inlet, cover and outlet pressures. When the inlet pressure is greater than outlet pres­sure (even by a small amount) the hydraulic forces, -- NOT THE SPRING hold the valve tightly closed.
Can the opening and closing speed of a CLA-VAL Valve be controlled?
Q
Yes. It is a matter of controlling the rate at which operating fluid flows into or out of the cover chamber.
A
Here is a typical valve equipped with both opening and closing speed controls. A simple needle valve can be used for these controls.
Normal so valve closes against the pressure
Can pressure other than line pressure be used to operate CLA-VAL Valves?
Q
Yes. Frequently, when line fluid is too dirty or otherwise unsuitable, a separate source of pressure is desired. Clean water, air (with some limitations), or oil
A
are suitable. The important point is to make sure the operating pressure is equal or greater than inlet pressure AT ALL TIMES.
What should be done if line pressure is very low? (Below 10 psi)
Q
Usually a separate source of operating pressure is required. A spring to open
A
the valve may be necessary. Consult the factory for recommendations.
Standard Flow
“Over-the-Disc”
Reverse Flow
Acceptable only under specific conditions
B-48 (R-3/2011)
CLA-VAL
PO Box 1325 Newport Beach CA 92659-0325
800-942-6326 Fax: 949-548-5441 Web Site: cla-val.com E-mail: claval@cla-val.com
CLA-VAL CANADA
4687 Christie Drive Beamsville, Ontario Canada L0R 1B4 Phone: 905-563-4963 Fax: 905-563-4040 E-mail sales@cla-val.ca
©COPYRIGHT CLA-VAL 2012 Printed in USA Specifications subject to change without notice.
CLA-VAL EUROPE
Chemin des Mésanges 1
CH-1032 Romanel/ Lausanne, Switzerland Phone: 41-21-643-15-55 Fax: 41-21-643-15-50 E-mail: cla-val@cla-val.ch
CLA-VAL UK
Dainton House, Goods Station Road Tunbridge Wells Kent TN1 2 DH England Phone: 44-1892-514-400 Fax: 44-1892-543-423 E-mail: info@cla-val.co.uk
CLA-VAL FRANCE
Porte du Grand Lyon 1 ZAC du Champ du Périer France - 01700 Neyron Phone: 33-4-72-25-92-93 Fax: 33-4-72-25-04-17 E-mail: cla-val@cla-val.fr
9
Page 10
Value Added Upgrades...
Cla-Valʼs flexible design allows for a wide
range of upgrades to further enhance
system performance.
Model X144 e-FlowMeter
patent pending
Inserts directly into an inlet
tapping of a control valve
X143 Series Power Generators
Model X143MP
Micro Turbine
Power Generator
Model X143IP
Intermediate
Power Generator
Model X143HP Hydro Power Generator
uses the hydraulic energy
of the distribution system to
produce power for site equipment
Model X101 Valve Position Indicator
10
Page 11
...Go Beyond Standard
X117 Series
Valve Position Indicator
X117D
Accurately monitor valve
position, IP-68 submersible
X105 Limit Switch
Assembly
X117E
X140-01 Locking
Security Cap
Electronic Pilot Controls
33 Series
33 Series:
Remote electronic control
CPC Series:
Position control
CTC
Series
CTC:
Timer-based control
CPC Series
Prevents
tampering of pilot
controls
Model X141
Pressure Gauge
Factory mounted on
valve inlet and outlet
Dura-Kleen® Stem
Delrin® Sleeved Stems
Helps to extend valve life
in applications with harsh
or corrosive fluids
Model X43H-Style Strainer
Ductile Iron, fusion-
bonded epoxy
coating and
Stainless Steel
strainer mesh for
longer service life
11
Page 12
U
n
d
e
r
g
r
o
u
n
d
S
o
u
r
c
e
R
a
w
W
a
t
e
r
f
r
o
m
12
Page 13
Page 14
100-01
(Full Internal Port)
MODEL
(Sizes 3/8"-36")
Hytrol Valve
Drip-Tight, Positive Seating
Service Without Removal From Line
Threaded, Flanged or Grooved Ends
Globe or Angle Pattern
100% Factory Tested
The Cla-Val Model 100-01 Hytrol Valve is a hydraulically operated, diaphragm actuated, globe or angle pattern valve. It consists of three major components: body, diaphragm assembly, and cover. The diaphragm assembly is the only moving part.
The diaphragm assembly is guided top and bottom by a precision machined stem. It utilizes a non-wicking diaphragm of nylon fabric bonded with synthetic rubber. A resilient synthetic rubber disc retained on three and one half sides by a disc retainer forms a drip-tight seal with the renewable seat when pressure is applied above the diaphragm.
The Model 100-01 is the basic valve used in nearly all Cla-Val Automatic Control Valves. It is the valve of choice for system applications requiring remote control, pressure regulation, solenoid operation, rate of flow control, liquid level control or check valve operation. The rugged simplici­ty of design and packless construction assure a long life of dependable, trouble-free operation. It is available in various materials and in a full range of sizes, with either threaded, flanged or grooved ends. Its applications are unlimited.
Principle of Operation
On-Off Control
Full Open Operation
When pressure in the is relieved to a zone of lower pres­sure, the line pressure at the valve inlet opens the valve, allowing full flow.
14
cover chamber
On-Off Control
Tight Closing Operation
When pressure from the valve inlet is applied to the cover chamber, the valve closes drip-tight.
Modulating
Control
Modulating Action
The valve holds any intermediate position when operating pressures are equal above and below the diaphragm. A Cla-Val “Modulating” Pilot Control will allow the valve to automatically compensate for line pressure changes.
Page 15
Specifications Model 100-01
Available Sizes
Pattern Threaded Flanged Grooved End
Globe
Angle 1" - 3" 11⁄2" - 16" & 24" 2" - 3" - 4"
Pressure Ratings
ASTM A536 Ductile Iron B16.42 250 400 400 400
ASTM A216-WCB Cast Steel B16.5 285 400 400 400
ASTM B62 Bronze B16.24 225 400 400 400
Note: * ANSI standards are for flange dimensions only.
Valves for higher pressure are available; consult factory for details
3
8" - 3" 11⁄2" - 36" 11⁄2"-2"- 21⁄2"- 3"- 4"- 6"- 8"
(Recommended Maximum Pressure - psi)
Valve Body & Cover
Grade Material
Flanged valves are available faced but not drilled.
‡ End Details machined to ANSI B2.1 specifications.
ANSI
Standards*
Pressure Class
Flanged Grooved Threaded
150
300
Class
Class
Operating Temp. Range
300
Class
End‡
Details
Materials
Component Standard Material Combinations
Body & Cover Ductile Iron Cast Steel Bronze
Available Sizes 3/8" - 36" 1" - 16" 1" -16"
Disc Retainer & Diaphragm Washer
Trim: Disc Guide, Seat & Cover Bearing
Disc Buna-N®Rubber Diaphragm Nylon Reinforced Buna-N®Rubber Stem, Nut & Spring Stainless Steel
For material options not listed, consult factory. Cla-Val manufactures valves in more than 50 different alloys.
Cast Iron Cast Steel Bronze
Bronze is Standard
Stainless Steel is optional
Fluids
-40°to 180°F
KO Anti-Cavitation Trim Option
KO DISC GUIDE
KO SEAT
COVER
Cover Bolt
6" and Smaller
*
DIAPHRAGM
*
DISC GUIDE
BODY
(Globe
or
Angle)
SPRING
DISC
SEAT
PIPE PLUG
COVER BEARING
STEM NUT
DIAPHRAGM WASHER
DISC RETAINER
*
SPACER WASHERS
STEM
Seat Screw
8" and Larger
SEAT O-RING
*
Repair Parts
HEX NUT
8" and Larger
PIPE PLUG
STUD
8" and Larger
PIPE PLUG
Viton®Rubber Parts- suffix KB
Optional diaphragm, disc and o-ring fabri­cated with Viton
®
synthetic rubber. Viton®is well suited for use with mineral acids, salt solutions, chlorinated hydrocarbons, and petroleum oils; and is primarily used in high temperature applications up to 250° F.
not use with epoxy coatings above
175° F.
Epoxy Coating - suffix KC
This option NSF 61 Listed and FDA approved, fusion bonded epoxy coating is for use with cast iron, ductile iron or steel valves. This coating is resistant to various water conditions, certain acids, chemicals, solvents and alkalies.
Epoxy coatings are applied in accordance with AWWA coating specifications C116-03. Do not use with temperatures above
175° F.
Dura-Kleen® Stem - suffix KD
This stem is designed for applications where water supplies containing dissolved minerals create deposits that build-up on a standard stem and hamper valve opera­tion. A patented, self-cleaning design on
Do
the stem allows all valve sizes to operate freely in the harshest conditions.
®
Delrin
The Delrin
Sleeved Stem- suffix KG
®
sleeved stem is designed for applications where water supplies contain dissolved minerals which can form deposits that build up on the valve stem and hamper valve operation. Scale build­up will not adhere to the Delrin stem. Delrin
®
sleeved stems are not rec­ommended for valves in continuous opera­tion where differential pressures are in
®
sleeve
-
Anti-Cavitation Trim
suffix KO
Anti-Cavitation Trim components consist of a stainless steel radial slotted disc guide and seat. This system is used when high differentials are present across the valve.
-
Water Treatment Clearance
suffix KW
This additional clearance is beneficial in applications where water treatment com­pounds can interfere with the closing of the valve. The smaller outside diameter disc guide provides more clearance between the disc guide and the valve seat. This option is best suited for valves used in on­off (non-modulating) service.
excess of 80 psi (2" and larger Hytrol valves).
For assistance in selecting appropriate valve options or valves manufactured with special design requirements, please contact our Regional Sales Office or Factory.
15
Page 16
12
1
1/2
23 4 6810 16
2
1/2
14 24
11/4
1
1
2
34
6
810
12
24
2
1/2
11/2
14
16
11/4
3630
20
18
1/2*1*3/4*
(*Non Guided Stem)
3/8*
1
10 20 30 40 60 80 100 200 500 1000 2000 5000 10,000 20,000 50,000
1
2
3
4
6
8
10
20
30
40
60
80
100
5 3
Angle Valve Sizes (Inches)
Globe Valve Sizes (Inches)
Pressure Drop — psi
Flow Rate gpm (water)
1
100,000
K =
894d
4
C
2
v
L =
K
12 f
K Factor (Resistance Coefficient)
The Value of K is calculated from the formula: (U.S. system units)
Equivalent Length of Pipe
Equivalent lengths of pipe (L) are determined from the formula: (U.S. system units)
Fluid Velocity
Fluid velocity can be calculated from the following formula: (U.S. system units)
d
V =
.4085 Q
2
d
C
V
Factor
Formulas for computing C Factor, Flow (Q) and Pressure Drop
V
( P):
C
V
=
Q
P
C
V
=
Q
P
C
V
=
Q
P
2
V
Where:
U.S. (gpm) @ 1 psi differential at 60 F water
(l/s) @ 1 bar (14.5 PSIG) differential
or
at 15 C water
inside pipe diameter of Schedule 40 Steel Pipe (inches)
friction factor for clean, new Schedule 40 pipe
(dimensionless) (from Cameron Hydraulic Data,
18th Edition, P 3-119)
Resistance Coefficient (calculated)
Equivalent Length of Pipe (feet)
Flow Rate in U.S. (gpm) or (l/s)
Fluid Velocity (feet per second) or (meters per second)
Pressure Drop in (psi) or (bar)
=
=
=
=
=
=
=
=
=
P
V
Q
L
K
f
d
C
Functional Data Model 100-01
Globe
Pattern
Angle
Pattern
Globe
Pattern
Angle
Pattern
Globe Pattern
Angle Pattern
Inches
mm.
Gal./Min.(gpm.)
Litres/Sec. (l/s.)
Gal./Min.(gpm.)
Litres/Sec. (l/s.)
Feet (ft.)
Meters (m.)
Feet (ft.)
Meters (m.)
Fl. Oz
U.S. Gal.
ml
Litres
Valve Size
C
V
Factor
Equivalent
Length
of
Pipe
K
Factor
Liquid Displaced
from Cover
Chamber When
Valve Opens
† Non Guided Stem
3
1
3
8
2
4†1
111⁄4 11⁄2 221⁄2 346810 12 14 16 18 20 24 30 36
10 15 20 25 25 32 40 50 65 80 100 150 200 250 300 350 400 450 500 600 750 900
1.8 6 8.5 13.3 20 30 32 54 85 115 200 440 770 1245 1725 2300 3130 3725 5345 7655 10150 14020
.43 1.44 2.04 3.2 4.8 7.2 7.7 13 20 28 48 106 185 299 414 552 752 894 1286 1837 2436 3200
————212729611011392405419901575 2500* 3060*4200* — — 9950* —
— — — — 5.0 6.5 7 15 24 33 58 130 238 378 600 734 1008 — — 2388
25 7 16 23 10 19 37 51 53 85 116 211 291 347 467 422 503 612 595 628 1181 2285
7.6 2.2 4.8 7.1 3.1 5.7 12 15.5 16 26 35 64 89 106 142 129 154 187 181 192 552 569
————9.0284640375880139176217222* 238* 247* — 372*
— — — — 2.8 8.7 14 12 11 18 25 43 54 66 68 73 75 113
16.3 3.7 5.7 6.1 2.7 3.6 5.9 5.6 4.6 6.0 5.9 6.2 6.1 5.8 6.1 5.0 5.2 5.2 4.6 4.0 5.3 7.8
— — — — 2.5 4.4 7.1 4.4 3.3 4.1 4.1 4.1 3.7 3.6 2.9 2.8 2.6 2.4
.12.34.34.70————————— — — — — — — — — —
— — — — .02 .02 .02 .03 .04 .08 .17 .53 1.26 2.51 4.0 6.5 9.6 11 12 29 42 90
3.5 10.1 10.120.7 20.775.7 75.7 121 163 303 643 — —
— — — — — — — — — — — 2.0 4.8 9.5 15.1 24.6 36.2 41.6 45.4 109.8 197 340
*Estimated
Model 100-01 Flow Chart (Based on normal flow through a wide open valve)
16
Page 17
CLA-VAL
Copyright Cla-Val 2012 Printed in USA Specifications subject to change without notice.
P.O. Box 1325 Newport Beach, CA 92659-0325 Phone: 949-722-4800 Fax: 949-548-5441 E-mail: claval@cla-val.com Website cla-val.com
©
Dimensions
100-01
3/8”, 1/2”, 3/4”, 1” Auxillary Hytrol Valves with non Guided Stems
B
Inlet Outlet
A
(Diameter)
B
100-01
Threaded &
Flanged
H
J
C
(MAX)
E
G
GG
GGG
Inlet
A
AA
AAA
Inlet
D
DD
DDD
J
K
C
(MAX)
Outlet
E
F
FF
Model 100-01
100-01
H
Inlet
Grooved
B
Inlet
AAAA
(Diameter)
J
K
DDDD
CC
(MAX)
EE
Outlet
GGGG
Valve Size (Inches) 3/8* 1/2* 3/4*1* 11 1/4 1 1/2 22 1/2 3468101214161820243036
A Threaded AA 150 ANSI AAA 300 ANSI AAAA Grooved End
B Dia. C Max. CC Max. Grooved End D Threaded DD 150 ANSI DDD 300 ANSI DDDD Grooved End E EE Grooved End F 150 ANSI FF 300 ANSI G Threaded GG 150 ANSI GGG 300 ANSI GGGG Grooved End H NPT Body Tapping J NPT Cover Center Plug K NPT Cover Tapping
Valve Stem Internal
Thread UNF
Stem Travel
Approx. Ship Wt. Lbs.
2.75 3.50 3.50 5.12 7.25 7.25 7.25 9.38 11.00 12.50 — — ——————8.509.3811.0012.0015.0020.0025.3829.7534.0039.0041.3846.0052.0061.5063.0076.00 — — 9.00 10.00 11.62 13.25 15.62 21.00 26.38 31.12 35.50 40.50 43.50 47.64 53.62 63.24 64.50 76.00 ——————8.509.0011.0012.5015.0020.0025.38—————————
2.50 3.12 3.12 4.38 5.62 5.62 5.62 6.62 8.00 9.12 11.50 15.75 20.00 23.62 28.00 32.75 35.50 41.50 45.00 53.16 56.00 66.00
2.33 5.88 5.88 6.25 5.50 5.50 5.50 6.50 7.56 8.19 10.62 13.38 16.00 17.12 20.88 24.19 25.00 39.06 41.90 43.93 54.60 61.50 — — 4.75 5.75 6.88 7.25 9.31 12.12 14.62 — — ————3.253.253.254.755.506.25— — — ————————— — — 4.00 4.75 5.50 6.00 7.50 10.00 12.69 14.88 17.00 19.50 20.81 — 30.75 — — ——————4.255.005.886.387.8810.5013.2515.5617.7520.2521.62— —31.62— — — — 4.75 — 6.00 7.50
1.25 0.88 0.88 1.63 1.12 1.12 1.12 1.50 1.69 2.06 3.19 4.31 5.31 9.25 10.75 12.62 15.50 12.95 15.00 17.75 21.31 24.56 — — 2.00 2.50 2.88 3.12 4.25 6.00 7.56 — ——————2.503.003.503.754.505.506.758.009.5010.5011.7515.0016.5019.2522.5025.60 — — 3.06 3.25 3.75 4.13 5.00 6.25 7.50 8.75 10.25 11.50 12.75 15.00 16.50 19.25 24.00 25.60 ————1.881.881.883.254.004.50— — — ————————— — — 4.00 3.25 4.00 4.00 5.00 6.00 8.00 8.62 13.75 14.88 15.69 — 22.06 — — ——————4.253.504.314.385.316.508.509.3114.5015.6216.50— —22.90— — — — 3.25 — 4.25 5.00 — —.125.125.25.375.375.375.375.50.50.75.751111111122
.125 .125 .125 .25 .25 .25 .25 .50 .50 .50 .75 .75 1 1 1.25 1.5 2 1.5 1.5 1.5 2 2
—.125.125.25.375.375.375.375.50.50.75.751111111122
— 10-32 10-32 10-32 10-32 10-32 1⁄4-28 1⁄4-28 3⁄8-24 3⁄8-24 3⁄8-24 3⁄8-24 3⁄8-24 1⁄2-20 3⁄4-16 3⁄4-16 3⁄4-16 3⁄4-16 3⁄4-16
————0.40.40.40.60.70.81.11.72.32.83.44.04.55.15.636.757.58.5
3 3 8 8 15 15 15 35 50 70 140 285 500 780 1165 1600 2265 2982 3900 6200 7703 11720
Note: The top two flange holes on valve size 36 are threaded to 1 1/2"-6 UNC.*Non Guided Stem Auxillary Hytrol Controls
Valve Size (mm) 10* 15* 20* 25* 25 32 40 50 65 80 100 150 200 250 300 350 400 450 500 600 750 900
A Threaded AA 150 ANSI AAA 300 ANSI AAAA Grooved End B Dia. C Max. CC Max. Grooved End D Threaded DD 150 ANSI DDD 300 ANSI DDDD Grooved End E EE Grooved End F 150 ANSI FF 300 ANSI G Threaded GG 150 ANSI GGG 300 ANSI GGGG Grooved End H NPT Body Tapping J NPT Cover Center Plug K NPT Cover Tapping
Valve Stem Internal Thread UNF
Stem Travel Approx. Ship Wt. Kgs.
Cla-Val Control Valves operate with maximum efficiency when mounted in horizontal piping with the main valve cover UP, however, other positions are acceptable. Due to component size and weight of 8 inch and larger valves, installation with cover UP is advisable. We recommend isolation valves be installed on inlet and outlet for maintenance. Adequate space above and around the valve for service personnel should be considered essential. A regular maintenance program should be established based on the specific application data. However, we recommend a thorough inspection be done at least once a year. Consult factory for specific recommendations.
70 89 89 130 184 184 184 238 279 318
——————2162382793053815086457568649911051 1168 1321 1562 1600 1930 — 229 254 295 337 397 533 670 790 902 1029 1105 1210 1362 1606 1638 1930
——————216228279318381508645————————— 64 80 80 111 143 143 143 168 203 232 292 400 508 600 711 832 902 1054 1143 1350 1422 1676 59 149 149 159 140 140 140 165 192 208 270 340 406 435 530 614 635 992 1064 1116 1387 1562
120 146 175 184 236 308 371
————838383121140159————————————
102 121 140 152 191 254 322 378 432 495 528 781
——————108127149162200267337395451514549——803——
121 152 191 — 32 23 23 42 29 29 29 38 43 52 81 110 135 235 273 321 394 329 381 451 541 624
52 64 73 79 108 152 192
——————64768995114140171203241267298381419489572650
78 83 95 105 127 159 191 222 260 292 324 381 419 489 610 650
————48484883102114————————————
102 83 102 102 127 152 203 219 349 378 399 560
——————10289110111135165216236368397419——582——
83 108 127
—.125.125.25.375.375.375.375.50.50.75.751111111122
.125 .125 .125 .25 .25 .25 .25 .50 .50 .50 .75 .75 1 1 1.25 1.5 2 1.5 1.5 1.5 2 2
—.125.125.25.375.375.375.375.50.50.75.751111111122
— 10-32 10-32 10-32 10-32 10-32
————1010
10 15 18 20 28 43 58 71 86 102 114 130 143 171 190 216
1⁄4-28 1⁄4-28 3⁄8-24 3⁄8-24 3⁄8-24 3⁄8-24 3⁄8-24 1⁄2-20 3⁄4-16 3⁄4-16 3⁄4-16 3⁄4-16 3⁄4-16
1.4 1.4 1.4 6 7 7 7 16 23 32 64 129 227 354 528 726 1027 1353 1769 2812 3494 5316
E-100-01 (R-8/2011)
17
Page 18
100-02
MODEL
(Full Internal Port)
Powertrol Valve
Drip-Tight, Positive Seating
Service Without Removal From Line
Threaded or Flanged Ends
Globe or Angle Pattern
Every Valve Factory Tested
The Cla-Val Model 100-02 is a hydraulically operated, diaphragm actuated, globe, or angle pattern valve. It consists of four major components: body, intermediate chamber, diaphragm assembly, and cover. The diaphragm assembly is the only moving part.
The diaphragm assembly which is guided top and center by a pre­cision machined stem, utilizes a non-wicking diaphragm of nylon fabric bonded with synthetic rubber. The diaphragm forms a seal between the cover chamber and intermediate chamber. A syn­thetic rubber disc retained on three and one half sides forms a drip-tight seal with the renewable seat when pressure is applied above the diaphragm. As pressure above the diaphragm is relieved and pressure is applied below the diaphragm, the valve opens wide for full flow. The rate of closing or opening can be con­trolled by modulating flow into or out of the diaphragm chambers.
The Model 100-02 is recommended where independent operating pressure is desired. Available in various materials and in a full range of sizes, with either threaded or flanged ends, its applica­tions are many and varied.
Principle of Operation
Four-Way Control
Full Open Operation
When operating pressure below the diaphragm is applied and operating, pressure is relieved from the cover chamber and, the valve is held open, allowing full flow.
18
Four-Way Control
Tight Closing Operation
When pressure below the diaphragm is relieved and operating pressure is applied to the cover chamber, the valve closes drip-tight.
Four-Way Control with Lock
Modulating Action
The valve holds any intermediate position when operating pressure is equal above and below the diaphragm. A Cla-Val four-way pilot control with "lock" position can main­tain this balance by stop­ping flow in the pilot con­trol system.
Page 19
Specifications
Available Sizes
Pattern Threaded Flanged Grooved End
Globe3⁄8" - 3" 11⁄2" - 30" 11⁄2"-2"- 21⁄2"- 3"- 4"- 6"- 8"
Angle 11⁄2" - 3" 2" - 16" 2" - 3" - 4"
Operating Temp. Range
Fluids
-40° to 180° F
PIPE PLUG
HEX NUT
BEARING COVER
UPPER DIAPHRAGM WASHER
Model 100-02
PIPE PLUG
COVER
UPPER STEM NUT
Pressure Ratings
Valve Body & Cover
Grade Material
(Recommended Maximum Pressure - psi)
Pressure Class
Flanged Threaded
ANSI
Standards*
150
Class
300†
Class
End‡
Details
ASTM A536 Ductile Iron B16.42 250 400 400
ASTM A216-WCB Cast Steel B16.5 285 400 400
ASTM B62 Bronze B16.24 225 400 400
Note: * ANSI standards are for flange dimensions only.
Flanged valves are available faced but not drilled. ‡ End Details machined to ANSI B2.1 specifications. † Consult factory when Maximum Operating Pressure
Differential (MOPD) is greater than 400 PSID
“Valves for higher pressure are available; consult factory for details”
Materials
Component Standard Material Combinations
Body & Cover Ductile Iron Cast Steel Bronze
Available Sizes 11⁄4" - 30" 11⁄4" - 16" 11⁄4" - 16"
Disc Retainer & Diaphragm Washer
Trim: Disc Guide, Seat & Cover Bearing
Disc Buna-N®Rubber Diaphragm Nylon Reinforced Buna-N®Rubber Stem, Nut & Spring Stainless Steel
For material options not listed, consult factory. Cla-Val manufactures valves in more than 50 different alloys.
Cast Iron Cast Steel Bronze
Bronze is Standard
Stainless Steel is Optional
LOWER DIAPHRAGM WASHER
POWERUNIT BODY
O-RING
POWERUNIT BEARING
DISC RETAINER
WASHER SPACER
LOCK WASHER
STUD/BOLT
BODY
DIAPHRAGM
RETAINING RING
SEAL GASKET
O-RING
STEM
DISC
DISC GUIDE
LOWER STEM NUT
SEAT
SEAT-O-RING
OUTLET
PIPE PLUG
INLET
Options
Epoxy Coating - suffix KC
This option NSF 61 Listed and FDA approved, fusion bonded epoxy coating is for use with cast iron, ductile iron or steel valves. This coating is resistant to various water conditions, certain acids, chemicals, solvents and alkalies.
Epoxy coatings are applied in accordance with AWWA coating specifications C116-03. Do not use with temperatures above
175° F
For assistance in selecting appropriate valve options or valves manufactured with special design requirements, please contact our
-
Viton® Rubber Parts
Optional diaphragm, disc and o-ring fabricated with Viton
®
synthetic rubber. Viton®is well suited
suffix KB
Regional Sales Office or Factory.
for use with mineral acids, salt solutions, chlori­nated hydrocarbons, and petroleum oils; and is primarily used in high temperature applications up to 250° F. Do not use with epoxy coating above 175°F.
For assistance in selecting appropriate valve options or valves manufactured with special design requirements, please contact our Regional Sales Office or Factory.
19
Page 20
8
1046
10 20 30 40 60 80 100 200 500 1000 2000 5000 10,000 20,000 50,000
1
2
3
4
6
8
10
20
30
40
60
80
100
53
Angle Valve Sizes (Inches)
Globe Valve Sizes (Inches)
2
34
6
810
12
12
24
1
1/2
21/2
11/2
23
14
16
16
1
1/4
21/2
Pressure Drop — psi
14
Flow Rate gpm (water)
20
30
1
18
1/2*1*3/4*
(*Non Guided Stem)
3/8*
K =
894d
4
C
2
v
L =
K
12 f
K Factor (Resistance Coefficient)
The Value of K is calculated from the formula: (U.S. system units)
Equivalent Length of Pipe
Equivalent lengths of pipe (L) are determined from the formula: (U.S. system units)
Fluid Velocity
Fluid velocity can be calculated from the following formula: (U.S. system units)
d
V =
.4085 Q
2
d
C
V
Factor
Formulas for computing C Factor, Flow (Q) and Pressure Drop
V
( P):
C
V
=
Q
P
C
V
=
Q
P
C
V
=
Q
P
2
V
Where:
U.S. (gpm) @ 1 psi differential at 60 F water
(l/s) @ 1 bar (14.5 PSIG) differential
or
at 15 C water
inside pipe diameter of Schedule 40 Steel Pipe (inches)
friction factor for clean, new Schedule 40 pipe
(dimensionless) (from Cameron Hydraulic Data,
18th Edition, P 3-119)
Resistance Coefficient (calculated)
Equivalent Length of Pipe (feet)
Flow Rate in U.S. (gpm) or (l/s)
Fluid Velocity (feet per second) or (meters per second)
Pressure Drop in (psi) or (bar)
=
=
=
=
=
=
=
=
=
P
V
Q
L
K
f
d
C
Functional Data
Valve Size
Globe
C
Factor
Equivalent
Length
of
Pipe
K
Factor
Liquid Displaced from
Cover Chamber When
Valve Opens
*Estimated
Pattern
V
Angle
Pattern
Globe
Pattern
Angle
Pattern
Globe Pattern
Angle Pattern
Inches
mm.
Gal./Min. (gpm.)
Litres/Sec. (l/s.)
Gal./Min. (gpm.)
Litres/Sec. (l/s.)
Feet (ft.)
Meters (m.)
Feet (ft.)
Meters (m.)
Fl. Oz
U.S. Gal.
ml
Litres
Model 100-02
3⁄81⁄23
10 15 20 25 32 40 50 65 80 100 150 200 250 300 350 400 450 500 600 750
1.8 6 8.5 13.3 30 32 54 85 11 5 200 440 770 1245 1725 2300 2940 3725 5345 7655 10150 .43 1.44 2.04 3.2 7.2 7.7 13 20 28 48 106 185 299 414 552 706 894 1286 1837 2436
29 61 101 139 240 541 990 1575 2500* 3060* 4200* — — — 7 15 24 33 58 130 238 378 600 734 1008 — — 25 7 16 23 19 37 51 53 85 116 211 291 347 467 422 503 612 595 628 1181
7.6 2.2 4.8 7.1 5.7 12 15.5 16 26 35 64 89 106 142 129 154 187 181 192 552 — 46 40 37 58 80 139 176 217 222* 238* 247* — — 14 12 12 18 25 43 54 66 68 73 75
16.3 3.7 5.7 6.1 3.6 5.9 5.6 4.6 6.0 5.9 6.2 6.1 5.8 6.1 5.0 5.2 5.2 4.6 4.0 5.3 — — 7.1 4.4 3.3 4.1 4.1 4.1 3.7 3.6 2.9 2.8 2.6
.12 .34 .34 .70 —
— .02 .02 .03 .04 .08 .17 .53 1.26 2.51 4.0 6.5 9.6 11 12 29 42
3.5 10.1 10.1 20.7 75.7 75.7 121 163 303 643 — — — — 2.0 4.8 9.5 15.1 24.6 36.2 41.6 45.4 109.8 197
4 1 11⁄4 11⁄2 2 21⁄2 3 4 6 8 10 12 14 16 18 20 24 30
Model 100-02 Flow Chart (Based on normal flow through a wide open valve)
20
Page 21
CLA-VAL
Copyright Cla-Val 2012 Printed in USA Specifications subject to change without notice.
