Carrier 48-50HJ004-014 User Manual

0 (0)

COBRA™ Energy Recovery Units 48/50HJ004-014 with 62AQ060-300 Single-Package Rooftop Units with Energy Recovery Capability

Installation, Start-Up,

and Service Supplement

IMPORTANT: This is a supplemental instruction for the 48/50HJ and the 62AQ Installation, Start-Up and Service Instructions. It is not intended to take the place of either instruction or to be a complete piece in itself.

CONTENTS

Page

SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1

GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-29

Step 1 — Inspect Shipment . . . . . . . . . . . . . . . . . . . . . . 2

Step 2 — Provide Unit Support . . . . . . . . . . . . . . . . . . . 2

• ROOF CURB

Step 3 — Field Fabricate Ductwork . . . . . . . . . . . . . . . 3

Step 4 — Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . 6

POSITIONING

Step 5 — Install Flue Hood (48HJ Only) . . . . . . . . . 11 Step 6 — Install Gas Piping (48HJ Only). . . . . . . . . 11

Step 7 — Install External Trap for Condensate Drain. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Step 8 — Make Electrical Connections . . . . . . . . . . 11

FIELD POWER SUPPLY

FACTORY-SUPPLIED NON-FUSED DISCONNECT

FIELD CONTROL WIRING

HEAT ANTICIPATOR SETTINGS

Step 9 — Assemble and Mount

Supply-Air Hood . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Step 10 — Mount the Barometric Relief Damper . . 28

Step 11 — Set the Outdoor Cooling and

Heating Thermostats. . . . . . . . . . . . . . . . . . . . . . . . . . 29

LIGHT COMMERCIAL THERMIDISTAT

ACCESSORY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30-34

General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Dehumidification Equipment and Connections . . . 30

Step 1 — Select Light Commercial

Thermidistat Location . . . . . . . . . . . . . . . . . . . . . . . . . 30

Step 2 — Set DIP Switches. . . . . . . . . . . . . . . . . . . . . . . 30

Step 3 — Install Light Commercial Thermidistat . . 31

Step 4 — Set Light Commercial Thermidistat

Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

Step 5 — Conduct Light Commercial

Thermidistat Start-Up and Checkout . . . . . . . . . . . 33

Step 6 — Make Final Settings . . . . . . . . . . . . . . . . . . . . 34

OPERATIONAL INFORMATION . . . . . . . . . . . . . . . . . . 34

PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35-37

TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . 38-41

ROOFTOP UNIT AND ENERGY$RECYCLER2

START-UP CHECKLIST . . . . . . . . . . . . . . . . CL-1, CL-2

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.

Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that apply.

Verify that the power source supplied to the unit matches the voltages and amperages listed on the unit rating plate.

Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations.

Disconnect gas piping from unit when leak testing at pressure greater than 1/2 psig. Pressures greater than 1/2 psig will cause gas valve damage resulting in hazardous condition. If gas valve is subjected to pressure greater than 1/2 psig, it must be replaced before use. When pressure testing fieldsupplied gas piping at pressures of 1/2 psig or less, a unit connected to such piping must be isolated by manually closing the gas valve.

Before performing service or maintenance operations on unit, turn off main power switch to unit and install a lockout tag. Electrical shock could cause personal injury.

GENERAL

Carrier’s factory-installed optional COBRA Energy Recovery units precondition ventilation air for the rooftop unit during winter and summer operation and recover energy from the building exhaust air. These units are designed to satisfy the higher ventilation requirements and other building codes while minimizing energy costs.

Factory installation of the energy recovery section provides the benefit of reduced field-installation time, single point power connections, and the assurance of a factory test for the complete COBRA Energy Recovery unit. The energy recovery section requires less maintenance than other energy recovery systems and can be serviced by any qualified refrigeration technician.

NOTE: Because of the location of the energy recovery section, the unit nameplate has been moved to the opposite end of the rooftop section, on the upper, right-hand part of the panel.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book

1

1

4

4

PC 111 Catalog No. 534-80122

Printed in U.S.A.

Form 48/50HJ,62AQ-2SIS

Pg 1

9-02

Replaces: 48/50HJ,62AQ-1SIS

Tab

1a

1b

6a

6b

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INSTALLATION

Step 1 — Inspect Shipment — File a claim with the shipping company if shipment is incomplete or damaged. See Fig. 1 for a typical shipping packaging for a COBRA™ energy recovery unit.

Step 2 — Provide Unit Support

ROOF CURB — The COBRA energy recovery unit can use a full-perimeter roof curb or a standard roof curb for the rooftop section of the unit with a supplemental equipment support for the

energy recovery section. The supplemental equipment support is not required. The standard rooftop unit roof curb is capable of supporting both the rooftop unit section and the energy recovery section. Assemble and install accessory roof curb in accordance with instructions shipped with curb. See Fig. 2A-4. Install insulation, cant strips, roofing felt, and counter flashing as shown.

Ductwork must be attached to curb, not to the unit. The accessory thru-the-bottom power and gas connection package must be installed before the unit is set on the roof curb.

