Carrier 50PCH User Manual

0 (0)

AQUAZONE™ 50PCH,PCV006-060 Compact High-Efficiency Water Source Heat Pumps

with PURON® Refrigerant (R-410A)

Installation, Start-Up, and

Service Instructions

 

CONTENTS

 

 

 

Page

SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . .

. .1,2

GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . 2

INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-22

Step 1 — Check Jobsite . . . . . . . . . . . . . . . . . . . . .

. . . 2

Step 2 — Check Unit . . . . . . . . . . . . . . . . . . . . . . . .

. . . 2

STORAGE

 

PROTECTION

 

INSPECT UNIT

 

Step 3 — Locate Unit. . . . . . . . . . . . . . . . . . . . . . . . . .

. . . 7

• FIELD CONVERSION OF DISCHARGE AIR

 

Step 4 — Mount the Unit . . . . . . . . . . . . . . . . . . . . . .

. . . 8

HORIZONTAL UNITS

 

VERTICAL UNITS

 

Step 5 — Check Duct System . . . . . . . . . . . . . . . . .

. . . 8

SOUND ATTENUATION

 

EXISTING DUCT SYSTEM

 

Step 6 — Install Condensate Drain . . . . . . . . . . . .

. . . 8

HORIZONTAL UNITS

 

VERTICAL UNITS

 

VENTING

 

Step 7 — Pipe Connections . . . . . . . . . . . . . . . . . . .

. . . 9

WATER LOOP APPLICATIONS

 

GROUND LOOP APPLICATIONS

 

• INSTALLATION OF SUPPLY AND RETURN HOSE

 

KIT

 

Step 8 — Wire Field Power Supply . . . . . . . . . . . .

. . 10

POWER CONNECTION

 

SUPPLY VOLTAGE

 

208-VOLT OPERATION

 

460-VOLT OPERATION

 

Step 9 — Wire Field Controls. . . . . . . . . . . . . . . . . .

. . 20

THERMOSTAT CONNECTIONS

 

WATER FREEZE PROTECTION

 

• AIR COIL FREEZE PROTECTION

 

ACCESSORY CONNECTIONS

 

WATER SOLENOID VALVES

 

WSHP OPEN WIRING

 

PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

22,23

System Checkout . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . 22

PSC Blower Speed Selection . . . . . . . . . . . . . . . .

. . 22

FIELD SELECTABLE INPUTS . . . . . . . . . . . . . . . .

24,25

Complete C Control Jumper Settings. . . . . . . . .

. . 24

Complete C Control DIP Switches. . . . . . . . . . . .

. . 24

Deluxe D Control Jumper Settings . . . . . . . . . . .

. . 24

Deluxe D Control DIP Switches . . . . . . . . . . . . . .

. . 24

Deluxe D Control Accessory Relay

 

 

Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . 25

Water Valve (Slow Opening) . . . . . . . . . . . . . . . . .

. . 25

Outside Air Damper (OAD) . . . . . . . . . . . . . . . . . .

. . 25

START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

25-33

Operating Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . 25

Scroll Compressor Rotation. . . . . . . . . . . . . . . . . . .

. . 26

Unit Start-Up Cooling Mode . . . . . . . . . . . . . . . . . . .

. . 26

Page

Unit Start-Up Heating Mode . . . . . . . . . . . . . . . . . . . . . 30

Unit Start-Up with WSHP Open Controls . . . . . . . . 30

Flow Regulation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Flushing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Antifreeze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Cooling Tower/Boiler Systems . . . . . . . . . . . . . . . . . . 32

OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33-36 Power Up Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

Units with Aquazone Complete C Control . . . . . . . 33 Units with Aquazone Deluxe D Control . . . . . . . . . . 33 Units with WSHP Open Multiple Protocol. . . . . . . . 33

COMPLETE C AND DELUXE D BOARD

SYSTEM TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36-38

Test Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

WSHP Open Test Mode. . . . . . . . . . . . . . . . . . . . . . . . . . 36

Retry Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

Aquazone Deluxe D Control LED Indicators . . . . . 37

SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38-40

Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

Water Coil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

Condensate Drain Pans . . . . . . . . . . . . . . . . . . . . . . . . . 38

Refrigerant System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

Fan Motors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

Condensate Drain Cleaning . . . . . . . . . . . . . . . . . . . . . 38

Air Coil Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

Condenser Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

Checking System Charge . . . . . . . . . . . . . . . . . . . . . . . 39

Refrigerant Charging. . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

Air Coil Fan Motor Removal . . . . . . . . . . . . . . . . . . . . . 40

Replacing the WSHP Open Controller’s

Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . 40-42 Thermistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 Control Sensors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 WSHP Open Controller . . . . . . . . . . . . . . . . . . . . . . . . . . 40

APPENDIX A — WSHP OPEN SCREEN CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . 43-48

50PCH,PCV START-UP CHECKLIST . . . . . CL-1, CL-2

IMPORTANT: Read the entire instruction manual before starting installation.

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.

Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Catalog No. 04-53500094-01

Printed in U.S.A.

Form 50PC-3SI

Pg 1

3-11

Replaces: 50PC-2SI

Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.

Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and the National Electrical Code (NEC) for special installation requirements.

Understand the signal words — DANGER, WARNING, and CAUTION. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards that could result in personal injury or death. CAUTION is used to identify unsafe practices, which would result in minor personal injury or product and property damage.

Recognize safety information. This is the safety-alert symbol ( ). When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.

WARNING

Electrical shock can cause personal injury or death. Before installing or servicing system, always turn off main power to system. There may be more than one disconnect switch. Turn off accessory heater power if applicable.

GENERAL

This Installation and Start-Up Instructions literature is for Aquazone™ water source heat pump systems.

Water source heat pumps (WSHPs) are single-package horizontally and vertically mounted units with electronic controls designed for year-round cooling and heating. Aquazone WSHPs are available in the following unit configurations:

PCH standard efficiency with horizontal airflow and right, left or back discharge

PCV standard efficiency with vertical airflow and top discharge

IMPORTANT: The installation of water source heat pump units and all associated components, parts, and accessories which make up the installation shall be in accordance with the regulations of ALL authorities having jurisdiction and MUST conform to all applicable codes. It is the responsibility of the installing contractor to determine and comply with ALL applicable codes and regulations.

INSTALLATION

Step 1 — Check Jobsite — Installation, operation and maintenance instructions are provided with each unit. Before unit start-up, read all manuals and become familiar with the unit and its operation. Thoroughly check out the system before operation. Complete the inspections and instructions listed below to prepare a unit for installation. See Table 1 for unit physical data.

HORIZONTAL UNITS (50PCH) — Horizontal units are designed for indoor installation only. Be sure to allow adequate space around the unit for servicing. See Fig. 1 for overall unit dimensions. Refer to Fig. 2 for an illustration of a typical horizontal installation.

VERTICAL UNITS (50PCV) — Vertical units are designed for indoor installations. While vertical units are typically

installed in a floor-level closet or a small mechanical room, the unit access guidelines for these units are very similar to those described for horizontal units. See Fig. 3 for overall dimensions. Refer to Fig. 4 for an example of a typical vertical installation.

CAUTION

To avoid equipment damage, do not use these units as a source of heating or cooling during the construction process. The mechanical components and filters used in these units quickly become clogged with construction dirt and debris which may cause system damage.

Step 2 — Check Unit — Upon receipt of shipment at the jobsite, carefully check the shipment against the bill of lading. Make sure all units have been received. Inspect the carton or crating of each unit, and inspect each unit for damage. Ensure the shipping company makes proper notation of any shortages or damage on all copies of the freight bill. Concealed damage not discovered during unloading must be reported to the shipping company within 15 days of receipt of shipment.

NOTE: It is the responsibility of the purchaser to file all necessary claims with the shipping company.

1.Verify unit is correct model for entering water temperature of job.

2.Be sure that the location chosen for unit installation provides ambient temperatures maintained above freezing. Well water applications are especially susceptible to freezing.

3.Be sure the installation location is isolated from sleeping areas, private offices and other acoustically sensitive spaces.

NOTE: A sound control accessory package may be used to help eliminate sound in sensitive spaces.

4.Check local codes to be sure a secondary drain pan is not required under the unit.