P.O. Box 1325 Newport Beach, CA 92659-0325 Phone: 949-722-4800 Fax: 949-548-5441 E-mail: claval@cla-val.com Website cla-val.com
©
(Diameter)
B
Dimensions
Valve Size (Inches) A Threaded AA 150 ANSI AAA 300 ANSI AAAA Grooved End B Dia. C Max. CC Max. Grooved End D Threaded DD 150 ANSI DDD 300 ANSI DDDD Grooved End E EE Grooved End F 150 ANSI FF 300 ANSI G Threaded GG 150 ANSI GGG 300 ANSI GGGG Grooved End H NPT Body Tapping J NPT Cover Center Plug K NPT Cover Tapping
Valve Stem Internal Thread UNF
Stem Travel Approx. Ship Wt. Lbs.
100-02
Threaded &
Flanged
H
Inlet
G
GG
GGG
3⁄81⁄23
AA
AAA
A
J
K
C
(MAX)
Outlet
E
F
FF
Inlet
D
DD
DDD
4 1 11⁄4 11⁄2 2 21⁄2 3 4 6 8 10 12 14 16 18 20 24 30
2.75 3.50 3.50 5.12 7.25 7.25 9.38 11.00 12.50 — — — — 8.50 9.38 11.00 12.00 15.00 20.00 25.38 29.75 34.00 39.00 41.38 46.00 52.00 61.50 63.00 — — 9.00 10.00 11.62 13.25 15.62 21.00 26.38 31.12 35.50 40.50 43.50 47.64 53.62 63.24 64.50 — — 8.50 9.00 11.00 12.50 15.00 20.00 25.38 —
2.50 3.12 3.12 4.38 5.62 5.62 6.62 8.00 9.12 11.50 15.75 20.00 23.62 28.00 32.75 35.50 41.50 45.00 53.16 56.00
2.33 5.88 5.88 6.25 7.62 7.62 8.56 10.31 11.19 14.25 18.44 21.81 23.38 29.31 32.12 35.00 49.43 53.09 56.50 68.70 — — 6.87 7.81 9.63 10.25 13.50 17.18 20.43 — — — — 3.25 3.25 4.75 5.50 6.25 — — — 4.00 4.75 5.50 6.00 7.50 10.00 12.69 14.88 17.00 19.50 20.81 — — — — 4.25 5.00 5.88 6.38 7.88 10.50 13.25 15.56 17.75 20.25 21.62 — — — — 4.75 6.00 7.50
1.25 0.88 0.88 1.63 1.12 1.12 1.50 1.69 2.06 3.19 4.31 5.31 9.25 10.75 12.62 15.50 12.95 15.00 17.75 21.31 — — 2.00 2.50 2.88 3.12 4.25 6.00 7.56 — — — 2.50 3.00 3.50 3.75 4.50 5.50 6.75 8.00 9.50 10.50 11.75 15.00 16.50 19.25 22.50 — — 3.06 3.25 3.75 4.13 5.00 6.25 7.50 8.75 10.25 11.50 12.75 15.00 16.50 19.25 24.00 — — 1.88 1.88 3.25 4.00 4.50 — — — 4.00 3.25 4.00 4.00 5.00 6.00 8.00 8.62 13.75 14.88 15.69 — — — — 4.25 3.50 4.31 4.38 5.31 6.50 8.50 9.31 14.50 15.62 16.50 — — ———— — —3.25— 4.255.00 — —
— .125 .125 .25 .375 .375 .375 .50 .50 .75 .75 1 1 1 1 1 1 1 1 2
.125 .125 .125 .25 .25 .25 .50 .50 .50 .75 .75 1 1 1.25 1.50 2 1.5 1.50 1.50 2
— .125 .125 .25 .375 .375 .375 .50 .50 .75 .75 1 1 1 1 1 1 1 1 2 — — 10-3210-32 10-32 10-321⁄4-281⁄4-283⁄8-243⁄8-243⁄8-243⁄8-243⁄8-241⁄2-20 3⁄4-163⁄4-163⁄4-163⁄4-16
0.4 0.4 0.6 0.7 0.8 1.1 1.7 2.3 2.8 3.4 4.0 4.5 5.1 5.63 6.75 7.5
8 8 8 13 22 22 40 65 95 190 320 650 940 1675 2460 3100 4300 5400 8150 10300
Note: The top two flange holes on valve size 36 are threaded to 1 1/2"-6 UNC.
100-02
Grooved
End
(MAX)
Valve Size (mm) 10 15 20 25 32 40 50 65 80 100 150 200 250 300 350 400 450 500 600 750 A Threaded AA 150 ANSI AAA 300 ANSI AAAA Grooved End B Dia. C Max. CC Max. Grooved End D Threaded DD 150 ANSI DDD 300 ANSI DDDD Grooved End E EE Grooved End F 150 ANSI FF 300 ANSI G Threaded GG 150 ANSI GGG 300 ANSI GGGG Grooved End H NPT Body Tapping J NPT Cover Center Plug K NPT Cover Tapping
Valve Stem Internal Thread UNF
Stem Travel
Approx. Ship Wt. Kgs.
Cla-Val Control Valves operate with maximum efficiency when mounted in horizontal piping with the main valve cover UP, however, other positions are acceptable. Due to component size and weight of 8 inch and larger valves, installation with cover UP is advisable. We recommend isolation valves be installed on inlet and outlet for maintenance. Adequate space above and around the valve for service personnel should be considered essential. A regular maintenance program should be established based on the specific application data. However, we recommend a thorough inspection be done at least once a year. Consult factory for specific recommendations.
70 89 89 130 184 184 238 279 318 — — 216 238 279 305 381 508 645 756 864 991 1051 1168 1321 1562 1600 — 229 254 295 337 397 533 670 790 902 1029 1105 1210 1362 1606 1638 — 216 216 228 279 318 381 508 645 — 64 80 80 111 143 143 168 203 232 292 400 508 600 711 832 902 1054 1143 1350 1422 59 149 149 159 194 194 217 262 284 362 468 554 594 744 816 889 1255 1348 1435 1745 — 174 174 198 245 260 343 436 519 — — 83 83 121 140 159 — — 102 121 140 152 191 254 322 378 432 495 528 — — 108 127 149 162 200 267 337 395 451 514 549 — — 121 152 191 — 32 23 23 42 29 29 38 43 52 81 110 135 235 273 321 394 329 381 451 541 — 52 52 64 73 79 108 152 192 — — 64 76 89 95 11 4 140 171 203 241 267 298 381 419 489 572 — 78 83 95 105 127 159 191 222 260 292 324 381 419 489 610 — 48 48 83 102 114 — — 102 83 102 102 127 152 203 219 349 378 399 — — 102 89 110 111 135 165 216 236 368 397 419 — — 83 108 127 — — .125 .125 .25 .375 .375 .375 .50 .50 .75 .75 1 1 1 1 1 1 1 1 2
.125 .125 .125 .25 .25 .25 .50 .50 .50 .75 .75 1 1 1.25 1.50 2 1.5 1.50 1.50 2
.125 .125 .25 .375 .375 .375 .50 .50 .75 .75 1 1 1 1 1 1 1 1 2 — — 10-32 10-32 10-32 10-321⁄4-281⁄4-283⁄8-243⁄8-243⁄8-243⁄8-243⁄8-241⁄2-20 3⁄4-163⁄4-163⁄4-163⁄4-16
10 10 15 18 20 28 43 58 71 86 102 114 130 143 171 191
1.4 1.4 1.4 6 10 10 18 30 43 86 145 295 426 760 1116 1406 1950 2449 3696 4672
E-100-02 (R-9/2011)
21
Page 22
100-03
(Full Internal Port)
MODEL
Powercheck Valve
Built-in Automatic Check Valve
Globe or Angle Pattern
Drip-Tight, Positive Seating
Threaded or Flanged Ends
Packless Construction
The Cla-Val Model 100-03 Powercheck Valve is a hydrauli­cally operated diaphragm valve with a built-in check feature to prevent return flow. Available in globe or angle pattern, it con­sists of four major components: body, intermediate chamber, diaphragm assembly, and cover. The diaphragm assembly is the only moving part.
The diaphragm assembly is guided top and center by a pre­cision machined stem and utilizes a non-wicking diaphragm of nylon fabric bonded with synthetic rubber. A synthetic rub­ber disc retained on three and one half sides forms a drip­tight seal with the renewable seat when pressure is applied above the diaphragm. When pressure above the diaphragm is relieved, the valve opens wide. The rate of closing or open­ing can be controlled by modulating flow into or out of the diaphragm chambers.
When a pressure reversal occurs, the valve will immediately close, preventing reverse flow thru the valve. The split stem will allow the disc retainer assembly to check closed regard­less of the position of the diaphragm.
Principle of Operation
Four-Way Control
Full Open Operation
When operating pressure below the diaphragm is applied and pressure is relieved from the cover chamber, the valve is held open allowing full flow.
Note: For optimum operation of built-in check feature, installation with stem vertically up is recommended.
22
Tight Closing Operation
When pressure below the diaphragm is relieved and operating pressure is applied to the cover chamber, the valve closes drip-tight.
Four-Way Control
When a static condition or pressure reversal occurs, the split stem
design allows the valve to instantly check closed. Return flow is pre­vented regardless of the diaphragm's position.
Four - Way Control
Check Action
Page 23
Specifications
Model 100-03
Available Sizes
Pattern Threaded Flanged
Globe 2
Angle 2
Pressure Ratings
Valve Body & Cover
Grade Material
1
2" - 3" 2 1⁄2" - 16"
1
2" - 3" 2 1⁄2" - 16"
(Recommended Maximum Pressure - psi)
ANSI
Standards*
Operating Temp. Range
Fluids
-40° to 180° F
Pressure Class
Flanged Grooved Threaded
150
Class
300
Class
300
Class
End‡
Details
ASTM A536 Ductile Iron B16.42 250 400 400 400
ASTM A216-WCB Cast Steel B16.5 285 400 400 400
ASTM B62 Bronze B16.24 225 400 400 400
Note: * ANSI standards are for flange dimensions only.
Flanged valves are available faced but not drilled.
‡ End Details machined to ANSI B2.1 specifications.
Valves for higher pressure are available; consult factory for details
Materials
Component Standard Material Combinations
Body & Cover Ductile Iron Cast Steel Bronze
Available Sizes 21⁄2" - 16" 21⁄2" - 16" 21⁄2" - 16"
Disc Retainer & Diaphragm Washer
Trim: Disc Guide, Seat & Cover Bearing
Disc Buna-N®Rubber Diaphragm Nylon Reinforced Buna-N®Rubber Stem, Nut & Spring Stainless Steel
For material options not listed, consult factory. Cla-Val manufactures valves in more than 50 different alloys.
Cast Iron Cast Steel Bronze
Bronze is Standard
Stainless Steel is Optional
PIPE PLUG
HEX NUT
BEARING COVER
UPPER DIAPHRAGM WASHER
LOWER DIAPHRAGM WASHER
POWERUNIT BODY
O-RING
POWERUNIT BEARING
UPPER STEM
SPRING
DISC RETAINER
WASHER SPACER
LOCK WASHER
SEAT
STUD/BOLT
BODY
PIPE PLUG
COVER
UPPER STEM NUT
DIAPHRAGM
RETAINING RING
SEAL GASKET
O-RING
LOWER STEM
DISC
DISC GUIDE
LOWER STEM NUT
SEAT-O-RING
OUTLET
Options
Epoxy Coating - suffix KC
This option NSF 61 Listed and FDA approved, fusion bonded epoxy coating is for use with cast iron, ductile iron or steel valves. This coating is resistant to various water conditions, certain acids, chemi­cals, solvents and alkalies.
ings are applied in accordance with AWWA coating specifications C116-03. Do not use with temperatures above
Viton® Rubber Parts
Optional diaphragm, disc and o-ring fabri­cated with Viton® synthetic rubber. Viton® is well suited for use with mineral acids, salt solutions, chlorinated hydrocarbons, and petroleum oils; and is primarily used in high temperature applications up to 250° F. above
Do not use with epoxy coating
175° F.
-
suffix KB
Epoxy coat-
175° F
PIPE PLUG
INLET
For assistance in selecting appropriate valve options or valves manufactured with special design requirements, please contact our Regional Sales Office or Factory.
23
Page 24
10 20 30 40 60 80 100 200 500 1000 2000 5000 10,000 20,000 50,000
1
2
3
4
6
8
10
20
30
40
60
80
100
53
Pressure Drop — psi
Flow Rate gpm (water)
Angle Valve Sizes (Inches)
8
1046
12
3
16
2
1/2
14
34
6
810
12
21/2
14
16
Globe Valve Sizes (Inches)
Functional Data
Valve Size
C
V
Factor
Equivalent
Length
of
Pipe
K
Factor
Liquid Displaced from
Cover Chamber When
Valve Opens
*Estimated
C
Factor
V
Formulas for computing C Factor, Flow (Q) and Pressure Drop
Q
=
C
V
K Factor (Resistance Coefficient)
The Value of K is calculated from the formula: (U.S. system units)
Equivalent Length of Pipe
Equivalent lengths of pipe (L) are determined from the formula: (U.S. system units)
Fluid Velocity
Fluid velocity can be calculated from the following formula: (U.S. system units)
Inches 21⁄2 3 4 6 8 10 12 14 16
Globe
Pattern
Angle
Pattern
Globe
Pattern
Angle
Pattern
Globe Pattern
Angle Pattern
mm.
Gal./Min. (gpm.)
Litres/Sec. (l/s.)
Gal./Min. (gpm.)
Litres/Sec. (l/s.)
Feet (ft.)
Meters (m.)
Feet (ft.)
Meters (m.)
Fl. Oz
U.S. Gal.
ml
Litres
65 80 100 150 200 250 300 350 400 85 11 5 200 440 770 1245 1725 2300 2940 20 28 48 106 185 299 414 552 706
101 139 240 541 990 1575 2500* 3060* 4200*
24 33 58 130 238 378 600 734 1008 53 85 116 211 291 347 467 422 503 16 26 35 64 89 106 142 129 154 37 58 80 139 176 217 222* 238* 247* 12 18 25 43 54 66 68 73 75
4.6 6.0 5.9 6.2 6.1 5.8 6.1 5.0 5.2
3.3 4.1 4.1 4.1 3.7 3.6 2.9 2.8 2.6 —
.04 .08 .17 .53 1.26 2.51 4.0 6.5 9.6
163 303 643
2.0 4.8 9.5 15.1 24.6 36.2
V
2
Q
K =
P
=
894d
C
v
C
V
4
2
=
C
P
Q
P
V
V =
( P):
L =
.4085 Q
d
K
12 f
2
d
Model 100-03
Where:
C
=
U.S. (gpm) @ 1 psi differential at 60 F water
V
(l/s) @ 1 bar (14.5 PSIG) differential
=
at 15 C water
=
inside pipe diameter of Schedule 40 Steel Pipe (inches)
d
friction factor for clean, new Schedule 40 pipe
=
f
(dimensionless) (from Cameron Hydraulic Data,
18th Edition, P 3-119)
Resistance Coefficient (calculated)
=
K
=
Equivalent Length of Pipe (feet)
L
=
Flow Rate in U.S. (gpm) or (l/s)
Q
=
Fluid Velocity (feet per second) or (meters per second)
V
=
Pressure Drop in (psi) or (bar)
P
or
Model 100-03 Flow Chart (Based on normal flow through a wide open valve)
24
Page 25
Dimensions
100-03
Threaded &
Flanged
H
B
(Diameter)
J
K
C
(MAX)
Model 100-03
Inlet
G
GG
GGG
A
AA
AAA
Inlet
D
DD
DDD
E
Outlet
F
FF
Valve Size (Inches) 2 1⁄2 3 4 6 8 10 12 14 16
A Threaded AA 150 ANSI AAA 300 ANSI
B Dia. C Max. D Threaded DD 150 ANSI DDD 300 ANSI E F 150 ANSI FF 300 ANSI G Threaded GG 150 ANSI GGG 300 ANSI H NPT Body Tapping J NPT Cover Center Plug K NPT Cover Tapping
Valve Stem Internal Thread UNF
Stem Travel
Approx. Ship Wt. Lbs.
11.00 12.50
11.00 12.00 15.00 20.00 25.38 29.75 34.00 39.00 41.38
11.62 13.25 15.62 21.00 26.38 31.12 35.50 40.50 43.50
8.00 9.12 11.50 15.75 20.00 23.62 28.00 32.75 35.50
10.31 11.19 14.25 18.44 21.81 23.38 29.31 32.12 35.00
5.50 6.25
5.50 6.00 7.50 10.00 12.69 14.88 17.00 19.50 20.69
5.81 6.63 7.81 10.50 13.19 15.56 17.75 20.25 21.75
1.69 2.06 3.19 4.31 5.31 9.25 10.75 12.62 15.50
3.50 3.75 4.50 5.50 6.75 8.00 9.50 10.50 11.75
3.75 4.13 5.00 6.25 7.50 8.75 10.25 11.50 12.75
4.00 4.50
4.00 4.00 5.00 6.00 8.00 8.62 13.75 14.88 15.69
4.31 4.38 5.31 6.50 8.50 9.31 14.50 15.62 16.50 .50 .50 .75 .75 1 1 1 1 1 .50 .50 .75 .75 1 1 1.25 1.50 2 .50 .50 .75 .75 1 1 1 1 1
10-32
1
4-28
1
4-28
3
8-24
3
8-24
3
8-24
3
8-24
3
8-24
1
2-20
0.7 0.8 1.1 1.7 2.3 2.8 3.4 4.0 4.5
65 95 190 320 650 940 1675 2460 3100
Valve Size (mm) 65 80 100 150 200 250 300 350 400 A Threaded AA 150 ANSI AAA 300 ANSI B Dia. C Max. D Threaded DD 150 ANSI DDD 300 ANSI E F 150 ANSI FF 300 ANSI G Threaded GG 150 ANSI GGG 300 ANSI H NPT Body Tapping J NPT Cover Center Plug K NPT Cover Tapping
Valve Stem Internal Thread UNF
Stem Travel Approx. Ship Wt. Kgs.
279 318 — 279 305 381 508 645 756 864 991 1051 295 337 397 533 670 790 902 1029 1105 203 232 292 400 508 600 711 832 902 262 284 362 468 554 594 744 816 889 140 159 — 140 152 191 254 322 378 432 495 526 148 168 198 267 335 395 451 514 552
43 52 81 109 135 235 273 321 394 89 95 114 140 171 203 241 267 298
95 105 127 159 191 222 260 292 324 102 114 — 102 102 127 152 203 219 349 378 399 110 111 135 165 216 236 368 397 419
.50 .50 .75 .75 1 1 1 1 1 .50 .50 .75 .75 1 1 1.25 1.50 2 .50 .50 .75 .75 1 1 1 1 1
10-32
1
4-28
1
4-28
3
8-24
3
8-24
3
8-24
3
8-24
3
8-24
1
18 20 28 43 58 71 86 102 11 4
30 43 86 145 295 426 760 1116 1406
2-20
Note: Various Flange Drilling to a Foreign and intranational Standards and Specifications are Available on Request.
Cla-Val Control Valves operate with maximum efficiency when mounted in horizontal piping with the main valve cover UP, however, other positions are acceptable. Due to component size and weight of 8 inch and larger valves, installation with cover UP is advisable. We recommend isolation valves be installed on inlet and outlet for maintenance. Adequate space above and around the valve for service personnel should be considered essential. A regular maintenance program should be established based on the specific application data. However, we recommend a thorough inspection be done at least once a year. Consult factory for specific recommendations.
CLA-VAL
©
Copyright Cla-Val 2012 Printed in USA Specifications subject to change without notice.
E-100-03 (R-8/2011)
P.O. Box 1325 Newport Beach, CA 92659-0325 Phone: 949-722-4800 Fax: 949-548-5441 E-mail: claval@cla-val.com Website cla-val.com
25
Page 26
100-20
(Reduced Internal Port)
MODEL
600 Series
Hytrol Valve
Reduced Cavitation Design
Drip-Tight, Positive Seating Action
Service Without Removal From Line
Globe or Angle Pattern
Every Valve Factory Tested
The Cla-Val Model 100-20 Hytrol Valve is a hydraulically operated, diaphragm actuated, globe or angle pattern valve. It consists of three major components: body, diaphragm assembly and cover. The diaphragm assembly is the only moving part.
The diaphragm assembly is guided top and bottom by a precision machined stem which utilizes a non-wicking diaphragm of nylon fabric bonded with synthetic rubber. A resilient synthetic rubber disc, retained on three and one-half sides by a disc retainer, forms a drip-tight seal with the renewable seat when pressure is applied above the diaphragm.
The reduced cavitation characteristics of the 100-20 Hytrol Valve is the basis for the Cla-Val 600 Series. The rugged simplicity of design and packless construction assure a long life of dependable, trouble-free operation. It's smooth flow passages and fully guided disc and diaphragm assembly assure optimum control when used in piping sys­tems requiring remote control, pressure regulation, solenoid operation, rate of flow control or check valve operation.
Available in various materials and in a wide range of sizes. It's appli­cations are unlimited.
Principle of Operation
On-Off Control
Full Open Operation
When pressure in the is relieved to a zone of lower pres­sure, the line pressure at the valve inlet opens the valve, allowing full flow.
26
cover chamber
On-Off Control
Tight Closing Operation
When pressure from the valve inlet is applied to the cover chamber, the valve closes drip-tight.
Modulating
Control
Modulating Action
The valve holds any intermediate position when operating pressure is equal above and below the diaphragm. Using a Cla-Val “Modulating” Control will allow the valve to automatically compensate for line pressure changes.
Page 27
Specifications
Model 100-20
Available Sizes
Pattern Flanged
Globe 3", 4", 6", 8", 10", 12", 14", 16", 18", 20", 24", 30", 36, 42", 48"
Angle 4", 6", 8", 10”, 12”, 14”, 16”, 18”, 20”, 24”
Pressure Ratings
Valve Body & Cover
Grade Material
ASTM A536 Ductile Iron B16.42 250 400
ASTM A216-WCB Cast Steel B16.5 285 400
ASTM B62 Bronze B16.24 225 400
Note: * ANSI standards are for flange dimensions only.
Flanged valves are available faced but not drilled.
Valves for higher pressure are available; consult factory for details
(Recommended Maximum Pressure - psi)
Pressure Class
Flanged
ANSI
Standards*
150
Class
Class
300
Materials
Component Standard Material Combinations
Body & Cover Ductile Iron Cast Steel Bronze
Available Sizes 3" - 48" 3" - 16" 3" - 16"
Disc Retainer & Diaphragm Washer
Trim: Disc Guide, Seat & Cover Bearing
Disc Buna-N®Rubber Diaphragm Nylon Reinforced Buna-N®Rubber Stem, Nut & Spring Stainless Steel
Cast Iron Cast Steel Bronze
Bronze is Standard
Stainless Steel is optional
For material options not listed consult factory. Cla-Val manufactures valves in more than 50 different alloys.
Options
Viton®Rubber Parts- suffix KB
Optional diaphragm, disc and o-ring fabri­cated with Viton
®
synthetic rubber. Viton®is well suited for use with mineral acids, salt solutions, chlorinated hydrocarbons, and petroleum oils; and is primarily used in high temperature applications up to 250° F.
not use with epoxy coatings above
175° F.
Epoxy Coating - suffix KC
This option NSF 61 Listed and FDA approved, fusion bonded epoxy coating is for use with cast iron, ductile iron or steel valves. This coating is resistant to various water conditions, certain acids, chemicals, solvents and alkalies.
Epoxy coatings are applied in accordance with AWWA coating specifications C116-03. Do not use with temperatures above
175° F.
Dura-Kleen® Stem - suffix KD
This stem is designed for applications where water supplies containing dissolved minerals create deposits that build-up on a standard stem and hamper valve opera­tion. A patented, self-cleaning design on
Do
the stem allows all valve sizes to operate freely in the harshest conditions.
®
Delrin
The Delrin
Sleeved Stem- suffix KG
®
sleeved stem is designed for applications where water supplies contain dissolved minerals which can form deposits that build up on the valve stem and hamper valve operation. Scale build­up will not adhere to the Delrin stem. Delrin
®
sleeved stems are not rec­ommended for valves in continuous opera­tion where differential pressures are in excess of 80 psi (2" and larger Hytrol valves).
Operating Temp. Range
Fluids
-40° to 180° F
KO Anti-Cavitation Trim Option
KO DISC GUIDE
KO SEAT
®
sleeve
COVER
Cover Bolt
6" and Smaller
SPRING
*
DIAPHRAGM
*
DISC
DISC GUIDE
SEAT
BODY
(Globe
or
Angle)
Anti-Cavitation Trim
PIPE PLUG
COVER BEARING
STEM NUT
DIAPHRAGM WASHER
*
SPACER WASHERS
STEM
SEAT O-RING
-
suffix KO
HEX NUT
10" and Larger
PIPE PLUG
DISC RETAINER
Seat Screw
10" annd Larger
10" and Larger
PIPE PLUG
*
Repair Parts
Anti-Cavitation Trim components consist of a stainless steel radial slotted disc guide and seat. This system is used when high differentials are present across the valve.
-
Water Treatment Clearance
suffix KW
This additional clearance is beneficial in applications where water treatment com­pounds can interfere with the closing of the valve. The smaller outside diameter disc guide provides more clearance between the disc guide and the valve seat. This option is best suited for valves used in on­off (non-modulating) service.
STUD
27
Page 28
K =
894d
4
C
2
v
L =
K 12 f
K Factor (Resistance Coefficient)
The Value of K is calculated from the formula: (U.S. system units)
Equivalent Length of Pipe
Equivalent lengths of pipe (L) are determined from the formula: (U.S. system units)
Fluid Velocity
Fluid velocity can be calculated from the following formula: (U.S. system units)
d
V =
.4085 Q
2
d
C
V
Factor
Formulas for computing C Factor, Flow (Q) and Pressure Drop
V
( P):
C
V
=
Q
P
C
V
=
Q
P
C
V
=
Q
P
2
V
Where:
U.S. (gpm) @ 1 psi differential at 60 F water
(l/s) @ 1 bar (14.5 PSIG) differential
or
at 15 C water
inside pipe diameter of Schedule 40 Steel Pipe (inches)
friction factor for clean, new Schedule 40 pipe
(dimensionless) (from Cameron Hydraulic Data,
18th Edition, P 3-119)
Resistance Coefficient (calculated)
Equivalent Length of Pipe (feet)
Flow Rate in U.S. (gpm) or (l/s)
Fluid Velocity (feet per second) or (meters per second)
Pressure Drop in (psi) or (bar)
=
=
=
=
=
=
=
=
=
P
V
Q
L
K
f
d
C
Functional Data Model 100-20
Valve Size
Globe
C
Factor
Equivalent
Length
of
Pipe
K
Factor
Liquid Displaced from
Cover Chamber
When Valve Opens
**Consult Factory
Pattern
V
Angle
Pattern
Globe
Pattern
Angle
Pattern
Inches 34681012141618202430364248
mm. 80 100 150 200 250 300 350 400 460 500 600 750 900 1000 1200
Gal./Min. (gpm.) 62 136 229 480 930 1458 1725 2110 2940* 3400* 4020 7900* 11910* 14500* 15800*
Litres/Sec. (l/s.) 15 32.5 55 115 223 350 414 506 705 816 966 1895 2858 3483 3796
Gal./Min. (gpm.) 135 233 545
Litres/Sec. (l/s.) 32 56 132
Feet (ft.) 293 251 777 748 621 654 750 977 983 1125 3005 2130 2862 4232 7028
Meters (m.) 89.3 76.4 237.1 228.1 189.5 199.4 229 298 300 343 917 650 872 1290 2142
Feet (ft.) 254 751 580
Meters (m.) 77.6 229 176.9
Globe Pattern 20.6 12.7 23.1 15.7 10.4 8.5 8.9 10.2 8.4 8.8 19.1 10.5 9.7 12.3 17.8
Angle Pattern 12.9 22.3 12.2
Fl. Oz ———————————— — — —
U.S. Gal. 0.32 .08 .17 .53 1.26 2.51 4.0 4.0 9.6 9.6 9.6 29.0 42 90 90
ml ———————————— — — —
Litres .12 .30 .64 2.0 4.8 9.5 15.1 15.1 36.2 36.2 36.2 11 0 197 340 340
CF** CF** CF** CF** CF** CF** CF**
CF** CF** CF** CF** CF** CF** CF**
CF** CF** CF** CF** CF** CF** CF**
CF** CF** CF** CF** CF** CF** CF**
CF** CF** CF** CF** CF** CF** CF**
————
————
*Estimated
Model 100-20 Flow Chart (Based on normal flow through a wide open valve)
28
Page 29
J
K
C
FF
H
A
AA
B (DIAMETER)
INLET
OUTLET
F
(Diameter)
B
100-20
Flanged
H
Inlet
J
K
C
(MAX)
Outlet
F
FF
E
EE
AA
Inlet
A
D
DD
Valve Size (Inches) 3 4 6 8 10 12 14 16 18 20 24 30 36 42 48
A 150 ANSI 10.25 13.88 17.75 21.38 26.00 30.00 34.25 35.00 42.12 48.00 48.00 63.25 65.00 76.00 94.50
AA 300 ANSI 11.00 14.50 18.62 22.38 27.38 31.50 35.75 36.62 43.63 49.62 49.75 63.75 67.00 76.00 94.50
B Dia. 6.62 9.12 11.50 15.75 20.00 23.62 27.47 28.00 35.44 35.44 35.44 53.19 56.00 66.00 66.00
C Max. 7.00 8.62 11.62 15.00 17.88 21.00 20.88 25.75 25.00 31.50 31.50 43.94 54.60 61.50 61.50
D 150 ANSI 6.94 8.88 10.69
DD 300 ANSI 7.25 9.38 11.19
E 150 ANSI 5.50 6.75 7.25
EE 300 ANSI 5.81 7.25 7.75
CF* CF* CF* CF* CF* CF* CF*
CF* CF* CF* CF* CF* CF* CF*
CF* CF* CF* CF* CF* CF* CF*
CF* CF* CF* CF* CF* CF* CF*
F 150 ANSI 3.75 4.50 5.50 6.75 8.00 9.50 11.00 11.75 15.88 14.56 17.00 19.88 25.50 28.00 31.50
FF 300 ANSI 4.12 5.00 6.25 7.50 8.75 10.25 11.50 12.75 15.88 16.06 19.00 22.00 27.50 28.00 31.50
H NPT Body Tapping .375 .50 .75 .75 1 1 1 1 1 1 1 1 2 2 2
J NPT Cover Center Plug .50 .50 .75 .75 1 1 1.25 1.25 2 2 2 2 2 2 2
K NPT Cover Tapping .375 .50 .75 .75 1 1 1 1 1 1 1 1 2 2 2
Valve Stem Internal Thread UNF 10-321⁄4-281⁄4-283⁄8-243⁄8-243⁄8-243⁄8-243⁄8-241⁄2-201⁄2-201⁄2-203⁄4-163⁄4-16 M20 M20
Stem Travel 0.6 0.8 1.1 1.7 2.3 2.8 3.4 3.4 4.5 4.5 4.5 6.5 7.5 8.5 8.5
Approx. Ship Wt. Lbs. 45 85 195 330 625 900 1250 1380 1500 2551 2733 6500 8545 12450 13100
*Consult Factory
Note: The top two flange holes on valve sizes 36 thru 48 are threaded to 1 1/2"-6 UNC.