Fig. 1 — Shipping Packaging (48/50HJ004-006 Shown)

 

Deck pans

 

 

37 3/16"

2" Return support.

 

Only used on some

 

67 3/8"

 

applications.

DUCT OPENING SIZES

3 1/4

 

Supply = 13 7/8" x 20 1/4"

R 1

 

 

Deck pans

R1 = 13 5/8" x 17 3/4"

 

 

R2

R2 = 13 5/8" x 12 5/16"

14”

 

 

Supply

 

 

 

14"

R1 = Return from building to HVAC

2"

 

R2 = Return from building to 62AQ

92 1/2"

 

 

37 3/16"

 

 

SIDE VIEW

END VIEW

Fig. 2A — COBRA Energy Recovery Unit Full-Perimeter Roof Curb — 48/50HJ004-007 with 62AQ060,100

2

 

Deck pans

 

 

49 15/16"

2" Return support.

 

Only used on some

 

 

 

78 1/4"

applications.

DUCT OPENING SIZES

3 1/4

 

Supply = 15 11/16" x 31 3/8"

R1

 

 

Deck pans

R1 = 15 5/16" x 29 1/16"

 

14"

R 2

R2 = 15 5/16" x 9"

 

 

Supply

 

 

 

14"

R1 = Return from building to HVAC

2"

 

110 11/16"

 

 

 

R2 = Return from building to 62AQ

 

49 15/16"

 

 

SIDE VIEW

END VIEW

Fig. 2B — COBRA™ Energy Recovery Unit Full-Perimeter Roof Curb — 48/50HJ008-014 with 62AQ200,300

If electric control power or gas service is to be routed through the basepan, a field-installed accessory thru-the- bottom connection must be used. Attach the accessory to the basepan per the information in the accessory installation instructions. Thru-the-bottom connections must be installed before unit is set on roof.

If the combined unit roof curb is not being used, additional support may be desired under the energy recovery section of the unit. An accessory support and pad for the energy recovery section can be used. See Fig. 4. Place the protective rubber pad on the roof so that the edge near the unit is located about 6-in. from the end of the energy recovery section. Measure the distance from the bottom of energy recovery rails to the pad. Adjust the energy recovery equipment support to match the measured distance and screw into place with the 4 screws provided. See Fig. 4. Place the support underneath the energy recovery unit and on the protective rubber pad. This is done by lifting the end of the energy recovery section slightly above level and then sliding the support underneath the rails.

IMPORTANT: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket supplied with the roof curb as shown in Fig. 3A and 3B. Improperly applied gasket can result in air leaks and poor unit performance.

Curb should be level. This is necessary for unit condensate drain to function properly. Refer to Accessory Roof Curb Installation Instructions for additional information as required.

Step 3 — Field Fabricate Ductwork — Secure all ducts to roof curb and building structure. Do not connect ductwork to unit. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes. See Fig. 5A and 5B for duct dimensions.

Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier. If a plenum return is used, the return should be ducted through the roof deck to comply with applicable fire codes.

A minimum clearance is not required around ductwork.

These units are designed for a minimum continuous heating return-air temperature of 50 F (dry bulb), or an intermittent operation down to 45 F (dry bulb), such as when used with a night set-back thermostat. To operate at lower return-air temperatures, a field-supplied outdoor-air temperature control must be used to initiate both stages of heat when the temperature is below 45 F. Indoor comfort may be compromised when these lower air temperatures are used with insufficient heating temperature rise.

3

CONNECTOR

 

 

 

B

 

 

C

 

 

D ALT

 

 

GAS

 

 

 

 

POWER

CONTROL

 

PKG. ACCY.

 

 

 

 

 

DRAIN HOLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CRBTMPWR001A00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3/4

 

3/4″ [19] NPT

1/2

CRBTMPWR002A00

 

1′-911/16

 

1′-4″

 

 

 

13/4

[19] NPT

 

 

11/4″ [31.7]

[12.7]

 

CRBTMPWR003A00

 

 

 

 

 

1

/2

 

3/4″ [19] NPT

 

 

 

 

 

 

[551]

 

 

[406]

[44.5]

 

 

 

 

 

 

 

 

1/2

 

 

 

 

 

 

 

 

 

 

 

 

 

[12.7] NPT

 

 

 

 

 

 

 

 

 

 

 

 

 

CRBTMPWR004A00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

/4

 

 

11/4″ [31.7]

[12.7]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[19] NPT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ROOF CURB

A

UNIT SIZE

ACCESSORY

 

 

CRRFCURB001A00

1′-2″

 

[356]

48/50HJ

 

CRRFCURB002A00

2′-0″

004-007

[610]

 

 

 

NOTES:

1.Roof curb accessory is shipped disassembled.

2.Insulated panels.

3. Dimensions in [ ] are in millimeters.

4.Roof curb: galvanized steel.

5.Attach ductwork to curb (flanges of duct rest on curb).

