Carrier SYSTXCCUID01 User Manual

4.5 (2)

SYSTXCCUID01

Infinity Control™

Visit www.carrier.com

Installation and Start-Up Instructions

 

HEAT

HOLD

COOL

 

OFF

Infinity Control™

SYSTXCCUID01

A03149

NOTE: Read the entire instruction manual before starting the

installation.

 

This symbol indicates a change since the last issue.

 

TABLE OF CONTENTS

 

SAFETY CONSIDERATIONS .....................................................

1

INTRODUCTION ..........................................................................

1

INSTALLATION AND START-UP OVERVIEW ......................

1

INSTALLATION ...........................................................................

2

INITIAL POWER-UP....................................................................

5

QUICK START..............................................................................

6

INSTALL / SERVICE MENUS....................................................

7

OPERATIONAL INFORMATION.............................................

11

TROUBLESHOOTING ...............................................................

12

SAFETY CONSIDERATIONS

Read and follow manufacturer instructions carefully. Follow all local electrical codes during installation. All wiring must conform to local and national electrical codes. Improper wiring or installation may damage Infinity Control System. Recognize safety information. This is the safety-alert symbol . When you see this symbol on the equipment and in the instruction manual, be alert to the potential for personal injury. Understand the signal words

DANGER, WARNING, and CAUTION.

These words are used with the safety-alert symbol. DANGER identifies the most serious hazards, which will result in severe personal injury or death. WARNING signifies a hazard, which could result in personal injury or death. CAUTION is used to identify unsafe practices, which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.

INTRODUCTION

The Infinity System consists of intelligent communicating components (User Interface, variable speed furnace or fan coil, AC or HP), which continually communicate with each other via a four-wire connection called the ABCD bus. Conventional 24-volt signals on dedicated wires are not needed. Commands, operating conditions, and other data are passed continually between the components over the ABCD bus. The result is a new level of comfort, versatility, and simplicity.

An Infinity System consists of a Infinity Control™ (thermostat plus much more) and an Infinity furnace or fan coil. All Infinity furnaces or fan coils are variable-speed and multi stage for maximum flexibility, efficiency, and comfort. They support controlled ventilation, humidification, dehumidification, and air quality control. Either an Infinity dual capacity (communicating), or a standard 24 vac controlled outdoor unit may be used.

When using conventional outdoor units, the Infinity furnace or fan coil provides the 24 volt signals needed to control them. Also, the Infinity Network Interface Module (NIM) allows connection of a conventional HRV or ERV without the need for a separate wall control.

All system components are controlled through the wall mounted Infinity Control™, which replaces the conventional thermostat and provides the homeowner with a single wall control for all the features of the system.

INSTALLATION AND START-UP OVERVIEW

This instruction covers installation of the Infinity Control™ only. Physical installation instructions for the indoor, outdoor equipment and accessories are provided with each unit.

Setup, commissioning, operation, and troubleshooting of the Infinity System is covered only in this installation instruction. It is your guide to connecting the system components and commissioning the system once all the physical components are installed. Special screen prompts and start-up capabilities are provided in the Infinity System to simplify and lead you through the initial commissioning of the system. So:

Install the Infinity Control™ according to this instruction.

Install the indoor unit, outdoor unit, and accessories according to their instructions.

Wire the complete system according to this instruction.

Setup, commission, and operate the system according to this instruction to assure yourself a smooth and trouble free start-up.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book

1

4

PC 101

Catalog No. 809-50020

Printed in U.S.A.

Form UID01-1SI

Pg 1

01-04

Replaces: NEW

Tab

misc.

misc.

 

 

 

 

 

 

INSTALLATION

STEP 1 — CHECK EQUIPMENT AND JOB SITE

INSPECT EQUIPMENT — File claim with shipping company, prior to installation, if shipment is damaged or incomplete.

STEP 2 — INFINITY CONTROL™ LOCATION AND WIRING CONSIDERATIONS

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or possible equipment damage.

Disconnect Power before routing control wiring.

All wiring must comply with national, local, and state codes.

INFINITY CONTROL™ LOCATION— The Infinity Control™ is the command center for the Infinity System. It should be located where it is easily accessible and visible to the adult homeowner or end user.

For accurate temperature measurement, the following guidelines should be followed:

The Infinity Control™ should be mounted:

Approximately 5 feet (1.5 meters) from the floor.

Close to or in a frequently used room, preferably on an inside partitioning wall.

On a section of wall without pipes or duct work.

The Infinity Control™ should NOT be mounted:

Close to a window, on an outside wall, or next to a door leading to the outside.

Exposed to direct light or heat from a lamp, sun, fireplace, or other temperature-radiating objects which could cause a false reading.

Close to or in direct airflow from supply registers.