Valve Size (mm) 80 100 150 200 250 300 350 400 450 500 600 750 900 1000 1200
A 150 ANSI 260 353 451 543 660 762 870 889 1070 1219 1219 1607 1651 1930 2400
AA 300 ANSI 279 368 473 568 695 800 908 930 1108 1260 1263 1619 1702 1930 2400
B Dia. 168 232 292 400 508 600 698 711 900 900 900 1351 1422 1676 1676
C Max. 178 219 295 381 454 533 530 654 635 800 800 111 6 1387 1562 1562
D 150 ANSI 176 226 272
DD 300 ANSI 184 238 284
E 150 ANSI 140 171 184
EE 300 ANSI 148 184 197
CF* CF* CF* CF* CF* CF* CF*
CF* CF* CF* CF* CF* CF* CF*
CF* CF* CF* CF* CF* CF* CF*
CF* CF* CF* CF* CF* CF* CF*
F 150 ANSI 95 114 140 171 203 241 279 298 403 370 432 505 648 711 800
FF 300 ANSI 105 127 159 191 222 260 292 324 403 408 483 559 699 711 800
H NPT Body Tapping .375 .50 .75 .75 1 1 1 1 1 1 1 1 2 2 2
J NPT Cover Center Plug .50 .50 .75 .75 1 1 1.25 1.25 2 2 2 2 2 2 2
K NPT Cover Tapping .375 .50 .75 .75 1 1 1 1 1 1 1 1 2 2 2
Valve Stem Internal Thread UNF 10-321⁄4-281⁄4-283⁄8-243⁄8-243⁄8-243⁄8-243⁄8-241⁄2-201⁄2-201⁄2-203⁄4-163⁄4-16 M20 M20
Stem Travel 15 20 28 43 58 71 86 86 86 11 4 114 165 191 216 216
Approx. Ship Wt. Kgs. 20 39 89 150 284 409 568 627 681 1157 1249 2951 3876 5647 5942
For assistance in selecting appropriate valve options or valves manufactured with special design requirements, please contact our Regional Sales Office or Factory.
Note: Various Flange Drilling to a Foreign and intranational Standards and Specifications are Available on Request.
Service and Installation
Cla-Val Control Valves operate with maximum efficiency when mounted in horizontal piping with the main valve cover UP, however, other positions are acceptable. Due to component size and weight of 10 inch and larger valves, installation with cover UP is advisable. We recommend isolation valves be installed on inlet and outlet for maintenance. Adequate space above and around the valve for service personnel should be considered essential. A regular maintenance program should be established based on the specific application data. However, we recommend a thorough inspection be done at least once a year. Consult factory for specific recommendations.
CLA-VAL
P.O. Box 1325 Newport Beach, CA 92659-0325 Phone: 949-722-4800 Fax: 949-548-5441 E-mail: claval@cla-val.com Website cla-val.com
©
Copyright Cla-Val 2012 Printed in USA Specifications subject to change without notice.
E-100-20 (R-11/2012)
29
Page 30
PILOT CONTROL VALVE
RESTRICTOR
SEATING AREA
CONTROL CHAMBER
INLET
Pilot Control Valve
RESTRICTOR
SEATING AREA
CONTROL CHAMBER
INLET
100-42
700 SERIES
ROLL SEAL
MODEL
• Compact Design, Proven Reliable
• Light Weight Materials
• High Pressure Rating Availability
• Easy Installation and Maintenance
The Cla-Val Model 100-42 Roll Seal valve is a hydraulically operated valve used to control liquid flow by means of a flexible control element: the liner. The basic valve consists of only two parts: a one piece, investment cast body and an elastomeric liner. The valve body is constructed with internal ribs and slots forming a grillwork which surrounds the liner to provide support. A normally closed type valve is formed by the installed liner which covers the grillwork and seats against the raised seating surface in the valve body. Upstream pressure actuates the valve to produce valve opening by rolling the liner off the seating surface and the slotted grillwork. The valve is actuated by upstream pressure as the loading pressure (pressure supplied to the control chamber) is varied by an external pilot control system. A typical pilot control system used to operate the Model 100-42 valve consists of a restriction and a suitable pilot connected to the valve.
Principle of Operation
Model 100-42 Valve
in Closed Position
Upstream pressure is introduced to the control chamber (the chamber formed behind the liner) of the Cla-Val Model 100-42 Roll Seal valve through the con­trol piping and restrictor. When the pilot is closed, full inlet pressure is supplied to the control chamber, thus balancing the force developed by inlet pressure acting on the upstream face on the liner. Under these conditions, the liner remains in the fully closed position. Since the operating pressure in the control chamber is greater than the out­let pressure, an additional closing force is developed across the liner, pressing the liner against the surrounding slotted grillwork area and seating surface.
30
PILOT CONTROL VALVE
RESTRICTOR
SEATING AREA
INLET
CONTROL CHAMBER
Model 100-42 Valve
in Partially Open Position
As loading pressure is lowered slightly below inlet pressure, the central portion of the liner is forced to invert and come to rest against the tip of the control chamber cavity. Reducing the loading pressure further (but still higher than outlet pressure) causes the liner to drape over the cone shaped portion of the control chamber cavity. This action causes the outer section of the liner to roll off the seating surface and a portion of the grillwork to partially open the valve.
Model 100-42 Valve
in Fully Open Position
The valve is fully opened when loading pressure is sufficiently reduced to allow the liner to roll back completely and expose the full slot area. Restoring loading pressure reverses the liner rolling action to return the liner to the fully closed position.
Page 31
Design Specification
PO Box 1325 Newport Beach CA 92659-0325
Phone: 949-722-4800 Fax: 949-548-5441
CLA-VAL
CLA-VAL CANADA CLA-VAL EUROPE
4687 Christie Drive Beamsville, Ontario Canada L0R 1B4 Phone: 905-563-4963 Fax: 905-563-4040
Chemin dés Mesanges 1 CH-1032 Romanel/ Lausanne, Switzerland Phone: 41-21-643-15-55 Fax: 41-21-643-15-50
©COPYRIGHT CLA-VAL 2012 Printed in USA
Specifications subject to change without notice.
www.cla-val.com
"E" N.P.T.
"E" N.P.T.
"E" N.P.T.
"D"
DIA.
"B"
DIA.
"C"
6", 8",10" and 12" Flanged Style
3/8" N.P.T. 3 PORTS
"A" TYP.
"BB" DIA.
FLOW
"CC"
2", 3", 4" and 6" Wafer Style
Sizes: 2, 3, 4, and 6 inch wafer style
End Detail Wafer: Fits ANSI B16.5 class 125,150,
End Detail Flanged: ANSI B16.5 class 150
End Detail Victaulic®: Fits standard steel pipe Operating Pressure: 720 psi maximum
Maximum Differential: 150 psid continuous,
Reverse Pressure: 125 psid maximum Temperature Range: 32 to 160 degrees F* Flange Operating Pressure: Class 125-175 psi maximum
®
Victaulic
*Standard natural rubber 65 durometer in water service. Temperature range depends on liner material. Higher differential pressure ratings available.
Ends Rating: 300 psi maximum
For other than standard ANSI flanges consult factory
DIN drilling available on all sizes
6, 8, 10, and 12 inch flanged 6, 8, 10, 12 inch Victaulic® Ends
250, and 300 flanges
(fits class 125) or ANSI B16.5 class 300 (fits class 250)
Victaulic®Ends - 300 psi max.
225 psid intermittent*
Class 150-275 psi maximum Class 250-300 psi maximum Class 300-720 psi maximum
Dimensions (100-42 Main Valve)
Valve Size (Inches) 2 3 4 6 8 10 12
A 27⁄8 39⁄16 41⁄8 51⁄4 -- -- -- B -- -- -- 107⁄8 143⁄8 18 215⁄8 BB 43⁄8 57⁄8 73⁄8 913⁄16 -- -- -- C -- -- -- 9 11 13 151⁄4 CC 21⁄2 31⁄4 4 51⁄2 -- -- -- D (ANSI 150) -- -- -- 11 131⁄2 16 19 D (ANSI 300) -- -- -- 121⁄2 15 171⁄2 201⁄2 E (Ports) NPT -- -- -­Approx. Wt. (150 lbs.) 4 71⁄2 14 58 115 190 290 Approx. Wt. (300 lbs.) 4 71⁄2 14 87 155 250 375
Max. Continuous Flow (gpm) 224 469 794 1787 3177 4964 7148
Valve Size (mm for ANSI) 50 80 100 150 200 250 300
A 73 90 105 133 -- -- -­B -- -- -- 276 356 457 549 BB 111 149 187 249 -- -- -­C -- -- -- 229 279 330 387 CC 64 83 102 140 -- -- -­D (ANSI 150) -- -- -- 279 343 406 483 D (ANSI 300) -- -- -- 318 381 445 521 E (Ports) NPT -- -- -­Approx. kg. (150 lbs.) 1.81 3.63 6.35 30 54.43 89 151.5 Approx. kg. (150 lbs.)with Studs & Nuts 2.72 4.54 10 -- -- -- -­Approx. kg. (300 lbs.) 1.81 3.63 6.35 41.73 72.57 116.57 191 Approx. kg. (300 lbs.)with Studs & Nuts 5 6.35 11.8 -- -- -- --
Max. Continuous Flow (l/s.) 14 30 50 113 200 301 451
3
3
8
8
3
3
8
8
Performance Specification
Capacity: See Technical Data Sheet CfFactor: 0.9
Cavitation: See Technical Data Sheet Rangeability: 500:1 Bearing Friction: No friction from slip-type
bearings
Material Specification
Body: 316L Stainless Steel Flanges: (Slip on) Carbon Steel/Clear Cad. Plated Bolt Kit: Carbon Steel/Zinc Plated Liner: Natural Rubber, 65 duro (standard)
Viton, EPDM, Nitrile, Silicone (available)
Liner Retainer: 316 Stainless Steel
Optional Materials
Escoloy 45D Duplex Stainless Steel Super Duplex Stainless Steel Nickel Aluminum Bronze Titanium
1
1
2
2
1
1
2
2
NSF Approved 2" thru 12"
When Ordering, Please Specify
1. Catalog No. 750-01 2. Valve Size 3. Fluid Being Handled 4. Fluid Temperature Range 5. Inlet Pressure Range
6. Outlet Pressure Range 7. Maximum Differential Pressure 8. Minimum Differential Pressure 9. Maximum Flow Rate
10. Pilot Set Point
E-100-42 (R-3/2011)
Represented By:
31
Page 32
100-44
(Reduced Internal Port)
MODEL
316SS Hytrol Valve
All 316 Stainless Steel
Reduced Cavitation Design
Drip-Tight, Positive Sealing Action
Service Without Removal From Line
Every Valve Factory Tested
Three-Year Warranty
The Cla-Val Model 100-44 Hytrol 316SS Valve is a hydraulically operated, diaphragm actuated, globe pattern valve with all 316 Stainless Steel metal parts. Specially designed 316 Stainless Steel removable slip-on flanges provide 150 or 300 ANSI class flange connections that meet ANSI and ISO standards. This valve is ideal for control valve applications where fluid compatibility is often a problem. The standard Electropolish finish on the 316 Stainless Steel parts offers extreme corrosion resistance to many industrial fluids such as seawater, high alkyl or high acid concentrations or other aggressive or corrosive fluids.
The Model 100-44 Hytrol consists of these major components: body, flanges, diaphragm assembly and cover. The diaphragm assembly is the only moving part and is guided top and bottom by a precision-machined stem. A non-wicking diaphragm of nylon fabric reinforced, synthetic rubber creates the control chamber for the valve. A resilient, synthetic rubber disc forms a drip-tight seal, with the renewable seat, when pressure is applied to the control chamber. The rugged simplicity of design and packless con­struction assures a long life of dependable, trouble-free operation. Smooth flow passages and fully guided diaphragm assembly assure optimum con­trol, when used in piping systems requiring remote control, pressure regula­tion, solenoid operation, rate of flow control or check valve operation.
Principle of Operation
On-Off Control
Full Open Operation
When pressure in the ber is relieved to a zone of lower pressure, the line pressure at the valve inlet opens the valve, allow­ing full flow.
32
cover cham-
On-Off Control
Tight Closing Operation
When pressure from the valve inlet is applied to the cover chamber, the valve closes drip-tight.
Modulating
Control
Modulating Action
The valve holds any intermediate position when operating pressure is equal above and below the diaphragm. Using a Cla-Val “Modulating” Control will allow the valve to automat­ically compensate for line pressure changes.
Page 33
PO Box 1325 Newport Beach CA 92659-0325 Phone: 949-722-4800 Fax: 949-548-5441 Web Site: cla-val.com E-mail: claval@cla-val.com
CLA-VAL
CLA-VAL CANADA CLA-VAL EUROPE
4687 Christie Drive Beamsville, Ontario Canada L0R 1B4 Phone: 905-563-4963 Fax: 905-563-4040 E-Mail: sales@cla-val.ca
Chemin des Mésanges 1 CH-1032 Romanel/ Lausanne, Switzerland Phone: 41-21-643-15-55 Fax: 41-21-643-15-50 E-Mail: cla-val@cla-val.ch
Copyright
CLA-VAL 2011 Printed in USA Specifications subject to change without notice.
CLA-VAL UK
Dainton House, Goods Station Road GB - Tunbridge Wells Kent TN1 2 DH England Phone: 44-1892-514-400 Fax: 44-1892-543-423 E-Mail: info@cla-val.co.uk
©
Specifications
Sizes
Globe (inch):
1
", 2
2", 3", 4", 6", 8", 10", 12"
2
End Detail
Slip-on Two Piece Flange Dimensions Per ANSI B16.5
Pressure Rating
ANSI Class 150:
Maximum 285 psi
ANSI Class 300:
Maximum 400 psi
Higher Pressure Available Please Contact Factory
D
EE
G, GG
NAMEPLATE
Model 100-44
Two Piece
FLANGE (QTY 2)
Inlet Outlet
E
F, FF
A
C, CC
AA
Operating Temperature
Fluids Compatible with Valve Materials
-40º to 180º F (-40º to 82º C)
Dimensions (in inches)
Materials
Body, Cover, Trim, Diaphragm Assembly, Flanges, and Fasteners
316 Series Stainless Steel Electropolished
Disc:
Buna-N
®
Rubber*
Diaphragm:
Nylon Fabric Reinforced Synthetic Buna-N
®
Rubber*
*Contact Factory for Other
Disc or Diaphragm Materials
Note: 100-44 valve uses the same internal parts as the basic Cla-Val standard main reduced internal port 100-20 Hytrol.
A 150 ANSI 9.06 11.42 12.20 13.78 18.90 23.62 28.74 33.46 AA 300 ANSI 9.06 11.42 12.20 13.78 18.90 23.62 28.74 33.46 B 5.70 8.06 6.69 9.25 11.61 15.75 20.08 23.62 C .89 .89 .93 .93 1.02 1.15 1.15 1.25 CC 300 ANSI .96 .96 1.00 1.00 1.10 1.15 1.46 1.50 D 6.50 7.95 8.20 10.12 13.32 16.39 19.12 20.95 E 3.05 3.54 3.74 4.53 5.61 6.79 7.97 9.55 EE 300 ANSI 3.25 3.75 4.13 5.01 6.30 7.48 8.76 10.24 F .71 .71 .71 .71 .91 .87 1.02 1.02 FF 300 ANSI .71 .75 .87 .87 .87 1.03 1.16 1.34 G 4.75 5.50 6.00 7.50 9.50 11.75 14.25 17.00 GG 300 ANSI 5.00 5.88 6.62 7.88 10.62 13.00 15.25 17.72
Flange Bolts (150 Class) 4 4 4 8 8 8 12 12 Flange Bolts (300 Class) 8 8 8 8 12 12 16 16 Approx. Ship Wt. Lbs. 25 40 40 75 160 290 419 728 Approx. Ship Wt. Kgs. 11 .4 19 19 35 73 132 190 330
Reduced Port Functional Data
Size (Inches) Cv (gpm)* Cv (l/s)**
2 38 9
21⁄2 50 12
3 67 16 4 138 33 6 242 58
8 555 133 10 923 222 12 1492 359
*Cv = gpm flow at 1 psi drop **Cv = l/s flow at 1 bar drop
B
Size (Inches) 2 2 1⁄2 3 4 6 8 10 12
Size (mm) 50 65 80 100 150 200 250 300
When Ordering Please Specify:
1. Catalog No. 100-44
2. Valve Size
3. Fluid Being Handled
4. Fluid Temperature
5. Inlet Pressure Range
6. Outlet Pressure Range
7. Maximum and Minimum Differential Pressure
8. Flow Rate Range
E-100-44 (R-10/2011)
Represented By:
33
Page 34
100-46
(Full Internal Port)
MODEL
316SS Hytrol Valve
All 316 Stainless Steel
Reduced Cavitation Design
Drip-Tight, Positive Sealing Action
Service Without Removal From Line
Every Valve Factory Tested
Three-Year Warranty
The Cla-Val Model 100-46 Hytrol 316SS Valve is a hydraulically operated, diaphragm actuated, globe pattern valve with all 316 Stainless Steel metal parts. Specially designed 316 Stainless Steel removable slip-on flanges provide 150 or 300 ANSI class flange connections that meet ANSI and ISO standards. This valve is ideal for control valve applications where fluid compatibility is often a problem. The standard Electropolish finish on the 316 Stainless Steel parts offers extreme corrosion resistance to many industrial fluids such as seawater, high alkyl or high acid concentrations or other aggressive or corrosive fluids.
The Model 100-46 Hytrol consists of these major components: body, flanges, diaphragm assembly and cover. The diaphragm assembly is the only moving part and is guided top and bottom by a precision-machined stem. A non-wicking diaphragm of nylon fabric reinforced, synthetic rubber creates the control chamber for the valve. A resilient, synthetic rubber disc forms a drip-tight seal, with the renewable seat, when pressure is applied to the control chamber. The rugged simplicity of design and packless con­struction assures a long life of dependable, trouble-free operation. Smooth flow passages and fully guided diaphragm assembly assure optimum con­trol, when used in piping systems requiring remote control, pressure regula­tion, solenoid operation, rate of flow control or check valve operation.
Principle of Operation
On-Off Control
Full Open Operation
When pressure in the ber is relieved to a zone of lower pressure, the line pressure at the valve inlet opens the valve, allow­ing full flow.
34
cover cham-
On-Off Control
Tight Closing Operation
When pressure from the valve inlet is applied to the cover chamber, the valve closes drip-tight.
Modulating
Control
Modulating Action
The valve holds any intermediate position when operating pressure is equal above and below the diaphragm. Using a Cla-Val “Modulating” Control will allow the valve to automati­cally compensate for line pressure changes.
Page 35
PO Box 1325 Newport Beach CA 92659-0325 Phone: 949-722-4800 Fax: 949-548-5441 Web Site: cla-val.com E-mail: claval@cla-val.com
CLA-VAL
CLA-VAL CANADA CLA-VAL EUROPE
4687 Christie Drive Beamsville, Ontario Canada L0R 1B4 Phone: 905-563-4963 Fax: 905-563-4040 E-Mail: sales@cla-val.ca
Chemin des Mésanges 1 CH-1032 Romanel/ Lausanne, Switzerland Phone: 41-21-643-15-55 Fax: 41-21-643-15-50 E-Mail: cla-val@cla-val.ch
Copyright
CLA-VAL 2011 Printed in USA Specifications subject to change without notice.
CLA-VAL UK
Dainton House, Goods Station Road GB - Tunbridge Wells Kent TN1 2 DH England Phone: 44-1892-514-400 Fax: 44-1892-543-423 E-Mail: info@cla-val.co.uk
©
Specifications
Sizes
Globe (inch):
1
2", 2", 2-1/2", 3", 4", 6"
1
End Detail
Slip-on Two Piece Flange Dimensions Per ANSI B16.5
Pressure Rating
ANSI Class 150:
Maximum 285 psi
ANSI Class 300:
Maximum 400 psi
Higher Pressure Available Please Contact Factory
Operating Temperature
Fluids Compatible with Valve Materials
-40º to 180º F (-40º to 82º C)
NAMEPLATE
Inlet Outlet
A
C, CC
AA
Two Piece
FLANGE (QTY 2)
D
EE
G, GG
Model 100-46
E
F, FF
B
Materials
Dimensions
Body, Cover, Trim, Diaphragm Assembly, Flanges, and Fasteners
316 Series Stainless Steel Electropolished
Disc:
Buna-N
®
Rubber*
Diaphragm:
Nylon Fabric Reinforced Synthetic Buna-N
®
Rubber*
*Contact Factory for Other
Disc or Diaphragm Materials
Note: 100-46 valve uses the same internal parts as the basic Cla-Val standard main full Internal port 100-01 Hytrol.
Full Port Functional Data
Size (Inches) Cv (gpm)* Cv (l/s)**
11⁄2 32 8
2 54 13
21⁄2 85 20
3 115 27 4 200 48 6 440 105
*Cv = gpm flow at 1 psi drop **Cv = l/s flow at 1 bar drop
Flange Bolts (150 Class) 444488 Flange Bolts (300 Class) 4888812 Approx. Ship Wt. Lbs. 25 35 55 75 160 290 Approx. Ship Wt. Kgs. 11.4 16 25 35 73 132
Size (In) 11⁄2 22
1
2 346
(mm) 40 50 65 80 100 150
A 150 ANSI 7.87 9.38 11.00 12.00 15.00 20.00 AA 300 ANSI 7.87 9.38 11.00 12.00 15.00 20.00 B 5.62 6.61 8.00 9.13 11.50 15.75 C .56 .62 .69 .75 .94 1.00 CC 300 ANSI .81 .88 1.00 1.12 1.25 1.44 D 5.90 6.25 7.25 8.20 10.21 13.32 E 2.56 3.05 3.54 3.75 4.53 5.61 EE 300 ANSI 3.05 3.25 3.74 4.13 5.02 6.30 F .62 .75 .75 .75 .75 .88 FF 300 ANSI .88 .75 .88 .88 .88 .88 G 3.88 4.75 5.50 6.00 7.50 9.50 GG 300 ANSI 4.50 5.00 5.88 6.62 7.88 10.62
When Ordering Please Specify:
1. Catalog No. 100-46
2. Valve Size
3. Fluid Being Handled
4. Fluid Temperature
5. Inlet Pressure Range
6. Outlet Pressure Range
7. Maximum and Minimum Differential Pressure
8. Flow Rate Range
E-100-46 (R-10/2011)
Represented By:
35
Page 36
Flange Dimensions and End Details
All flanged Cla-Val valves are furnished faced and drilled unless otherwise specified. The dimensions and drilling of end flanges conform to standards of the American National Standards Institute. The ANSI tables are provided here for your convenience. When ANSI standards call for 1/16" raised face, this face is includ­ed in the dimensions for the thickness of flange. All dimensions are shown in inches.
Ductile Iron Valves* Class 150 and 300 (ANSI B16.42 — 1987)
Nominal
Pipe Size
Pressure Class 150 300 150 300 150 300 150 300 150 300 150 300 150 300
1.5 5.00 6.12 .56 .81 2.88 2.88 3.88 4.50 4 4 .50 .75 .62 .88 2 6.00 6.50 .62 .88 3.62 3.62 4.75 5.00 4 8 .63 .63 .75 .75
2.5 7.00 7.50 .69 1.00 4.12 4.12 5.50 5.88 4 8 .63 .75 .75 .88 3 7.50 8.25 .75 1.12 5.00 5.00 6.00 6.62 4 8 .63 .75 .75 .88 4 9.00 10.00 .94 1.25 6.19 6.19 7.50 7.88 8 8 .63 .75 .75 .88 6 11.00 12.50 1.00 1.44 8.50 8.50 9.50 10.62 8 12 .75 .75 .88 .88 8 13.50 15.00 1.12 1.62 10.62 10.62 11.75 13.00 8 12 .75 .88 .88 .1.00
10 16.00 17.50 1.19 1.88 12.75 12.75 14.25 15.25 12 16 .88 1.00 1.00 1.12 12 19.00 20.50 1.25 2.00 15.00 15.00 17.00 17.75 12 16 .88 1.12 1.00 1.25 14 21.00 23.00 1.38 2.12 16.25 16.25 18.75 20.25 12 20 1.00 1.12 1.12 1.25 16 23.50 25.50 1.44 2.25 18.50 18.50 21.25 22.50 16 20 1.00 1.25 1.12 1.38 18 25.00 28.00 1.56 2.38 21.00 21.00 22.75 24.75 16 24 1.12 1.25 1.25 1.38 20 27.50 30.50 1.69 2.50 23.00 23.00 25.00 27.00 20 24 1.13 1.25 1.25 1.38 24 32.00 36.00 1.88 2.75 27.25 27.25 29.50 32.00 20 24 1.25 1.50 1.38 1.62 30 38.75 43.00 2.12 3.00 37.19 36.00 39.25 28 28 1.25 1.75 1.38 2.00 36 46.00 50.00 2.38 3.38 42.69 42.75 46.00 32 32 1.50 2.00 1.62 2.25
Nominal
Pipe Size
Pressure Class 125 250 125 250 125 250 125 250 125 250 125 250 125 250
1.5 5.00 6.12 .56 .81 2.88 3.88 4.50 4 4 .50 .75 .62 .88 2 6.00 6.50 .62 .88 3.62 4.75 5.00 4 8 .63 .63 .75 .75
2.5 7.00 7.50 .69 1.00 4.12 5.50 5.88 4 8 .63 .75 .75 .88 3 7.50 8.25 .75 1.12 5.00 6.00 6.62 4 8 .63 .75 .75 .88 4 9.00 10.00 .94 1.25 6.19 7.50 7.88 8 8 .63 .75 .75 .88 6 11.00 12.50 1.00 1.44 8.50 9.50 10.62 8 12 .75 .75 .88 .88 8 13.50 15.00 1.12 1.62 10.62 11.75 13.00 8 12 .75 .88 .88 .1.00
10 16.00 17.50 1.19 1.88 12.75 14.25 15.25 12 16 .88 1.00 1.00 1.12 12 19.00 20.50 1.25 2.00 15.00 17.00 17.75 12 16 .88 1.12 1.00 1.25 14 21.00 23.00 1.38 2.12 16.25 18.75 20.25 12 20 1.00 1.12 1.12 1.25 16 23.50 25.50 1.44 2.25 18.50 21.25 22.50 16 20 1.00 1.25 1.12 1.38 18 25.00 28.00 1.56 2.38 21.00 23.00 22.75 24.75 16 24 1.12 1.25 1.25 1.38 20 27.50 30.50 1.69 2.50 23.00 25.00 27.00 20 24 1.13 1.25 1.25 1.38 24 32.00 36.00 1.88 2.75 27.25 29.50 32.00 20 24 1.25 1.50 1.38 1.62
Diameter of
Flange
Diameter of
Flange
Thickness
of Flange
Diameter of
Raised Face
Diameter of
Bolt Circle
Number of Bolts
Cast Iron Valves* Class 125 and 250 (ANSI B16.1 — 1989)
Thickness
of Flange
Diameter of
Raised Face
Diameter of
Bolt Circle
Number of Bolts
Diameter
of Bolts
Diameter
of Bolts
Diameter of
Bolt Holes
Diameter of
Bolt Holes
Bronze Valves* Class 150 and 300 (ANSI 16.24 — 1979)
Nominal
Pipe Size
Pressure Class 150 300 150 300 150 300 150 300 150 300 150 300 150 300
1.5 5.00 6.12 .44 .69 3.88 4.50 4 4 .50 .75 .62 .88
2 6.00 6.50 .50 .75 4.75 5.00 4 8 .63 .63 .75 .75
2.5 7.00 7.50 .56 .81 5.50 5.88 4 8 .63 .75 .75 .88
3 7.50 8.25 .62 .91 6.00 6.62 4 8 .63 .75 .75 .88 4 9.00 10.00 .69 1.06 7.50 7.88 8 8 .63 .75 .75 .88 6 11.00 12.50 .81 1.19 9.50 10.62 8 12 .75 .75 .88 .88
8 13.50 15.00 .94 1.38 11.75 13.00 8 12 .75 .88 .88 .1.00 10 16.00 1.00 14.25 12 .88 1.00 — 12 19.00 1.06 17.00 12 .88 1.00
Diameter of
Flange
Thickness
of Flange
Diameter of
Raised Face
Diameter of
Bolt Circle
Number of Bolts
Diameter
of Bolts
Diameter of
Bolt Holes
Cast Steel Valves* Class 150 and 300 (ANSI 16.5 — 1988)
Nominal
Pipe Size
Pressure Class 150 300 150 300 150 300 150 300 150 300 150 300 150 300
1.5 5.00 6.12 .56 .81 2.88 2.88 3.88 4.50 4 4 .50 .75 .62 .88
2 6.00 6.50 .62 .88 3.63 3.63 4.75 5.00 4 8 .63 .63 .75 .75
2.5 7.00 7.50 .69 1.00 4.13 4.13 5.50 5.88 4 8 .63 .75 .75 .88
3 7.50 8.25 .75 1.12 5.00 5.00 6.00 6.62 4 8 .63 .75 .75 .88 4 9.00 10.00 .94 1.25 6.19 6.19 7.50 7.88 8 8 .63 .75 .75 .88 6 11.00 12.50 1.00 1.44 8.50 8.50 9.50 10.62 8 12 .75 .75 .88 .88
8 13.50 15.00 1.12 1.62 10.63 10.63 11.75 13.00 8 12 .75 .88 .88 .1.00 10 16.00 17.50 1.19 1.88 12.75 12.75 14.25 15.25 12 16 .88 1.00 1.00 1.12 12 19.00 20.50 1.25 2.00 15.00 15.00 17.00 17.75 12 16 .88 1.12 1.00 1.25 14 21.00 23.00 1.38 2.12 16.25 16.25 18.75 20.25 12 20 1.00 1.12 1.12 1.25 16 23.50 25.50 1.44 2.25 18.50 18.50 21.25 22.50 16 20 1.00 1.25 1.12 1.38 18 25.00 28.00 1.56 2.38 21.00 23.00 22.75 24.75 16 24 1.12 1.25 1.25 1.38 20 27.50 30.50 1.69 2.50 23.00 23.00 25.00 27.00 20 24 1.13 1.25 1.25 1.38 24 32.00 36.00 1.88 2.75 27.25 27.25 29.50 32.00 20 24 1.25 1.50 1.38 1.62
E-ED (R-3/2012)
Diameter of
Flange
Thickness
of Flange
Diameter of
Raised Face
*Cla-Val valves can be furnished in aluminum.
Diameter of
Bolt Circle
Number of Bolts
Diameter
of Bolts
Diameter of
Bolt Holes
36
Page 37
Anti-Cavitation Main Valve
KO Anti-Cavitation Trim
Cla-Val’s KO anti-cavitation trim represents a dramatic departure from the standard approaches usually employed to fight cavitation in valves that are required to undergo extreme pressure differentials and high velocity flow conditions.
Constructed of 316 Stainless Steel, the seat and disc guide feature dual interlocked sleeves containing cast radial slots that deflect internal flow to impinge upon itself, harmlessly dissipating potential noise and cavitation damage. The cast radial slots create a larger flow path than is possible with the standard drilled holes typically employed by other anti­cavitation valves currently available in the market place. The uniquely designed radial slots in the seat and disc guides also lessen the possibility of fouling if small particles are present in the water.