6.Service clearance: 4 ft on each side.

7. Direction of airflow.

8.Connector packages CRBTMPWR001A00 and 002A00 are for thru-the-curb type gas. Packages CRBTMPWR003A00 and 004A00 are for thru-the- bottom type gas connections.

TO ENSURE AIRTIGHT CONNECTION.

PLACE UNIT AS CLOSE TO THIS

END AS POSSIBLE

TO ENSURE AIRTIGHT CONNECTION.

PLACE UNIT AS CLOSE TO THIS

END AS POSSIBLE

Fig. 3A — Roof Curb Details (48/50HJ004-007 Section Only)

4

CONNECTOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D ALT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

 

 

 

C

 

 

DRAIN

 

 

 

GAS

POWER

 

 

 

CONTROL

PKG. ACCY.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HOLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CRBTMPWR001A00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3/4

3/4″ [19] NPT

 

 

 

 

 

1/2

CRBTMPWR002A00

 

 

2′-87/16

 

1′-1015/16

 

 

 

 

13/4

 

[19] NPT

11/4″ [31.7]

 

 

 

[12.7] NPT

CRBTMPWR003A00

 

 

 

 

 

 

 

1

/2

3/4″ [19] NPT

 

 

 

 

 

 

 

 

 

 

 

[827]

 

 

 

 

[583]

 

 

 

[44.5]

 

 

 

 

 

 

 

 

 

 

 

1/2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[12.7] NPT

 

 

 

 

 

 

 

 

 

 

 

 

CRBTMPWR004A00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

/4

11/4″ [31.7]

 

 

 

[12.7] NPT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[19] NPT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ROOF CURB

“A”

UNIT SIZE

ACCESSORY

48/50HJ

 

CRRFCURB003A00

1′-2″ [356]

008-014

CRRFCURB004A00

2′-0″ [610]

 

NOTES:

1.Roof curb accessory is shipped disassembled.

2.Insulated panels: 1-in. thick polyurethane foam,

13/4 lb density.

3. Dimensions in [ ] are in millimeters.

4.Roof curb: 16-gage steel.

5.Attach ductwork to curb (flanges of duct rest on curb).

6.Service clearance 4 ft on each side.

7. Direction of airflow.

8.Connector packages CRBTMPWR001A00 and 2A00 are for thru-the-curb gas type. Packages CRBTMPWR003A00 and 4A00 are for thru- the-bottom type gas connections.

TO ENSURE AN AIRTIGHT CONNECTION,

PLACE UNIT ON CURB AS CLOSE TO

DUCT END AS POSSIBLE.

TO ENSURE AN AIRTIGHT CONNECTION,

PLACE UNIT ON CURB AS CLOSE TO

DUCT END AS POSSIBLE.

Fig. 3B — Roof Curb Details (48/50HJ008-014 Section Only)

5

 

UNIT SIZE

EQUIPMENT SUPPORT

DIMENSIONS (in.)

 

4”

PART NUMBER

A

B

C

 

 

 

3-6 Ton

CRAQSUPT001A00

36.9

40

8 to 14

 

 

A

CRAQSUPT002A00

36.9

40

14 to 24

 

 

 

 

 

CRAQSUPT003A00

49.7

54

8 to 14

 

71/2-121/2

Ton

CRAQSUPT004A00

49.7

54

14 to 24

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ENERGY

HVAC UNIT

 

 

RECOVERY

 

C”

 

SECTION

 

 

 

 

 

SCREW

 

 

 

SUPPORT

 

 

 

IN PLACE

PAD

 

 

ADJUSTABLE

CURB

 

 

 

EQUIPMENT

 

 

ROOF

 

 

SUPPORT

 

 

 

 

10” x B (SEE CHART) PROTECTIVE RUBBER PAD (EPDM)

Fig. 4 — Supplemental Energy Recovery Section Equipment Support

Step 4 — Rig and Place Unit — Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit. Rollers may be used to move unit across a roof. Remove the bottom wooden skids that are under the unit by removing the wooden plates that hold the bottom wooden frame to the unit. Level by using unit frame as a reference. Lifting holes are provided in base rails as shown in Fig. 6A and 6B. Refer to rigging instructions on unit.

All panels must be in place when rigging.

POSITIONING — Maintain clearance around and above unit to provide minimum distance from combustible materials, proper airflow, and service access. A properly positioned unit will have the following clearances between unit and roof curb: 1/4-in. clearance between roof curb and base rails on each side and duct end of unit; 1/4-in. clearance between roof curb and condenser coil end of unit.

Do not install unit in an indoor location. Do not locate unit air inlets near exhaust vents or other sources of contaminated air.

Be sure that unit is installed such that snow will not block the combustion intake or flue outlet.

Unit may be installed directly on wood flooring or on Class A, B, or C roof-covering material when roof curb is used.

Although unit is weatherproof, guard against water from higher level runoff and overhangs.

Flue vent discharge must have a minimum horizontal clearance of 4 ft from electric and gas meters, gas regulators, and gas relief equipment.