5.Be sure unit is mounted at a height sufficient to provide an adequate slope of the condensate lines. If an appropriate slope cannot be achieved, a field-supplied condensate pump may be required.

6.Provide sufficient space for duct connection.

7.Provide adequate clearance for filter replacement and drain pan cleaning. Do not allow piping, conduit, etc. to block filter access.

8.Provide sufficient access to allow maintenance and servicing of the fan and fan motor, compressor and coils. Removal of the entire unit from the closet should not be necessary.

9.Provide an unobstructed path to the unit within the closet or mechanical room. Space should be sufficient to allow removal of unit if necessary.

10.Provide ready access to water valves and fittings, and screwdriver access to unit side panels, discharge collar, and all electrical connections.

11.Where access to side panels is limited, pre-removal of the control box side mounting screws may be necessary for future servicing.

STORAGE — If the equipment is not needed immediately at the jobsite, it should be left in its shipping carton and stored in a clean, dry area of the building or in a warehouse. Units must be stored in an upright position at all times. If carton stacking is necessary, stack units a maximum of 3 high. Do not remove any equipment from its shipping package until it is needed for installation.

PROTECTION — Once the units are properly positioned on the jobsite, cover them with either a shipping carton, vinyl film,

2

or an equivalent protective covering. Cap open ends of pipes stored on the jobsite. This precaution is especially important in areas where painting, plastering, or spraying of fireproof material, etc. is not yet complete. Foreign material that accumulates within the units can prevent proper start-up and necessitate costly clean-up operations.

Before installing any of the system components, be sure to examine each pipe, fitting, and valve, and remove any dirt or foreign material found in or on these components.

CAUTION

DO NOT store or install units in corrosive environments or in locations subject to temperature or humidity extremes (e.g., attics, garages, rooftops, etc.). Corrosive conditions and high temperature or humidity can significantly reduce performance, reliability, and service life. Always move units in an upright position. Tilting units on their sides may cause equipment damage.

INSPECT UNIT — To prepare the unit for installation, complete the procedures listed below:

1.Compare the electrical data on the unit nameplate with ordering and shipping information to verify that the correct unit has been shipped.

2.Verify that the unit is the correct model for the entering water temperature of the job.

3.Do not remove the packaging until the unit is ready for installation.

4.Verify that the refrigerant tubing is free of kinks or dents, and that it does not touch other unit components.

5.Inspect all electrical connections. Be sure connections are clean and tight at the terminals.

6.Loosen compressor bolts until the compressor rides freely on springs. Remove shipping restraints.

7.Remove the four 1/4 in. shipping bolts from compressor support plate (two bolts on each side) to maximize vibration and sound alternation.

CAUTION

Failure to remove shipping brackets from spring-mounted compressors will cause excessive noise and could cause component failure due to added vibration.

8.Remove any blower support cardboard from inlet of the blower.

9.Locate and verify any accessory kit located in compressor section.

10.Remove any access panel screws that may be difficult to remove once unit is installed.

Table 1 — Physical Data — 50PCH,PCV Units

50PCH,PCV UNIT

006

 

 

009

 

 

012

 

015

 

 

018

 

024

 

030

 

 

036

 

042

 

048

 

 

060

COMPRESSOR (1 each)

 

 

 

 

 

 

Rotary

 

 

 

 

 

 

 

 

 

 

 

Scroll

 

 

 

 

 

REFRIGERANT TYPE

 

 

 

 

 

 

 

 

 

 

 

 

 

R-410A

 

 

 

 

 

 

 

 

 

 

 

 

Factory Charge (oz)

17

 

 

18.5

 

 

23

 

32

 

 

43

 

43

 

47

 

 

50

 

70

 

74

 

 

82

 

 

 

 

 

 

 

 

 

 

FAN MOTOR AND BLOWER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan Motor Type/Speeds

 

 

 

 

 

 

 

 

 

 

 

 

 

PSC/3

 

 

 

 

 

 

 

 

 

 

 

 

Fan Motor (hp)

1/25

 

 

1/10

 

 

1/10

 

1/6

 

 

1/6

 

1/4

 

3/4

 

 

1/2

 

3/4

 

3/4

 

 

1

 

 

 

 

 

 

 

 

 

 

Blower Wheel Size (Dia x W) (in.)

5 x 5

 

 

6 x 5

 

8 x 7

 

9 x 7

 

 

9 x 8

 

10 x 10

 

 

11 x 10

COAX VOLUME (gal.)

0.123

 

 

0.143

 

 

0.167

 

0.286

 

 

0.450

 

0.286

 

0.323

 

 

0.323

 

0.890

 

0.738

 

 

0.939

WATER CONNECTION SIZE FPT (in.)

 

 

 

 

 

 

1/2

 

 

 

 

 

 

 

3/4

 

 

 

 

 

1

HORIZONTAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air Coil Dimensions (H x W)(in.)

 

 

 

10 x 15

 

 

 

 

 

16 x 22

 

 

 

 

20 x 25

 

20 x 35

 

 

 

 

 

 

 

 

 

 

 

Standard Filter - (Qty)

 

(1) 10 x 18

 

 

(1) 16 x 25

 

(1) 18 x 25

 

 

(1) 20 x 28 or

 

(1) 20 x 24,

 

 

 

 

 

 

1 in. Throwaway

 

 

 

 

 

 

(2) 20 x 14

 

(1) 20 x 14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Weight (lb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operating

103

 

 

105

 

 

114

 

153

 

 

158

 

174

 

182

 

 

203

 

218

 

263

 

 

278

 

 

 

 

 

 

 

 

Packaged

113

 

 

115

 

 

124

 

158

 

 

163

 

179

 

187

 

 

209

 

224

 

270

 

 

285

Corner Weight (lb)*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Left-Front

37

 

 

38

 

 

42

 

53

 

 

55

 

62

 

67

 

 

75

 

81

 

98

 

 

103

Right-Front

24

 

 

24

 

 

26

 

36

 

 

37

 

40

 

41

 

 

47

 

50

 

60

 

 

64

Left-Back

23

 

 

23

 

 

25

 

34

 

 

35

 

39

 

40

 

 

44

 

48

 

58

 

 

61

Right-Back

19

 

 

20

 

 

21

 

30

 

 

31

 

33

 

34

 

 

37

 

39

 

47

 

 

75

VERTICAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air Coil Dimensions (H x W)(in.)

 

 

 

10 x 15

 

 

 

 

 

20 x 17.25

 

 

 

 

24 x 17.75

 

24 x 28.25

 

 

 

 

 

 

 

 

 

 

 

Standard Filter - (Qty)

 

(1) 10 x 18

 

 

 

 

 

(1) 20 x 20

 

 

 

 

(1) 24 x 24

 

(1) 14 x 24,

1 in. Throwaway

 

 

 

 

 

 

 

 

 

 

 

(1) 18 x 24

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Weight (lb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operating

103

 

 

105

 

 

114

 

153

 

 

158

 

189

 

197

 

 

203

 

218

 

263

 

 

278

 

 

 

 

 

 

 

 

 

 

Packaged

113

 

 

115

 

 

124

 

158

 

 

163

 

194

 

202

 

 

209

 

224

 

270

 

 

285

LEGEND

 

 

 

 

 

 

 

 

 

*Front is located at control box end.

 

 

 

 

 

 

 

FPT — Female Pipe Thread

 

 

 

 

 

 

 

 

 

NOTES:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1. All units have grommet compressor mountings, and 1/2-in. and

PSC — Permanent Split Capacitor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3/4-in. electrical knockouts.