Seat with Radial Slots
Slotted Disc Guide
Typical Applications
• Pressure Reducing Valve Stations
• Tank Fill Valve Applications
• Noise Reduction in High-Rise Building Valve Stations
• Reservoir Level Control Valve Applications
• Booster Pump Bypass Stations
• Offshore Fire Pump Relief Valve Protection
• Applications with discharge to atmosphere
• Any application where valves are
patented
subjected to extreme pressure differentials or high velocity flow conditions
Cla-Val KO Anti-Cavitation Valve Principals of Operation
First Stage Pressure Reduction
• Flow enters through seat slots and reduces pressure
Second Stage Pressure Reduction
• Flow impinges upon itself within the seat and disc guide assembly to dissipate cavitation and further reduce pressure
Third Stage Pressure Reduction
• Flow exits through disc guide for final pressure reduction
• Diagonal disc guide slots direct flow away from surfaces
37
Page 38
The dark shaded portion of the chart illustrates the region where cavi­tation damage may occur. The lighter shaded portion is where signifi­cant cavitation noise and vibration may occur. Operating conditions inside the dark shaded area is permissible for infrequent periods of short duration. The guide is for modulating service valves. For on/off valves, consult factory.
The chart is based on cavitation index (sigma) values as defined by Utah State University Water Research Laboratory.
2 — Pv
)
(P
= where
1 — P2
(P
)
1
= cavitation index, P
v
(psi), P
= water vapor pressure (psia).
= inlet pressure (psi), P2 = outlet pressure
The dark shaded portion is below of 0.5 and the lighter shaded area is below of 0.8. The chart is to be used for typical valve oper­ating conditions below 40% open at standard water temperature and elevation below 1000 feet.
More accurate cavitation conditions are determined from the Cla-CAV analysis program including static and dynamic inlet and outlet pres­sures, flow range, elevation, water temperature, and service condi­tions. If operation is inside the shaded areas, the Cla-CAV analysis can be used to determine whether added backpressure from an orifice plate, a second valve in series, or adding KO Anti-Cavitation trim (see 100-01KO data sheet). is necessary.
CAVITATION GUIDE
CLA-CAV DETAILED ANALYSIS CHART
For a more detailed cavitation analysis or if operation will be outside of the above chart, request a Cla-CAV computer analysis. Cla-CAV can evaluate what options best solve any potential cavitation prob­lem. In the example shown, a 6 inch 100-01 modulating service valve requires an orifice plate downstream to prevent damaging cavitation. For wider flow range service, either an extra valve in series or the addition of KO Anti-Cavitation trim to the valve may be necessary (see 100-01KO data sheet). Consult factory for a free analysis for wide open or modulating service valves.
Cavitiation Characteristics
1.4
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.0
0
200 400 600 800
Valve 1
Flow (gpm)
Orifice 1
1000
38
If the lines go above 1.0 there will be cavitiation damage.
Page 39
MODEL
100-01KO
(Full Internal Port)
Anti-Cavitation Hytrol Valve
Virtually Cavitation Free Operation
100G-01KO ANTI-CAVITATION VALVE CURVES
1 1/2"
2 1/2"
2"
100
3"
4"
6"
1000
FLOW RATE (gpm)
8"
10"
14"
12"
16"
18"
10000
20"
24"
30"
36"
400 300
100
PRESSURE DROP (psi)
SOLID LINE IS FULL OPEN FLOW CURVES FOR 18 FT/SEC CONTINUOUS DUTY APPLICATIONS
DASHED LINE IS FULL OPEN FLOW CURVE FOR 25 FT/SEC INTERMITTENT DUTY APPLICATIONS
10
1
10
1 1/4"
1"
Notes: On Operating Differential
1. For atmospheric discharge, the maximum inlet pressure cannot exceed 150 psi.
2. For pressure differentials greater than 300 psi the maximum flow velocity should not exceed 18 ft/sec.
Severe Service Design - High Pressure
Differentials
Reduced Noise and Vibration
316 Stainless Steel Disc Guide and Seat
Standard
Drip-Tight, Positive Sealing
Service Without Removal From Line
Retrofit to Standard Hytrol Valves
The Cla-Val Model 100-01KO Anti-Cavitation Hytrol Valve is designed for applications where there is a high potential for damage from cavitation. Specify this valve series for a wide variety of control valve applications having pressure differen-
100000
tials up to 300 psid or for relief valves having atmospheric discharge up to 150 psid.
The 100-01KO Hytrol main valve provides optimum internal pressure control through a unique anti-cavitation trim design. Constructed of 316 Stainless Steel, the seat and disc guide trim components feature dual interlocked sleeves containing radial slots that deflect internal flow to impinge upon itself in the center of the flow path, harmlessly dissipating the poten­tial cavitation damage. This unique design also lessens the possibility of fouling if large particles in the water are present due to the large flow path of the radial slots.
3. Flow velocities greater than 25 ft/sec are not recommended.
4. Recommended minimum flow velocity is 1 ft/sec.
The 100-01KO Hytrol is the basic valve used in Cla-Val Automatic Control Valves for high differential applications requiring remote control, pressure regulation, solenoid oper­ation, rate of flow control, or liquid level control.
5. Consult factory for conditions exceeding these recommenda-
tions.
Functional Data
Valve Size
C
Pattern
V
Factor
Pattern
Equivalent
Length of
Pipe
K Factor
Liquid Displaced from Cover Chamber When
For assistance in selecting appropriate valve options or valves manufactured with special design requirements, please contact our Regional Sales Office or Factory.
Pattern
Pattern
Valve Opens
Inches 11⁄4 11⁄2 221⁄2 3468101214161820243036
32 40 50 65 80 100 150 200 250 300 350 400 450 500 600 750 900 14 14 25 37 52 90 218 362 602 900 1100 1200 1550 1950 3900 4660 7100
3.4 3.4 6.0 8.9 12.5 21.6 52 87 144 216 264 288 360 469 938 1120 1706 15 15 26 39 55 95 232 388 560 790 1075 1175 3775
3.6 3.6 6.2 9.4 13.2 22.8 56 93 134 190 258 282 906
196 196 237 277 416 572 858 1315 1483 2118 1937 3022 3537 4199 4532 6678 6567
60 60 72 84 127 174 262 401 452 646 590 921 1078 1280 1381 2035 2002
171 171 219 250 372 514 757 1145 1714 2226 2021 3152 2583
52 52 67 76 113 157 231 349 522 678 616 961 787
30.6 30.6 26.1 24.3 29.3 29.0 25.5 27.7 24.9 27.7 22.8 31.4 30.2 29.5 15.4 30.1 25.1
26.7 26.7 24.1 21.8 26.2 26.0 22.5 24.1 28.7 29.1 23.8 32.8 16.4
0.2 0.2 .03 .04 .08 .17 .53 1.26 2.5 4.0 6.5 9.6 11 12 29 65 90
0.8 0.8 .12 .16 .30 .64 2.0 4.8 9.5 15.1 25.6 36.2 41.6 45.4 110 246 340
Globe
Angle
Globe
Angle
Globe Pattern
Angle Pattern
mm.
Gal./Min. (gpm.)
Litres/Sec. (l/s.)
Gal./Min. (gpm.)
Litres/Sec. (l/s.)
Feet (ft.)
Meters (m.)
Feet (ft.)
Meters (m.)
U.S. Gal.
Litres
The Anti-Cavitation Trim components can be retrofitted to existing valves if the application indicates an appropriate need. Please consult factory for details.
39
Page 40
100-20KO
(Reduced Internal Port)
MODEL
Anti-Cavitation Hytrol Valve
Virtually Cavitation Free Operation
SOLID LINE IS FULL OPEN FLOW CURVES AT 18 FT/SEC FOR CONTINUOUS DUTY APPLICATIONS
DASHED LINE IS FULL OPEN FLOW CURVE AT 25 FT/SEC FOR INTERMITTENT DUTY APPLICATIONS
400 300
100
10
PRESSURE DROP (psi)
1
10
100G-20KO ANTI-CAVITATION VALVE CURVES
3"
100
6"
4"
FLOW RATE (gpm)
8"
1000
10"
12"
16"
14"
20"
24"
18"
30"
10000
Notes: On Operating Differential
The 100-20KO Series is the reduced internal port size version
*
of the 100-01KO Series.
1. For atmospheric discharge, the maximum inlet pressure cannot exceed 150 psi.
2. For pressure differentials greater than 300 psi the maximum flow velocity should not exceed 18 ft/sec.
3. Flow velocities greater than 25 ft/sec are not recommended.
4. Recommended minimum flow velocity is 1 ft/sec.
Severe Service Design - High Pressure
*
Differentials
*
Reduced Noise and Vibration
316 Stainless Steel Disc Guide and Seat
Standard
Drip-Tight, Positive Sealing
Serviced Without Removal From Line
Retrofit to Standard Hytrol Valves
The Cla-Val Model 100-20KO Anti-Cavitation Hytrol Valve is designed for applications where there is a high potential for damage from cavitation. Specify this valve series for a wide variety of control valve applications having pressure differen­tials up to 350 psid or for relief valves having atmospheric discharge up to 150 psid.
The 100-20KO Hytrol main valve provides optimum internal pressure control through a unique anti-cavitation trim design. Constructed of 316 Stainless Steel, the seat and disc guide trim components feature dual interlocked sleeves containing radial slots that deflect internal flow to impinge upon itself in the center of the flow path, harmlessly dissipating the poten­tial cavitation damage. This unique design also lessens the possibility of fouling if large particles in the water are present due to the large flow path of the radial slots.
The 100-20KO Hytrol is the basic valve used in Cla-Val Automatic Control Valves for high differential applications requiring remote control, pressure regulation, solenoid oper­ation, rate of flow control, or liquid level control.
5. Consult factory for conditions exceeding these recommenda-
tions.
Functional Data
Valve Size
K
V
Opens
Pattern
Pattern
Pattern
Pattern
C
Factor
Equivalent
Length of Pipe
Factor
Liquid Displaced from Cover
Chamber When Valve
For assistance in selecting appropriate valve options or valves manufactured with special design requirements, please contact our Regional Sales Office or Factory.
Inches mm. Gal./Min. (gpm.)
Globe
Litres/Sec. (l/s.) Gal./Min. (gpm.)
Angle
Litres/Sec. (l/s.) Feet (ft.)
Globe
Meters (m.) Feet (ft.)
Angle
Meters (m.)
Globe Pattern Angle Pattern
U.S. Gal. .03 .08 .17 .53 1.26 2.5 4.0 4.0 9.6 9.6 9.6 29.0 Litres .12 .30 .64 2.0 4.8 9.5 15.1 15.1 36.2 36.2 36.2 110
3 4 6 8 10 12 14 16 18 20 24 30 80 100 150 200 250 300 350 400 450 500 600 760 25 46 98 240 409 660 910 925 1175 1225 1271 3900
6.0 11 .0 23.5 57.7 98 159 219 222 342 348 358 708 — 49 105 230 — — 11 .8 25.2 55
1435 2191 4244 3404 3884 8107 3359 6472 4185 6961 16582 14633
437 668 1294 1038 1184 2471 1024 1973 1276 2122 5054 4460
1931 3697 3257 — — 589 1127 993
101 111 126 72 65 42 40 67 36 53 106 68
98 110 69
The Anti-Cavitation Trim components can be retrofitted to existing valves if the application indicates an appropriate need. Please consult factory for details.
Model 100-20KO
40
Page 41
50-01
(Full Internal Port)
MODEL
650-01
(Reduced Internal Port)
Pressure Relief & Pressure Sustaining Valve
Accurate Pressure Control
Optional Check Feature
Fast Opening to Maintain Line Pressure
Slow Closing to Prevents Surges
Completely Automatic Operation
The Cla-Val Model 50-01/650-01 Pressure Relief Valve is a hydraulically operated, pilot-controlled, modulating valve designed to maintain constant upstream pressure within close limits. This valve can be used for pressure relief, pressure sustaining, back pressure, or unloading functions in a by-pass system.
In operation, the valve is actuated by line pressure through a pilot control system, opening fast to maintain steady line pressure but closing gradually to prevent surges. Operation is completely automatic and pressure settings may be easily changed.
If a check feature is added, and a pressure reversal occurs, the down­stream pressure is admitted into the main valve cover chamber, closing the valve to prevent return flow.
Schematic Diagram
Item Description
1 Hytrol (Main Valve) 2 X42N-2 Strainer & Needle Valve 3 CRL Pressure Relief Control
Optional Features
Item Description
B CK2 (Isolation Valve) D Check Valves with Isolation Valve F Remote Pilot Sensing H Drain to Atmosphere P X141 Pressure Gauge
S CV Speed Control (Opening) V X101 Valve Position Indicator
Typical Applications
Supply
CLA-VAL 60-73
Booster Pump
Control Valve
Pump
CLA-VAL 50-01/650-01 Pressure Sustaining Valve
Isolation Valve
Service
Upper Zone
Isolation Valve
CLA-VAL
50-01/650-01
Pressure Relief
Pressure Sustaining
Valve
Area Of Heavy Demand
Pressure Relief Service
This fast opening, slow closing relief valve provides system protection against high pressure surges on pump start up and pump shut down by dissipating the excess pressure to a safe location.
Pressure Sustaining Service
When installed in a line between an upper zone and a lower area of heavy demand, the valve acts to maintain desired upstream pressure to prevent "robbing" of the upper zone. Water in excess of pressure setting is allowed to flow to an area of heavy demand, control is smooth, and pressure regulation is positive.
41
Page 42
CLA-VAL
Copyright Cla-Val 2014 Printed in USA Specifications subject to change without notice.
P.O. Box 1325 Newport Beach, CA 92659-0325 Phone: 949-722-4800 Fax: 949-548-5441 E-mail: claval@cla-val.com Website cla-val.com
©
50-01
Valve
Selection
100-01 Pattern: Globe (G), Angle (A), End Connections: Threaded (T), Grooved (GR), Flanged (F) Indicate Available Sizes
Inches 1 11⁄4 11⁄2 2 21⁄2 3 4 6 8 10 12 14 16 18 20 24 30 36
mm 25 32 40 50 65 80 100 150 200 250 300 350 400 450 500 600 750 900
Basic Valve
100-01
Suggested
Flow
(gpm)
Suggested
Flow
(Liters/Sec)
100-01 Series is the full internal port Hytrol. *Globe Grooved Only
650-01
Valve
Selection
Basic Valve
100-20
Pattern
End Detail T T
Maximum
Maximum Surge
Maximum
Maximum Surge
Inches 3 4 6 8 10 12 14 16 18 20 24 30 36 42 48
mm 80 100 150 200 250 300 350 400 450 500 600 750 900 1000 1200
Pattern
End DetailFFFFFFFFFFFFFFF
G, A G, A G, A G, A G, A G, A G, A G, A G, A G, A G, A G, A G, A G G G, A G G
T, F,
T, F,GrT, F,
Gr*
55 93 125 210 300 460 800 1800 3100 4900 7000 8400 11000 14000 17000 25000 42000 50000
120 210 280 470 670 1000 1800 4000 7000 11000 16000 19000 25000 31000 39000 56500 63000 85000
3.5 6 8 13 19 29 50 113 195 309 442 530 694 883 1073 1577 2650 3150
7.6 13 18 30 42 63 113 252 441 693 1008 1197 1577 1956 2461 3560 3975 5360
100-20 Pattern: Globe (G), Angle (A), End Connections: Flanged (F) Indicate Available Sizes
GG, AG, AG, AGGGG GGGGGGG
T, F,GrF, GrF,
Gr*
Gr*
F,
FFFFFFFFF
Gr*
Suggested
Flow
(gpm)
Suggested
Flow
(Liters/Sec)
100-20 Series is the reduced internal port size version of the 100-01 Series.
Maximum
Maximum Surge
Maximum
Maximum Surge
260 580 1025 2300 4100 6400 9230 9230 16500 16500 16500 28000 33500 57000 57000
440 990 1760 3970 7050 11000 15900 15900 28200 28200 28200 56500 58600 90000 90000
16 37 65 145 258 403 581 581 1040 1040 1040 1764 2115 3596 3596
28 62 111 250 444 693 1002 1002 1777 1777 1777 3560 3700 5678 5678
Product Dimensions Data:
For the 50-01 Main Valve (100-01) dimensions, see pages 17. For the 650-01 Main Valve (100-20) dimensions, see pages 29.
Pilot System Specifications
Adjustment Ranges
0 to 75 psi Max. 20 to 105 psi 20 to 200 psi *
100 to 300 psi
*Supplied unless otherwise specified.
Other ranges available, please consult factory.
Temperature Range
Water: to 180°F
Materials
Standard Pilot System Materials
Pilot Control: Bronze ASTM B62
Trim: Stainless Steel Type 303
Rubber: Buna-N
®
Synthetic Rubber
Tubing & Fitting: Copper and Bronze
Optional Pilot System Materials Pilot Systems are available with optional Aluminum, Stainless Steel or Monel materials at additional cost.
When Ordering, Please Specify
1. Catalog No. 50-01 or No. 650-01
2. Valve Size
3. Pattern - Globe or Angle
4. Pressure Class
5. Threaded or Flanged
6. Trim Material
7. Adjustment Range
8. Desired Options
9. When Vertically Installed
42
E-50-01/650-01 (R-3/2014)
Page 43
Schematic Diagram
Item Description
1 Hytrol (100-01KO Main Valve) 2 X42N-2 Strainer & Needle Valve 3 CRL Pressure Relief Control
MODEL
50-01KO
(Full Internal Port)
Anti-Cavitation Pressure Relief and
Pressure Sustaining Valve
Virtually Cavitation Free Operation
Sensitive and Accurate Pressure Control
Easy Adjustment and Maintenance
Tamper Resistant
Optional Check Feature
Fully Supported Frictionless Diaphragm
The Cla-Val Model 50-01KO Anti-Cavitation Pressure Relief Valve is a hydraulically operated, pilot-controlled, modulating valve designed to main­tain constant upstream pressure within close limits. This valve can be used for pressure relief, pressure sustaining, back pressure, or unloading functions in a by-pass system.
In operation, the valve is actuated by line pressure through a pilot control system, opening fast to maintain steady line pressure but closing gradually to prevent surges. Operation is completely automatic and pressure settings may be easily changed.
If a check feature is added, and a pressure reversal occurs, the down­stream pressure is admitted into the main valve cover chamber, closing the valve to prevent return flow.
Optional Features
Item Description
B CK2 (Isolation Valve) D Check Valves with Isolation Valve F Remote Pilot Sensing H Drain to Atmosphere P X141 Pressure Gauge S CV Speed Control (Opening) V X101 Valve Position Indicator
Product Dimensions Data:
For the 50-01KO Main Valve (100-01) dimensions, see pages 17.
Typical Applications
Supply
CLA-VAL 60-73
Booster Pump
Control Valve
Pump
CLA-VAL Model 50-01KO Pressure Relief Pressure Sustaining Valve
Isolation Valve
Service
Upper Zone
Isolation Valve
CLA-VAL Model 50-01KO
Pressure Relief
Pressure Sustaining
Val ve
Area Of Heavy Demand
Pressure Relief Service
This fast opening, slow closing relief valve provides system protection against high pressure surges on pump start up and pump shut down by dissipating the excess pressure to a safe location.
Pressure Sustaining Service
When installed in a line between an upper zone and a lower area of heavy demand, the valve acts to maintain desired upstream pressure to prevent "robbing" of the upper zone. Water in excess of pressure setting is allowed to flow to an area of heavy demand, control is smooth, and pressure regulation is positive.
43
Page 44
Pump
Discharge To Atmosphere
Isolation
Valve
Pressure Sensing Line
Discharge To System
Discharge To Atmosphere
CLA-VAL
52-03/652-03
Surge Anticipator Valve
CLA-VAL
81-02/681-02 Check Valve
CLA-VAL
61-02/661-02
Pump Control Valve
52-03
(Full Internal Port)
MODEL
652-03
(Reduced Internal Port)
Pressure Relief & Surge Anticipator Valve
• System Saver
• Protects Against Water Hammer Surges
• Opens on Initial Low Pressure Wave
• Closes Slowly to Prevent Subsequent Surges
• Adjustable Over a Wide Range of Settings
The Cla-Val Model 52-03/652-03 Surge Anticipator Valve is indispensable for protecting pumps, pumping equipment and all applicable pipelines from dangerous pressure surges caused by rapid changes of flow veloci­ty within a pipeline.
When pumping systems are started and stopped gradually, harmful surges do not occur. Should a power failure take place, however the abrupt stopping of the pump can cause dangerous surges in the system which could result in severe equipment damage.
Power failure to a pump will usually result in a down surge in pressure, fol­lowed by an up surge in pressure. The surge control valve opens on the initial low pressure wave, diverting the returning high pressure wave from
Schematic Diagram
Item Description
1 Hytrol (Main Valve) 2 X102F Flow Limiter 3 X101 Valve Position Indicator * 4 CK2 Isolation Valve 5 100-01 Hytrol (Reverse Flow) 6 CRL Pressure Relief Control 7 CRA Pressure Reducing Control 8 X58B Restriction Tube Assembly
9 CSC Swing Check Valve 10 X42N-3 Strainer Needle Valve 11 Bell Reducer 12 Pressure Gage 13 CK2 Isolation Valve
14 CK2 Isolation Valve
*Note: X101 or X105L Accessories not available in 4" and smaller sizes.
the system.*In effect, the valve has anticipated the returning high pressure wave and is open to dissipate the damage causing surge. The valve will then close slowly without generating any further pressure surges.
* An adjustable hydraulic flow control limits the valve opening for a controlled initial surge relief.
Product Dimensions Data:
For the 52-03 Main Valve (100-01) dimensions, see pages 17. For the 652-03 Main Valve (100-20) dimensions, see pages 29.
44
Typical Application
The 52-03/652-03 discharges to atmosphere from a tee in the pump discharge header. The valve antici­pates surges caused by power failure as well as acting as a standard overpressure relief valve.
Note: The remote pressure sensing line should
Note: We recommend protecting tubing and valve from freezing temperatures.
3
4
" minimum I.D. installed with a 2° slope
be from the valve to the pipeline to avoid air pockets.
Page 45
Schematic Diagram
Item Description
1 Hytrol (Main Valve) 2 X42N-3 Strainer & Needle Valve 3 CRL Pressure Relief Control 4 CS3 Solenoid Control 5 100-01 Hytrol (Reverse Flow)
58-01
(Full Internal Port)
MODEL
658-01
(Reduced Internal Port)
Combination Back Pressure
& Solenoid Shut-Off Valve
Accurate Pressure Control
Wide Adjustment Ranges
Optional Check Feature Available
Quick Acting Solenoid Shut-Off
Easy Installation and Maintenance
The Cla-Val Model 58-01/658-01 valve performs two separate functions. It maintains a constant back pressure by discharging excess pressure down­stream and when the solenoid is activated the valve closes drip-tight.
In operation, the valve is actuated by hydraulic line pressure through the pilot control system. When inlet pressure is greater than the control setting, the valve opens. When inlet pressure is equal to the control set­ting, the pilot modulates the valve, maintaining the preselected back pressure. When inlet pressure is less than the control setting, the pilot system closes the valve drip tight. Changing the pressure setting sim­ply involves turning an adjusting screw on the pilot control.
The solenoid control is available in energize to open or de-energize to open models.
Optional Features
Item Description
B Shutoff Isolation Valve - Isolates Pilot System
D Check Valves with Isolation Valve
F Remote Pilot Sensing
H Drain to Atmosphere
P X141 Pressure Gauge S CV Speed Control (Opening)
V X101 Valve Position Indicator
Product Dimensions Data:
For the 58-01 Main Valve (100-01) dimensions, see pages 17. For the 658-01 Main Valve (100-20) dimensions, see pages 29.
Typical Applications
Electrode
Supply System
Gound
Storage
Tan k
CLA-VAL 58-01/658-01 Combination Back Pressure and Solenoid Shut-Off Valve
Back Pressure Maintenance Service
A frequent application of this valve is to maintain minimum back pressure in the system while supplying water to a reservoir. The electrode in the storage tank activates the solenoid shutoff feature when the tank reaches a preset level.
Pump
The "D" feature on a vertically installed 6" and larger valve
Electronic Control Service
Using a timer connected to the solenoid control of the valve, flow from the high pressure system to the low pressure system can be controlled at certain times during the day.
must be horizontally oriented.
High Pressure System
CLA-VAL
58-01/658-01
Combination Back
Pressure and Solenoid
Shut-Off Valve
Time Clock
Low Pressure
System
45
Page 46
750-01
MODEL
Pressure Relief, Sustaining & Back Pressure Valve
Description
The Cla-Val Model 750-01 is a hydraulically operated pilot actuated automatic control valve for pressure sustaining, relief and/or back pressure service. The main valve consists of only two parts, a stainless steel body and an elastomeric liner or control element.
The main valve will open when inlet pressure begins to exceed a preset pressure and will allow enough flow to maintain that inlet pressure. In pressure sustaining service, Model 750-01 will conserve pressure in an upper system during periods of high demand in a system below. In pressure relief service, the Model 750-01 will modulate to exhaust line pressure to keep it below a set point maximum. On a pump bypass system, the valve will allow flow back to the pump suction when pump discharge pressure exceeds the set point.
Cla-Val Model 750-01 will control from no flow to full open flow without any chattering or slamming under low flow conditions. For this reason, on by-pass, relief, and pressure sustaining service, there is never a
Performance Specification
Capacity: See Technical Data Sheet CfFactor: 0.9
Cavitation: See Technical Data Sheet Rangeability: 500:1 Bearing Friction: No friction from slip-type
bearings
Design Specification
Sizes: 2, 3, and 6 inch wafer style
6, 8, 10, and 12 inch flanged 6, 8, 10, 12, inch Victaulic® Ends
End Detail Wafer: Fits ANSI B16.5 class 125,150,
250, and 300 flanges
End Detail Flanged: ANSI B16.5 class 150
(fits class 125) or ANSI B16.5 class 300
®
End Detail Victaulic Operating Pressure: 720 psi maximum
Maximum Differential: 150 psid continuous,
Reverse Pressure Temperature Range: 32 to 160 degrees F* Flange Operating Pressure: Class 125-175 psi maximum
Victaulic
*Standard natural rubber 65 durometer in water service. Temperature range depends on liner material. Higher differential pressure ratings available.
For other than standard ANSI flanges consult factory
DIN drilling available on all sizes
®
Ends Rating: 300 psi maximum
: Fits standard steel pipe
: 125 psid maximum
(fits class 250)
®
Victaulic
225 psid intermittent*
Class 150-275 psi maximum Class 250-300 psi maximum Class 300-720 psi maximum
Ends - 300 psi max.
Product Dimensions Data:
For the 750-01 Main Valve (100-42) dimensions, see pages 31.
region of control instability. There is no slip-type friction because the valve has no bearings. Cla-Val Model 750-01 valves have excellent resistance to cavitation with a Cf factor of 0.9. These valves can be supplied as combination control valve with check. Pilot controls, options, and accessories are fully piped at the factory and the Cla-Val Model 750-01 is shipped ready for installation.
Purchase Specification
Valve and control system shall maintain inlet pressure at a predetermined set point; shall open as pressure starts to increase above the set point, and close as pressure falls below the set point. Control valve shall be constructed of two parts: a stainless steel body and an elastomeric liner or control element. Minimum rangeability shall be 500:1 based on capacity at flowing pressure conditions. Cf shall be greater than or equal to 0.9. Valve and control system shall be similar in all respects to Cla-Val Model 750-01 as manufactured by Cla-Val, Newport Beach, California.
Material Specification
Body: 316L Stainless Steel Liner: Natural Rubber, 65 durometer (std)
Liner Retainer: 316 Stainless Steel
Pilot
Body: ASTM B62 Bronze* Spring Cover: ASTM B62 Bronze* Wetted Parts: Bronze/Stainless Steel* Buna-N
Accessories
Shut-off Isolation Valve: Brass* Speed Controls: Brass* Check Controls: Brass* “Y” Strainer: Bronze* Control Piping: Copper* Control Fittings: Brass*
*316 stainless steel available
Viton, EPDM, Nitrile, Silicone (available)
®
46
Page 47
Schematic Diagram
Item Description
1 Hytrol (Main Valve) 2 X42N-2 Strainer & Needle Valve 3 CDB-7 Differential Control
250-01
MODEL
(Full Internal Port)
605-01
(Reduced Internal Port)
Differential Pressure Relief Valve
Accurate Differential Pressure Control
Controls Maximum Flow Through Pumps
Circulating Loop Flow Control
Completely Automatic Operation
The Cla-Val Model 250-01/605-01 Differential Pressure Relief Valve is a hydraulically operated, pilot-controlled, modulating valve. It is designed to maintain a constant pressure differential between any two pressure points in a system where the closing of the valve directly caus­es the differential pressure to increase. The valve tends to open on an increase in differential pressure and close on a decrease in differential pressure.
In operation, the valve is actuated by line pressure through a pilot con­trol system sensing from two points across which a differential is to be maintained. Operation is completely automatic and pressure settings may be easily changed.
Optional Features
Item Description
B CK2 (Isolation Valve)
D Check Valves with Isolation Valve
F Remote Pilot Sensing (H.P.) P X141 Pressure Gauge S CV Speed Control (Opening) V X101 Valve Position Indicator
Product Dimensions Data:
For the 250-01 Main Valve (100-01) dimensions, see pages 17. For the 605-01 Main Valve (100-20) dimensions, see pages 29.
Typical Applications
PUMP SUCTION LOW PRESSURE SENSING
CONNECTED TO DIFFERENTIAL CONTROL
VARIABLE
VARIABLE
PRESSURE
MAIN
PUMP
CLA-VAL 250-01/605-01 DIFFERENTIAL RELIEF
& CHECK VALVE
The Model 250-01/605-01 Differential Pressure Relief Valve main­tains a constant differential across centrifugal pump regardless of variable upstream pressures or downstream demand. By maintaining a constant differential pressure across a centrifugal pump operating at a known capacity, the maximum flow rate is controlled.
DEMAND
Supply to Cirulating Loop
Chilled Water Supply
CLA-VAL
250-01/605-01
Differential Pressure
Relief Valve
Return From Loop
On a chilled water circulating loop system the 250-01/605-01 Differential Pressure Relief Valve is installed between loop supply and return lines to maintain a constant differential across the loop. The loop differential pressure remains constant regardless of the loop demand change there­by increasing cooling system efficiency.
47
Page 48
90-01
(Full Internal Port)
MODEL
690-01
(Reduced Internal Port)
Pressure Reducing Valve
• Sensitive and Accurate Pressure Control
• Easy Adjustment and Maintenance
• Tamper Resistant
• Optional Check Feature
• Fully Supported Frictionless Diaphragm
The Cla-Val Model 90-01/690-01 Pressure Reducing Valve automatically reduces a higher inlet pressure to a steady lower downstream pressure, regardless of changing flow rate and/or varying inlet pressure. This valve is an accurate, pilot-operated regulator capable of holding downstream pressure to a pre-determined limit. When downstream pressure exceeds the pressure setting of the control pilot, the main valve and pilot valve close drip-tight.