Minimum distance between unit and other electrically live parts is 48 inches.

Flue gas can deteriorate building materials. Orient unit such that flue gas will not affect building materials. Locate mechanical draft system flue assembly at least 48 in. from an adjacent building or combustible material.

Adequate combustionand ventilation-air space must be provided for proper operation of this equipment. Be sure that installation complies with all local codes and Section 5.3, Air for Combustion and Ventilation, NFGC (National Fuel Gas Code), and ANSI (American National Standards Institute) Z223.1, and NFPA (National Fire Protection Association) 54 TIA-54-84-1. In Canada, installation must be in accordance with the CAN1-B149 installation codes for gas burning appliances.

After unit is in position, remove rigging skids and shipping materials.

6

REAR

 

RIGHT

LEFT

SIDE

SIDE

 

7

FRONT

RIGHT SIDE

LEFT SIDE

FRONT

Fig. 5A — Base Unit Dimensions — COBRA™ Energy Recovery Unit — 48/50HJ004-007 with 62AQ060,100

Carrier 48-50HJ004-014 User Manual

8

Fig. 5A — Base Unit Dimensions — COBRA™ Energy Recovery Unit — 48/50HJ004-007 with 62AQ060,100 (cont)

9

Fig. 5B — Base Unit Dimensions — COBRA™ Energy Recovery Unit — 48/50HJ008-014 with 62AQ200,300

10

Fig. 5B — Base Unit Dimensions — COBRA™ Energy Recovery Unit — 48/50HJ008-014 with 62AQ200,300 (cont)

 

 

MAX WEIGHT

 

A

 

B

 

 

C

 

 

lb

kg

in.

mm

in

 

mm

in.

 

mm

48HJ004 w/62AQ060

890

404

95.6

2428.20

57.38

 

1457.30

33.35

 

847

48HJ004 w/62AQ100

905

411

95.6

2428.20

57.38

 

1457.30

33.35

 

847

48HJ005 w/62AQ060

900

409

95.6

2428.20

57.38

 

1457.30

33.35

 

847

48HJ005 w/62AQ100

915

415

95.6

2428.20

57.38

 

1457.30

33.35

 

847

48HJ006 w/62AQ060

920

418

95.6

2428.20

57.38

 

1457.30

33.35

 

847

48HJ006 w/62AQ100

935

425

95.6

2428.20

57.38

 

1457.30

33.35

 

847

48HJ007 w/62AQ060

995

452

95.6

2428.20

57.38

 

1457.30

42.12

 

1070

48HJ007 w/62AQ100

1010

459

95.6

2428.20

57.38

 

1457.30

42.12

 

1070

50HJ004 w/62AQ060

795

361

95.6

2428.20

57.38

 

1457.30

33.35

 

847

50HJ004 w/62AQ100

810

368

95.6

2428.20

57.38

 

1457.30

33.35

 

847

50HJ005 w/62AQ060

805

365

95.6

2428.20

57.38

 

1457.30

33.35

 

847

50HJ005 w/62AQ100

820

372

95.6

2428.20

57.38

 

1457.30

33.35

 

847

50HJ006 w/62AQ060

825

375

95.6

2428.20

57.38

 

1457.30

33.35

 

847

50HJ006 w/62AQ100

840

381

95.6

2428.20

57.38

 

1457.30

33.35

 

847

50HJ007 w/62AQ060

880

400

95.6

2428.20

57.38

 

1457.30

42.12

 

1070

50HJ007 w/62AQ100

895

407

95.6

2428.20

57.38

 

1457.30

42.12

 

1070

Fig. 6A — Rigging Label — COBRA™ Energy Recovery Unit — Sizes 48/50HJ004-007

Step 5 — Install Flue Hood (48HJ Rooftop Sections Only) — Refer to the 48HJ installation instructions for information on installing the flue hood.

Step 6 — Install Gas Piping (48HJ Rooftop Sections Only) — Refer to the 48HJ installation instructions for information on installing the gas piping.

Step 7 — Install External Trap For Condensate Drain — The condensate from the rooftop unit along with condensate from the upper coil of the energy recovery section is internally piped to the condensate pan in the lower section of the energy recovery section. For this reason, the bottom drain on the rooftop unit CANNOT be used for a condensate drain. The 3/4-in. drain connection on the energy recovery section is located near the bottom left of the exhaust air section. See Fig. 5A and 5B. The energy recovery section must have a field-fabricated, external, P-trap installed for condensate drainage. Trap must be at least 4-in. deep to protect against freezeup. If the drain line is installed downstream from the external

trap, pitch the line away from the unit at 1-in. per 10-ft of run. Do not use a pipe smaller than the connection (3/4-in.).

Step 8 — Make Electrical Connections

Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code), ANSI/NFPA, latest edition, and local electrical codes. Do not use gas piping as an electrical ground. Failure to follow this warning could result in the installer being liable for personal injury of others.

FIELD POWER SUPPLY — All units except 208/230-v units are factory wired for the voltage shown on the nameplate.

