Carrier Humcclbp18a, Humcclfp1218, Humcclfp1318, P110lfp1418 Installation Guide

0 (0)
Carrier Humcclbp18a, Humcclfp1218, Humcclfp1318, P110lfp1418 Installation Guide

READ COMPLETE SAFETY INSTRUCTIONS AND INSTALLATION TEMPLATE BEFORE STARTING

ATTENTION INSTALLER:

This product must be installed by a qualified heating and air conditioning contractor. Failure to do so could result in serious injury from electrical shock. This product must be installed in compliance with all local, state and federal codes.

FAN POWERED HUMIDIFIER

WARNING

1. ELECTRICAL SHOCK HAZARD.

Disconnect electrical power to the furnace and install lock-out tag before starting installation. Failure to do so could result in serious injury from electrical shock.

2. SHARP EDGES HAZARD. Sharp

edges may cause serious injury from cuts. Use care when making plenum openings and handling ductwork.

3. RISK OF SCALDING. Water

temperature over 125°F can cause severe burns and scald instantly. Shut off the hot water supply before disconnecting or tapping into any hot water supply line.

CAUTION

 

SPECIFICATIONS

 

 

 

RISK OF PROPERTY AND EQUIPMENT DAMAGE.

 

HUMIDIFIER DIMENSIONS

1. Do not install humidifier where freezing temperatures

5. Do not connect the humidifierpower cord to multi-speed

 

 

Width 15 2932

could occur. The water line could freeze and crack

furnace blower motors or blower motors other than 120 VAC.

 

 

Height (including solenoid valve

causing water damage to the home.

Premature component failure may result.

 

 

and drain spud) 18”

2. Do not install humidifier on the furnace cabinet.

6. When installing Manual Humidifier Control on a downflow

 

 

Depth 101132

3. Do not install humidifier on a plenum face where the

furnace, ensure blower continues to run after a heat call is

 

satisfied to eliminate high temperatures from damaging the

 

PLENUM OPENING

blanked off ends of the cooling coil will restrict air

 

movement through the humidifier.

Control.

 

1434”W x 14516”H

7. Do not install humidifier where water pressure exceeds

 

4. Do not set humidity level above recommended or to

 

WATER FEED RATE

125 psi, since damage to the humidifier may result. Follow

 

recommended level if condensation exists on inside

 

codes in effect concerning pressure reduction.

 

6 gph

windows of any unheated space, as condensation

 

damage may result. Excess humidity can cause

8. Do not install humidifier on the supply plenum where static

 

ELECTRICAL DATA

moisture accumulation which can allow the possibility

pressure exceeds 0.4 in. wg.

 

 

 

for mold growth in the home.

 

 

120 VAC-60 Hz, 0.8 AMP

 

 

 

 

WIRING DIAGRAMS

HumidiTrac

Automatic Humidifier Control

For detailed Automatic Humidifier Control installation and wiring instructions, see Form IM-AHC-02 included with Control.

DIAGRAM C

THERMIDISTAT™ HOOK-UP WITH

ALL INDOOR EQUIPMENT

DIAGRAM A

STANDARD FURNACE VARIABLE SPEED FURNACE VARIABLE SPEED FAN COIL

HUMIDIFIER CORD PLUGGED INTO

120 VAC POWER SOURCE

C

HUM

24V COIL NORMALLY OPEN RELAY (FIELD SUPPLIED PART# HN61KQ120)

HUMIDIFIER

24 VAC LEADS

MANUAL

HUMIDISTAT

90-847

DIAGRAM B

STANDARD FAN COIL

HUMIDIFIER C ORD PLUGGED INTO 120 VAC POW ER SOURCE

FURNACE / AC

BLOWER MOTOR

COMMO N LEAD

C

HI

LO

HUMIDIFIER

24 VAC LEADS

MANUAL

HUMID ISTAT

CURRENT SE NSING RELAY

PART NO . P-110-005

90-848

DIAGRAM D

DIAGRAM E

ZONING HOOK-UP

NEW COMMUNICATING CONTROL HOOK-UP

WITH EQUIPMENT CONTROLLER

WITH ALL INDOOR EQUIPMENT

HUMIDIFIER

HUMIDIFIER CORD

PLUGGED INTO

120 VAC POWER SOURCE

THERMIDISTAT™

CONTROL

C

HUM

24V COIL NORMALLY OPEN REL AY

90-849

(FIELD SUPPLIED PART# HN61KQ120)

 

 

 

HUMID IFIER

 

 

 

 

 

 

 

 

 

INDOOR

 

 

EQUIPMENT

 

 

 

UNIT

 

 

 

 

 

 

 

 

CONTROLLER

HUMIDIFIER CORD

 

 

A

 

24 VAC

 

PLUGGED INTO

 

 

 

 

 

 

 

 

 

120 VAC POWER SOURCE

 

24 VAC

B

 

LEADS

 

 

 

 

 

 

LEADS

 

 

 

 

 

 

 

 

 

 

 

 

C

WARNING:

HUM

 

 

 

D

 

 

 

 

DO NOT CONNECT

INDOOR

 

 

 

 

FURNACE HUM

 

 

 

 

UNIT

 

90-850

 

C

TERMINAL

DIRECTLY

 

 

 

C

 

 

 

HUM

TO THERMIDISTAT

 

 

 

HUM

TERMINAL

 

24V COIL NORMALLY OPEN REL AY

 

 

 

 

 

 

(FIELD SUPPLIED PART# HN61KQ120)

 

 

 

7310 West Morris St., Indianapolis, IN 46231

TEMPLATE MUST BE LEVEL

©2010 CAC/BDP

 

 

 

 

 

 

 

 

 

 

 

HUMID IFIER

 

HUMIDIFIER CORD

 

PLUGGED INTO

24 VAC

120 VAC POWER SOURCE

 

LEADS

90-851

24V COIL NORMALLY OPEN RELAY (FIELD SUPPLIED PART# HN61K Q120)

INSTALLATION OPTIONS

Typical

Alternate

 

Installation

Installation

 

RETURN

HOT WATER

 

RETURN

 

SUPPLY

SUPPLY

 

90-921

Orientation of Humidifier

to Cooling Coils

BLANKED OFF

END OF COIL

90-922

COOLING COILS IN

WARM AIR PLENUM

Humidifier to be installed as shown in relation to cooling coils.

NOTES

1.The humidifier is not suitable for installation on ducts with horizontal airflow. Performance will be reduced.

2.When installing humidifier on a heat pump system, use hot water. The heated water supplements the reduced supply air temperature as added heat for evaporation.