If a check feature is added, and a pressure reversal occurs, the down­stream pressure is admitted in the main valve cover chamber, closing the valve to prevent return flow.
Schematic Diagram
Item Description
1 Hytrol (Main Valve) 2 X58 Restriction Fitting 3 CRD Pressure Reducing Control
Optional Features
Item Description
A X46A Flow Clean Strainer
B CK2 (Isolation Valve) C CV Flow Control (Closing)* D Check Valves with Isolation Valve
P X141 Pressure Gauge
V X101 Valve Position Indicator
S CV Flow Control (Opening) Y X43 "Y" Strainer
The closing speed control (optional) on this valve should
*
always be open at least three (3) turns off its seat.
Typical Applications
Typical applications include pressure reducing valve station using Model 90-01BY/690-01BY and Model 90-01AS/690-01AS in parallel to handle wide range of flow rates. Larger Model 90­01BY/690-01BY valve meets requirements of peak loads and smaller Model 90-01AS/690-01AS handles low flows.
High Pressure
CLA-VAL 90-01BY/690-01BY
Pressure Reducing Valve
Isolation Valve
Gauge
CLA-VAL 90-01AS/690-01AS
Pressure Reducing Valve
Constant Downstream Pressure
48
Cla-Val Model Anti-Cavitation Trim provides for optimum downstream pressure control while reducing noise and eliminating damage associated with cavitation.
See Cavitation Guide to determine if the valve is a candidate for the KO Anti-Cavitation Trim.
High Pressure
90-01KO/690-01KO
CLA-VAL Model
90-01KO
Anti-Cavitation Trim
for Excess Pressure Drop
Consult Cavitation Chart
Pressure Reducing Valve with
Isolation Valve
Gauge
Constant Downstream Pressure
Page 49
CLA-VAL
Copyright Cla-Val 2014 Printed in USA Specifications subject to change without notice.
P.O. Box 1325 Newport Beach, CA 92659-0325 Phone: 949-722-4800 Fax: 949-548-5441 E-mail: claval@cla-val.com Website cla-val.com
©
90-01
Valve
Selection
100-01 Pattern: Globe (G), Angle (A), End Connections: Threaded (T), Grooved (GR), Flanged (F) Indicate Available Sizes
Inches 1 11⁄4 11⁄2 2 21⁄2 3 4 6 8 10 12 14 16 18 20 24 30 36
mm 25 32 40 50 65 80 100 150 200 250 300 350 400 450 500 600 750 900
Basic Valve
100-01
Suggested
Flow
(gpm)
Suggested
Flow
(Liters/Sec)
100-01 Series is the full internal port Hytrol. For Lower Flows Consult Factory *Globe Grooved Only
690-01
Valve
Selection
Basic Valve
100-20
Pattern
End Detail T T
Maximum
Maximum Intermittent
Minimum
Maximum
Maximum Intermittent
Minimum
Inches 3 4 6 8 10 12 14 16 18 20 24 30 36 42 48
mm 80 100 150 200 250 300 350 400 450 500 600 750 900 1000 1200
Pattern
End DetailFFFFFFFF FFFFFFF
G, A G, A G, A G, A G, A G, A G, A G, A G, A G, A G, A G, A G, A G G G, A G G
T, F,
T, F,GrT, F,
Gr*
55 93 125 210 300 460 800 1800 3100 4900 7000 8400 11000 14000 17000 25000 42000 50000
68 120 160 260 370 580 990 2250 3900 6150 8720 10540 13700 17500 21700 31300 48000 62500
1111224101535507095120150275450650
3.5 6 8 13 19 29 50 113 195 309 442 530 694 883 1073 1577 2650 3150
4.3 7.6 10 16 23 37 62 142 246 387 549 664 863 1104 1369 1972 3028 3940
.03 .03 .03 .06 .09 0.13 0.25 0.63 0.95 2.2 3.2 4.4 6.0 7.6 9.5 17.4 28.4 41.0
100-20 Pattern: Globe (G), Angle (A), End Connections: Flanged (F) Indicate Available Sizes
GG, AG, AG, AGGGG GGGGGGG
T, F,GrF, GrF,
Gr*
Gr*
F,
FFFFFFFFF
Gr*
Suggested
Flow
(gpm)
Suggested
Flow
(Liters/Sec)
100-20 Series is the reduced internal port size version of the 100-01 Series. For Lower Flows Consult Factory
Maximum
Minimum
Maximum
Minimum
Product Dimensions Data:
For the 90-01 Main Valve dimensions, see pages 17. For the 690-01 Main Valve dimensions, see pages 29.
Pilot System Specifications
Adjustment Ranges
2 to 30 psi
15 to 75 psi
20 to 105 psi 30 to 300 psi*
*Supplied unless otherwise specified Other ranges available, please consult factory
Temperature Range
Water: to 180°F
260 580 1025 2300 4100 6400 9230 9230 16500 16500 16500 28000 33500 57000 57000
1 2 4 10 15 35 50 50 95 95 95 275 450 450 450
16 37 65 145 258 403 581 581 1040 1040 1040 1764 2115 3596 3596
.06 .13 .25 .63 .95 2.2 3.2 3.2 6.0 6.0 6.0 17.4 28.4 41.0 41.0
Many factors should be considered in sizing pressure reducing valves including inlet pressure, outlet pressure and flow rates. For sizing questions or cavitation analysis, consult Cla-Val with system details.
When Ordering, Please
Materials
Standard Pilot System Materials
Pilot Control: Bronze ASTM B62
Trim: Stainless Steel Type 303
Rubber: Buna-N
®
Synthetic Rubber
Optional Pilot System Materials
Pilot Systems are available with optional Aluminum, Stainless Steel or Monel materials at additional cost.
Note: Available with remote sensing control.
Specify
1. Catalog No. 90-01 or No. 690-01
2. Valve Size
3. Pattern - Globe or Angle
4. Pressure Class
5. Threaded, Flanged or Grooved
6. Trim Material
7. Adjustment Range
8. Desired Options
9. When Vertically Installed
10. Product Enhancements
E-90-01/690-01 (R-3/2014)
49
Page 50
90-01KO
(Full Internal Port)
MODEL
Anti-Cavitation Pressure Reducing Valve
Virtually Cavitation Free Operation
Sensitive and Accurate Pressure Control
Easy Adjustment and Maintenance
Tamper Resistant
Optional Check Feature
Fully Supported Frictionless Diaphragm
Schematic Diagram
Item Description
1 Hytrol (100-01KO Main Valve) 2 X58 Restriction Fitting 3 CRD Pressure Reducing Control
Optional Features
Item Description
A X46A Flow Clean Strainer B CK2 (Isolation Valve) C CV Flow Control (Closing)* D Check Valves with Isolation Valve P X141 Pressure Gauge
CV Speed Control (Opening)
S
X101 Valve Position Indicator
V Y X43 "Y" Strainer
*The closing speed control (optional) on this valve should
always be open at least three (3) turns off its seat.
Product Dimensions Data:
For the 90-01KO Main Valve (100-01) dimensions, see pages 17.
The Cla-Val Model 90-01KO Valve automatically reduces a higher inlet pressure to a steady lower downstream pressure, regardless of changing flow rate and/or varying inlet pressure. This valve is an accurate, pilot-operated regulator capable of holding downstream pressure to a pre-determined limit. When down­stream pressure exceeds the pressure setting of the control pilot, the main valve and pilot valve close drip-tight.
If a check feature is added, and a pressure reversal occurs, the down­stream pressure is admitted in the main valve cover chamber, closing the valve to prevent return flow.
The "D" check feature on a vertically installed 6"
and larger valves must be horizontally installed.
Anti-Cavitation Hytrol
Pressure Reducing
Typical Applications
Typical applications include pressure reducing valve station using Model 90-01BYKO and Model 90-01ASKO in parallel to handle wide range of flow rates. Larger Model 90-01BYKO valve meets requirements of peak loads and smaller Model 90-01ASKO handles low flows.
High Pressure
CLA-VAL 90-01BYKO
Pressure Reducing Valve
Isolation Valve
Gauge
CLA-VAL 90-01ASKO
Pressure Reducing Valve
Constant Downstream Pressure
50
Cla-Val Model Cavitation Trim provides for optimum downstream pressure con­trol while reducing noise and eliminating damage associated with cavitation.
See Cavitation Guide to determine if the valve is a candidate for the KO Anti-Cavitation Trim.
High Pressure
90-01KO
CLA-VAL Model
Anti-Cavitation Trim
for Excess Pressure Drop
Consult Cavitation Chart
Pressure Reducing Valve with Anti-
90-01KO
Isolation Valve
Gauge
Constant Downstream Pressure
Page 51
90-48
MODEL
(Full Internal Port)
690-48
(Reduced Internal Port)
Pressure Reducing Valve with
Low Flow By-Pass
Modulating Control
Maintains Constant Outlet Pressure Over a
Wide Range of Flows
Durable Construction
Convenient and Space Saving
The Cla-Val Model 90-48/690-48 Pressure Reducing Valve with Low Flow By-Pass automatically reduces a higher inlet pressure to a steady lower downstream pressure, regardless of changing flow rate. The low flow by-pass capability is achieved by using the Cla­Val Model CRD-40 Direct Acting Pressure Reducing Valve as an integral part of the main valve. By doing this, space is saved and installation and maintenance become much easier.
The pressure reducing valve is hydraulically operated and con­trolled by a Cla-Val CRD pilot control, which senses pressure at the main valve outlet. An increase in outlet pressure forces the CRD pilot control to close and a decrease in outlet pressure opens the control. This causes the main valve cover pressure to vary, modu­lating the main valve, thereby, maintaining constant outlet pres­sure.
Schematic Diagram
Item Description
1 Hytrol (Main Valve) 2 X47A Ejector 3 CRD Pressure Reducing Control 4 CRD-40 Pressure Reducing Valve 5 CK2 (Isolation Valve)
Optional Features
Item Description
A X46A Flow Clean Strainer B CK2 (Isolation Valve) C CV Flow Control (Closing)* D Check Valves with Isolation Valve P X141 Pressure Gauge
S CV Speed Control (Opening) V X101 Valve Position Indicator Y X43 "Y" Strainer
*The optional closing speed control on this valve should
always be open at least three (3) turns off its seat.
*
Typical Applications
This valve has the flexibility to be installed in a distribution sys­tem where the demand varies over a wide range. This frequent­ly occurs in industrial, residential, educational, high-rise build­ings and other applications. Another important feature of the valve is its space efficient configuration, allowing easy installa­tion and maintenance.
The Model CRD-40 low flow pressure reducing by-pass is preset to a higher pressure than the CRD pilot control. The CRD-40 responds to pressure changes at the main valve outlet. When the CRD closes, the Model CRD-40 remains open, allowing low flow to by-pass the main valve. The CRD-40 closes when the flow decreases and the downstream pressure reaches its set-point .
The Cla-Val Model 90-48/690-48 is not a substitute for a low flow bypass valve in all cases. This valve is commonly used in building where 1-15 gpm low flows are common in off peak usage. The bypass on this valve is limited to the body tapping size on the main valve.
Product Dimensions Data:
For the 90-48 Main Valve (100-01) dimensions, see pages 17. For the 690-48 Main Valve (100-20) dimensions, see pages 29.
51
Page 52
92-01
(Full Internal Port)
MODEL
692-01
(Reduced Internal Port)
Combination Pressure Reducing & Pressure Sustaining Valve
Accurate Response to Slight Pressure Changes
Check Feature Available
Completely Automatic Operation
Drip-Tight, Positive Seating Action
Operation is Fully Hydraulic
The Cla-Val Model 92-01/692-01 Combination Pressure Reducing and Pressure Sustaining Valve automatically performs two inde­pendent functions. It maintains a constant downstream pressure, regardless of fluctuating demand and sustains the upstream pres­sure to a pre-determined minimum.
The pressure reducing control responds to slight variations in down­stream pressure and immediately repositions the main valve to maintain the desired downstream pressure. The pressure sustaining control is normally held open by the upstream pressure, but modu­lates should the pressure drop to the control set point. This, in turn, modulates the main valve to sustain the desired upstream pressure.
Schematic Diagram
Item Description
1 Hytrol (Main Valve) 2 X44A Strainer & Orifice 3 CRD Pressure Reducing Control 4 CRL Pressure Relief Control 5 CV Flow Control (Opening)
If a check feature is added, and a pressure reversal occurs, the downstream pressure is admitted into the main valve cover cham­ber and the valve closes to prevent return flow.
Optional Features
Item Description
B CK2 (Isolation Valve) C CV Flow Control (Closing)* D Check Valves With Isolation Valve
F Remote Pilot Sensing
P X141 Pressure Gauge
V X101 Valve Position Indicator
* The (optional) closing speed control on this valve should
always be open at least three (3) turns off its seat.
Product Dimensions Data:
For the 92-01 Main Valve (100-01) dimensions, see pages 17. For the 692-01 Main Valve (100-20) dimensions, see pages 29.
Isolation Valve
High Pressure Main
CLA-VAL MODEL
Combination Pressure Reducing
92-01/692-01
& Pressure Sustaining Valve
Distribution
Typical Applications
A Combination Pressure Reducing and Pressure Sustaining Valve is typical used to automatically reduce pressure for the downstream distribution network and sustain a minimum pressure in the high pressure main regardless of distribution demand.
52
Page 53
Schematic Diagram
Item Description
1 Hytrol (Main Valve) 2 X58C Restriction Assembly 3 CRD Pressure Reducing Control 4 100-01 Hytrol (Reverse Flow) 5 CS3 Solenoid Control
93-01
(Full Internal Port)
MODEL
693-01
(Reduced Internal Port)
Pressure Reducing &
Solenoid Shut-Off Valve
Accurate Pressure Control
Wide Adjustment Ranges
Optional Check Feature Available
Quick Acting Solenoid Shut-Off
Easy Installation and Maintenance
The Cla-Val Model 93-01/693-01 Combination Pressure Reducing and Solenoid Shut-Off Valve consists of a Cla-Val Hytrol main valve, a reduc­ing control and a solenoid control connected to the main valve. This valve automatically reduces higher inlet pressure to a steady lower downstream pressure, regardless of changing flow rate and/or varying inlet pressure.
The 93-01/693-01 is an accurate, pilot-operated regulator capable of holding downstream pressure to a pre-determined delivery pressure. When downstream pressure exceeds the pressure setting of the control pilot, the pilot valve and main valve close drip-tight. A solenoid control is provided to intercept the operation of the pressure reducing control and close the main valve. This valve is furnished either normally open (de­energized to open), or normally closed (energized to open). Pressure setting adjustment is made with a single adjusting screw.
Optional Features
Item Description
A X46A Flow Clean Strainer B CK2 (Isolation Valve) C CV Flow Control (Closing)* D Check Valves with Isolation Valve H Solenoid Drain To Atmosphere P X141 Pressure Gauge S CV Speed Control (Opening) V X101 Valve Position Indicator Y X43 "Y" Strainer
The closing speed control (optional) on this valve should
*
always be open at least three (3) turns off its seat.
Product Dimensions Data:
For the 93-01 Main Valve (100-01) dimensions, see pages 17. For the 693-01 Main Valve (100-20) dimensions, see pages 29.
Typical Applications
Electronic Control Service
A typical application for this valve is to reduce high transmission line pressures to lower distribution system levels, while opening and closing on command. The solenoid control feature can be activated by an electrical signal from a timer or programmer.
Fire Service
The 93-01/693-01 can be installed in a distribution line where there is a need to close the valve on the starting of a fire pump. The solenoid control is activat­ed on pump start-up and closes the valve.
53
Page 54
94-01
(Full Internal Port)
MODEL
694-01
(Reduced Internal Port)
Combination Pressure Reducing and Surge Control Valve
Sensitive and Accurate Pressure Control
Easy Adjustment and Maintenance
Tamper Resistant
Optional Check Feature
Fully Supported Frictionless Diaphragm
The Cla-Val Model 94-01/694-01 Combination Pressure Reducing and Surge Control Valve automatically reduces a higher inlet pressure to a steady lower downstream pressure, regardless of changing flow rate and/or varying inlet pressure. This valve is an accurate, pilot-operated con­trol valve capable of holding downstream pressure to a pre-determined limit. When downstream pressure rapidly exceeds the pressure setting of the pressure reducing control pilot, the surge pilot (CRL) will open quickly to prevent a rapid pressure rise downstream.
Schematic Diagram
Item Description
1 100-01 Hytrol (Main Valve) 2 X58C Restriction Assembly 3 CRD Pressure Reducing Control 4 CRL Pressure Relief Control
If a check feature is added, and a pressure reversal occurs, the down­stream pressure is admitted in the main valve cover chamber closing the valve to prevent return flow.
Optional Features
Item Description
A X46A Flow Clean Strainer
B CK2 (Isolation Valve) C CV Flow Control (Closing)* D Check Valves with Isolation Valve
F Remote Pilot Sensing
P X141 Pressure Gauge S CV Speed Control (Opening)
V X101 Valve Position Indicator Y X43 "Y" Strainer
*The closing speed control (optional) on this valve should
always be open at least three (3) turns off its seat.
Product Dimensions Data:
For the 94-01 Main Valve (100-01) dimensions, see pages 17. For the 694-01 Main Valve (100-20) dimensions, see pages 29.
Typical Application
Should the downstream pressure sudden­ly increase above the setting of the pres­sure reducing control due to on-off opera­tion of two or more downstream systems, the Surge Control tracks rapidly enough to prevent high pressure surges from enter­ing any of the downstream systems, when any one of the downstream systems is rapidly closed off. The typical combination pressure reducing and surge control valve station uses Model 94-01BY/694-01BY to control surges in downstream piping as remote control valves change from one downstream zone to another. Surge Control is set approximately 10 psi above Pressure Reducing Control to prevent high pressure surge entering other down­stream zones.
54
Page 55
MODEL
990
Balanced Direct Acting
Pressure Reducing Valve
• Balanced, Single Seat Design
• Operates in Any Position
• Easy Installation
• Stainless Steel Trim Standard
• Gauge Connections Standard
• All Bronze Body and Cover
The Cla-Val Model 990 Pressure Reducing Valve automatically reduces a higher inlet pressure to a steady lower downstream pres­sure with our unique balanced design. This valve is an accurate reg­ulator capable of holding downstream pressure to a predetermined amount, regardless of upstream pressure fluctuations.
Periodic maintenance consist of regular cleaning of internal strainer that is accessed by removing bottom plug. There are no user serv­iceable components.
Typical Applications
High rise buildings use 990 Pressure Reducing Valves
in various water systems (potable water, boiler feed air conditioning, etc.) to control pressure fluctuations between floors.
Industrial plants use 990 Pressure Reducing Valves between a high pressure supply system and equipment requiring lower pressure. Typically 990 Pressure Reducing Valves are used at supply connections for water heaters, boiler feed water or other process water systems.
Municipal water systems use 990 Pressure Reducing Valves at service connections in a high pressure distribution zone.
Depending on flow requirements, 990's may be installed in parallel. One 990 provides desired outlet pressure while the second 990 handles low flow conditions. If necessary, addi­tional 990s can be added for more flow capacity. The 990 is also ideal for a low flow bypass around a larger Cla-Val 90 Series Pressure Reducing Valve.
Flow
Isolation Valve
55
Page 56
790-01
SINGAPORE
PUB
MODEL
Pressure Reducing Valve
Description
The Cla-Val Model 790-01 is a hydraulically operated, pilot actuated automatic control valve for pressure reducing service. The main valve consists of only two parts: a stainless steel body, and an elastomeric liner or control element.
Pressure reducing valves are used to lower pipeline pressure to a predetermined set point. Cla-Val Model 790-01 automatically controls downstream pressure, from no flow to full open flow, without regard to changes in inlet pressure. Outlet pressure control is smooth and precise since the friction and hysteresis of the valve and pilot is negligible.
Because the valve will not chatter or slam under low flow conditions, it is not necessary to parallel Cla-Val Model 790-01 with a second smaller size control valve to obtain accurate pressure control at low flow rates. In any size, Cla-Val Model 790-01 will control pressure right down to shutoff.
Performance Specification
Capacity: See Technical Data Sheet CfFactor: 0.9 Cavitation: See Technical Data Sheet Rangeability: 500:1 Bearing Friction: No friction from slip-type
bearings
Design Specification
Sizes: 2, 3, and 6 inch wafer style
6, 8, 10, and 12 inch flanged 6, 8, 10, 12 inch Victaulic
End Detail Wafer: Fits ANSI B16.5 class 125,150,
250, and 300 flanges
End Detail Flanged: ANSI B16.5 class 150
(fits class 125) or ANSI B16.5 class 300
End Detail Victaulic Operating Pressure: 720 psi maximum
Maximum Differential: 225 psid
Reverse Pressure
Approvals: PUB Listed.........Sizes 2" thru 6"
Temperature Range: 32 to 160 degrees F* Flange Operating Pressure: Class 125-175 psi maximum
Victaulic
*Standard natural rubber 65 durometer in water service.
Temperature range depends on liner material. Higher differential pressure ratings available.
For other than standard ANSI flanges consult factory
DIN drilling available on all sizes
56
®
Ends Rating: 300 psi maximum
®
: Fits standard steel pipe
: 125 psid maximum
(fits class 250)
Victaulic
For higher differential consult factory
Class 150-275 psi maximum Class 250-300 psi maximum Class 300-720 psi maximum
®
Ends - 300 psi max.
®
Ends
Pressure reducing valves can be supplied as a combination with check valve. Control systems are fully piped at the factory and the Cla-Val Model 790-01 is shipped ready for installation.
Purchase Specification
Valve and control system shall lower line pressure to a predetermined set point and shall maintain that set point regardless of variations in flow or inlet pressure. Control valve shall be constructed of two parts: a stainless steel body, and an elastomeric liner or control element. Minimum rangeability shall be 500:1 based on capacity at flowing pressure conditions. C and control system shall be similar in all respects to Cla-Val Model 790-01 as manufactured by Cla-Val, Newport Beach, California.
f shall be greater than or equal to 0.9. Valve
Material Specification
Body: 316L Stainless Steel Liner: Natural Rubber, 65 durometer (standard)
Viton, EPDM, Nitrile, Silicone (available)
Liner Retainer: 316 Stainless Steel
Pilot
Body: ASTM B62 Bronze* Spring Cover: ASTM B62 Bronze* Wetted Parts: Bronze/Stainless Steel*, Buna-N
®
Accessories
Shut-off Isolation Valve: Brass* "Y" Strainer: Bronze* Speed Controls: Brass* Check Controls: Brass* Control Piping: Copper* Control Fittings: Brass*
316 stainless steel available
*
Product Dimensions Data:
For the 790-01 Main Valve (100-42) dimensions, see pages 31.
Page 57
2
INLET
B
B
6A
P1
S
C
6B
3
7
1
5
9
ADJUSTMENT
HIGH PRESSURE
10
LOW
ADJUSTMENT
PRESSURE
11
4
B
8
ADJUSTMENT SCREW
P2
MODEL
98-06
(Full Internal Port)
698-06
(Reduced Internal Port)
(2"-10")
(3"-12")
Hydraulic
Pressure Management Control Valve
with Dual Setpoints
100% Hydraulic Control
Two Adjustable Downstream Set Points for
High and Low Pressure
Simple to Setup and Adjust
Smooth Transition from High to Low Pressure
Retrofits to Existing Valve Without Removal
From Pipeline
Helps Prevent Pipe Breaks and Background Leaks
The Cla-Val Model 98-06/698-06 Pressure Management Control Valve is a pressure reducing valve that allows for two downstream set points. A high pressure set point is selected for high flow demand and a low pressure set point is selected for low flow demand. This dual set point arrangement allows for reduction in water loss by not over pressurizing the system during times of low demand, while providing adequate pressure during high or fire demand. The design is 100% hydraulic and in addition to the dual pressure set points the transition point at which the pressure changes based on the flow is adjustable as well. The patent pending design of the valve allows for smooth transition from one
Patent
Pending
Schematic Diagram
Item Description
1 Hytrol (Main Valve) 2 X43 “Y” Strainer 3 X58C Restriction Assembly 4 CPM-A Pressure Management Control 5 X78-4 Stem Assembly + X101 Valve
Position Indicator Assembly
6 CK2 (Isolation Valve) 7 X44A Strainer Orifice Assembly 8 X141 Gage Assembly
9 6120 Needle Valve 10 X58E Restriction Assembly 11 Accumulator (Air Charged)
Optional Features
Item Description
B CK2 (Isolation Valve) C CV Flow Control (Closing) P X141 Gage Assembly S CV Flow Control (Opening)
Typical Performance
A dual system pressure with reduced system pressure during low demand periods is illustrated in the chart. At low flows a minimum pressure is maintained and as flow increases to the switch point delivery pressure increases to the maximum pressure set point for switch. The point between low pressure and high pressure setpoints is adjustable to fine tune valve to system requirements.The “water saving zone” below maximum pressure line represents valve effectiveness in reducing water losses and pipeline breakage in a system.
set point to the other.
P1
Upstream
Pressure
Upstream
Pressure
(P1)
Go to www.cla-val.com for Purchase Specification
Water Saving Zone for reduced leakage and fewer pipe breaks
Water Saving Zone
Pressure
Modulating Profile
flow
Low Demand
Flow
Downstream
Pressure
P2 (Q max.)
P2 (Q min.)
Q = Flow
High Demand
(Fire Flow, Irrigation, etc.)
LP
Savings
Setpoint High
Downstream
Pressure (P2)
Setpoint Low
HP
57
Page 58
Y
CS3
2
1
3
5
4
3B
3A
H
SOLENOID DRAIN TO
ATMOSPHERE
C
D2
D3
B
B
S
2
D1
B
A
1
INLET OUTLET
90-11
(Full Internal Port)
690-11
(Reduced Internal Port)
MODEL
790-11
Pressure Reducing Valve with Two Stage - Solenoid Selected Pressure
• Two Adjustable Setpoints
• Sensitive and Accurate Pressure Control
• Ideal For Use with SCADA System
• Low Power Required
• Low Maintenance Cost
The Cla-Val Model 90-11 Two-Stage Pressure Reducing Control valve allows selection between two different pressure-reducing set points. It has one pilot set at a higher pressure setting; a second pilot set at a lower pressure setting and a sole­noid control to select the active pilot control for the main valve. The valve smooth­ly changes setpoint and will control pressure regardless of inlet pressure fluctua­tions or downstream demand changes. Set point switching is achieved by ener­gizing the solenoid control for the desired time that the low pressure is needed. The two set points are easily changed in the field.
This valve is suitable for many pressure control applications where downstream conditions change sufficiently to require a lowered pressure during part of the time. A variety of electronic controls can be use with the 90-11 ranging from a simple bat­tery powered timer to extensive SCADA systems. In leakage abatement applica­tions, the 90-11 offers simplified two-pressure control of a distribution zone. For times of high demand, the higher pressure control is used and for times of low demand, the lower pressure control is selected.
Schematic Diagram
Item Description
1 Hytrol (Main Valve) 2 X58 Restriction Fitting 3 CRD Pressure Reducing Control 4 100-01 Auxiliary Hytrol (Reverse Flow) 5 CS3 Solenoid Control
Optional Features
Item Description
A X46A Flow Clean Strainer B CK2 (Isolation Valve) C CV Flow Control (Closing) D Check Valves with Isolation Valve H Solenoid Drain to Atmosphere S CV Flow Control (Opening) Y X43 "Y" Strainer
Typical Application
The valve can be used to conserve water by lowering the system pressure during low demand periods.The valve is designed to be used with a SCADA system that will select which setpoint to use. provide a control system to determine when to shift the solenoid so as to prevent holding the low pressure set point during unforeseen high flow demands such as fire flow.
Product Dimensions Data:
For the 90-11 Main Valve (100-01) dimensions, see pages 17. For the 690-11 Main Valve (100-20) dimensions, see pages 29. For the 790-11 Main Valve (100-42) dimensions, see pages 31.
58
The customer must
Page 59
CLA-VAL
Schematic Diagram
Item Description
1 Hytrol (Main Valve) 2 X58C Restriction Assembly 3 CRD Pressure Reducing Control 4 CTC Electronic Timer Control 5 100-01 Auxiliary Hytrol
97-20
MODEL
(Full Internal Port)
697-20
(Reduced Internal Port)
Dual Stage Pressure Reducing Control Valve
with Programmable Timer Control
Precise Valve On-Off Control
Completely Self-contained
High Energy Efficiency
Battery Life Exceeds 3 Years
Direct Control of Valve Opening and Closing Four Times Daily
Combines with Pressure, Flow or Level Control
Ideal for Remote Valve Location Control
FLOW
The Cla-Val Model 97-20/690-20 Dual Stage Pressure Reducing Control Valve with Programmable Timer Control allows selection between two differ­ent pressure-reducing set points. It has one pilot set at a higher pressure set­ting; a second pilot set at a lower pressure setting and a solenoid control to select the active pilot control for the main valve. The valve smoothly changes setpoint and will control pressure regardless of inlet pressure fluctuations or downstream demand changes. Set point switching is achieved by energiz­ing the solenoid control for the desired time that the low pressure is needed. The two set points are easily changed in the field. This valve is suitable for many pressure control applications where down­stream conditions change sufficiently to require a lowered pressure during part of the time. In leakage abatement applications, the 97-20 offers simpli­fied two-pressure control of a distribution zone. For times of high demand, the higher pressure control is used and for times of low demand, the lower pressure control is selected. Timer function and parameters are changed using downloadable software from the Cla-Val website www.cla-val.com and special USB cable part number 20519203A. Future software and firmware upgrades will be avail­able from Cla-Val website. Powered by a long-life lithium battery, the CTC control offers powerful valve control for remote locations and other valve automation applications.
Optional Features
Item Description
A X46A Flow Clean Strainer B CK2 (Isolation Valve)*
C CV Flow Control (Closing) D Check Valves with Isolation Valve
S CV Flow Control (Opening) Y X43 “Y” Strainer
*Standard on 1-1/4” and larger
Product Dimensions Data:
For the 97-20 Main Valve (100-01) dimensions, see pages 17. For the 697-20 Main Valve (100-20) dimensions, see pages 29.
Typical Application
The valve can be used to conserve water by lowering the system pressure during low demand periods.The valve is designed to help prevent pipe breaks in the system. determine when to shift the solenoid so as to prevent holding the low pressure set point during unforeseen high flow demands such as fire flow.
The customer must provide a control system to
Upper Zone
CLA-VAL
Dual Stage Pressure Reducing Valve
97-20/697-20
with Programmable Timer Control
System Pressure High Pressure-For high flow demand Low Pressure-For low flow demand
Isolation Valve
59
Page 60
40-01
(Full Internal Port)
MODEL
640-01
(Reduced Internal Port)
Rate of Flow Control Valve
Accurately Limits Flow Rate
Completely Automatic Operation
Includes Orifice Plate with Holder
Optional Check Feature
Easily Adjusted
The Cla-Val Model 40-01/640-01 Rate of Flow Control Valve prevents excessive flow by limiting flow to a preselected maximum rate, regard­less of changing line pressure. It is a hydraulically operated, pilot con­trolled, diaphragm valve. The pilot control responds to the differential pressure produced across an orifice plate installed downstream of the valve. Accurate control is assured as very small changes in the control­ling differential pressure produce immediate corrective action of the main valve. Flow rate adjustments are made by turning an adjusting screw on the pilot control.