11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAX WEIGHT

 

 

 

 

 

A

 

 

 

B

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

lb

 

 

kg

 

 

in.

 

 

 

 

 

mm

 

in.

 

mm

in.

mm

48HJ008 w/62AQ200

1310

 

595

77.42

1966.5

66.50

1689.10

42.12

1070

48HJ008 w/62AQ300

1355

 

616

77.42

1966.5

66.50

1689.10

42.12

1070

48HJ009 w/62AQ200

1315

 

597

77.42

1966.5

66.50

1689.10

42.12

1070

48HJ009 w/62AQ300

1360

 

618

77.42

1966.5

66.50

1689.10

42.12

1070

48HJ012 w/62AQ200

1400

 

636

77.42

1966.5

66.50

1689.10

50.12

1273

48HJ012 w/62AQ300

1445

 

657

77.42

1966.5

66.50

1689.10

50.12

1273

48HJ014 w/62AQ200

1440

 

655

77.42

1966.5

66.50

1689.10

50.12

1273

48HJ014 w/62AQ300

1485

 

675

77.42

1966.5

66.50

1689.10

50.12

1273

50HJ008 w/62AQ200

1240

 

564

77.42

1966.5

66.50

1689.10

42.12

1070

50HJ008 w/62AQ300

1285

 

584

77.42

1966.5

66.50

1689.10

42.12

1070

50HJ009 w/62AQ200

1245

 

566

77.42

1966.5

66.50

1689.10

42.12

1070

50HJ009 w/62AQ300

1290

 

586

77.42

1966.5

66.50

1689.10

42.12

1070

50HJ012 w/62AQ200

1325

 

602

77.42

1966.5

66.50

1689.10

42.12

1070

50HJ012 w/62AQ300

1370

 

623

77.42

1966.5

66.50

1689.10

42.12

1070

50HJ014 w/62AQ200

1345

 

620

77.42

1966.5

66.50

1689.10

42.12

1070

50HJ014 w/62AQ300

1410

 

641

77.42

1966.5

66.50

1689.10

42.12

1070

Fig. 6B — Rigging Label — COBRA™ Energy Recovery Unit — Sizes 48/50HJ008-014

If the 208/230-v unit is to be connected to a 208-v power supply, the transformer must be rewired by moving the black wire with the 1/4-in. female space connector from the 230-volt connection and moving to the 200-volt 1/4-in. male terminal on the primary side of the transformer.

Refer to unit label diagram for additional information. Pigtails are provided for field wire connections. Use factorysupplied splices or UL (Underwriters’ Laboratories) approved copper/aluminum connector.

When installing units, provide a disconnect per the NEC.

All field wiring must comply with NEC and local requirements.

Install field wiring as follows:

1.Install conduit through side panel openings. Install conduit between disconnect and control box.

2.Install power lines to terminal connections as shown in Fig. 7.

Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate (see Tables 1A-1H). On 3-phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in the legend for Tables 1A-1H, Note 2 to determine the percent of voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and

may cause damage to electrical components. Such operation would invalidate any applicable Carrier warranty.

FACTORY-SUPPLIED NON-FUSED DISCONNECT — The factory-supplied disconnect is capable of handling disconnect amps up to 80 A for a COBRA Energy Recovery unit. For disconnect amps greater than 80 A, a field-supplied disconnect is required.

FIELD CONTROL WIRING — Install a Carrier-approved accessory thermidistat assembly according to installation instructions included with the accessory. Locate thermidistat assembly on a solid wall in the conditioned space to sense average temperature in accordance with thermidistat installation instructions on page 30. Connect thermidistat wires to terminal board.

Route thermidistat cable or equivalent single leads of colored wire from subbase terminals through connector on unit to low-voltage connections (shown in Fig. 8). Thermidistat control wiring is routed to both the rooftop unit control box and the energy recovery section control box.

If a PremierLink™ control is used, a thermidistat does not need to be used. A humidistat and a separate room air sensor are used. Two extra terminal blocks (TB2 and TB3) are provided in the control box for all units with PremierLink controls. No wiring should be directly connected to the PremierLink control. Wire sensors to TB2 or TB3. Humidistat is wired to TB1 and energy recovery section control box.

12

NOTE: For wire runs up 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.

Pass the control wires through the hole provided in the corner post; then feed wires through the raceway built into the corner post to the 24-v barrier located on the left side of the

control box. See Fig. 10. The raceway provides the UL required clearance between highand low-voltage wiring.

NOTE: A humidistat and a temperature sensor can be used in place of a thermidistat for PremierLink™ units.

HEAT ANTICIPATOR SETTINGS — Set heat anticipator settings at .14 amp for the first stage and .14 amp for secondstage heating, when available.