 

 

 

 

 

 

 

 

2. Maximum water working pressure is 500 psig.

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEFT RETURN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RIGHT RETURN

 

 

 

 

 

 

 

 

 

 

 

 

 

2 FT [610 MM] SERVICE

 

 

 

 

 

OPTIONAL 2 FT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BSP — Blower Service Panel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ACCESS

 

 

 

 

 

 

 

 

 

 

 

CSP

[610 MM]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CAP — Control Access Panel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 FT [610 MM] SERVICE

 

 

 

 

 

 

 

 

 

 

 

 

 

SERVICE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CSP — Compressor Service Panel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FRONT

ACCESS

 

 

 

 

 

 

 

 

 

FRONT

 

 

 

 

 

 

 

 

ACCESS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FPT — Female Pipe Thread

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OPTIONAL 2 FT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[610 MM]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER SUPPLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SERVICE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEFT RETURN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ACCESS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 / 4" [19.1 MM] KNOCKOUT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RIGHT RETURN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 / 2"

 

 

 

 

 

 

 

1.1 [27.9 MM] G

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[12.7 MM]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CSP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.3" KNOCKOUT

 

 

 

K

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F

 

 

 

 

 

 

3.3"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[83.8 MM]

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[83.8 MM]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW VOLTAGE

 

 

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 / 2" [12.7 MM]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KNOCKOUT

 

 

 

 

 

 

 

 

CAP

 

 

 

 

 

 

 

D

 

 

0.7"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RIGHT/STRAIGHT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

0.7" [17.8 MM]

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

[17.8 MM]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEFT/STRAIGHT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DISCHARGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DISCHARGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BACK CONDENSATE

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

CONDENSATE

 

 

BACK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: CHOOSE EITHER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FRONT-VIEW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DISCHARGE 3 / 4" FPT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: CHOOSE EITHER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 / 4" FPT

DISCHARGE

 

 

 

 

 

 

 

BACK OR STRAIGHT DISCHARGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BACK OR STRAIGHT DISCHARGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: BLOWER SERVICE PANEL REQUIRES 2 FT SERVICE ACCESS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

O

 

 

 

 

N

 

 

 

 

 

 

SIDE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT HANGER DETAIL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SIDE

 

 

 

 

 

N

 

 

 

 

 

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BSP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COILAIR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FRONT

036-042

47.1 [119.6]

22.2 [56.4]

 

18.0 [45.7]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COILAIR

 

 

 

BLOWER

 

 

 

 

 

 

 

 

 

 

BSP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MODEL

 

 

 

 

U

 

 

 

 

 

V

 

 

 

 

 

 

 

W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

006-012 34.1 [86.6]

21.1 [53.6]

 

 

18.9 [42.9]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTLET

 

 

 

 

M

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLOWER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V

 

 

 

 

 

 

 

 

 

 

W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

a50-8695

 

 

 

 

 

 

 

 

 

 

 

OUTLET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

015-030

43.1 [109.5]

22.2 [56.4]

 

 

18.0 [45.7]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

048-060

54.1 [137.4]

26.2 [66.5]

 

 

22.0 [55.9]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

O

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEFT RETURN BACK DISCHARGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RIGHT RETURN BACK DISCHARGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N

 

 

 

 

 

 

 

 

O

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BSP

 

 

 

 

 

 

L

 

 

 

 

 

 

 

 

 

N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLOWER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BSP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTLET

 

 

 

 

 

M

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLOWER

 

 

 

 

M

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CSP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTLET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FRONT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FRONT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEFT RETURN STRAIGHT DISCHARGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

O

 

 

 

 

 

 

 

 

 

 

RIGHT RETURN STRAIGHT DISCHARGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.75 [44.5 MM]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIR COIL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T

 

S

 

 

 

 

 

 

 

 

 

 

 

Q

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIR COIL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Q

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S

 

 

T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

 

R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CSP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FRONT

 

 

 

 

 

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FRONT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEFT RETURN

 

 

LEFT VIEW -

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RIGHT RETURN RIGHT VIEW -

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIR COIL OPENING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50PCH006-060 UNITS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIR COIL OPENING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WATER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DISCHARGE CONNECTIONS

 

 

RETURN CONNECTION

 

 

OVERALL CABINET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ELECTRICAL KNOCKOUTS

 

 

 

 

 

 

 

 

 

 

 

 

DUCT FLANGE

 

 

 

 

 

 

 

 

 

USING RETURN AIR

 

 

 

 

 

 

 

 

 

CONNECTIONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50PCH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

( 0.10 in., 2.5 mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OPENING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

2

 

 

3

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

 

 

 

 

 

 

 

J

 

 

 

 

 

 

K

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M

 

 

 

 

N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Q

 

 

R

 

 

 

SIZE

 

 

A

 

 

 

B

 

C

 

 

 

Loop In

 

Loop Out

 

Size

 

1/2-in.

 

 

 

 

1/2-in.

 

 

 

 

3/4-in.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Width

 

Depth

Height

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(IPT)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L

 

Supply

 

Supply

 

 

 

O

 

 

P

 

Return

 

 

Return

 

S

T

 

 

 

 

 

 

E

 

 

F

 

G

 

 

 

Low

 

 

 

 

 

Low

 

 

 

 

Power

 

 

 

 

 

 

 

Height

 

Width

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Depth

 

 

Height

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage

 

 

Voltage

 

 

 

 

Supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

006-

in.

19.1

 

 

 

34.1

 

 

11.1

 

9.6

 

1.1

 

1.5

1.1

 

 

 

1/2

 

 

 

8.1

 

 

 

5.1

 

 

 

 

2.1

 

 

 

 

 

0.8

8.9

 

 

6.7

 

 

8.2

1.3

 

16.1

 

 

9.8

 

1.1

0.6

012

cm

48.5

 

 

 

86.6

 

 

28.2

 

24.3

 

2.7

 

3.8

2.7

 

 

 

1.3

 

 

 

20.6

 

 

 

13.0

 

 

 

 

5.4

 

 

 

 

 

1.9

22.7

 

 

17.0

 

 

13.3

3.3

 

41.0

 

 

25.0

 

2.7

1.5

015

in.

20.1

 

 

 

43.1

 

 

17.0

 

15.1

 

1.4

 

3.2

1.4

 

 

 

1/2

 

 

 

12.1

 

 

 

9.1

 

 

 

 

6.1

 

 

 

 

 

2.6

13.3

 

 

9.9

 

 

4.1

1.3

 

23.0

 

 

15.0

 

1.1

1.0

cm

51.1

 

 

 

109.5

 

 

43.2

 

38.4

 

3.4

 

8.1

3.5

 

 

 

1.3

 

 

 

30.8

 

 

 

23.2

 

 

 

 

 

15.6

 

 

 

 

 

6.6

33.8

 

 

25.1

 

 

10.5

3.3

 

58.4

 

 

 

38.1

 

2.8

2.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

018

in.

20.1

 

 

 

43.1

 

 

17.0

 

15.1

 

1.4

 

4.1

1.4

 

 

 

1/2

 

 

 

12.1

 

 

 

9.1

 

 

 

 

 

6.1

 

 

 

 

 

2.6

13.3

 

 

9.9

 

 

4.1

1.3

 

23.0

 

 

 

15.0

 

1.1

1.0

cm

51.1

 

 

 

109.5

 

 

43.2

 

38.4

 

3.4

 

10.4

3.5

 

 

 

1.3

 

 

 

30.8

 

 

 

23.2

 

 

 

 

 

15.6

 

 

 

 

 

6.6

33.8

 

 

25.1

 

 

10.5

3.3

 

58.4

 

 

 

38.1

 

2.8

2.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

024

in.

20.1

 

 

 

43.1

 

 

18.3

 

15.1

 

1.4

 

4.4

1.4

 

 

 

3/4

 

 

 

12.1

 

 

 

9.1

 

 

 

 

 

6.1

 

 

 

 

 

2.6

13.3

 

 

9.9

 

 

4.1

1.3

 

23.0

 

 

 

16.3

 

1.1

1.0

cm

51.1

 

 

 

109.5

 

 

46.5

 

38.4

 

3.4

 

11.3

3.5

 

 

 

1.9

 

 

 

30.8

 

 

 

23.2

 

 

 

 

 

15.6

 

 

 

 

 

6.6

33.8

 

 

25.1

 

 

10.5

3.3

 

58.4

 

 

 

41.4

 

2.8

2.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

030

in.