In areas with poor air circulation, such as behind a door or in an alcove.

REMOTE SENSOR OPTION — A remote room sensor can be used with the Infinity Control™ to take the place of the internal temperature sensor. This allows the control to be mounted in areas with less than optimal airflow (such as near an exterior door, window or in a closet). The remote sensor is wired to the terminal block connectors labeled S1 and S2. The Infinity Control™ will automatically detect the remote sensor and ignore its internal sensor. It is also important to note the humidity sensor cannot be remotely located, so do not locate the Infinity Control™ in an area where humidity sensing may not be accurate.

NOTE: S1 & S2 connection on UI back-plate is now used for the Remote Room Sensor, NOT for OAT Sensor hookup (S1 & S2 was previously used for OAT).

WIRING CONSIDERATIONS — Ordinary thermostat wire is recommended. Use 22 AWG or larger for normal wiring applications. Continuous wire lengths over 100 ft. should use 20 AWG or larger.

NOTE: ABCD bus wiring only requires a four-wire connection; however, it is good practice to run thermostat cable having more than four wires in the event of a damaged or broken wire during the installation.

Each device in the Infinity System has a four-pin connector labeled ABCD. It is recommended that the following color code be used when wiring each device:

A — Green = Data A

B — Yellow = Data B

C — White = 24VAC (Com)

D — Red = 24VAC (Hot)

It is not mandatory that the above color code be used, but each ABCD connector in the system MUST be wired consistently.

MOUNTING INFINITY CONTROL™ — There are two options

for mounting the Infinity Control™ to the wall. First, familiarize yourself with all plastic assembly pieces shown in Figs. 2 through 9. The User Interface will snap together with either the Recess Mount or the Surface Mount backplate.

RECESS MOUNT — This provides the thinnest mounting configuration (See Fig. 3). The backplate containing the recessed terminal block can be mounted directly to the wall by cutting a hole 1 ½wide by 2 1/8high. Mark location and cut hole in wall.

NOTE: Always ensure the Infinity Control™ location is acceptable before cutting any holes in wall.

SURFACE MOUNT — This provides surface mounting configuration, which allows use of a small hole in the wall. A surface mount backplate is supplied (See Fig. 4). Attach backplate as shown in figure 7, and the assembly will mount directly to the wall requiring only a small hole in the wall allowing a four wire connection to pass through.

NOTE: Once Infinity Control™ is secured to wall with the backplate assembly (snapped together), care must be taken not to bend or break the interlocking tabs when removing. Gently remove Infinity Control by rocking up/down until interlocking tabs release.

DECORATIVE BACKPLATE — Supplied, is a thin, decorative backplate (see Fig. 5), to hide any marks/screw holes left from the previous thermostat. This decorative backplate (or beauty ring) can be used in either the recess or surface mount installation by snapping it onto the back of the recessed mount backplate or surface mount backplate before securing to the wall. See Fig. 8 and 9 for a larger decorative backplate (5.75wide X 6tall), which can be ordered separately.

A03185

Fig. 2—Infinity Control™

STEP 3 — INSTALLING INFINITY CONTROL™

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Before installing Infinity Control™, turn off all power to equipment. There may be more than one power source to disconnect.

1.Turn off all power to equipment.

2.If an existing thermostat is being replaced:

a.Remove existing thermostat from wall.

b.Disconnect wires from existing thermostat.

2

Carrier SYSTXCCUID01 User Manual

A03186

Fig. 3—Recessed Mount Backplate

A03187

Fig. 4—Surface Mount Backplate

A04017

Fig. 5—Thin Decorative Backplate

c. Discard or recycle old thermostat.

NOTE: Mercury is a hazardous waste and MUST be disposed of properly.

3.Select Infinity Control™ mounting plastic (recess mount or surface mount and decorative backplate if desired).

4.Route wires through large hole in mounting plastic. Level rear plastic against wall (for aesthetic value only - Infinity Control™ need not be level to operate properly) and mark wall through two mounting holes.

5.Drill two 3/16 inch mounting holes in wall where marked.

6.Secure mounting plastic to wall using two screws and anchors provided.

7.Adjust length and routing of each wire to reach each wire entry on the connector backplate. Strip ¼ inch of insulation from each wire.

Recessed terminal block in wall 11/2˝ wide by 2 1/8˝ high

Recessed Mount

Interlocking Tabs (4)

A03190

Fig. 6—Recessed Mount Assembly

Surface Mount

Backplate to wall

Interlocking Tabs (4)

A03191

Fig. 7—Surface Mount Assembly

A03188

Fig. 8—Large Decorative Backplate

8.Match and connect thermostat wires to proper terminals on User Interface backplate. See wiring diagram figures 12, 13 and 14.