Table 1A — Electrical Data (COBRA™ Energy Recovery 48HJ004-007 Units with 62AQ060)

 

NOMINAL

IFM

CONV

62AQ

POWER SUPPLY

DISCONNECT SIZE*

UNIT

V-PH-Hz

TYPE

OUTLET

FLA

MCA

FUSE OR

FLA

LRA

 

HACR BKR

 

 

 

 

 

 

 

 

 

208/230-1-60

STD

NO

9.2

34.8/34.8

40/40

35/35

135/135

 

STD

YES

9.2

40.8/40.8

45/45

41/41

140/140

 

 

 

 

STD

NO

9.2

27.7/27.7

35/35

29/29

124/124

 

208/230-3-60

STD

YES

9.2

33.7/33.7

40/35

34/34

129/129

 

HIGH STATIC

NO

9.2

28.6/28.6

35/35

30/30

154/154

48HJ004

 

 

HIGH STATIC

YES

9.2

34.6/34.6

40/40

35/35

158/158

 

 

 

 

STD

NO

9.2

13.6

20

14

63

 

460-3-60

STD

YES

9.2

16.3

20

20

67

 

 

HIGH STATIC

NO

9.2

14.0

20

15

77

 

 

HIGH STATIC

YES

9.2

16.7

20

20

82

 

208/230-1-60

STD

NO

9.2

44.4/44.4

60/60

44/44

173/173

 

STD

YES

9.2

50.4/50.4

60/60

50/50

178/178

 

 

 

 

STD

NO

9.2

31.7/31.7

40/40

33/33

140/140

 

208/230-3-60

STD

YES

9.2

37.7/37.7

40/40

38/38

145/145

48HJ005

 

HIGH STATIC

NO

9.2

32.6/32.6

40/40

34/34

170/170

 

HIGH STATIC

YES

9.2

38.6/38.6

45/45

39/39

174/174

 

 

 

 

STD

NO

9.2

15.2

20

16

70

 

460-3-60

STD

YES

9.2

17.9

20

21

75

 

HIGH STATIC

NO

9.2

15.6

20

16

84

 

 

 

 

HIGH STATIC

YES

9.2

18.3

20

22

89

 

208/230-1-60

STD

NO

9.2

55.5/55.5

70/70

56/56

250/250

 

STD

YES

9.2

61.5/61.5

70/70

61/61

255/255

 

 

 

 

STD

NO

9.2

38.1/38.1

45/45

39/39

202/202

 

208/230-3-60

STD

YES

9.2

44.1/44.1

50/50

44/44

207/207

 

HIGH STATIC

NO

9.2

39.8/39.8

45/45

41/41

221/221

48HJ006

 

 

HIGH STATIC

YES

9.2

45.8/45.8

50/50

46/46

226/226

 

 

 

 

STD

NO

9.2

19.3

25

20

101

 

460-3-60

STD

YES

9.2

22.0

25

25

106

 

HIGH STATIC

NO

9.2

20.1

25

20

110

 

 

 

 

HIGH STATIC

YES

9.2

22.8

25

26

115

 

208/230-3-60

STD

NO

9.2

42.0/42.0

50/50

42/42

234/234

 

STD

YES

9.2

48.0/48.0

60/60

48/48

239/239

 

 

 

208/230-3-60

HIGH STATIC

NO

9.2

43.7/43.7

50/50

44/44

253/253

 

HIGH STATIC

YES

9.2

49.7/49.7

60/60

50/50

258/258

48HJ007

 

 

STD

NO

9.2

19.8

25

20

114

 

 

 

460-3-60

STD

YES

9.2

22.5

25

26

118

 

HIGH STATIC

NO

9.2

20.6

25

21

123

 

 

 

 

HIGH STATIC

YES

9.2

23.3

30

26

128

 

LEGEND

FLA

Full Load Amps

HACR

Heating, Air Conditioning and Refrigeration

IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection

NEC

National Electrical Code

UL

Underwriters’ Laboratories

*Used to determine minimum disconnect per NEC.

†Single point box CRSINGLE017A00 is part of base unit.

NOTES:

1.In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. UL, Canada units may be fuse or circuit breaker.

2.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance.

= 100 x

max voltage deviation from average voltage

average voltage

Example: Supply voltage is 460-3-60.

AB = 452 v

BC = 464 v

AC = 455 v

Average Voltage =

452 + 464 + 455

3

=

1371

3

= 457

Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v

(BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

7 % Voltage Imbalance = 100 x 457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

13

Table 1B — Electrical Data (COBRA™ Energy Recovery 50HJ004-007 Units with 62AQ060)

 

 

 

 

 

HEATER

HEAT

 

POWER SUPPLY

 

 

SINGLE

DISCONNECT SIZE*

UNIT

NOMINAL

IFM

CONV

62AQ

CRHEATER

 

 

 

FUSE OR

 

 

POINT BOX

 

 

 

V-PH-Hz

TYPE

OUTLET

FLA

FLA

MCA

MOCP

CRSINGLE

FLA

LRA

 

---A00

HACR BKR

 

 

 

 

 

 

 

 

 

 

---A00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NONE

—/—

34.8/ 34.8

40/40

 

35/ 35

135/135

 

 

 

 

 