20.1

 

 

 

43.1

 

 

18.3

 

15.1

 

1.4

 

3.1

1.4

 

 

 

3/4

 

 

 

12.1

 

 

 

9.1

 

 

 

 

 

6.1

 

 

 

 

 

2.6

13.3

 

 

9.9

 

 

4.1

1.3

 

23.0

 

 

 

16.3

 

1.1

1.0

cm

51.1

 

 

 

109.5

 

 

46.5

 

38.4

 

3.4

 

7.8

3.5

 

 

 

1.9

 

 

 

30.8

 

 

 

23.2

 

 

 

 

 

15.6

 

 

 

 

 

6.6

33.8

 

 

25.1

 

 

10.5

3.3

 

58.4

 

 

 

41.4

 

2.8

2.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036

in.

20.1

 

 

 

47.1

 

 

21.0

 

15.1

 

1.4

 

5.3

1.4

 

 

 

3/4

 

 

 

16.1

 

 

 

13.1

 

 

 

 

 

10.1

 

 

 

 

 

2.5

16.1

 

 

11.0

 

 

3.0

2.5

 

25.9

 

 

 

19.0

 

1.1

1.0

cm

51.1

 

 

 

119.6

 

 

53.3

 

38.4

 

3.4

 

13.4

3.5

 

 

 

1.9

 

 

 

41.0

 

 

 

33.3

 

 

 

 

 

25.7

 

 

 

 

 

6.3

40.9

 

 

27.9

 

 

7.7

6.4

 

65.8

 

 

 

48.3

 

2.8

2.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

042

in.

20.1

 

 

 

47.1

 

 

21.0

 

15.1

 

1.4

 

4.4

1.4

 

 

 

3/4

 

 

 

16.1

 

 

 

13.1

 

 

 

 

 

10.1

 

 

 

 

 

2.5

16.1

 

 

11.0

 

 

3.0

2.5

 

25.9

 

 

 

19.0

 

1.1

1.0

cm

51.1

 

 

 

119.6

 

 

53.3

 

38.4

 

3.4

 

11.3

3.5

 

 

 

1.9

 

 

 

41.0

 

 

 

33.3

 

 

 

 

 

25.7

 

 

 

 

 

6.3

40.9

 

 

27.9

 

 

7.7

6.4

 

65.8

 

 

 

48.3

 

2.8

2.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

048

in.

24.1

 

 

 

54.1

 

 

21.0

 

15.1

 

1.4

 

4.4

1.4

 

 

 

1

 

 

 

 

 

16.1

 

 

 

13.1

 

 

 

 

 

10.1

 

 

 

 

 

3.7

16.1

 

 

13.7

 

 

4.1

1.3

 

35.9

 

 

 

19.0

 

1.1

1.0

cm

61.2

 

 

 

137.4

 

 

53.3

 

38.4

 

3.4

 

11.1

3.5

 

 

 

2.5

 

 

 

41.0

 

 

 

33.3

 

 

 

 

 

25.7

 

 

 

 

 

9.5

41.0

 

 

34.8

 

 

10.3

3.2

 

91.2

 

 

 

48.3

 

2.8

2.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

060

in.

24.1

 

 

 

54.1

 

 

21.0

 

15.1

 

1.4

 

3.8

1.4

 

 

 

1

 

 

 

 

 

16.1

 

 

 

13.1

 

 

 

 

 

10.1

 

 

 

 

 

1.7

18.1

 

 

13.7

 

 

4.1

1.3

 

35.9

 

 

 

19.0

 

1.1

1.0

cm

61.2

 

 

 

137.4

 

 

53.3

 

38.4

 

3.4

 

9.7

3.5

 

 

 

2.5

 

 

 

41.0

 

 

 

33.3

 

 

 

 

 

25.7

 

 

 

 

 

4.4

46.0

 

 

34.8

 

 

10.3

3.2

 

91.2

 

 

 

48.3

 

2.8

2.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTES:

1.While clear access to all removable panels is not required, installer should take care to comply with all building codes and allow adequate clearance for future field service.

2.Horizontal units shipped with filter bracket only. This bracket should be removed for return duct connection.

3.Discharge flange and hanger brackets are factory installed.

4.Condensate is 3/4-in. (19.1 mm) FPT copper.

5.Blower service panel requires 2 ft (610 mm) service access.

6.Blower service access is through back panel on left or right discharge units or through panel opposite air coil on back discharge units.

Fig. 1 — 50PCH Unit Dimensions

4

Field-supplied transition to minimize pressure loss

Supply Air

 

Flexible

 

Insulated supply duct with

Connection

 

at least one 90 degree elbow

Accessory

to reduce air noise

Electric Heat

(field supplied)

(if applicable)

 

 

Return Loop

3/8" threaded rods

Supply Loop

(by others)

 

Water In

Filter Access

 

 

 

 

Water Out

 

Return Air

 

(Ductwork

 

 

 

 

 

not shown)

 

 

 

 

 

Thermostat

 

Power Wiring

 

Wiring

Balancing Valve (Field

 

 

Accessory

 

 

 

 

installed and calibrated

 

 

 

 

stainless steel

accessory)

 

 

 

 

braid hose

 

 

 

 

 

with integral

Low Pressure Drop Water

 

 

 

 

“J” swivel

Control Valve (optional) or

 

 

 

 

 

 

 

(field-installed accessory)

Unit Power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit Power

Water Out

Disconnect

Water In

Unit Hanger

Ball Valve Accessory with optional

 

integral P/T plug (typical for supply

 

and return piping)

3/8" Threaded Rod (by others)

Vibration Isolator (white compressor end and red blower end)

Washer (by others)

Double Hex Nuts

(by others)

Integral hanger support- pre-attached in factory

a50-7842ef

UNIT HANGER ISOLATION DETAIL

Fig. 2 — Typical Installation — 50PCH Units

5

 

P

N

O

 

 

Q

AIR COIL AND FRONT SIDE

TOP VIEW-FRONT RETURN

 

P

N

O

FRONT

 

 

 

Q

AIR COIL SIDE

 

TOP VIEW-RIGHT RETURN

LEGEND

ASP — Alternate Service Panel

BSP — Blower Service Panel

CAP — Control Access Panel

CSP — Compressor Service Panel

FPT — Female Pipe Thread

HV — High Voltage

LV — Low Voltage

 

B

 

 

N

P

 

 

 

 

FRONT

O

 

 

 

 

 

 

A

 

AIR COIL SIDE

 

M

 

 

 

TOP VIEW-LEFT RETURN

FIELD INSTALLED

ACCESS PANELS

DISCHARGE FLANGE

 

STANDARD FILTER BRACKET

 

AIR COIL

 

BSP

 

 

ASP

 

OPTIONAL

 

2 FT [610 MM]

 

SERVICE

CSP

ACCESS

LEFT RTN

CAP

(RIGHT RTN

 

OPPOSITE

 

SIDE)

R

S

S

R

 

ISOMETRIC

 

 

 

 

 

2 FT [610 MM]

 

 

 

 

 

 

SERVICE

 

VIEW

 

 

 

U

 

U

 

 

 

 

 

 

1.00 [25.4 MM]

 

 

 

 

 

 

 

 

 

AIR COIL

 

AIR COIL

 

 

 

 

 

 

T

 

T

a50-8696

 

BSP

 

 

 

 

 

 

 

 

 

 

C

 

C

 

 

 

 

G

 

 

 

 

 

 

 

 

 

CONDENSATE

 

 

 

POWER SUPPLY

 

 

 

 

 

 

 

 

 

 

 

 

 

3/4" FPT

 

 

 

3/4" [19.1 MM] HV

 

 

 

 

 

 

 

 

 

KNOCKOUT

 

 

2

 

 

 

 

 

 

LOW VOLTAGE

 

CAP

 

 

 

 

 

 

1/2" [12.7 MM] LV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KNOCKOUT

 

 

 

 

 

 

 

CSP

CSP

LOW VOLTAGE

 

 

3

 

 

F

 

1/2" [12.7 MM] LV

 

L

 

 

 

 

 

KNOCKOUT

 

K

 

 

I

 

FRONT

BACK

BACK

FRONT

 

 

 

H

CSP

J

 

 

 

1

 

 

 

 

 

D

 

 

 

 

 

 

 

 

RIGHT RETURN RIGHT VIEW

LEFT RETURN LEFT VIEW

 

 

 

 

E

 

 

 

- AIR COIL OPENING

- AIR COIL OPENING

 

 

FRONT-VIEW

 

 

 

 

 

 

 

 

50PCV006-060 UNITS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DISCHARGE CONNECTION

RETURN CONNECTION

 

 

 

OVERALL CABINET

 

 

WATER CONNECTIONS

 

ELECTRICAL KNOCKOUTS

DUCT FLANGE INSTALLED

USING RETURN AIR

50PCV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

( 0.10 in., 2.5 mm)

 

 

OPENING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J

K

L

 

 

 

 

 

 

 

 

 

UNIT

 

 

 

 

 

1

 

2

 

 

3

 

 

1/2-in.