Schematic Diagram
Item Description
1 Hytrol (Main Valve) 2 X58C Restricting Fitting 3 CDHS18 Differential Control 4 X52E Orifice Plate Assembly
Optional Features
Item Description
A X46A Flow Clean Strainer B CK2 (Isolation Valve) C CV Flow Control (Closing) D Check Valves with Isolation Valve P X141 Pressure Gauge
S CV Speed Control (Opening) V X101 Valve Position Indicator Y X43 "Y" Strainer
Product Dimensions Data:
For the 40-01 Main Valve (100-01) dimensions, see pages 17. For the 640-01 Main Valve (100-20) dimensions, see pages 29.
Typical Applications
The Model 40-01/640-01 includes an orifice plate with a holder that should be installed one to five pipe diameters downstream of the valve. If the check feature option is added and a pressure reversal occurs, the downstream pressure is admitted into the main valve cover chamber and the valve closes to prevent return flow. See X52E data sheet for sizing selection.
The 40-01/640-01 is typically installed where water supply to a system must be limited to a preset maximum flow rate. The valve is easily set to maintain the maximum allowable flow rate.
60
The 40-01/640-01 is typically installed as a pressure type filter effluent control valve where a constant flow rate is maintained as head loss through the filter varies.
Page 61
Schematic Diagram
Item Description
1 Hytrol (Main Valve) 2 X58C Restriction Fitting 3 100-01 Hytrol (Reverse Flow) 4 CDHS18 Differential Control 5 CS3 Solenoid Control 6 X52E Orifice Plate Assembly
43-01
(Full Internal Port)
MODEL
643-01
(Reduced Internal Port)
Combination Rate of Flow Control
& Solenoid Shut-Off Valve
Multi-functional Capability
Includes Orifice Plate with Holder
Optional Check Feature
Easily Adjusted
Every Valve Factory Tested
The Cla-Val Model 43-01/643-01 Combination Rate of Flow Control and Solenoid Shut-Off Valve limits the maximum flow rate, regard­less of changing line pressure. It is a hydraulically operated, pilot controlled, diaphragm valve. The pilot control is actuated by the differential pressure produced across an orifice plate installed downstream of the valve. Accurate control is assured as very small changes in the controlling differential pressure pro­duce immediate corrective action of the main valve. A solenoid con­trol is provided to intercept the operation of the differential control and close the main valve.
The Model 43-01/643-01 includes a orifice plate with a holder that should be installed one to five pipe diameters downstream of the main valve. If the check feature option is added and a pressure reversal occurs, the downstream pressure is admitted into the main valve cover chamber and the valve closes to prevent return flow.
Optional Features
Item Description
A X46A Flow Clean Strainer B CK2 (Isolation Valve) C CV Flow Control (Closing) D Check Valves with Isolation Valve
H Solenoid Drain to Atmosphere P X141 Pressure Gauge S CV Speed Control (Opening) V X101 Valve Position Indicator
Y X43 “Y” Strainer
Product Dimensions Data:
For the 43-01 Main Valve (100-01) dimensions, see pages 17. For the 643-01 Main Valve (100-20) dimensions, see pages 29.
The 43-01/643-01 is typically installed where water supply to a system must be limited to a pre-set maximum flow rate at certain times of day. The valve is easily set to maintain the maximum allowable flow rate and is to open or close on an electrical signal.
The "D" feature on a vertically installed 6" and larger valves must be horizontally installed.
The 43-01/643-01 is typically installed as a pressure type filter effluent control valve where a constant flow rate is maintained as head loss through the fil­ter varies. The valve opens or closes on an electri­cal signal.
61
Page 62
49-01
(Full Internal Port)
MODEL
649-01
(Reduced Internal Port)
Combination Rate of Flow & Pressure Reducing Valve
Multi-Functional Capability
Accurate and Immediate Control
Includes Orifice Plate with Holder
Optional Check Feature
Easily Adjustable Controls
The Cla-Val Model 49-01/649-01 Rate of Flow and Pressure Reducing Valve automatically reduces a higher inlet pressure to a steady lower downstream pressure regardless of changing flow rate and/or varying inlet pressure, as long as the flow rate is below a preset maximum. It also prevents excessive flow by limiting flow to a preselected maxi­mum rate.
This valve is a hydraulically operated, pilot controlled diaphragm valve. The pilot system includes a direct acting pressure reducing pilot and a rate of flow differential control. The pressure reducing pilot is respon­sive to slight variations in downstream pressure and immediately con­trols the main valve to maintain the desired line pressure.
Schematic Diagram
Item Description
1 Hytrol (Main Valve) 2 X58A Restriction Fitting 3 CRA Pressure Reducing Control 4 X52E Orifice Plate Assembly 5 CDHS18 Differential Control
Optional Features
Item Description
A X46A Flow Clean Strainer B CK2 (Isolation Valve) C CV Flow Control (Closing) D Check Valves with Isolation Valve P X141 Pressure Gauge S CV Speed Control (Opening) V X101 Valve Position Indicator Y X43 "Y" Strainer
Product Dimensions Data:
For the 49-01 Main Valve (100-01) dimensions, see pages 17. For the 649-01 Main Valve (100-20) dimensions, see pages 29.
The rate of flow control responds to the differential pressure produced across an orifice plate in the main line. Accurate control is assured as very small changes in the controlling differential pressure produce immediate corrective action by the main valve.
If the check feature option is added and a pressure reversal occurs, the downstream pressure is admitted into the main valve cover cham­ber and the valve closes to prevent return flow.
62
Supply
Main
Meter
Cla-Val 49-01/649-01
Isolation Valve
Flow
Typical Application
Installed where water supply to a system must be limited to a preset flow to prevent lowering the supply pressure. Easily set to main­tain the maximum allowable flow rate.
Page 63
Schematic Diagram
Item Description
1 Hytrol (Main Valve) 2 CF1-C1 Float
Control
Optional Features
MODEL
(Sizes 1/2"- 6"Full Internal Port)
624-01
124-01
(Sizes 3"- 8"Reduced Internal Port)
Float Valve
• Accurate and Repeatable Level Control
• On-Off or Non-Modulating Action
• Fully Adjustable High and Low Level Settings
• Simple Design, Proven Reliable
• Easy Installation and Maintenance
The Cla-Val Model 124-01/624-01 Float Valve is a non-modulating valve that accurately controls the liquid level in tanks. This valve is designed to open fully when the liquid level reaches a pre-set low point and close drip-tight when the level reaches a preset high point.
This is a hydraulically operated, diaphragm valve with the pilot control and float mechanism mounted on the cover of the main valve. The float positions the pilot control to close the valve when the float contacts the upper stop. The high and low liquid levels are adjusted by positioning the stop collars on the float rod. The dif­ference between high and low levels can be adjusted to as little as one inch, or to as much as eighteen inches.
Level settings can be as much as eleven and one half feet below the valve. The float mechanism may be located remotely from the main valve. See the technical data sheet on Model CF1-C1 Float Control for additional information.
Note: For 8
" and Larger Float Valve Sizes use Model 124-02/624-02
Item Description
A X46A Flow Clean Strainer B CK2 (Isolation Valve) C CV Flow Control (Closing) F Independent Operating Pressure P X141 Pressure Gauge
S CV Speed Control (Opening) V X101 Valve Position Indicator
Y X43 "Y" Strainer
CLA-VAL
124-01/624-01
Float Valve
Supply
Tank
Stilling Well
Product Dimensions Data:
For the 124-01 Main Valve (100-01) dimensions, see pages 17. For the 624-01 Main Valve (100-20) dimensions, see pages 29.
Typical Applications
The Model 124-01/624-01 Float Valve is commonly mounted above the high water level in a tank. Globe pattern valves are supplied standard with the float control mounted on the cover as illustrated, with a horizontal discharge. Angle valves are configured to discharge downward. Note: 1. We recommend protecting
tubing and valve from freezing temperatures.
2. Must be inspected periodically
Installation
A stilling well (8" minimum diameter) must be provided around the float. When the valve is mounted on top of the tank roof, a 2" clearance hole should be provided for side movement of the float rod where the rod goes through the top of the tank.
A clear independent source of air or water may be used to operate the valve (option F). The pressure from this independent source must at all times be equal to or greater than pressure at the valve inlet.
If minimum flowing line pressure is less than 10 psi, consult factory.
If the float control is remotely mounted from the main valve, the control may be installed at any elevation above the valve, provided the flowing line pressure in psi is greater than the vertical distance in feet between the valve and the float control. See the technical data sheet on Model CF1-C1 for additional information.
63
Page 64
129-01
(Full Internal Port)
MODEL
629-01
(Reduced Internal Port)
Float Valve
Schematic Diagram
• Accurate and Repeatable Level Control
• Proportional Flow
• Reliable Hydraulic Operation
• Drip-Tight Positive Shut-Off
• Completely Automatic Operation
The Cla-Val Model 129-01/629-01 Float Valve maintains a relatively constant level in storage tanks and reservoirs by admitting flow into the tank in direct proportion to the flow out of the tank. It is a hydraulically operated, pilot controlled, diaphragm valve. The rotary disc type float operated pilot control is installed at the high liquid level in the reservoir and is connected via tubing or pipe to the main valve. As the liquid level changes, the float control proportionally opens or closes the main valve, keeping the liquid level nearly constant. If the check feature option "D" is added and a pressure reversal occurs, the downstream pressure is admitted into the main valve cover chamber and the valve closes to prevent return flow.
Item Description
1 Hytrol (Main Valve) 2 X47A Ejector 3 Bell Reducer 4 CFM2 Float Control
Optional Features
Item Description
A X46A Flow Cleaner Strainer B CK2 (Isolation Valve) C CV Flow Control (Closing) D Check Valves With Isolation Valve F Independent Operating Pressure P X141 Pressure Gauge
S CV Speed Control (Opening) V X101 Valve Position Indicator
Typical Applications
Product Dimensions Data:
For the 129-01 Main Valve (100-01) dimensions, see pages 17. For the 629-01 Main Valve (100-20) dimensions, see pages 29.
Piping and Tank Sizing
Install valve and control as shown in the diagram above. The float control should be located in a still liquid surface. If it is necessary to obtain this condition, a stilling well should be constructed. Mount the float control on the connecting piping with the outlet port at the desired high water level. supply pressure (Option F) is used by the pilot control system, that pressure must at all times be constant and equal to or greater than the pressure at the valve inlet.
64
When a separate source of
Filter Liquid Level Control
Maintains constant level in rapid sand filter. Usually requires the use of an independent operating pressure as shown.
DO NOT USE FOR ON-OFF SERVICE.
Note: We recommend protecting tubing and valve from freezing temperatures.
Page 65
Schematic Diagram
Isolation
Valve
Control Lines 3/4" Min. I.D.
Open Tank-"Air Gap" Valve
Closes on Rising Level
Balances Tank Effluent Rate
to Equal Influent Rate.
Stilling Well
Flow
CFM9
Water Level
Cla-Val 428-01/628-01 Modulating Float Valve
Item Description
1
Hytrol Main Valve
2 CFM-9 Float Control 3 CK2 (Isolation Valve)
428-01
(Full Internal Port)
MODEL
628-01
(Reduced Internal Port)
Modulating Float Valve
Accurate Level Control
Completely Automatic Operation
Simple Operation
Drip-Tight Shut-Off
Easy Installation and Maintenance
The Cla-Val Model 428-01/628-01 Float Valve modulates to maintain a constant liquid level in a storage tank by compensating for variations in supply or demand. It can be installed to control the flow into or out of the tank by either closing on a rising level or opening on a rising level. This valve is a hydraulically operated, pilot controlled diaphragm valve.
The pilot control system consists of an integral variable orifice in the main valve cover and a remotely mounted float control. A slight change in liquid level moves the float control. This action varies the pressure in the valve cover, causing the main valve to seek a new position. The integral variable orifice automatically regulates the flow into the cover chamber until the valve reaches a position that is in direct relation to the position of the float control.
Optional Features
Item Description
A X46A Flow Clean Strainer D Check Valves with Isolation Valve F Independent Operating Pressure P X141 Pressure Gauge
Y X43 “Y” Strainer
Product Dimensions Data:
For the 428-01 Main Valve (100-32) dimensions, see pages 17. For the 628-01 Main Valve (100-33) dimensions, see pages 29.
Installation Data
The valve may be installed in any position. The remote float control may be mounted at any convenient location above the liquid level. Float rods are available in lengths from 2' to 12' in one-foot increments.
A stilling well (8" min. diameter) should be provided around the float if the liquid surface is subject to turbu­lence, ripples or wind.
The float control may be installed at any elevation above the valve providing that the amount of flowing line pres­sure (in psi) is equal to or greater than the vertical dis­tance in feet between the valve and the float control.
When a separate source of supply pressure (Option F) is used by the pilot control system, that pressure must at all times be constant and equal to or greater than the pres­sure at the valve inlet.
DO NOT USE FOR ON-OFF SERVICE.
Note: We recommend protecting tubing and valve
from freezing temperatures.
Typical Applications
65
Page 66
210-01
(Full Internal Port)
MODEL
610-01
(Reduced Internal Port)
Altitude Valve For One-Way Flow
Accurate and Repeatable Level Control
• Drip-Tight, Positive Shut-Off
• Reliable Hydraulic Operation
• Easily Adjustable Control
• Completely Automatic Operation
The Cla-Val Model 210-01/610-01 Altitude Valve controls the high water level in reservoirs without the need for floats or other devices. It is a non­throttling valve that remains fully open until the shut-off point is reached. This valve is designed for one-way flow only.
This valve is hydraulically operated and pilot controlled. The pilot control operates on the differential in forces between a spring load and the water level in the reservoir. The desired high water level is set by adjusting the spring force. The pilot control measures the reservoir head through a customer supplied sensing line* connected directly to the reservoir.
This valve can also be furnished with auxiliary controls to meet the need for multiple functions, such as: pressure sustaining, pressure reduction,
Schematic Diagram
Item Description
1 Hytrol (Main Valve) 2 CDS6A Altitude Control 3 X101 Valve Position Indicator 4 Bell Reducer 5 CV Flow Control (Closing)
rate of flow control, solenoid override, etc.
If the check feature option is added and a pressure reversal occurs, the downstream pressure is admitted into the main valve cover chamber and the valve closes to prevent return flow.
Optional Features
Item Description
A X46A Flow Clean Strainer B CK2 (Isolation Valve) D Check Valve with Isolation Valve F Independent Operating Pressure H Dry Drain P X141 Pressure Gauge
R Reservoir Gauge with Tester S CV Flow Control (Opening) Y X43 "Y" Strainer
Typical Applications
Used on reservoirs where the water is withdrawn through a separate line or through a bypass equipped with a check valve. The valve opens to refill the reser­voir when the water lowers below the shut-off level. For more information see data sheet E-CDS6A.
*Note: The reservoir pressure sensing line should be
3
4
" minimum I.D. installed with a 2° slope from
the valve to the reservoir to avoid air pockets.
Note: We recommend protecting tubing and valve
from freezing temperatures.
Product Dimensions Data:
For the 210-01 Main Valve (100-01) dimensions, see pages 17. For the 610-01 Main Valve (100-20) dimensions, see pages 29.
66
Note: When "D" check feature is ordered, the "H" feature is required.
Page 67
Schematic Diagram
Item Description
1 Hytrol (Main Valve) 2 CDS6A Altitude Control 3 X101 Valve Position Indicator 4 Bell Reducer 5 CRL Pressure Relief Valve
6. 100-01 Hytrol (Reverse Flow) 7 X42N-3 Strainer
210-09
(Full Internal Port)
MODEL
610-09
(Reduced Internal Port)
Combination Altitude and
Back Pressure Valve
Accurate and Repeatable Level Control
Prevents Low Supply Pressure When Filling
Drip Tight Positive Shut-Off
Reliable Hydraulic Operation
Easily Adjustable Controls
The Cla-Val Model 210-09/610-09 Combination Altitude and Back Pressure Valve controls the high water level in reservoirs without the need for floats or other devices. The valve modulates to maintain upstream pressure within close limits to prevent over drawing system supply while filling reservoir. When the shut-off point of the hydraulic pilot control is reached, the valve closes smoothly without surges. This valve is designed for one-way flow only.
The 210-09/610-09 Valve is hydraulically-operated and pilot-controlled for optimum automatic level and pressure control. The level pilot control operates on a differential in forces between spring load and reservoir head level. When force of spring is overcome by force of reservoir head, the pilot shifts and closes main valve. Desired high water level is set by adjusting spring force. The level pilot control measures the reservoir head through a customer supplied separate sensing line* connected directly to reservoir. The pressure sustaining pilot control senses upstream system pressure and modulates the main valve more open on a rise in pressure to maintain a minimum inlet pressure when filling reser­voir.
The valve can also be furnished with auxiliary controls to meet the need for additional functions, such as: rate of flow control, pressure reduction, solenoid override, etc. If the check feature option is added and a pres­sure reversal occurs, reservoir pressure is admitted into main valve cover chamber and valve closes to prevent return flow.
Optional Features
Item Description
B CK2 (Isolation Valve) D Check Valve with Isolation Valve F Remote Pilot Sensing R Reservoir Gauge with Tester S CV Flow Control (Opening)
Product Dimensions Data:
For the 210-09 Main Valve (100-01) dimensions, see pages 17. For the 610-09 Main Valve (100-20) dimensions, see pages 29.
Typical Applications
Used on reservoirs where water is withdrawn through a separate line or through a bypass equipped with a check valve. Valve closes at the desired high water level and reopens for filling when reservoir head lowers below the shut off level. Valve controls minimum supply pressure to keep from overdrawing supply while filling reservoir. Water in excess of system pressure flows to reservoir at controlled rate. For more information see data sheet E-CDS6A.
3
4
*Note: The reservoir pressure sensing line should be a 2° slope from the valve to the reservoir to avoid air pockets.
Note: We recommend protecting tubing and valve from freezing temperatures.
" minimum I.D. installed with
67
Page 68
To Elevated Storage
Shutoff Cock
Isolation Valve
Supply Source
Distribution
CLA-VAL 210-16/610-16 Alititude Valve
Sensing Line (Customer Supplied)
210-16
R(Full Internal Port)
MODEL
610-16
(Reduced Internal Port)
Altitude Valve For Two-Way Flow
Accurate and Repeatable Level Control
Drip-Tight Positive Shut-Off
Reliable Hydraulic Operation
Easily Adjustable Control
Completely Automatic Operation
The Cla-Val Model 210-16/610-16 Altitude Valve controls the high water level in reservoirs without the need for floats or other devices. It is a non­throttling valve that remains fully open until the shut off point is reached. This valve closes at a high water level, and opens for return flow when the pressure at the valve inlet is less than the reservoir pressure.
This valve is hydraulically operated and pilot controlled. The pilot control operates on the differential in forces between a spring load and the water level in the reservoir. When the force of the spring is overcome by the force of the reservoir head, the pilot closes the main valve. The desired high water level is set by adjusting the spring force. The pilot control measures the reservoir head through a customer supplied sensing line*
Schematic Diagram
Item Description
1 Hytrol (Main Valve) 2 CDS6A Altitude Control 3 X101 Valve Position Indicator 4 Bell Reducer 5 Check Valve 6 CV Flow Control (Closing) 7 CK2 Isolation Valve
connected directly to the reservoir.
This valve can also be furnished with auxiliary controls to meet the need for multiple functions, such as: pressure sustaining, pressure reduction, rate of flow control, solenoid override, etc.
Optional Features
Item Description
A X46A Flow Clean Strainer B CK2 Isolation Valve H Dry Drain P X141 Pressure Gauge
R Reservoir Gauge with Tester S CV Flow Control (Opening) Y X43 "Y" Strainer
Typical Applications
Used on reservoirs where water is withdrawn through the Altitude Valve. The valve closes at the high water level and opens for return flow when the pressure at the valve inlet lowers below the reservoir pressure.
For more information see data sheet E-CDS6A
3
*Note: The reservoir pressure sensing line should be
We recommend protecting tubing and valve from freezing temperatures.
Product Dimensions Data:
For the 210-16 Main Valve (100-01) dimensions, see pages 17. For the 610-16 Main Valve (100-20) dimensions, see pages 29.
68
minimum I.D. installed with a 2° slope from valve to reservoir to avoid air pockets.
4"
Page 69
Schematic Diagram
Item Description
1 Hytrol (Main Valve) 2 CDS6A Altitude Control 3 X101 Valve Position Indicator 4 Bell Reducer 5 102C-3H Three-way Valve 6 CS3 Solenoid Control 7 CV Flow Control (Closing)
8 Union
Optional Features
210-17
(Full Internal Port)
MODEL
610-17
(Reduced Internal Port)
Altitude and Solenoid Shut-Off Valve
Accurate and Repeatable Level Control
Easy Interface With Remote Control Systems
Drip Tight Positive Shut Off
Reliable Hydraulic Operation
Easily Adjustable Control
The Cla-Val Model 210-17/610-17 Altitude Valve controls the high water level in reservoirs with out the need for floats or other devices. It is a non-throttling valve that remains fully open until the solenoid is activat­ed or the shut-off point of the hydraulic pilot control is reached. The valve closes at high water level and opens for return flow when the pressure at the valve inlet is less than reservoir pressure.
This valve is hydraulically-operated and pilot-controlled. The level pilot control operates on the differential in forces between a spring load and reservoir head level. When force of the spring is overcome by the force of reservoir head, the pilot shifts and closes main valve. Desired high water level is set by adjusting the spring force. The pilot control meas­ures the reservoir head through a customer supplied separate sensing line* connected directly to the reservoir. A three-way solenoid control and a high-capacity three-way pilot control valve provide override shut­off of valve from a remote location, such as a SCADA control system. It is furnished either normally open (de-energize solenoid to open) or nor­mally closed (energize solenoid to open).
The valve can also be furnished with auxiliary controls to meet the need for additional functions, such as: pressure sustaining, rate of flow con­trol, pressure reduction, etc.
Item Description
A X46A Flow Clean Strainer B CK2 Isolation Valve D Check Valve with Isolation Valve
F Independent Operation Pressure H Dry Drain R Reservoir Gauge with Tester P X141 Pressure Gauge S CV Flow Control (Opening) Y X43 "Y" Strainer
Product Dimensions Data:
For the 210-17 Main Valve (100-01) dimensions, see pages 17. For the 610-17 Main Valve (100-20) dimensions, see pages 29.
Typical Applications
Used on reservoirs where water is supplied and withdrawn through the Altitude Valve. Valve closes at the desired high water level controlled remotely via SCADA system signal to solenoid or automatically with preset level control (usually set higher). Also, valve automatically opens for return flow when the pressure at the valve inlet lowers below the reservoir head pressure. For more information see data sheet E-CDS6A.
3
*Note: The reservoir pressure sensing line should be 2° slope from valve to reservoir to avoid air pockets.
Note: We recommend protecting tubing and valve from freezing temperatures.
4” minimum I.D. installed with a
69
Page 70
131 Series
(Full Internal Port)
MODEL
631 Series
(Reduced Internal Port)
Electronic Control Valves
Model 131-01/631-01
Simple Proven Design
Quality Solenoid Pilot Controls
Ideal For SCADA Systems
Multi-Function Capability; Hydraulic Backup
Security System to Prevents Unauthorized Changes
Easy to Maintain
The Cla-Val Series 131/631 Electronic Control Valves are designed specifically for applications where remote control of the valve is preferred. It is a hydraulically operated, pilot controlled, diaphragm valve. The sole­noid pilot controls are actuated by electrical signals from the optional 131VC-1 Electronic Valve Controller. The solenoid pilots either add or relieve line pressure from the cover chamber of the valve, causing it to open or close as directed by the electronic controller.
Series 131/631 Electronic Control valves can be configured to perform a wide range of functions, such as; pressure reducing, pressure sustaining, flow control, or level control. The electric controls can also be combined with hydraulic controls to create dual function, or fail-safe capability.
Schematic Diagram
Item Description
1 Hytrol (Main Valve) 2 CS2 Solenoid Control 3 CK2 (Solenoid By-Pass)
Optional Features
The basic 131-01/631-01 Electronic Control Valve (Schematic shown below) includes the main valve and solenoid pilot controls. Optional fea­tures include the 131VC-1 Electronic Valve Controller and the X117D Valve Position Transmitter. If the check feature option is added, and a pressure reversal occurs, the downstream pressure is admitted into the cover, closing the valve.
Item Description
A X46A Flow Clean Strainer
B CK2 (Isolation Valve) C CV Flow Control (Closing) D Check Valves With Isolation Valve
E X117D/X117E Position Transmitter
F Independent Operating Pressure H Atmospheric Drain N Electronic Controller
P X141 Pressure Gauge
S CV Flow Control (Opening)
Y X43 "Y" Strainer
Product Dimensions Data:
For the 131 Series Main Valve dimensions, see pages 17. For the 631 Series Main Valve dimensions, see pages 29.
Typical Applications
This brochure contains typical application that are modifications to the basic 131-01/631-01 Electronic Control Valve shown here. It is typical installed in a pipeline with a 131VC Series Controller that receives a process variable signal that is compared to set­point and adjusts the main valve's capacity until the signals match. There are many different variations not shown in this brochure. Contact us with your specific application and we will provide a field proven solution.
70
Page 71
Schematic Diagram
Item Description
1 Hytrol (Main Valve) 2 CS2 Solenoid Control 3 CK2 Cock (Solenoid By-Pass) 4 CDS6A Altitude Control 5 100-02 Powertrol (Reverse Flow) 6 100-01 Hytrol (Reverse Flow)
Optional Features
Item Description
A X46A Flow Clean Strainer B CK2 Cock (Isolation Valve) C CV Flow Control (Closing) D Check Valves with Isolation Valve E X117D/X117E Position Transmitter
F Independent Operating Pressure H Atmospheric Drain N Electronic Controller P X141 Pressure Gauge S CV Flow Control (Opening) Y X43 "Y" Strainer
131-06/631-06
Combination Electronic Control And High Level Shut-Off Valve
This valve is used in reservoir applica­tions where the filling or draining rate is controlled and modulated by the elec­tronic controller. Flow pressure and valve position can also be controlled. Should the liquid in the reservoir reach a high level, the hydraulic altitude control auto­matically overrides the electronic control and closes the valve. The altitude control can be adjusted to close the valve over a wide range of settings. The optional check feature will close the valve if there is a pressure reversal in the line.
131-09/631-09
Modulating Float Valve With Solenoid Lockout of Float Control and Electronic Positioning
The electronic controller modulates the flow through this valve to control liquid level in a tank. If power failure should occur, the third solenoid shifts, and the float control will allow the valve to modu­late using hydraulic line pressure. The 131VC Electronic Valve Controller and X117D Valve Position Transmitter are used in combination with an electronic level sensing device to provide modulat­ing flow control of the valve.
3
CS3
2
4A
2
D1
Y
B
CS3
7A
3
6A
S
E
4B
B
Schematic Diagram
Item Description
1 Hytrol (Main Valve) 2 X74B-3 Stem Valve 3 CFM-7 Float Pilot 4 100-01 Hytrol (Reverse Flow) 5 CS3 Solenoid Control 6 CS2 Solenoid Control 7 CK2 Solenoid By-Pass
Optional Features
Item Description
A X46A Flow Clean Strainer B CK2 Cock (Isolation Valve) E X117D/X117E Position Transmitter F Independent Operating Pressure
N Electronic Controller
P X141 Pressure Gauge Y X43 "Y" Strainer
Schematic Diagram
CS2
N
5
6B
Item Description
1
Hytrol (Main Valve) 2 X58C Restriction Assembly 3 CS3 Solenoid Control 4 100-01 Hytrol (Reverse Flow) 5 CRD Pressure Reducing Control 6 CK2 Solenoid Control 7 CK2 Solenoid Bypass
Optional Features
7B
D2
D3
OUTLET INLET
Item Description
B
A X46A Flow Clean Strainer B CK2 Isolation Valve C CV Flow Control ( Closing) D Check Valves Isolation Valve E X117D/X117E Position Transmitter N Electronic Controller (Single) P X141 Pressure Gauge S CV Flow Control (Opening) Y X43 "Y" Strainer
131-18/631-18
Electronic Control Valve Equipped with Hydraulic Pressure Reducing Solenoid Selected
Flow, pressure, level or valve position is normally controlled by the electronic con­troller that operates two solenoids to modulate the valve to maintain the process variable. Should a power failure occur, a parallel hydraulically operated pressure reducing pilot system takes control of the valve maintaining a preset outlet pressure. When power is restored, the valve automatically reverts back to the electronic mode. The optional check feature automatically will close the valve if a pressure reversal occurs in the pipeline.
71
Page 72
131-22/631-22
Electronic Control Valve (Power Fail Closed)
Flow, pressure, level or valve position is normally controlled by the electron­ic controller that operates two sole­noids to modulate the valve to main­tain the process variable. Should a power failure occur, the valve can be configured to go open or closed. The optional check feature automatically will close the valve if a pressure reversal occurs in the pipeline.
Schematic Diagram
Item Description
1 100-01 Hytrol (Main Valve) 2 CS2 Solenoid Control 3 CK2 (Solenoid By-Pass)
Optional Features
Item Description
A X46A Flow Clean Strainer B CK2 Isolation Valve C CV Flow Control (Closing) D Check Valves with Isolation valve E X117D/X117E Position Transmitter F Independent Operating Pressure H Atmospheric Drain N Electronic Controller P X141 Pressure Gauge S CV Flow Control (Opening) Y X43 "Y" Strainer
N
N
131-EJ/631-EJ
Electronic Interface Control with Pressure Sustaining Feature, Hydraulically Operated
Flow, pressure, level or valve position is normally controlled by the electronic controller that operates two solenoids to modulate the valve to maintain the process variable. Should a power failure occur, a parallel hydraulically operated pressure sustaining pilot system takes control of the valve limiting the minimum inlet pressure. When power is restored, the valve automatically reverts back to the electronic mode. The optional check­feature automatically will close the valve if a pressure reversal occurs in the pipeline
Schematic Diagram
Item Description
1
Hytrol (Main Valve) 2 CS2 Solenoid Control 3 CK2 Solenoid By-Pass 4 CRL5 Pressure Relief Control 5 X58C Restriction Assembly
Optional Features
Item Description
A X46A Flow Clean Strainer B CK2 Isolation Valve C CV Flow Control ( Closing) D Check Valves with Isolation Valve E X117D/X117E Position Transmitter
F Independent Operating Pressure N Electronic Controller (Single) P X141 Pressure Gauge S CV Flow Control (Opening) Y X43 "Y" Strainer
Schematic Diagram
Item Description
1
Hytrol (Main Valve) 2 CS2 Solenoid Control 3 CK2 Solenoid By-Pass 4 CRA Pressure Reducing Control 5 X58C Restriction Assembly
Optional Features
Item Description
A X46A Flow Clean Strainer B CK2 Isolation Valve C CV Flow Control ( Closing) D Check Valves with Isolation Valve E X117D/X117E Position Transmitter
F Independent Operating Pressure
H Atmospheric Drain N Electronic Controller (Single) P X141 Pressure Gauge S CV Flow Control (Opening) Y X43 "Y" Strainer
131-CW/631-CW
Electronic Interface Control with Pressure Reducing Feature, Hydraulically Operated
Flow, pressure, level or valve position is normally controlled by the electronic controller that operates two solenoids to modulate the valve to maintain the process variable. Should a power failure occur, a parallel hydraulically operated pressure reducing pilot system takes control of the valve limiting the maximum outlet pressure. When power is restored, the valve automatically reverts back to the electronic mode. The optional check feature automatically will close the valve if a pressure reversal occurs in the pipeline
72
Page 73
Optional Remote Control
Modem
Modem
Computer
131-01
Control Valve
Signal Transmitter
4-20 mA
SERIES
131VC
Electronic Control Systems
Electronic Control of Hydraulic
Cla-Val Valves
Programmable Monitoring and
Control of Flow, Pressure, Delta P, Level or Valve Position
Accurate Control of Valve Speed and
Response
Remote Set-Point Control
Security System - Prevents
Unauthorized Changes
Control Backup Systems in the
Event of an Emergency
Electronic Control of Hydraulic Valves
The 131VC-1 Electronic Control System is designed to work in conjunction with Cla-Val 131 Series hydraulic control valves— a combination that takes advantage of the simplicity of hydraulic valve operation and the control possibilities available with electronics.