001

15.9/18.3

35.7/

38.8

40/45

 

35/

37

135/135

 

 

STD

NO

9.2

002

23.5/27.1

45.2/

49.7

50/50

 

43/

47

135/135

 

 

003

31.4/36.3

55.1/

61.2

60/

70

004

52/

58

135/135

 

 

 

 

 

 

 

 

 

 

004

37.9/43.8

63.2/

70.5

70/

80

004

60/

67

135/135

 

208/230-1-60

 

 

 

002+002

46.9/54.2

74.5/

83.6

80/

90

005

70/

79

135/135

 

 

 

 

NONE

—/—

40.8/ 40.8

45/45

 

41/ 41

140/140

 

 

 

 

 

 

 

 

 

 

 

001

15.9/18.3

40.8/

43.0

45/50

 

41/

42

140/140

 

 

STD

YES

9.2

002

23.5/27.1

50.0/

53.9

60/60

 

49/

52

140/140

 

 

003

31.4/36.3

59.9/

65.4

60/

70

004

58/

63

140/140

 

 

 

 

 

 

 

 

 

 

004

37.9/43.8

68.0/

74.7

70/

80

005

65/

71

140/140

 

 

 

 

 

002+002

46.9/54.2

79.3/

87.8

80/

90

005

76/

83

140/140

 

 

 

 

 

NONE

—/—

27.7/ 27.7

35/35

 

29/ 29

124/124

 

 

 

 

 

001

9.2/10.6

27.7/

29.1

35/35

 

29/

29

124/124

 

 

STD

NO

9.2

002

13.6/15.6

32.8/

35.4

40/40

 

32/

34

124/124

 

 

003

18.1/20.9

38.5/

42.0

45/45

 

37/

40

124/124

 

 

 

 

 

 

 

 

 

 

 

004

21.9/25.3

43.2/

47.4

45/50

 

41/

45

124/124

 

 

 

 

 

005

33.4/38.5

57.5/

64.0

60/

70

002

55/

60

124/124

 

 

 

 

 

NONE

—/—

33.7/ 33.7

40/35

 

34/ 34

129/129

 

 

 

 

 

001

9.2/10.6

33.7/

33.7

40/40

 

34/

34

129/129

 

 

STD

YES

9.2

002

13.6/15.6

37.6/

39.6

45/45

 

37/

39

129/129

 

 

003

18.1/20.9

43.3/

46.2

50/50

 

43/

45

129/129

 

 

 

 

 

 

 

 

 

 

 

004

21.9/25.3

48.0/

51.6

50/60

 

47/

50

129/129

 

208/230-3-60

 

 

 

005

33.4/38.5

62.3/

68.2

70/

70

002

60/

65

129/129

 

 

 

 

NONE

—/—

28.6/ 28.6

35/35

 

30/ 30

154/154

 

 

 

 

 

 

 

 

 

 

 

001

9.2/10.6

28.6/

30.0

35/35

 

30/

30

154/154

 

 

HIGH STATIC

NO

9.2

002

13.6/15.6

33.7/

36.3

40/40

 

33/

35

154/154

 

 

003

18.1/20.9

39.4/

42.9

45/45

 

38/

41

154/154

50HJ004

 

 

 

 

 

 

 

 

 

004

21.9/25.3

44.1/

48.3

50/50

 

42/

46

154/154

 

 

 

 

 

005

33.4/38.5

58.4/

64.9

60/

70

002

56/

62

154/154

 

 

 

 

 

NONE

—/—

34.6/ 34.6

40/40

 

35/ 35

158/158

 

 

 

 

 

001

9.2/10.6

34.6/

34.6

40/40

 

35/

35

158/158

 

 

HIGH STATIC

YES

9.2

002

13.6/15.6

38.5/

40.5

45/45

 

38/

40

158/158

 

 

003

18.1/20.9

44.2/

47.1

50/50

 

44/

46

158/158

 

 

 

 

 

 

 

 

 

 

 

004

21.9/25.3

48.9/

52.5

60/60

 

48/

51

158/158

 

 

 

 

 

005

33.4/38.5

63.2/

69.1

70/

70

003

61/

66

158/158

 

 

 

 

 

NONE

13.6

20

 

14

 

63

 

 

 

 

 

006

7.2

16.7

20

 

14

 

63

 

 

STD

NO

9.2

007

10.6

20.9

25

 

15

 

63

 

 

 

 

 

008

13.8

25.0

25

 

24

 

63

 

 

 

 

 

009

16.8

28.7

30

 

27

 

63

 

 

 

 

 

NONE

16.3

20

 

20

 

67

 

 

 

 

 

006

7.2

18.8

25

 

20

 

68

 

 

STD

YES

9.2

007

10.6

23.0

25

 

20

 

68

 

 

 

 

 

008

13.8

27.1

30

 

29

 

68

 

460-3-60

 

 

 

009

16.8

30.8

35

 

32

 

68

 

 

 

 

NONE

14.0

20

 

15

 

77

 

 