1/2-in.

3/4-in.

 

 

O

P

 

 

S

T

 

SIZE

 

A

B

C

 

 

 

 

 

 

 

 

Size

(1.3 cm)

(1.3 cm)

(1.3 cm)

 

 

 

 

 

 

 

 

Width

Depth

Height

 

 

 

 

 

 

 

 

(IPT)

 

 

 

M

N

Supply

Supply

Q

R

Return

Return

U

 

 

 

D

E

 

F

G

 

 

 

Low

Low

Power

 

 

Width

Depth

 

 

Depth

Height

 

 

 

 

 

 

 

 

H

 

I

 

 

 

 

 

 

 

 

 

 

 

 

Loop In

 

Loop Out

 

 

Voltage

Voltage

Supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

006-

 

in.

19.1

19.1

22.0

1.4

1.6

 

9.5

1.6

6.1

 

1.6

1/2

2.9

5.9

8.9

8.9

5.1

9.0

9.0

5.5

2.1

16.2

9.9

0.7

012

 

cm

48.5

48.5

55.9

3.6

4.1

 

24.1

4.3

15.6

 

4.1

1.3

7.3

14.9

22.5

22.7

12.9

22.9

22.9

14.0

5.3

41.1

25.1

1.9

015

 

in.

21.5

21.5

39.0

1.9

1.4

 

13.8

1.4

8.1

 

1.4

1/2

4.1

7.1

10.1

6.4

3.8

14.0

14.0

5.3

2.3

18.3

20.9

0.7

 

cm

54.6

54.6

99.1

4.8

3.6

 

35.1

3.6

20.6

 

3.6

1.3

10.5

18.1

25.7

16.1

9.5

35.6

35.6

13.6

5.8

46.5

53.1

1.9

 

 

 

 

018

 

in.

21.5

21.5

39.0

1.9

1.4

 

12.9

1.4

8.1

 

1.4

1/2

4.1

7.1

10.1

6.4

3.8

14.0

14.0

5.3

2.3

18.3

20.9

0.7

 

cm

54.6

54.6

99.1

4.8

3.6

 

32.8

3.6

20.6

 

3.6

1.3

10.5

18.1

25.7

16.1

9.5

35.6

35.6

13.6

5.8

46.5

53.1

1.9

 

 

 

 

024

 

in.

21.5

21.5

40.0

1.9

1.4

 

13.8

1.4

8.1

 

1.4

3/4

4.1

7.1

10.1

6.4

3.8

14.0

14.0

5.3

2.3

18.3

20.9

0.7

 

cm

54.6

54.6

101.6

4.8

3.6

 

35.1

3.6

20.6

 

3.6

1.9

10.5

18.1

25.7

16.1

9.5

35.6

35.6

13.6

5.8

46.5

53.1

1.9

 

 

 

 

030

 

in.

21.5

21.5

40.0

1.9

1.4

 

15.2

1.4

8.1

 

1.4

3/4

4.1

7.1

10.1

6.4

3.8

14.0

14.0

5.3

2.3

18.3

20.9

0.7

 

cm

54.6

54.6

101.6

4.8

3.6

 

38.6

3.6

20.6

 

3.6

1.9

10.5

18.1

25.7

16.1

9.5

35.6

35.6

13.6

5.8

46.5

53.1

1.9

 

 

 

 

036

 

in.

21.5

26.0

45.0

1.9

1.4

 

15.7

1.4

8.1

 

1.4

3/4

4.1

7.1

10.1

6.4

3.8

14.0

14.0

5.1

2.3

22.8

23.9

0.7

 

cm

54.6

66.0

114.3

4.8

3.6

 

39.9

3.6

20.6

 

3.6

1.9

10.5

18.1

25.7

16.1

9.5

35.6

35.6

13.1

5.8

57.9

60.7

1.9

 

 

 

 

042

 

in.

21.5

26.0

45.0

1.9

1.4

 

16.6

1.4

8.1

 

1.4

3/4

4.1

7.1

10.1

6.4

3.8

14.0

14.0

5.1

2.3

22.8

23.9

0.7

 

cm

54.6

66.0

114.3

4.8

3.6

 

42.0

3.6

20.6

 

3.6

1.9

10.5

18.1

25.7

16.1

9.5

35.6

35.6

13.1

5.8

57.9

60.7

1.9

 

 

 

 

048

 

in.

24.0

32.5

46.0

1.9

1.4

 

16.6

1.4

8.1

 

1.4

1

4.1

7.1

10.1

6.9

7.3

16.0

18.0

5.1

2.3

29.3

22.5

0.7

 

cm

61.0

82.6

116.8

4.8

3.6

 

42.2

3.6

20.6

 

3.6

2.5

10.5

18.1

25.7

17.4

18.4

40.6

45.7

13.1

5.8

74.4

57.0

1.9

 

 

 

 

060

 

in.

24.0

32.5

46.0

1.9

1.4

 

16.7

1.4

8.1

 

1.4

1

4.1

7.1

10.1

6.9

7.3

16.0

18.0

5.1

2.3

29.3

22.5

0.7

 

cm

61.0

82.6

116.8

4.8

3.6

 

42.4

3.6

20.6

 

3.6

2.5

10.5

18.1

25.7

17.4

18.4

40.6

45.7

13.1

5.8

74.4

57.0

1.9

 

 

 

 

NOTES:

1.Shaded areas are recommended service areas. Installer should take care to comply with all building codes and allow adequate clearance for future field service.

2.Front and side access is preferred for service access. However, all components may be serviced from the front access panel if side access is not available except on 50PCV009030 with front return.

3.Discharge flange is field installed.

4.Condensate is 3/4 in. (19.1 mm) FPT.

5.Units shipped with filter rails. These rails should be removed for return duct connection. See WSHP Accessory Price Page for accessory air filter frame with duct collar.

Fig. 3 — 50PCV Unit Dimensions

6

Supply Air

a50-6803ef

 

 

Building

 

Flexible

Loop

 

 

 

Connection

 

 

Water

 

 

Out

 

 

Water

 

 

In

Balancing Valve

 

 

(field installed

Field-supplied

and calibrated

stainless steel

accessory)

braid

hose

 

with integral

Low Pressure

“ J” swivel

Drop Water

Power

 

Control Valve

Thermostat

 

(optional)

 

(field-installed

Wiring

 

accessory)

 

Ball Valve with optional

Compressor

integral P/T plug

Access Panel

(typical for supply and

 

return piping)

NOTE: Ball valve with integral pressure temperature plug recommended.

Fig. 4 — Typical Vertical Installation of 50PCV Unit

Step 3 — Locate Unit — The following guidelines should be considered when choosing a location for a WSHP:

Units are for indoor use only.

Locate in areas where ambient temperatures are between 40 F and 100 F and relative humidity is no greater than 75%.

Provide sufficient space for water, electrical and duct connections.

Locate unit in an area that allows easy access and removal of filter and access panels.

Allow enough space for service personnel to perform maintenance.

Return air must be able to freely enter the space if unit needs to be installed in a confined area such as a closet.

Install the unit on a piece of rubber, neoprene or other mounting pad material for sound isolation. The pad should be at least 3/8 in. [10 mm] to 1/2 in. [13 mm] in thickness. Extend the pad beyond all four edges of the unit.

Provide adequate clearance for filter replacement and drain pan cleaning. Do not block filter access with piping, conduit or other materials. Refer to Fig. 1 and 3 for dimensional data.

Provide access for fan and fan motor maintenance and for servicing the compressor and coils without removing the unit.

Provide an unobstructed path to the unit within the closet or mechanical room. Space should be sufficient to allow removal of the unit, if necessary.