The 131VC-1 Electronic Control System receives transmitted signals and activates dual solenoid pilots on the hydraulic con­trol valve. These pilots direct hydraulic pressure within the sys­tem to position and regulate the valve. By continuously com­paring system conditions to the programmed set-point, the sys­tem is automatically maintained at the desired value.
Additional important control features, unique to this type of valve control, are offered as standard. They are designed for user friendly operation and system safety and are addressed in this brochure.
The Cla-Val 131VC-1 Electronic Control System is designed to achieve unprecedented valve control accuracy and stability. Ideal for remote valve control, the 131VC-1 Electronic Control System provides the interface between SCADA system computers and hydraulic control valves sites.
Key Advantages
• Proven reliable hydraulic control valve
• Low electric power requirement
• Solid state electronic components
• No motors, bearings, bushings or packings to wear out or leak
We Not Only Sell Valves—
We Provide Solutions
73
Page 74
How it Works
131-01 Valve
Transmitter
Dead
Band
Set-Point Command
131-01 Valve
Transmitter
Transmitter Feedback Signal
Deviation
Transmitter
131-01 Valve
Devitation
Transmitte Feedback Signal
1. Set-Point Command
Set-point command is received from a remote location or entered via the key pad into the Electronic Valve Controller.
2. Feedback and Comparison
The Electronic Valve Controller compares the feedback signal from the transmitter to the set-point. If the deviation exceeds the deadband, the valve control system is activated.
3. Valve Actuation
The Electronic Valve Controller actu­ates the solenoid controls, causing the valve to modulate as needed to regain the set-point condition.
Keypad & Display
Display
The 131VC-1 has been engineered to be the industryʼs most user friendly controller. With three digital displays areas (two offering up to 9 characters of true alphanumeric), the 131VC-1 effectively eliminates cryptic messages, sub-routines and loops that could confuse even the most experienced operator. The bright, crisp display is vacuum fluorescent, and offers much better readability than any other display technology. Additional operator-friendly features include: custom programmable alarm messages, illuminated keys, and an easy-to-use menu system.
Status Indicators - Four status indicators show the controllerʼs operating status at all times:
Manual Key Light: For manual control.
Set-point Key Light: For indication of remote control.
Output Indicator: “OUT” and indicator lights illuminate
when either output 1 or 2 are on.
Alarm Indicator: “ALM” and indicator lights illuminate when either output 1 or 2 are on.
Keys Pads: All menu entry, configuration, tuning and set-point controls is entered through rugged backlit rubber keys. A simple menu system prompts the operator, step by step, through all procedures. Security system prevents unauthorized changes to all values.
74
Page 75
T
Schematic Diagram
Item Description
1 Hytrol (Main Valve) 2 CS2S Solenoid Control 3 CK2 Solenoid By-Pass 4 DPT Differential Pressure Transmitter 5 131VC-3T Electronic Controller 6 X117D Position Transmitter 7 CK2 Isolation Valve
133-01
MODEL
(Full Internal Port)
633-01
(Reduced Internal Port)
Metering Valve
Automatically Measures and Controls Flow Rate
Without a Separate Metering Device
Completely Self Contained
Reliable Analog Communications
Retransmission Capabilities
Ideal for Retrofitting Existing Valves
Security System to
Optional Totalizing Capabilities
The Cla-Val Model 133-01/633-01 Metering Valve is a completely self contained valve and control system that accurately meters and/or controls flow rate when used on valves with pressure differ­entials of less than 100 psid.
Using a 131VC-3T Cla-Val Microprocessor, data from valve mounted differ­ential pressure and position transmitters are assimilated into a proprietary algorithm program that is based on valve size and configuration to arrive at a flow measurement. This information is used for retransmission and/or compared with a local or remote set-point for valve flow control. The 133-01 Control System can also be installed on new or existing hydraulic pilot control valves such as: pressure reducing, pressure sustaining, flow limiting and level control to transmit flow rate without disturbing the valve's primary hydraulic function(s). Specify Kit 133-01 for these applications. Consult factory.
Prevents Unauthorized Changes
Optional Features
Item Description
A X46A Flow Clean Strainer B CK2 Isolation Valve C CV Flow Control (Closing) D Check Feature F Independent Operation Pressure H Atmospheric Drain P S CV Flow Control (Opening) Y X43 "Y" Strainer
X141 Pressure Gauge
Typical Applications
The Model 133-01/633-01 Metering and Flow Rate Controller is typically installed in a fluid delivery system where the flow rate is measured and changed from a remote location such as a SCADA system.
Main Transmission
Line
Product Dimensions Data:
For the 133-01 Main Valve (100-01) dimensions, see pages 17. For the 633-01 Main Valve (100-20) dimensions, see pages 29.
For all applications, specify voltage, minimum/maximum pressures and flow rates, valve size, pressure class and optional features. Consult your local representative or the Factory for engineering assistance and valve selection.
Please refer to the 131VC “Electronic Control Systems” brochure for specific information regarding valve theory of operation, standard and optional features, control parameters and electrical component specifications.
131VC-3T Electronic
133-01/633-01
Metering & Flow Rate Controller
Valve Controller
131VC-3T
To Optional Remote
Computer Control (Local)
Optional Remote Control
Optional Remote Control
Modem
Computer
Modem
Computer
75
Page 76
Improved Filter Backwashing
Advanced Cla-Val Electronic Backwash Valves with metering capability
All water treatment plant filters must be regularly backwashed to clear away impurities left by raw water and to ensure optimum filtration results. Conventional systems, utilizing a combination of devices, often succumb to the ravages of cavitation caused by high system pressure and pose space challenges because of the long runs of piping required between components to guarantee proper function.
Cla-Val electronic metering valves equipped with KO anti-cavitation trim can handle the pressure and can perform the backwashing function without external metering or control components, greatly reducing space requirements and installation/maintenance costs.
This multi-functional control valve cost effectively meets the following operational requirements:
• Low-rate wash • High-rate wash
• Remote valve closure • Flow metering and totalizing
• Hydraulic pressure override • Can interface with SCADA systems
In addition to being available on new valves, any existing, installed Cla-Val Pressure Reducing Valve can be field retrofit­ted with the Model 133 electronic control and metering kit to perform backwashing at peak efficiency.
76
Conventional
Backwash System
Advanced Electronic
Backwash System
visit www.cla-val.com
and click the “Backwash” Quick Link
Page 77
138-01
(Sizes 3"- 12")
(Full Internal Port)
MODEL
638-01
(Sizes 4"- 16")
(Reduced Internal Port)
Electronic Actuated Positioning Control Valve
Product Features and Benefits
Precise Valve Position Control
Completely Self-contained
High Energy Efficiency with Low Operation Friction
Direct Control of Valve Opening and Closing
Combines with Pressure, Flow or Level Control
Ideal for SCADA Control
• Easy adjustment and maintenance
• Fully Supported Frictionless Diaphragm for trouble­free service and low maintenance
Product Enhancements
Get more from your valve by adding any of the following optional features.
• KO Anti-Cavitation Trim
• Epoxy Coating
• X141 Pressure Gauge
• Stainless Steel Tubing and Fittings
• X43H-Style Strainer
• Stem Upgrade to Delrin® or Dura-Kleen®
Schematic Diagram
Item Description
1 Hytrol (Main Valve) 2 X58A Restriction Fitting 3 CS3 Solenoid Control 4 100-01 Auxiliary Hytrol (Reverse Flow) 5 CPC Electronic Actuator Positioning Control
Optional Features
Item Description
A X46A Flow Clean Strainer B CK2 (Isolation Valve)
C CNA Needle Valve (Closing)
F Independent Operating Pressure
H Solenoid Drain to Atmosphere
P X141 Pressure Gauge S CNB Needle Valve (Opening) Y X43 "Y" Strainer
How It Works
The Cla-Val Model 138-01/638-01 Electronic Actuated Positioning Control Valve regulates flow or pressure or other system parameter by changing valve position from full open to shut-off. Exact valve position for large-scale waterworks or industrial applications is achieved with CPC pilot control that consists of electronic actuator and hydraulic pilot sub-assembly. The CPC controls valve position by limiting valve opening using hydraulically-assisted technology. The pilot sub-assembly has two calibrated orifices that are posi­tioned proportional to valve position to vary main valve control chamber operating pressure. The CPC actuator creates slight changes in orifice position and in turn operating pressure hydrauli­cally changes valve position. The pilot sub-assembly requires very little torque and is virtually frictionless for long service life. The actu­ator features high repeatable-accuracy brush-less motor technolo­gy and low energy consumption. Precision, no-contact hall-effect internal position sensor assures accuracy and durability. The CPC has factory pre-configured parameters of full valve stroke, preset rotation speed, and default setting on loss of set point. Actuator parameters can be changed using free downloadable software and special USB cable. Valve fully-closed position is assured by signal­ing solenoid to lock control pressure in main valve operating cham­ber when valve is very close to seat (adjustable). Operating on 24 VDC and with customer supplied battery backup, the 138-01/638­01 valve can eliminate downtime due to power failures.
77
Page 78
Model 138-01 Electronic Position Process Control Valve
RTU
CPC
MODEL
Electronic Actuated Positioning Pilot Control
Precise Valve Position Control
Completely Self-contained
High Energy Efficiency with Low Operation Friction
Direct Control of Valve Opening and Closing
Combines with Pressure, Flow or Level Control
Ideal for SCADA Control
Optional 133VF Valve-Mounted Flow Monitoring
The Cla-Val CPC Electronic Actuated Positioning Control regulates flow through Cla-Val Main Valves by changing valve position from full open to shut-off. The CPC consists of electronic actuator and hydraulic pilot sub-assembly. The CPC controls valve position by hydraulically limiting valve opening with hydraulically-assisted pilot modulating main valve. The pilot sub-assembly has two calibrated ori­fices that are positioned proportional to valve position to vary Cla-Val basic valve control chamber operating pressure. The CPC actuator creates slight changes in orifice position and in turn operating pressure hydraulically changes valve position. The pilot sub-assembly requires very little torque and is virtually frictionless for long service life. The actuator features high repeatable-accuracy brush-less motor technol­ogy and low energy consumption. Precision, no-contact hall-effect internal position sensor assures durability. The CPC is factory pre­configured to full stroke, preset rotation speed, and default setting on loss of set point. Actuator parameters can be changed using free downloadable software and special USB cable. Valve fully-closed position is assured by signaling solenoid to lock control pressure in main valve operating chamber when valve is very close to seat (adjustable). Operating on 24 VDC and with customer supplied battery backup, the CPC can eliminate downtime due to power failures.
Typical Applications
78
Note: When retrofitting an existing valve, high capacity cover bearing must be installed. This requires removing the valve cover. Consult factory for details.
The CPC Electronic Actuated Positioning Control is used with 138 Series Electronic Actuated Control Valves in high rise building chill water circulating system applications. Building SCADA control systems often use multiple circulating system parameters to control valve position for optimizing water circu­lating system. Also, 138 Series valves are used in large water transmission systems where several system parameters must be controlled by one valve. SCADA system monitors various water distribution system parameters, such as downstream pressure, upstream pressure, tank level, time of day, flow rates in several zones, etc., and then remotely changes 138 Series valve position to meet several system requirements as all parameters continue changing.
Cla-Val 138 Series valves can have optional 133VF Flow Metering System installed for flow rate moni- toring. Consult factory for details.
Page 79
MODEL
Q = C
v DP / SG
133VF
Valve Flow Measurement
133VF Retrofittable Metering
Kit Option
131VF Flow Module
X117 Series
X117E
Position
Transmitter
X117D
DP Differential
Pressure Transmitter
The 131VF flow module accepts 4-20 mA analog signals of valve differential pressure and valve position to determine the flow rate.
The partially-open valve Cv is derived from valve position then used to calculate flow rate with formula shown below:
Where:
Q = flow (gpm) DP = differential pressure (psi) SG = specific gravity of fluid (water = 1.0)
Automatic Control Valve
with Metering Kit
Installed
System accurately measures flow rate
No external meter is required
For new installations and retrofitting
existing valves
Completely self-contained, requiring
12 to 24 VDC power
Simple integration
The Cla-Val 133VF Flow Metering System is an effective means of obtaining real-time flow data from a Cla-Val control valve regardless of valve function and without an external flow device. Now all Cla-Val control valves in a water distribution system can be economically integrated into SCADA control or pressure and flow management strategies.
The 133VF System is completely self-contained and when factory installed on new Cla-Val automatic control valves or field installed on existing valves, accurately measures flow rate and transmits it as a 4 - 20 mA analog signal. It can be used on virtually all valve sizes from two through twenty-four inch and is typically used at pressure reduc­ing, back pressure, flow limiting, and level control valve stations.
The system features the “heart” of the 133-01 Flow Metering Control Valve technology and adapts it for sin­gle-valve flow monitoring-only applications. The 133VF System major components are an X117D valve position transmitter, a differential or inlet and outlet pressure transmitters and a 131VF flow calculating module. All components are 24 VDC powered and weather protect­ed to IP-68 submersible rating. The 131VF module, with standard DIN rail mounting, contains powerful mini-com­puter technology for calculating valve flow based on inputs from the sensors and using the appropriate flow curve for a particular Cla-Val valve. For increased accu­racy the 131VF module uses third-party certified flow curves tested for this particular metering application. Valve differential pressure measurement can be located either at the valve inlet and outlet bosses or on pipe adjacent to the valve providing installation versatility in all applications and operating conditions.
For applications requiring flow measurement and remote set point control, see 133-01 Metering Valve catalog data sheet.
79
Page 80
340-02
(Full Internal Port)
MODEL
3640-02
(Reduced Internal Port)
Electronic Actuated Rate of Flow Control Valve
Schematic Diagram
Item Description
1 Hytrol (Main Valve) 2 X58C Restriction Fitting 3 CDHS-33 Electronic Differential Control 4 X52E Orifice Plate Assembly
Optional Features
Item Description
A X46A Flow Clean Strainer
B CK2 (Isolation Valve) C CV Flow Control (Closing) D Check Valves with Isolation Valve
P X141 Pressure Gauge
S CV Flow Control (Opening)
V X101 Valve Position Indicator Y X43 "Y" Strainer
Simplified Remote Valve Set-Point Control
12 to 24 VDC Input Power
Isolated Input
Reverse Polarity Protection
Reliable Hydraulic Operation
IP-68 (Submersible)
The Cla-Val Model 340-02/3640-02 Electronic Actuated Rate of Flow Control Valve combines the precise control of field proven Cla-Val hydraulic pilots and simple remote valve control. The Model 340-02/3640-02 valve controls flow by limiting flow to a preselected maximum rate (within a four to one ratio), regardless of changing line pressure. It is a hydraulically operated, pilot controlled, diaphragm actuated control valve. The valve uses a CDHS-33 actuated pilot con­trol, consisting of a hydraulic pilot and integral controller that accepts a remote set­point command input and makes set-point adjustments to the pilot. The recommended control method is simple remote set point change from an RTU (Remote Telemetry Unit) to the CDHS-33 where the 4-20 mA command signal is ranged to specific flow range of orifice plate and hydraulic pilot control components. Very accurate control can be achieved when span does not exceed 4:1 turndown. Since the CDHS-33 is pre-ranged to full spring range, some on-site calibration may be necessary when this control method is used. Free downloadable software is available from Cla-Val website for this purpose. The CDHS-33 can also accommodate control systems where the RTU com­pares flow rate transmitter signal to the remote set point command signal. The RTU adjusts the CDHS-33 with 4-20 mA command signal containing an ade­quate deadband to prevent actuator dithering after the two signals agree. Internal continuous electronic monitoring of actuator position results in virtually instantaneous position change with no backlash or dithering when control sig­nal is changed. In the event of a power or control input failure, the CDHS-33 pilot remains in hydraulic control virtually assuring system stability under chang­ing conditions. If check feature (“D”) is added, and pressure reversal occurs, the valve closes to prevent return flow.
Typical Applications
The valve is designed to be used with supervisor control systems (SCADA), having an isolated remote analog set-point output and a process variable flow transmitter input. It is also an effective solution for lowering costs asso­ciated with “confined space” requirements by eliminating the need for entry into valve structure for set-point adjustments and system information. Additional pilot controls, hydraulic and/or electronic, can be easily added to perform multiple control functions to fit exact system requirements.
Product Dimensions Data:
For the 340-02 Main Valve (100-01) dimensions, see pages 17. For the 3640-02 Main Valve (100-20) dimensions, see pages 29.
80
Page 81
MODELS
CDHS-33
Electronic Actuated
Rate of Flow Pilot Control
Simplified Remote Valve Set-Point Control
12-24VDC Input Power
Isolated Input
Reverse Polarity Protection
Reliable Hydraulic Operation
IP-68 Submersible
The Cla-Val Model CDHS-33 Electronic Actuated Differential Pressure Pilot Control provides remote set-point adjustment and accurate dif­ferential pressure control for rate of flow control on Cla-Val 340 Series Control Valves. Remote set-point command signals can be from any SCADA-type control system using analog 4-20 mA signal or by con­tact closure for cc/ccw rotation. A precision orifice plate installed with valve creates differential pressure used for rate of flow control by the CDHS-33. Operating on 12 to 24 VDC and consuming very little power, it is an ideal control system for remote valve sites that may even be solar powered. Existing manually-set Cla-Val 40 Series Rate-of-Flow control valves can be retrofitted with CDHS-33 to add remote set-point control. Verification of differential pressure and cor­responding flow rate may be sent to SCADA system from customer supplied differential pressure sensor attached to orifice plate.
The CDHS-33 consists of a hydraulic pilot and integral controller that accepts a 4-20 mA remote set-point and positions the pilot to maintain a maximum pressure differential at orifice plate and corresponding flow rate within preset limits. Pressure differential settings are linear between these settings. Special USB connector cable and free down­loadable software can be used to change built-in electronic range lim­its for differential pressure and corresponding flow rate. Continuous internal monitoring of actuator position results in smooth transitions between pilot set-points with no backlash or dithering. When power or control input fail, the CDHS-33 pilot remains in automatic hydraulic control assuring system stability under all conditions.
Typical Applications
The CDHS-33 Is installed on Cla-Val 340 Series valves that maintain flow rate and require this flow to be changed from a remote location. It is also an effective solution for lowering costs associated with "confined space" requirements by eliminating the need for entry in valve structure for set-point adjustment. Additional pilot controls, hydraulic and/or electronic, are also available to perform multiple functions to fit exact system requirements.
81
Page 82
350-02
(Full Internal Port)
MODEL
3650-02
(Reduced Internal Port)
Electronic Actuated Pressure Sustaining Control Valve
Simplified Remote Valve Set-Point Control
12 to 24 VDC Input Power
Isolated Input
Reverse Polarity Protection
Reliable Hydraulic Operation
IP-68 (Submersible)
The Cla-Val Model 350-02/3650-02 Electronic Actuated Pressure Sustaining Control Valve combines precise control of field proven Cla-Val hydraulic pilots and simple, remote valve control. The Model 350­02/3650-02 is a hydraulically operated, pilot controlled, modulating valve designed to maintain constant upstream pressure within close limits. This valve can be used for pressure sustaining, back pressure or unloading functions in a by-pass system. The valve uses a CRL-33 pilot control, consisting of a hydraulic pilot and integral controller, that accepts a remote set-point command input and makes set-point adjustments to the pilot.
Schematic Diagram
Item Description
1 Hytrol (Main Valve) 2 X42N-2 Strainer & Needle Valve 3 CRL-33 Electronic Pressure Sustaining Control
Optional Features
Item Description
B CK2 (Isolation Valve) D Check Valves with Isolation Valve F Remote Pilot Sensing H Drain to Atmosphere
P X141 Pressure Gauge S CV Flow Control (Opening)
V X101 Valve Position Indicator
The recommended control method is simple remote set point change from an RTU (Remote Telemetry Unit) to the CRL-33 where the 4-20 mA com­mand signal is ranged to specific pressure range. Very accurate control can be achieved when span does not exceed 100 psi. Since the CRL-33 is pre-ranged to the full spring range, some on-site calibration may be nec­essary when this control method is used. Free downloadable software is available from the Cla-Val website for this purpose. The CRL-33 can also accommodate control systems where the RTU compares pressure trans­mitter signal to the remote set point command signal. The RTU adjusts the CRL-33 with 4-20 mA command signal containing an adequate dead­band to prevent actuator dithering after the two signals agree.
Internal continuous electronic monitoring of actuator position results in vir­tually instantaneous position change with no backlash or dithering when control signal is changed. In the event of a power or control input failure, the CRL-33 pilot remains in hydraulic control virtually assuring system sta­bility under changing conditions. If check feature ("D") is added, and pres­sure reversal occurs, the valve closes to prevent return flow.
Product Dimensions Data:
For the 350-02 Main Valve (100-01) dimensions, see pages 17. For the 3560-02 Main Valve (100-20) dimensions, see pages 29.
82
Typical Applications
The valve is designed to be used with supervisory control systems (SCADA), having remote analog set-point output and process variable upstream pressure input. It is also an effective solution for lowering costs associated with “confined space” requirements by eliminating need for entry into valve structure for set­point adjustment. Additional pilot controls, hydraulic and/or electronic, can be easily added to per­form multiple control functions to fit exact system requirements.
Page 83
MODELS
CRL-33
Electronic Actuated
Pressure Sustaining Pilot Control
Simplified Remote Valve Set-Point Control
12-24VDC Input Power
Isolated Input
Reverse Polarity Protection
Reliable Hydraulic Operation
IP-68 Submersible
The Cla-Val Model CRL-33 Electronic Actuated Pressure Sustaining Pilot Control provides remote set-point adjustment and accurate pressure sus­taining control on Cla-Val 350 Series Control Valves. Remote set-point command signals can be from any SCADA-type control system using an analog 4-20 mA signal or by contact closure for cc/ccw rotation.
The CRL-33 senses upstream pressure with a remote hydraulic connec­tion. Operating on 12 to 24 VDC and consuming very little power, it is an ideal control system for remote valve sites that may even be solar pow­ered. Existing manually-set Cla-Val 50 Series Pressure Sustaining control valves can be retrofitted with CRL-33 to add remote set-point control of minimum inlet pressure. Verification of inlet pressure may be sent to SCADA system from customer supplied pressure sensor attached upstream of valve.
The CRL-33 consists of a hydraulic pilot and integral controller that accepts a 4-20 mA remote set-point and positions the pilot to maintain a minimum pressure at valve inlet within preset limits. Pressure settings are linear between these settings. Pressure settings are calibrated to the spe­cific spring range of the control. Special USB connector cable and free downloadable software can be used to change this range if needed. Continuous internal monitoring of actuator position results in smooth tran­sitions between pilot set-points with no backlash or dithering. Should power or control input fail, the CRL-33 pilot remains in automatic hydraulic control assuring system stability under all conditions.
Typical Applications
The CRL-33 is installed on Cla-Val 350 Series valves that main­tain minimum upstream pressure by relieving excess pressure to lower zone and require this pressure setting to be changed from a remote location. It is also an effective solution for lower­ing costs associated with "confined space" requirements by eliminating the need for entry in valve structure for set point adjustment. Flow information can also be provided from the main valve, see E-133VF. Additional pilot controls, hydraulic and/or electronic, are also available to perform multiple functions to fit exact system requirements.
83
Page 84
390-02
(Full Internal Port)
MODEL
3690-02
(Reduced Internal Port)
Electronic Actuated Pressure Reducing Valve
Schematic Diagram
Item Description
1 Hytrol (Main Valve) 2 X58C Restriction Fitting 3 CRD-33 Electronic Pressure Reducing Control
Optional Features
Item Description
A X46A Flow Clean Strainer B CK2 (Isolation Valve) C CV Flow Control (Closing)
D Check Valves with Isolation Valve P X141 Pressure Gauge S CV Flow Control (Opening)
V X101 Valve Position Indicator
Simplified Remote Valve Set-Point Control
Isolated Input
Ideal for Pressure Management
12-24VDC Input Power
Reverse Polarity Protection
IP-68 (Submersible)
The Cla-Val Model 390-02/3690-02 Electronic Actuated Pressure Reducing Control Valve combines precise control of field proven Cla-Val hydraulic pilots and simple, remote valve control. The Cla-Val Model 390-02/3690-02 Pressure Reducing Valve automatically reduces a higher inlet pressure to a steady lower downstream pressure regardless of changing flow rate and/or varying inlet pressure. This valve is an accurate, pilot-operated regulator capa­ble of holding downstream pressure to a pre-determined limit. The valve uses a CRD-33 pilot control, consisting of a hydraulic pilot and integral controller, that accepts a remote set-point command input and makes set-point adjust­ments to the pilot.
The recommended control method is simple remote set-point change from an RTU (Remote Telemetry Unit) to the CRD-33 where the 4-20 mA command signal is ranged to specific pressure range. Very accurate control can be achieved when span does not exceed 100 psi. Since the CRD-33 is pre­ranged to the full spring range, some on-site calibration may be necessary when this control method is used. Free downloadable software is available from Cla-Val website for this purpose. The CRD-33 can also accommodate control systems where the RTU compares pressure transmitter signal to the remote set point command signal. The RTU adjusts the CRD-33 with 4-20 mA command signal containing an adequate deadband to prevent actuator dither­ing after the two signals agree.
Typical Applications
The Cla-Val 390 Series valves that maintain downstream pressure and require this pressure to be changed from a remote location. It can be an effective solution for lowering costs associated with "con­fined space" requirements by eliminating the need for entry in valve structure for set-point adjustment. It is also ideal for pressure man­agement, and can be programmed to minimum night time and opti­mum daytime pressures. Optional profiler can be used to create cus­tom correlation between pressure and flow information. Flow information can also be provided from the main valve, see 133VF. Additional pilot controls, hydraulic and/or electronic, are also avail­able to perform multiple functions to fit exact system requirements.
84
Internal continuous electronic monitoring of actuator position results in virtual­ly instantaneous position change with no backlash or dithering when control signal is changed. In the event of a power or control input failure, the CRD-33 pilot remains in hydraulic control virtually assuring system stability under changing conditions. If check feature ("D") is added, and pressure reversal occurs, the valve closes to prevent return flow.
Product Dimensions Data:
For the 390-02 Main Valve (100-01) dimensions, see pages 17. For the 3690-02 Main Valve (100-20) dimensions, see pages 29.
Page 85
MODEL
CRD-33 and CRA-33
Electronic Actuated
Pressure Reducing Pilot Control
Ideal for Pressure Management
Simplified Remote Valve Set-Point Control
Isolated Input
12-24VDC Input Power
Reverse Polarity Protection
IP-68 Submersible
The Cla-Val Model CRD-33 and CRA-33 Electronic Actuated Pressure Reducing Pilot Controls provide remote set-point adjustment and accurate downstream pressure control on Cla-Val 390 Series Control Valves. Remote set-point command signals can be from any SCADA-type control system using an analog 4-20 mA signal or by contact closure for cc/ccw rotation.
The CRD-33 senses valve outlet pressure directly and the CRA-33 sens­es downstream pressure with remote hydraulic connection. Operating on 12 to 24 VDC and consuming very little power, they are an ideal control system for remote valve sites that may even be solar powered. Existing manually-set Cla-Val 90 Series Pressure Reducing control valves can be retrofitted with CRD-33 or CRA-33 to add remote set-point control of deliv­ery pressure. Verification of downstream pressure may be sent to SCADA system from customer supplied pressure sensor attached to valve outlet.
The CRD-33 and CRA-33 consists of a hydraulic pilot and integral con­troller that accepts a 4-20 mA remote set-point and positions the pilot to maintain a pressure at valve outlet within preset limits. Pressure settings are linear between these settings. Pressure settings are calibrated to the specific spring range of the control. Special USB connector cable and free downloadable software can be used to change this range if needed. Continuous internal monitoring of actuator position results in smooth tran­sitions between pilot set-points with no backlash or dithering. Should power or control input fail, the CRD-33 or CRA-33 pilot remains in auto­matic hydraulic control assuring system stability under all conditions.
Typical Applications
The CRD-33 and CRA-33 are installed on Cla-Val 390 Series valves that maintain downstream pressure and require this pressure to be changed from a remote location. It can be an effective solution for low­ering costs associated with "confined space" requirements by eliminat­ing the need for entry in valve structure for set-point adjustment. It is also ideal for pressure management, and can be programmed to mini­mum night time and optimum daytime pressures. Optional profiler can be used to create custom correlation between pressure and flow information. Flow information can also be provided from the main valve, see E-133VF. Additional pilot controls, hydraulic and/or electronic, are also available to perform multiple functions to fit exact system requirements.
85
Page 86
136-01
(Full Internal Port)
(Sizes 1/2"-4")
MODEL
636-01
(Reduced Internal Port)
(Sizes 3"-6")
Solenoid Control Valve
• Fast Acting Solenoid Control
• Reliable, Drip-Tight Shut-Off
• Simple Design, Proven Reliable
• Optional Check Feature
• Easy Installation and Maintenance
The Cla-Val Model 136-01/636-01 Solenoid Control Valve is an on-off control valve that either opens or closes upon receiving an electrical signal to the solenoid pilot control. This valve consists of a Hytrol main valve and a three-way solenoid valve that alternately applies pressure to or relieves pressure from the diaphragm chamber of the main valve. It is furnished either normally open (de-energized sole­noid to open) or normally closed (energized solenoid to open).
If the check feature option is added and a pressure reversal occurs, the
Schematic Diagram
Item Description
1 Hytrol (Main Valve) 2 CS3 Solenoid Control
downstream pressure is admitted into the main valve cover chamber and the valve closes to prevent return flow.