A — Green = Data A

B — Yellow = Data B

C — White = 24VAC (Com)

D — Red = 24VAC (Hot)

NOTE: It is not mandatory that the above color code be used, but each ABCD connection in the system MUST be wired consistently. A separate ABCD Connector comes inside packaging and should be used when connecting to the furnace (or fan coil). (See Fig. 10)

NOTE: Insert connector properly into circuit board.

3

A03192

Fig. 9—Decorative Backplate Assembly

A B C D

A03193

Fig. 10—4–Wire ABCD Connector

ELECTRICAL OPERATION HAZARD

Failure to follow this caution will result in equipment damage or improper operation.

Improper wiring of the ABCD connector will cause the Infinity Control™ to operate improperly. Check to make sure all wiring is correct before proceeding with installation or turning on power.

9.Push any excess wire into the wall. Seal hole in wall to prevent any air leaks. Leaks can affect operation.

10.Attach Infinity Control™ to the mounting plastic by lining up the plastic guides on the back of the control with the opening on the mounting plastic and push on.

11.Perform installation of all other system equipment (i.e. humidifier, ventilator, UV lights, etc.)

12.Turn on power to equipment.

EQUIPMENT WIRING DIAGRAMS:

See wiring diagram Figs. 12, 13 and 14.

NOTE: For other applications not listed, refer to the Network Interface Module (NIM) Installation Instructions.

See wiring diagram figure 12 for a Typical Four-Wire Connection Diagram, which includes an Infinity indoor communicating furnace or FE fan coil with a 2-speed Puron® communicating outdoor unit. No additional OAT (outdoor air temperature) sensor is required because the Infinity Control will use the temperature sensor inside the 2-speed unit.

See wiring diagram figure 13 for a Typical Connection Diagram, which includes an Infinity indoor communicating furnace or FE fan coil, with a 1-speed air conditioning unit (non-communicating outdoor). An Outdoor Air Temperature sensor may be installed (not required) at the indoor furnace or fan coil OAT terminals. When OAT is applied, the Infinity System will provide full system features and benefits.

See wiring diagram Fig. 14 for a Typical Connection Diagram for FE fan coil with a 1-speed heat pump (using non-communicating outdoor unit). When OAT is applied, the Infinity System will provide full system features and benenfits.

Humidity/OAT

Fan Button

Button

 

Display Screen (LCD)

Left-Side

Button

Time (+/-)

Button

Hold

Button

Schedule & Vacation

Program Buttons

Up/Down

Scroll Buttons

HOLD

SCROLL

SCHEDULE VACATION

PROGRAM

Schedule

Vacation

to program

to start/end

temperature

vacation

schedule

 

Scroll up & down

 

 

Right-Side

 

 

Button

 

HEAT

Heat Button

 

 

 

COOL

Cool Button

 

 

Temperature

 

 

(+/-) Button

 

 

System

BASIC

ADVANCED

On/Off Button

 

 

Basic & Advanced

SETUPS

Setup Buttons

Basic

Advanced

Flip Down

to set time,

for all other

humidity

settings

Door

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A03194

 

 

 

 

 

 

Fig. 11—Functional Overview

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Variable-Speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Furnace/ Fan Coil

 

 

User Interface

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2-Spd. AC or HP

 

 

 

 

 

 

 

 

 

 

 

 

Green

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Green

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

Yellow

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yellow

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

White

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

White

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

Red

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Red

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S1

 

 

 

 

 

Optional Remote

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Room Sensor

 

 

 

 

 

 

 

 

 

 

 

 

ABCD

 

 

 

S2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Humidifier

 

HUM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connections

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OAT

 

 

 

 

 

Sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Optional)

 

 

Fig. 12—Universal Four-Wire Connection Diagram

A03146

HUMIDIFIER CONNECTION — A 24vac bypass or fan powered humidifier may be installed.

NOTE: Do Not Use a traditional humidistat to control humidifier operation. If a humidifier is installed, let the Infinity System control humidifier operation.

Bypass Humidifiers — A bypass humidifier should be wired directly to the furnace or fan coil HUM and 24vac COM terminals. The Infinity Control will automatically energize the HUM output during a call for humidification.

Fan Powered Humidifiers — Most fan powered humidifiers produce internal 24vac in order to energize upon a switch or contact closure. For this application, a 24vac N.O. Isolation Relay (DPST) MUST be used to prevent mixing the internal humidifier power with the indoor equipment transformer. Applying 24vac isolation relay coil to furnace or fan coil HUM and COM terminals will allow the Infinity Control to automatically energize the HUM output during a call for humidification. The N.O. relay contacts will be used to energize the humidifier. See fan powered humidifier installation instructions for more details.

4