In limited side access installations, pre-removal of the control box side mounting screws will allow control box removal for future servicing.

Provide access to water valves and fittings and screwdriver access to the unit side panels, discharge collar and all electrical connections.

NOTE: Correct placement of the horizontal unit can play an important part in minimizing sound problems. Since ductwork is normally applied to these units, the unit can be placed so that the principal sound emission is outside the occupied space in sound-critical applications. A fire damper may be required by the local code if a fire wall is penetrated.

FIELD CONVERSION OF DISCHARGE AIR — The discharge air of the 50PCH horizontal units can be converted

between side and back discharge in the field. The conversion process is the same for right and left return configurations. See Fig. 5 and 6.

NOTE: It is not possible to convert return air between left or right return models in the field due to refrigerant piping changes.

Preparation — The unit should be on the ground in a well lit area for conversion. Hung units should be taken down to ground level before converting.

Water

Remove Screws

Connection End

 

Return Air

Side Discharge

Water

Connection End

Rotate

Return Air

 

Move to Side

Water

Replace Screws

Connection End

 

Return Air

Drain

Back Discharge

Discharge Air

Fig. 5 — Conversion Left Return,

Side Discharge to Back Discharge

Water

Connection End

Return Air

Supply

Duct

Side Discharge

Water

 

Connection End

Return Air

Drain

a50-6257ef

Back Discharge

Discharge Air

Fig. 6 — Conversion Right Return,

Side Discharge to Back Discharge

7

Side to Back Discharge Conversion

1.Remove screws to free the top and discharge panels. See Fig. 5.

2.Remove the access panel and set aside.

3.Lift the discharge panel from side of unit and rotate it to back using care not to damage blower wiring.

4.Check blower wire routing and connections for undue tension or contact with sheet metal edges. Re-route if necessary.

5.Check refrigerant tubing for contact with other components. Adjust if necessary.

6.Reinstall top panel using screws set aside in Step 1.

NOTE: Location for some screws at bottom of discharge panel may have to be changed.

7.Manually spin fan wheel to check for obstructions. Adjust for any obstruction found.

8.Replace access panel.

Back to Side Discharge Conversion — Follow instructions above for Side to Back Discharge Conversion, noting the panels would be reversed.

Step 4 — Mount the Unit

HORIZONTAL UNITS (50PCH) —Horizontal units should be mounted using the factory-installed hangers. Proper attachment of hanging rods to building structure is critical for safety. See Fig. 2 and 7. Rod attachments must be able to support the weight of the unit. See Table 1 for unit operating weights.

a50-8489

 

COMPRESSOR

AIR HANDLER

 

 

 

 

SECTION

SECTION

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 7 — Horizontal Hanger Bracket

(Factory Installed)

VERTICAL UNITS (50PCV) — Vertical units are available in left or right return air configurations. See Fig. 3. Mount the unit on a vibration absorption pad slightly larger than the entire base to minimize vibration transmission. It is not necessary to mount the unit on the floor. See Fig. 8.

a50-6259ef

Vibration

Absorption

Pad

Fig. 8 — 50PCV Unit Mounted with

Vibration Absorption Pad

NOTE: Some codes require the use of a secondary drain pan under vertical units. Check local codes for more information.

Step 5 — Check Duct System — Size the duct system to handle the design airflow quietly.

NOTE: Depending on the unit, the fan wheel may have a shipping support installed at the factory. This must be removed before operating unit.

SOUND ATTENUATION — To eliminate the transfer of vibration to the duct system, a flexible connector is recommended for both discharge and return air duct connections on metal duct systems. The supply and return plenums should include internal duct liner of fiberglass or be made of duct board construction to maximize sound attenuation of the blower. Installing the WSHP unit to uninsulated ductwork in an unconditioned space is not recommended since it will sweat and adversely affect the unit’s performance.

To reduce air noise, at least one 90-degree elbow could be included in the supply and return air ducts, provided system performance is not adversely impacted. The blower speed can also be changed in the field to reduce air noise or excessive airflow, provided system performance is not adversely impacted.

EXISTING DUCT SYSTEM — If the unit is connected to existing ductwork, consider the following:

Verify that the existing ducts have the proper capacity to handle the unit airflow. If the ductwork is too small, install larger ductwork.

Check existing ductwork for leaks and repair as necessary.

NOTE: Local codes may require ventilation air to enter the space for proper indoor air quality. Hard-duct ventilation may be required for the ventilating air supply. If hard ducted ventilation is not required, be sure that a proper air path is provided for ventilation air to unit to meet ventilation requirement of the space.

Step 6 — Install Condensate Drain

HORIZONTAL UNITS (50PCH) — Slope the unit toward the drain at a 1/4 in. drop at drain end. See Fig. 9. If it is not possible to meet the required pitch, install a condensate pump at the unit to pump condensate to building drain.

1/4” Pitch for Drainage

a50-6260ef

Pitch Toward

 

Drain

Drain Connection

Fig. 9 — Horizontal Unit Pitch

Horizontal units are not internally trapped, therefore an external trap is necessary. Install each unit with its own individual trap and means to flush or blow out the condensate drain line. Do not install units with a common trap or vent. For typical condensate connections see Fig. 10.

NOTE: Never use a pipe size smaller than the connection.

VERTICAL UNITS (50PCV) — Each unit uses a condensate hose inside all cabinets as a trapping loop, therefore an external trap is not necessary and should not be used. See Fig. 11.

8

a50-6261tf

NOTE: Trap should be deep enough to offset maximum unit static difference. A 4-in. trap is recommended.

Fig. 10 — Trap Condensate Drain

3/4” Copper FPT/PVC

 

3/4” PVC

 

 

 

 

Vent

a50-6262ef

1/2”

1/4” per foot

 

 

slope to drain

Water

 

1/2”

Connections

 

Alternate

 

 

 

 

Condensate

 

 

Location

NOTE: Unit does not need to be sloped toward drain.

Fig. 11 — Vertical Condensate Connection

Each unit must be installed with its own individual vent and means to flush or blow out the condensate drain line. Do not install units with a common trap or vent.

VENTING — Install a vent in the condensate line of any application that may allow dirt or air to collect in the line. Consider the following:

Always install a vent where an application requires a long horizontal run.

Always install a vent where large units are working against higher external static pressure and to allow proper drainage for multiple units connected to the same condensate main.

Be sure to support the line where anticipated sagging from the condensate or when “double trapping” may occur.

If condensate pump is present on unit, be sure drain connections have a check valve to prevent back flow of condensate into other units.

Step 7 — Pipe Connections — Depending on the application, there are 3 types of WSHP piping systems to choose from: water loop, ground-water and ground loop. Refer to Piping Section of Carrier System Design Manual for additional information.

All WSHP units use low temperature soldered female pipe thread fittings for water connections to prevent annealing and out-of-round leak problems which are typically associated with high temperature brazed connections. Refer to Table 1 for connection sizes. When making piping connections, consider the following:

Use a backup wrench when making screw connections to unit to prevent internal damage to piping.

Insulation may be required on piping to avoid condensation in the case where fluid in loop piping operates at temperatures below dew point of adjacent air.

Piping systems that contain steel pipes or fittings may be subject to galvanic corrosion. Dielectric fittings may be used to isolate the steel parts of the system to avoid galvanic corrosion.

WATER LOOP APPLICATIONS — Water loop applications usually include a number of units plumbed to a common piping system. Maintenance to any of these units can introduce air into the piping system. Therefore, air elimination equipment comprises a major portion of the mechanical room plumbing.

The flow rate is usually set between 2.25 and 3 gpm per ton of cooling capacity. For proper maintenance and servicing, pressure-temperature (P/T) ports are necessary for temperature and flow verification.

In addition to complying with any applicable codes, consider the following for system piping:

Piping systems using water temperatures below 50 F require 1/2-in. closed cell insulation on all piping surfaces to eliminate condensation.

Avoid all plastic to metal threaded fittings due to the potential to leak. Use a flange fitted substitute.

Teflon tape thread sealant is recommended to minimize internal fouling of the heat exchanger.

Use backup wrench. Do not overtighten connections.

Route piping to avoid service access areas to unit.

Flush the piping system prior to operation to remove dirt and foreign materials from the system.