 

 

 

 

 

 

 

 

 

 

006

7.2

17.1

20

 

15

 

77

 

 

HIGH STATIC

NO

9.2

007

10.6

21.3

25

 

15

 

77

 

 

 

 

 

008

13.8

25.4

30

 

24

 

77

 

 

 

 

 

009

16.8

29.1

30

 

28

 

77

 

 

 

 

 

NONE

16.7

20

 

20

 

82

 

 

 

 

 

006

7.2

19.2

25

 

20

 

82

 

 

HIGH STATIC

YES

9.2

007

10.6

23.4

25

 

20

 

82

 

 

 

 

 

008

13.8

27.5

30

 

29

 

82

 

 

 

 

 

009

16.8

31.2

35

 

32

 

82

 

 

 

 

 

NONE

—/—

44.4/ 44.4

60/60

 

44/ 44

173/173

 

 

 

 

 

001

15.9/18.3

44.4/

44.4

60/60

 

44/

44

173/173

 

 

STD

NO

9.2

003

31.4/36.3

55.1/

61.2

60/

70

004

52/

58

173/173

 

 

002+002

46.9/54.2

74.5/

83.6

80/

90

005

70/

79

173/173

 

 

 

 

 

 

 

 

 

 

003+003

62.8/72.5

94.4/106.5

100/110

005

88/100

173/173

 

208/230-1-60

 

 

 

004+004

75.8/87.5

110.6/125.2

125/150

005

103/117

173/173

 

 

 

 

NONE

—/—

50.4/ 50.4

60/60

 

50/ 50

178/178

 

 

 

 

 

 

 

 

 

 

 

001

15.9/18.3

50.4/

50.4

60/60

 

50/

50

178/178

 

 

STD

YES

9.2

003

31.4/36.3

59.9/

65.4

60/

70

004

58/

63

178/178

 

 

002+002

46.9/54.2

79.3/

87.8

80/

90

005

76/

83

178/178

 

 

 

 

 

 

 

 

 

 

003+003

62.8/72.5

99.2/110.7

100/125

005

94/104

178/178

 

 

 

 

 

004+004

75.8/87.5

115.4/129.4

125/150

005

109/122

178/178

 

 

 

 

 

NONE

—/—

31.7/ 31.7

40/40

 

33/ 33

140/140

 

 

 

 

 

002

13.6/15.6

32.8/

35.4

40/40

 

33/

34

140/140

 

 

STD

NO

9.2

003

18.1/20.9

38.5/ 42.0

45/45

 

37/ 40

140/140

 

 

 

 

 

005

33.4/38.5

57.5/

64.0

60/

70

002

55/

60

140/140

 

 

 

 

 

004+004

43.8/50.5

70.6/

79.0

80/

80

003

67/

74

140/140

50HJ005

 

 

 

 

NONE

—/—

37.7/ 37.7

40/40

 

38/ 38

145/145

 

 

 

 

002

13.6/15.6

37.7/

39.6

45/45

 

38/

39

145/145

 

 

STD

YES

9.2

003

18.1/20.9

43.3/ 46.2

50/50

 

43/ 45

145/145

 

 

 

 

 

005

33.4/38.5

62.3/

68.2

70/

70

002

60/

65

145/145

 

208/230-3-60

 

 

 

004+004

43.8/50.5

75.4/

83.2

80/

90

003

72/

79

145/145

 

 

 

 

NONE

—/—

32.6/ 32.6

40/40

 

34/ 34

170/170

 

 

 

 

 

 

 

 

 

 

 

002

13.6/15.6

33.7/

36.3

40/40

 

34/

35

170/170

 

 

HIGH STATIC

NO

9.2

003

18.1/20.9

39.4/ 42.9

45/45

 

38/ 41

170/170

 

 

 

 

 

005

33.4/38.5

58.4/

64.9

60/

70

002

56/

62

170/170

 

 

 

 

 

004+004

43.8/50.5

71.5/

79.9

80/

80

003

68/

75

170/170

 

 

 

 

 

NONE

—/—

38.6/ 38.6

45/45

 

39/ 39

174/174

 

 

 

 

 

002

13.6/15.6

38.6/

40.5

45/45

 

39/

40

174/174

 

 

HIGH STATIC

YES

9.2

003

18.1/20.9

44.2/ 47.1

50/50

 

44/ 46

174/174

 

 

 

 

 

005

33.4/38.5

63.2/

69.1

70/

70

003

61/

66

174/174

 

 

 

 

 

004+004

43.8/50.5

76.3/

84.1

80/

90

003

73/

80

174/174

 

 

 

 

 

NONE

15.2

20

 

16

 

70

 

460-3-60

STD

NO

9.2

006

7.2

16.7

20

 

16

 

71

 

008

13.8

25.0

25

 

18

 

71

 

 

 

 

 

009

16.8

28.7

30

 

27

 

71

 

 

 

 

 

008+008

27.7

42.3

45

 

025

40

 

71

14

Loading...
+ 30 hidden pages