Optional Features
Item Description
A X46A Flow Clean Strainer B CK2 (Isolation Valve) C CNA Closing Speed Control D Check Valves with Isolation Valve P X141 Pressure Gauge S CNA Needle Valve (Opening) V X101 Valve Position Indicator Y X43 "Y" Strainer
Product Dimensions Data:
For the 136-01 Main Valve (100-01) dimensions, see pages 17. For the 636-01 Main Valve (100-20) dimensions, see pages 29.
Typical Applications
Industrial uses for the solenoid control valve are many and include accurate control of process water for batching, mixing, washing, blending or other on-off type uses.
86
Liquid level control can be provided by using a float switch or electrode probe which sends an electrical signal to open or close the valve as needed.
Page 87
Schematic Diagram
136-03
(Sizes 4"and Larger)
(Full Internal Port)
MODEL
636-03
(Sizes 6"and Larger)
(Reduced Internal Port)
Solenoid Control Valve
• Fast Acting Solenoid Control
• Drip Tight Shut-Off
• Simple Design, Proven Reliable
• Optional Check Feature
• Easy Installation & Maintenance
The Cla-Val Model 136-03/636-03 Solenoid Control Valve is an on-off control valve which either opens fully or closes drip-tight upon receiv­ing an electrical signal to the solenoid pilot control. This valve consists of a Hytrol main valve, a three way solenoid and a high capacity three­way pilot valve. The solenoid control operates the three-way valve which alternately applies pressure to or relieves pressure from the diaphragm chamber of the main valve. It is furnished either normally open (de-energize solenoid to open) or normally closed (energize sole­noid to open).
If the check feature option is added and a pressure reversal occurs, the downstream pressure is admitted into the main valve cover chamber and the valve closes to prevent return flow.
Item Description
1 Hytrol (Main Valve) 2 CS3 Solenoid Control 3 102C-3H Three-Way Valve 4 CNA Needle Valve (Closing)
Optional Features
Item Description
A X46 Flow Clean Strainer B CK2 (Isolation Valve) D Check Valves With Isolation Valve F Independent Operating Pressure H Atmospheric Drain P X141 Pressure Gauge
S CNA Needle Valve (Opening) V X101 Valve Position Indicator Y X43 "Y" Strainer
Typical Applications
Product Dimensions Data:
For the 136-03 Main Valve (100-01) dimensions, see pages 17. For the 636-03 Main Valve (100-20) dimensions, see pages 29.
Industrial uses for the solenoid control valve are many and include accurate control of process water for batching, mixing, washing, blending or other on-off type uses.
Liquid level control can be provided by using a float switch or electrode probe which sends an electrical signal to open or close the valve as needed.
87
Page 88
139-01
(Full Internal Port)
MODEL
639-01
(Reduced Internal Port)
Programmable Timer Control Valve
Precise Valve On-Off Control
Completely Self-contained
High Energy Efficiency
Battery Life Exceeds 3 Years
Direct Control of Valve Opening and Closing Four Times Daily
Combines with Pressure, Flow or Level Control
Ideal for Remote Valve Location Control
The Cla-Val Model 139-01/639-01 Programmable Timer Control Valve is an on-off control valve for applications using a programmable time schedule. Using the CTC Electronic Timer Control up to four opening and closing times per day can be set for a weekly schedule.
Timer function and parameters are changed using downloadable soft-
www.cla-val.com and special USB
Schematic Diagram
Item Description
1 Hytrol (Main Valve) 2 CTC Electronic Timer Control 3 X58C Restriction Assembly
ware from the Cla-Val website cable part number 20519203A. Future software and firmware upgrades will be available from Cla-Val website. Powered by a long­life lithium battery, the CTC control offers powerful valve control for remote locations and other valve automation applications.
Optional Features
Item Description
A X46A Flow Clean Strainer B CK2 (Isolation Valve) D Check Valves with Isolation Valve P X141 Pressure Gauge
V X101 Valve Position Indicator Y X43 “Y” Strainer
*Standard on 1-1/4” and larger
*
Typical Applications
Model 139-01 Programmable Timer Control Valve is ideal for automating dis­tribution system flushing applications. The valve is installed in distribution sys­tem locations that require a regular flush­ing schedule to maintain system water quality within disinfection and health standard limits. The valve vents a small quantity of water for a short time on a regular schedule to create desired water turnover. Other Model 139-01 applications requir­ing remote, stand alone valve opening and closing on a predetermined sched­ule include night-time tank filling, service line limiting time of use, automatic line strainer flushing, etc.
Product Dimensions Data:
For the 139-01 Main Valve (100-01) dimensions, see pages 17. For the 639-01 Main Valve (100-20) dimensions, see pages 29.
88
Page 89
CLA-VAL
FLOW
to drain
CLA-VAL
MODEL
CTC
Electronic Timer Control
Precise Valve On-Off Control
Completely Self-contained
High Energy Efficiency
Battery Life Exceeds 3 Years
Direct Control of Valve Opening and Closing 4 Times Daily
Combines with Pressure, Flow or Level Control
Ideal for Remote Valve Location Control
The Cla-Val CTC Electronic Timer Control is a battery powered, pro­grammable on-off control used for opening and closing Cla-Val main valves according to time schedule. Up to four opening and closing times per day can be set for a weekly schedule.
Timer function and parameters are changed using downloadable soft­ware from the Cla-Val website cable part number 20519203A. Future software and firmware upgrades will also be available from Cla-Val website. Powered by a long-life lithium battery, the CTC offers powerful valve control for remote locations and valve automation applications.
www.cla-val.com and special USB
CTC Electronic Timer Control Specifications
Pressure Connection: 1/4"NPT
Operating Pressure: Maximum 145 psi (10 bar)
°
Temperature Range: 14
Enclosure Protection: IP-68 (submersible)
Battery Type: Lithium 9V/PP3
F to 176°F (-10°C to + 80°C)
Typical Application
The CTC Electronic Timer Control is used for pressure man­agement applications in water distribution systems where SCADA control is not available. A Cla-Val Pressure Control Valve is programmed with CTC to change pressure during high flow and low flow demand times according to pre-engineered schedule reducing leaks and pipe burst frequency.
CLA-VAL
P.O. Box 1325 Newport Beach, CA 92659-0325 Phone: 949-722-4800 Fax: 949-548-5441 E-mail: claval@cla-val.com Website cla-val.com
©
Copyright Cla-Val 2012 Printed in USA Specifications subject to change without notice.
Fluids: Water, others compatible with materials
Materials: Enclosure: PVC
Valve Body: Glass-Fiber Nylon Body Seals: Buna-N®
Programming Interface: Custom USB cable (1 m, supplied stan­dard); Windows NT, 2000, XP, Vista Programming Software is free download from Cla-Val website.
The CTC Electronic Timer Control is used in 139 Series Programmable Control Valves to automate circulating water requirements in distribution system applications. Valve open­ing and closing time of day and duration are programmed for convenient system flushing and circulating during times of low flow to optimize water quality.
E-CTC (R-9/2011)
89
Page 90
60-08
(Full Internal Port)
MODEL
660-08
(Reduced Internal Port)
Booster Pump Control Valve
with High Capacity Pilot System
Schematic Diagram
Designed for Larger Sized Pump Stations
Low Head Loss
Built-in Check Valve
Opening and Closing Rates Separately Adjusted
Proven Reliable Design
The Cla-Val Model 60-08/660-08 Pump Control Valve is a pilot­operated valve designed for installation on the discharge of booster pumps to eliminate pipeline surges caused by the start­ing and stopping of the pump.
The pump starts against a closed valve. When the pump is start­ed, the solenoid control is energized and the valve begins to open slowly, gradually increasing line pressure to full pumping head. When the pump is signaled to shut-off, the solenoid con­trol is de-energized and the valve begins to close slowly, gradu­ally reducing flow while the pump continues to run. When the valve is closed, a limit switch assembly, which serves as an elec­trical interlock between the valve and the pump, releases the pump starter and the pump stops.
Should a power failure occur, a built-in, lift-type check valve closes the moment flow stops, preventing reverse flow regardless of solenoid or diaphragm assembly position.
Item Description
1 Powercheck (Main Valve) 2 CV Flow Control 3 CS4SM 4-Way Solenoid Control 4 X105LCW Switch Assembly 5 CVS-1 Shuttle Valve
Optional Features
Item Description
A X46A Flow Clean Strainer B CK2 (Isolation Valve) P X141 Pressure Gauge Y X43 "Y" Strainer
Product Dimensions Data:
For the 60-08 Main Valve (100-03) dimensions, see pages 25. For the 660-08 Main Valve (100-22) dimensions, www.cla-val.com
Typical Installation
Install Model 60-08/660-08 valve as shown. Flexible conduit should be used for electrical connections to the solenoid control and the limit switch. A Model 52-02/652-03 Surge Anticipator Valve is recom­mended for power failure protection.
Note: For optimum operation of built-in check feature, installation must be with valve stem vertically up.
The Model 60-08/660-08 is for 10" and larger valves or when the pressure is above 300 psi.
90
Page 91
Pump
CLA-VAL 60-11/660-11
Booster Pump
Control Valve
CLA-VAL 52-03/652-03 Surge Anticipator Valve
Discharge to Atmosphere
Isolation Valve
Discharge To System
60-11
MODEL
(Full Internal Port)
660-11
(Reduced Internal Port)
Booster Pump Control Valve
Built-in Check Valve
Valve Uses Line Pressure for Operation
Opening and Closing Rates Adjusted Separately
Solenoid Control Can Be Operated Manually
The Cla-Val Model 60-11/660-11 Booster Pump Control Valve is a pilot-operated valve designed for installation on the discharge of booster pumps to eliminate pipeline surges caused by the starting and stopping of the pump.
The pump starts against a closed valve. When the pump is start­ed, the solenoid control is energized and the valve begins to open slowly, gradually increasing line pressure to full pumping head. When the pump is signaled to shut-off, the solenoid control is de­energized and the valve begins to close slowly, gradually reducing flow while the pump continues to run. When the valve is closed, a limit switch assembly, which serves as an electrical interlock between the valve and the pump, releases the pump starter and the pump stops.
Schematic Diagram
Item Description
1 Powercheck (Main Valve) 2 CV Flow Control 3 CSM11-A2-2 Solenoid Control 4 X105LCW Switch Assembly 5 CVS-1 Shuttle Valve
Optional Features
Item Description
A X46A Flow Clean Strainer B CK2 (Isolation Valve) P X141 Pressure Gauge Y X43 "Y" Strainer
Product Dimensions Data:
For the 60-11 Main Valve (100-03) dimensions, see pages 25. For the 660-11 Main Valve (100-22) dimensions, www.cla-val.com
Typical Installation
Install Model 60-11/660-11 valve as shown. Flexible conduit should be used for electrical connections to the solenoid control and the limit switch. A Cla-Val Model 52-03/652-03 Surge Anticipator Valve is rec­ommended for power failure protection.
Note: Installation with valve stem vertical up is recommended. For horizontal stem installation use Cla-Val Model 60-73/660-73.
Should a power failure occur, a built-in lift-type check valve closes the moment flow stops, preventing reverse flow regardless of sole­noid or diaphragm assembly position.
91
Page 92
60-31
(Full Internal Port)
MODEL
660-31
(Reduced Internal Port)
Booster Pump Control Valve
Simple Hydraulic Operation
Low Head Loss
Built-in Check Valve
Proven Reliable Design
The Cla-Val Model 60-31/660-31 Booster Pump Control valve is a pilot-operated valve designed for installation on the discharge of booster pumps to eliminate pipeline surges caused by the start­ing and stopping of the pump.
The pump starts against a closed valve. When the pump is start­ed, the solenoid control is energized and the valve begins to open slowly, gradually increasing line pressure to full pumping head. When the pump is signaled to shut-off, the solenoid control is de­energized and the valve begins to close slowly, gradually reduc­ing flow while the pump continues to run. When the valve is closed, a limit switch assembly, which serves as an electrical interlock between the valve and the pump, releases the pump starter and the pump stops.
Schematic Diagram
Item Description
1 Hycheck (Main Valve) 2 102C-3H Three Way Hytrol 3 CS3SM Solenoid Control 4 X105LCW Switch Assembly 5 CDC Disk Check Valve 6 CDC/CSC Check Valve 7 CNA Angle Valve 8 CK2 Cock (Isolation Valve)
Item Description
A X46A Flow Clean Strainer B CK2 Cock (Isolation Valve) P X141 Pressure Gauge Y X43 "Y" Strainer
Product Dimensions Data:
For the 60-31 Main Valve (100-04) dimensions, see www.cla-val.com For the 660-31 Main Valve (100-23) dimensions, www.cla-val.com
Typical Application
Install Model 60-31/660-31 valve as shown in multiple pump applications. Flexible conduit should be used for electrical connections to the solenoid control and the limit switch. A Model 52-03/652-03 Surge mended for power failure
Anticipator Valve is recom-
protection.
The Model 60-31/660-31 is an automatic valve of a modified globe-type design with a built-in, lift type, check feature. It is hydraulically operated and diaphragm-actuated. A three-way solenoid valve controls the valve operation. Flow control valves located in the pilot control system provide regulation of both the opening and closing rate. Pilot system strainer insures that the pilot control supply is clean.
92
Page 93
60-32
MODEL
(Full Internal Port)
660-32
(Reduced Internal Port)
Combination Pump Control and Back
Schematic Diagram
Item Description
1 Hycheck (Main Valve) 2 CRL Pressure Relief Control 3 X47A Ejector 4 100-01 Hytrol (Reverse Flow) 5 CS3M Solenoid Control 6 X105LCW Switch Assembly 7 CK2 Cock (Isolation Valve)
8 CV Flow Control (Opening and Closing Speed) 9 CDC/CSC Check Valve
Pressure Valve
(4" and Larger)
Built-in Check Valve
Accurate Pressure Control
Low Head Loss
Smooth Control of Pump Surges
Easy Maintenance Design
The Cla-Val Model 60-32/660-32 Combination Pump Control and Back Pressure Valve is a pilot-operated control valve designed for booster pump discharge installation to eliminate pipeline surges caused by starting and stopping of pump and to provide adjustable back pressure on pump while it is running. The valve features a modified globe-design with diaphragm-actuation, and hydraulic operation for smooth, reliable automatic operation dur­ing pump starting and stopping. A built-in lift-type check feature automatically closes valve on electric power failure or any time pressure reversal occurs to protect pump from back spinning.
In operation, when pump is off, the pump control valve is closed by downstream system pressure. When pump is started, the solenoid control is energized and valve opens slowly to gradually increase pump flow and line pressure to desired back pressure setting for pumping conditions. When pump is signaled to shut­off, the solenoid control is de-energized and the valve begins to slowly close, gradually reducing flow while pump continues to run. When valve is closed, the included limit switch assembly turns off pump. Adjustable flow controls are included to easily regulate valve opening and closing speed to prevent surges. Using Cla-Val wiring diagram (see page 4) ensures safe electrical interlock control of pump and valve.
CS3
2
3
1
Optional Features
Item Description
A X46A Flow Clean Strainer B CK2 Cock (Isolation Valve) P X141 Pressure Gauge
Y X43 "Y" Strainer
Typical Application
Install Model 60-32/660-32 valve as shown in multiple pump applications. Flexible water-tight conduit should be used for electrical connections to the solenoid control and the limit switch. A Model 52-03/652-03 Surge recommended for power failure
Anticipator Valve is
protection.
Product Dimensions Data:
For the 60-32 Main Valve (100-04) dimensions, see www.cla-val.com For the 660-32 Main Valve (100-23) dimensions, www.cla-val.com
93
Page 94
61-02
(Full Internal Port)
MODEL
661-02
(Reduced Internal Port)
Deep Well Pump Control Valve
Prevent Surges in Pipelines
Simple Hydraulic Operation
Adjustable Opening and Closing Speeds
Solenoid Control Can Be Operated Manually
Proven Reliable Design
The Cla-Val Model 61-02/661-02 Deep Well Pump Control Valve is designed to protect pipelines from surges caused by the start­ing and stopping of deep well pumps. This is a hydraulically operated diaphragm valve which is controlled by a solenoid pilot valve. Separate adjustable flow control valves in the pilot system regulate the opening and closing rates. A limit switch on the valve stem serves as an electrical interlock between the valve and the pump motor.
The operation of the valve is completely automatic and con­trolled by the solenoid valve. With the pump off, the valve is wide open. When the pump is started, the solenoid is energized and the valve begins to close slowly, discharging air and the initial rush of sand and water from the pump column to atmosphere. As the valve closes the pump output is gradually diverted into the main line, preventing the development of a starting surge.
Schematic Diagram
Item Description
1 Powertrol (Main Valve) 2 CSM11-A2-2 Solenoid Control 3 CV Flow Control 4 X105LOW Switch Assembly 5 CK (Isolation Valve) 6 X43 "Y" Strainer 7 Union
Item Description
P X141 Pressure Gauge
Note: For main valve option descriptions, refer to 100-02 (61-02) or 100­21 (661-02) Technical Data Sheets.
Product Dimensions Data:
For the 61-02 Main Valve (100-02) dimensions, see pages 21. For the 661-02 Main Valve (100-21) dimensions, www.cla-val.com
Typical Installation
Install Model 61-02/661-02 valve as shown. Use a minimum of 1/2" tubing to connect operating pressure connection of the valve to the system side of check valve. Flexible conduit should be used for electrical connections to the solenoid con­trol and the limit switch assembly. A Model 52-02/652-03 Surge Anticipator is recommended for power failure and surge protection.
When it is time to shut-off the pump, the solenoid is de-ener­gized. The pump continues to run while the pump control valve opens slowly, diverting pump output to atmosphere. As pump pressure gradually decreases, the main line check valve closes slowly, preventing shock or slam during the pump stopping cycle. When the pump control valve is wide open, the limit switch assembly releases the pump starter and the pump stops.
94
Page 95
81-01
MODEL
(Full Internal Port)
681-01
(Reduced Internal Port)
Check Valve
Simple Proven Design
No-Slam Operation
Drip-Tight Shut-Off
No Packing Glands or Stuffing Boxes
Easy to Install & Maintain
The Cla-Val Model 81-01/681-01 Check Valve is a hydraulically operated No-Slam Check Valve. This valve opens when the pres­sure at the inlet exceeds the discharge pressure. A gradual rate of opening prevents sudden opening surges. When a pressure rever­sal occurs the higher downstream pressure is applied to the cover chamber through the control tube lines, and the valve closes drip tight.
This valve is ideally suited for use where a positive shutoff is required. The rubber disc assures tight sealing even if the fluid con­tains grit or other small-size particles. The simple packless design insures reliable operation and freedom from leaks.
Schematic Diagram
Item Description
1 Hytrol (Reverse Flow Main Valve)
Product Dimensions Data:
For the 81-01 Main Valve (100-01) dimensions, see pages 17. For the 681-01 Main Valve (100-20) dimensions, see pages 29.
Note: The effectiveness of this valve is related to pipeline velocity. We recommend a maximum flow based on pipeline velocity of 6 feet per second. If pipeline velocities exceed 6 feet per second, consid­eration should be given to adding a Cla-Val Model 50-01 Pressure Relief Valve or a Cla-Val Model 52 Series Surge Control Valve to the system.
Inlet Outlet
M
1
Typical Applications
Smaller sizes of this valve are used in pilot control sys­tems in Cla-Val Automatic Control valves. This valve can also be used in any piping system where one-way flow is desired.
Install on the discharge of booster pumps to prevent return flow into tank when pump is off. Relief valve as shown is good practice to minimize surges when pump stops.
For valve sizes larger than 3", use Model 81-02.
95
Page 96
81-02
(Full Internal Port)
MODEL
681-02
(Reduced Internal Port)
Check Valve
Simple Proven Design
No-Slam Operation
Drip-Tight Shut-Off
Dual Speed Control
No Packing Glands or Stuffing Boxes
Available in a Variety of Materials
The Cla-Val Model 81-02/681-02 Check Valve is a hydraulically operated No-Slam Check Valve with dual speed controls. This valve opens when the pressure at the inlet exceeds the discharge pressure. A gradual rate of opening prevents sudden opening surges. When a pressure reversal occurs, the higher downstream pressure is applied to the cover chamber through the control tube lines, and the valve closes drip tight.
This valve is ideally suited for use where a positive shutoff is required. The rubber disc assures tight sealing even if the fluid contains grit or other small-size particles. The simple packless design insures reliable operation and freedom from leaks.
Schematic Diagram
Item Description
1 Hytrol (Reverse Flow Main Valve) 2 CGA Angle Valve (Closing) 3 CNA Needle Valve (Opening) 4 CSC Swing Check Valve
Optional Features
Item Description
P X141 Pressure Gauge V X101 Valve Position Indicator
Product Dimensions Data:
For the 81-02 Main Valve (100-01) dimensions, see pages 17. For the 681-02 Main Valve (100-20) dimensions, see pages 29.
Typical Applications
Note: The effectiveness of this valve is related to pipeline velocity. We rec­ommend a maximum flow based on pipeline velocity of 6 feet per second. If pipeline velocities exceed 6 feet per second, consideration should be given to adding a Cla-Val Model 50-01 Pressure Relief Valve or a Cla-Val Model 52 Series Surge Control Valve to the system.
Deep Well Pump
This valve should be an integral part of any well designed pump­ing system. It is used to prevent damaging and sometimes expen­sive flow reversal.
96
Booster Pump
Install on the discharge of booster pumps to prevent return flow into tank when pump is off. Relief valve as shown is good practice to min­imize
surges when pump stops.
Page 97
81-12
MODEL
(Full Internal Port)
681-12
(Reduced Internal Port)
Check Valve
Simple Proven Design
No-Slam Operation
Drip-Tight Shut-Off
Recommended for Variable Speed Pumps
No Packing Glands or Stuffing Boxes
Easy to Install & Maintain
The Cla-Val Model 81-12 Check Valve is a hydraulically operated No-Slam Check Valve. This valve opens when the pressure at the inlet exceeds the discharge pressure. A gradual rate of opening pre­vents sudden opening surges. When a pressure reversal occurs the higher downstream pressure is applied to the cover chamber through the control tube lines, and the valve closes drip tight.
This valve is ideally suited for use where a positive shutoff is required. The rubber disc assures tight sealing even if the fluid con­tains grit or other small-size particles. The simple packless design insures reliable operation and freedom from leaks.
Schematic Diagram
Item Description
1 Hytrol (Main Valve)
Product Dimensions Data:
For the 81-12 Main Valve (100-01) dimensions, see pages 17.
Typical Applications
Install on the discharge of booster pumps to prevent return flow when pump is off. Relief valve as shown is good practice to minimize surges when pump stops.
For valve sizes 3" and larger consult factory
97
Page 98
Series 501A
Wafer Swing Check Valve
Standard Style
2”-12”
SPECIFICATIONS
The wafer swing check valve shall have torsional a spring-assisted fast closure to minimize possibility of water hammer. The valve shall be constructed of either cast iron or steel body.
The body shall have a machined dovetail groove to
®
retain a field replaceable Nitrile (Buna-N provides water-tite shut-off at low/high pressure
) Seal that
Low Head Loss
Watertight Nitrile Seat
Spring Assisted, Fast Closure
Extremely Light Weight
DESCRIPTION
Cla-Val Series 501A Wafer Swing Check Valve has a quick, spring-assisted closure that minimizes the possibility of water hammer. The swing check design offers low head loss and a full-flow passageway making it ideal for water or waste­water applications. The short lay length of the valve allows for a space-saving design. It is available in sizes 2” to 30”, with either a 125 lb. or 150 lb. pressure class rating.
Available in a variety of materials, including all 316 stain­less steel, the Cla-Val Wafer Swing Check Valve uses a standard soft seat to ensure a drip-tight seal. For ease of installation, valves 6” and larger are supplied with a tapped hole to mount an eye bolt for lifting. All materials conform to ASTM specifications, ensuring performance reliability.
Typical Applications with Correct Valve Location
Avoid These Applications with Incorrect Valve Location
The valve disc/arm assembly shall be one piece design utilizing an integral disc arm for connection to the shalt for positive shut-off and no disc flutter.
For corrosion resistance the valve shall be Electroless Nickel Plated
Valve Body:
2" -12" Cast Iron ASTM A48 Electroless-Nickel Plated 14" - 30" Carbon Steel ASTM A216 WCB Electroless-Nickel Plated
Valve Trim :
2" - 12" 316 Stainless Steel ASTM A23, 14" - 30" Carbon Steel ASTM A216 WCB Electroless-Nickel Plated Seat O-ring: Nitrile, Other Seat Materials Available
All materials conform to ASTM specifications, The valve shall be a Cla-Val Series 501A Wafer Swing Check Valve, Newport Beach, CA 92659-0325
Note: Allow minimum (2) pipe diameters clearance downstream of check valve with disc open to promote smooth flow
Recommendations for Installation Position
1. Install the valve in horizontal or upward flow for proper valve closure. Caution: Do not use with reciprocating compressors, or in other pulsating services.
98
Page 99
Silent Wafer Check Valve
SPECIFICATIONS
The silent wafer check valve shall consist of a heavy cast iron body, bronze seat, bronze disc, and stain­less steel spring. The valve disc shall be center guided at both ends with an integral shaft and shall be spring loaded for silent operation. The spring shall be helical or conical and stone tumbled to achieve a micro-finish to resist mineral deposits. For ease of maintenance, the seat and disc shall be replaceable in the field.
Check valve shall be capable of silent operation when installed in vertical or horizontal positions with either flow up or flow down. The flow area through the body shall be equal to or greater than the cross­section area of the equivalent pipe size. The valve shall be a Cla-Val Series 580 Silent Wafer Check Valve.
All materials of construction shall conform to ASTM specifications as follows:
Valve Body: Wafer Style Cast Iron ASTM A126
Class B
Disc & Seat: Bronze ASTM B584
Spring: Stainless Steel ASTM A313.5
Stone Tumbled
Sizes: 2" to 10"
Series 580
Short Lay Length
Watertight Seating
Field Replaceable Parts
Factory Mutual Approved
Optional Resilient Seat
The Cla-Val Series 580 Silent Wafer Check Valve has a spring­loaded poppet that allows the valve to close before flow reversal occurs, resulting in a silent, non-slam closure. It is a truly silent check valve. For ease of installation, the valve can be installed in vertical or horizontal positions with flow up or flow down. The short lay length of the valve allows for a space-saving design. Silent Wafer Check Valves are available in sizes 2” to 10”, with either a 125 lb. or 250 lb. pressure class rating.
Constructed of a cast iron body with bronze trim, the Cla-Val Silent Wafer Check Valve offers watertight shutoff with metal-to­metal seating. For special applications, stainless steel trim and Buna-N resilient seats are available as options. All materials conform to ASTM specifications, ensuring long lasting reliable performance. As a confirmation of Cla-Valʼs commitment to quality, all Series 580 125 lb. class valves are Factory Mutual approved.
Series 580 Pressure Loss Curve
3
2
1
Pressure Loss PSI
12
WAFER AND GLOBE STYLE SILENT CHECK VALVES
TEMP
DEG F.
0 -150º
200º 250º
TEST
PRES.
* Ductile Iron Recommended For Hot Water Service Above 200º F.
GRAY IRON
125 LB. CLASS
2” - 12”
200 190
*
300
3
PRESSURE / TEMPERATURE RATINGS
MAXIMUM NON-SHOCK WATER SERVICE PRESSURE
14” - 42”
150 135
*
230
(Typical)
45678 9 10 11 12
Fluid Velocity / FPS
DUCTILE IRON 150 LB. CLASS
2” - 12”
300 280 270
450
14” - 42”
250 230 220
375
GRAY IRON
250 LB. CLASS
2” - 12”
400 370
*
600
14” - 42”
300 280
450
2” - 12”
*
DUCTILE IRON 300 LB. CLASS
500 460 440
750
7
6
5
4
3
2
1
14” - 42”
®
Pressure Loss Ft. of Water
400 370 355
600
99
Page 100
12
3
45678 9 10 11 12
Series 581 Pressure Loss Curve
3
2
1
7
6
5
4
3
2
1
Pressure Loss PSI
Pressure Loss Ft. of Water
Fluid Velocity / FPS
(Typical)
Series 581
Silent Globe Check Valve
Operates Horizontally or Vertically
Watertight Seating
Field Replaceable Parts
Factory Mutual Approved – Various Sizes
Optional Resilient Seat
The Cla-Val Series 581 Silent Globe Check Valve has a spring­loaded poppet that allows the valve to close before flow reversal occurs, resulting in a silent, non-slam closure. It is a truly silent check valve. For ease of installation, the valve can be installed in vertical or horizontal positions with flow up or flow down. Silent Globe Check Valves are available in 2 1/2” to 42” sizes, with either a 125 lb. or 250 lb. pressure class rating. Silent Globe Check Valves in 3” to 10” sizes have enough outlet clearance to allow them to be bolted directly to wafer style butterfly valves.
SPECIFICATIONS
The silent globe check valve shall consist of a heavy cast iron body, bronze seat, bronze disc, and stain­less steel spring. The valve disc shall be center guided at both ends with an integral shaft and shall be spring loaded for silent operation. The spring shall be helical or conical and stone tumbled to achieve a micro-finish to resist mineral deposits. For ease of maintenance, the seat and disc shall be replaceable in the field.
Constructed of a cast iron body with bronze trim, the Cla-Val Silent Globe Check Valve offers watertight shutoff with metal-to­metal seating. For special applications, stainless steel trim and
®
Buna-N
resilient seats are available as options. All materials conform to ASTM specifications, ensuring long lasting reliable performance. As a confirmation of Cla-Valʼs commitment to quality, 2 1/2” to 12” 125 lb. class Series 581 valves are Factory Mutual approved.
Check valve shall be capable of silent operation when installed in vertical or horizontal positions with either flow up or flow down. The flow area through the body shall be equal to or greater than the cross­section area of the equivalent pipe size. Sizes 2 1/2” to 10” shall allow bolting a wafer style butterfly valve directly to the outlet flange without a spool piece.
All materials of construction shall conform to ASTM specifications as follows:
Valve Body:
Disc & Seat:
Spring:
Sizes:
Cast Iron ASTM A126 Class B Bronze ASTM B584
Stainless Steel ASTM A313.5 Stone Tumbled & Stress Relieved.
3" thru 10" shall accept a direct con­nected Butterfly Valve for isolation use and space saving in the pump station.
The valve shall be a Cla-Val Series 581 Silent Globe Check Valve.
Cla-Val Series 581 Silent Globe Check Valve avaliable in all 316 Stainless Steel Material.
Note:
PRESSURE / TEMPERATURE RATINGS
WAFER AND GLOBE STYLE SILENT CHECK VALVES
TEMP
DEG F.
º
0 -150
200º 250º
TEST
PRES.
* Ductile Iron Recommended For Hot Water Service Above 200º F.
MAXIMUM NON-SHOCK WATER SERVICE PRESSURE
GRAY IRON
125 LB. CLASS
2” - 12”
14” - 42” 200 190
*
300
150 135
*
230
DUCTILE IRON 150 LB. CLASS
2” - 12”
300 280 270
450
14” - 42”
250 230 220
375
GRAY IRON
250 LB. CLASS
2” - 12”
400 370
600
14” - 42”
300 280
*
450
2” - 12”
*
DUCTILE IRON 300 LB. CLASS
14” - 42” 500 460 440
750
400 370 355
600
100