GROUND-LOOP APPLICATIONS — Temperatures between 25 and 110 F and a cooling capacity of 2.25 to 3 gpm of flow per ton is recommended. In addition to complying with any applicable codes, consider the following for system piping:

Limit piping materials to only polyethylene fusion in the buried sections of the loop.

Do not use galvanized or steel fittings at any time due to corrosion.

Avoid all plastic to metal threaded fittings due to the potential to leak. Use a flange fitted substitute.

Do not overtighten connections.

Route piping to avoid service access areas to unit.

Use pressure-temperature (P/T) plugs to measure flow of pressure drop.

INSTALLATION OF SUPPLY AND RETURN HOSE KIT — Follow these piping guidelines.

1.Install a drain valve at the base of each supply and return riser to facilitate system flushing.

2.Install shutoff/balancing valves and unions at each unit to permit unit removal for servicing.

3.Place strainers at the inlet of each system circulating pump.

4.Select the proper hose length to allow slack between connection points. Hoses may vary in length by +2% to –4% under pressure.

5.Refer to Table 2. Do not exceed the minimum bend radius for the hose selected. Exceeding the minimum bend radius may cause the hose to collapse, which reduces water flow rate. Install an angle adapter to avoid sharp bends in the hose when the radius falls below the required minimum.

NOTE: Piping must comply with all applicable codes.

Table 2 — Metal Hose Minimum Bend Radii

HOSE DIAMETER (in.)

MINIMUM BEND RADII (in.)

1/2

21/2

3/4

4

1

51/2

9

Insulation is not required on loop water piping except where the piping runs through unheated areas or outside the building or when the loop water temperature is below the minimum expected dew point of the pipe ambient. Insulation is required if loop water temperature drops below the dew point.

IMPORTANT: Do not bend or kink supply lines or hoses.

Pipe joint compound is not necessary when Teflon* threaded tape is pre-applied to hose assemblies or when flared-end connections are used. If pipe joint compound is preferred, use compound only in small amounts on the male pipe threads of the fitting adapters. Prevent sealant from reaching the flared surfaces of the joint.

NOTE: When anti-freeze is used in the loop, assure that it is compatible with Teflon tape or pipe joint compound employed.

Maximum allowable torque for brass fittings is 30 ft-lb. If a torque wrench is not available, tighten finger-tight plus one quarter turn. Tighten steel fittings as necessary.

Optional pressure-rated hose assemblies designed specifically for use with Carrier units are available. Similar hoses can be obtained from alternate suppliers. Supply and return hoses are fitted with swivel-joint fittings at one end to prevent kinking during installation.

CAUTION

Backup wrench is required when tightening water connections to prevent water line damage. Failure to use a backup wrench could result in equipment damage.

Refer to Fig. 12 for an illustration of a supply/return hose kit. Male adapters secure hose assemblies to the unit and risers. Install hose assemblies properly and check them regularly to avoid system failure and reduced service life.

A50-7734

Swivel

 

Brass

 

 

 

 

 

 

 

Brass

 

 

 

 

 

 

 

Rib Crimped

Fitting

 

Fitting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Length

(2 ft Length Standard)

MPT

Fig. 12 — Supply/Return Hose Kit

Step 8 — Wire Field Power Supply

WARNING

To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position during installation.

CAUTION

Use only copper conductors for field-installed electrical wiring. Unit terminals are not designed to accept other types of conductors. Failure to follow this safety precaution could lead to equipment damage.

All field installed wiring, including the electrical ground, MUST comply with the National Electrical Code (NEC) as well as applicable local codes. In addition, all field wiring must conform to the Class II temperature limitations described in the NEC.

*Registered trademark of E. I. du Pont de Nemours and Company.

Refer to unit wiring diagrams Fig. 13-20 for a schematic of the field connections, which must be made by the installing (or electrical) contractor. Refer to Table 3 for fuse sizes.

Consult the unit wiring diagram located on the inside of the compressor access panel to ensure proper electrical hookup. The installing (or electrical) contractor must make the field connections when using field-supplied disconnect.

Operating voltage must be the same voltage and phase as shown in Table 3.

Make all final electrical connections with a length of flexible conduit to minimize vibration and sound transmission to the building.

POWER CONNECTION — Make line voltage connection by connecting the incoming line voltage wires to the L side of the CC terminal as shown in Fig. 21. See Table 3 for correct wire and maximum overcurrent protection sizing.

SUPPLY VOLTAGE — Operating voltage to unit must be within voltage range indicated on unit nameplate.

On 3-phase units, voltages under load between phases must be balanced within 2%. Use the following formula to determine the percentage voltage imbalance:

% Voltage Imbalance

= 100 x

max voltage deviation from average voltage

 

average voltage

Example: Supply voltage is 460-3-60.

AB = 452 volts BC = 464 volts AC = 455 volts

Average Voltage = 452 + 464 + 455 3

= 1371 3

= 457 Determine maximum deviation from average voltage:

(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

Maximum deviation is 7 v. Determine percent voltage imbalance.

% Voltage Imbalance =

100 x

 

7

 

457

=

1.53%

 

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components.

NOTE: If more than 2% voltage imbalance is present, contact your local electric utility.

208-VOLT OPERATION — All 208-230 volt units are factory wired for 208 volts. The transformers may be switched to 230-volt operation by switching the red (208 volt) wire with the orange (230 volt) wire at the L1 terminal.

460-VOLT OPERATION — Units using 460-v and internal secondary pump will require a neutral wire from the supply side in order to feed accessory with 265-v.

10

Complete C

11

LEGEND

AL

Alarm Relay Contacts

LOC

Loss of Charge Pressure Switch

 

 

 

 

 

 

 

Relay/Contactor Coil

 

BM

Blower Motor

MV

Motorized Valve

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BMC

Blower Motor Capacitor

MVES

Motorized Valve End Switch

 

 

 

 

 

 

 

 

 

BR

Blower Relay

NEC

National Electrical Code

 

 

 

 

 

 

 

Condensate Pan

 

 

 

 

 

 

 

 

 

CAP

Compressor Capacitor

P1

Field Wiring Terminal Block

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CB

Circuit Breaker

PSC

Permanent Split Capacitor

 

 

 

 

 

 

 

Solenoid Coil

 

CC

Compressor Contactor

RV

Reversing Valve Coil

 

 

 

 

 

 

 

 

a50-8490

TRANS

Transformer

 

 

 

 

 

 

 

Temperature Switch

CO

Sensor, Condensate Overflow

 

 

 

 

 

 

 

 

FP1

Sensor, Low Temperature Protection Water Coil

TXV

Thermostatic Expansion Valve

 

 

 

 

 

 

 

Thermistor

 

FP2

Sensor, Low Temperature Protection Air Coil

 

Field Line Voltage Wiring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HP

High-Pressure Switch

 

Field Low Voltage Wiring

 

 

 

 

 

 

 

Ground

 

HPWS — High-Pressure Water Switch

 

 

 

 

 

 

 

 

 

 

Printed Circuit Trace

 

 

 

 

 

 

 

 

 

HWTS

High Leaving Water Temperature Switch

 

 

 

 

 

 

 

 

Wire Nut

 

JW1

Jumper, Alarm

 

Optional Wiring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Optional.

NOTES:

1.Compressor and blower motor thermally protected internally.

2.All wiring to the unit must comply with NEC and local codes.

3.Transformer for 208/230 v will be connected for 208 v operation. For 230 v operation, switch RED wire to ORG wire. Insulate open end of RED lead. Transformer is energy limiting or may have circuit breaker.

4.FP1 thermistor provides freeze protection for water. When using antifreeze solutions, cut JW3 jumper.

5.Typical heat pump thermostat wiring shown. Refer to thermostat installation instructions for wiring to the unit. Wire “Y” from thermostat to “Y” Complete C when a motorized valve is not used. “O” terminal is not used in cooling only applications. Thermostat wiring must be Class 1 and voltage rating equal to or greater than unit supply voltage.

6.24-v alarm signal shown. For dry alarm contact, cut JW1 jumper and for anti-freeze solutions, cut JW3 jumper.

7.Transformer secondary ground via green wire with yellow stripe from “C” terminal to control box.

8.Hot water generator pump only in models with hot water generation and internal pump option.

9.For auxiliary staging options, consult electric heat installation manual.

10.Fan motors factory wired for medium speed. For high or low speed, remove BLU wire from fan motor speed trap “M” and connect to “H” for high speed or “L” for low speed.

11.Aquastat is with unit and must be wired in series with the hot leg to the pump. Aquastat is rated for voltage up to 277 v.

Fig. 13 — 50PCH,PCV Units with Complete C Controller, Single-Phase

12

Deluxe D

 

 

LEGEND

 

 

 

 

 

 

 

 

 

 

 

AL

Alarm Relay Contacts

LOC

Loss of Charge Pressure Switch

 

 

 

 

 

 

 

 

 

 

Relay/Contactor Coil

BM

Blower Motor

MV

Motorized Valve

 

 

 

 

 

 

 

 

 

 

BMC

Blower Motor Capacitor

MVES

Motorized Valve End Switch

 

 

 

 

 

 

 

 

 

 

 

CB

Circuit Breaker

NEC

National Electrical Code

 

 

 

 

 

 

 

 

 

 

Condensate Pan

 

 

 

 

 

 

 

 

 

 

CC

Compressor Contactor

P1

Field Wiring Terminal Block

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CO

Sensor, Condensate Overflow

RVS

Reversing Valve Solenoid

 

 

 

 

 

 

 

 

 

 

Solenoid Coil

FP1

Sensor, Low Temperature Protection Water Coil

TRANS

Transformer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FP2

Sensor, Low Temperature Protection Air Coil

TXV

Thermostatic Expansion Valve

 

 

 

 

 

 

 

 

 

 

Thermistor

HP

High-Pressure Switch

 

Field Line Voltage Wiring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HPWS

High-Pressure Water Switch

 

 

 

 

 

 

 

 

 

 

 

Ground

 

Field Low Voltage Wiring

 

 

 

 

 

 

 

 

 

 

HWTS

High Leaving Water Temperature Switch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

JW1

Jumper, Alarm

 

Printed Circuit Trace

 

 

 

 

 

 

 

 

 

 

Wire Nut

*Optional.

 

 

Optional Wiring

 

 

 

 

 

 

 

 

 

 

 

NOTES:

1.Compressor thermally protected internally.

2.All wiring to the unit must comply with NEC and local codes.

3.Transformer is wired to 208-v RED lead for 208-3-60 units. For 230-3-60, switch RED and ORG leads at L1 and insulate RED lead. Transformer is energy limiting or may have circuit breaker.

4.FP1 thermistor provides freeze protection for water. When using antifreeze solutions, cut JW3 jumper.

5.Refer to microprocessor control, LON, or thermostat installation instructions for wiring to the unit. Wire “Y” from thermostat to “Y1” Deluxe D

a50-8491

when motorized valve is not used. Thermostat wiring must be Class 1 and voltage rating equal to or greater than unit supply voltage. Heat/cool thermostats not compatible with motorized water valve.

6.24-v alarm signal shown. For dry alarm contact, cut JW4 jumper and dry contact will be available between AL1 and AL2.

7.Transformer secondary ground via green wire with yellow stripe from “C” terminal to control box.

8.Blower motor is factory wired for medium and high speeds. For any other combination of speeds, attach black wire to the higher of the two desired speed taps and the blue wire to the lower of the two desired speed taps.

Fig. 14 — 50PCH,PCV Units with Deluxe D Controller, Three-Phase (208/230 V)

Deluxe D

13

 

 

LEGEND

 

 

 

 

 

 

 

 

 

 

 

 

 

AL

Alarm Relay Contacts

LOC

Loss of Charge Pressure Switch

 

 

 

 

 

 

 

 

 

 

Relay/Contactor Coil

 

BM

Blower Motor

MV

Motorized Valve

 

 

 

 

 

 

 

 

 

 

 

BMC

Blower Motor Capacitor

MVES

Motorized Valve End Switch

 

 

 

 

 

 

 

 

 

 

 

 

BR

Blower Relay

NEC

National Electrical Code

 

 

 

 

 

 

 

 

 

 

Condensate Pan

 

 

 

 

 

 

 

 

 

 

 

 

CB

Circuit Breaker

P1

Field Wiring Terminal Block

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CC

Compressor Contactor

PB

Power Block

 

 

 

 

 

 

 

 

 

 

Solenoid Coil

 

CO

Sensor, Condensate Overflow

RVS

Reversing Valve Solenoid

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FP1

Sensor, Low Temperature Protection Water Coil

TRANS

Transformer

 

 

 

 

 

 

 

 

 

 

Thermistor

 

FP2

Sensor, Low Temperature Protection Air Coil

TXV

Thermostatic Expansion Valve

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HP

High-Pressure Switch

 

Field Line Voltage Wiring

 

 

 

 

 

 

 

 

 

 

Ground

 

HPWS

High-Pressure Water Switch

 

Field Low Voltage Wiring

 

 

 

 

 

 

 

 

 

 

Wire Nut

a50-8492

 

 

 

 

 

 

 

 

 

 

 

JW1

Clippable Field Selection Jumper

 

 

 

 

 

 

 

 

 

 

 

 

Printed Circuit Trace

 

 

 

 

 

 

 

 

 

 

*Optional.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Optional Wiring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTES:

 

 

6.

24-v alarm signal shown. For dry alarm contact, cut JW4 jumper and dry

 

1. Compressor thermally protected internally.

 

 

contact will be available between AL1 and AL2.

 

2. All wiring to the unit must comply with NEC and local codes.

 

7.

Transformer secondary ground via green wire with yellow stripe from “C”

 

3. Transformer is wired to 460-v BLK/RED lead for 460-3-60 units or 575-v

 

terminal to control box.

 

 

 

 

 

 

 

 

 

 

 

 

GRY lead for 575-3-60 units. Transformer is energy limiting or may have

8.

Blower motor is factory wired for medium and high speeds. For any

 

circuit breaker.

 

 

other combination of speeds, attach black wire to the higher of the two

 

4. FP1 thermistor provides low temperature protection for water. When

 

desired speed taps at the motor. Attach the blue wire to the lower of the

 

using antifreeze solutions, cut JW3 jumper.

 

 

two desired speed taps.

 

 

 

 

 

 

 

 

 

 

 

 

5. Refer to microprocessor control, LON, or thermostat installation instruc-

9.

Blower motor is factory wired for high and low speeds. No other combi-

 

tions for wiring to the unit. Wire “Y” from thermostat to “Y1” Deluxe D

 

nation of speeds is available.

 

 

 

 

 

 

 

 

 

 

 

 

when motorized valve is not used. Thermostat wiring must be Class 1

10.

The 460-v units using an internal secondary pump will require a neutral

 

and voltage rating equal to or greater than unit supply voltage. Heat/cool

 

wire from the supply side in order to feed the accessory with 265-v.

 

thermostats not compatible with motorized water valve.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 15 — 50PCH,PCV Units with Deluxe D Controller, Three-Phase (460 V)

a50-8493

Complete C

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL

Alarm Relay Contacts

P1

Field Wiring Terminal Block

 

 

 

 

BM

Blower Motor

RVS

Reversing Valve Solenoid

 

 

 

Thermistor

BMC

Blower Motor Capacitor

TRANS

Transformer

 

 

 

Ground

BR

Blower Relay

TXV

Thermostatic Expansion Valve

 

 

 

CB

Circuit Breaker

 

 

 

 

 

Field Line Voltage Wiring

 

 

 

Wire Nut

CC

Compressor Contactor

 

 

 

 

 

 

 

 

 

 

 

 

 

Field Low Voltage Wiring

 

 

 

CO

Sensor, Condensate Overflow

 

 

 

 

 

 

 

 

Relay Contacts - N.C.

FP1

Sensor, Low Temperature Protection, Water Coil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Printed Circuit Trace

 

 

 

 

 

 

 

 

 

 

 

FP2

Sensor, Low Temperature Protection, Air Coil

 

 

 

 

 

Optional Wiring

 

 

 

 

 

 

Relay Contacts - N.O.

HP

High-Pressure Switch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HPWS — High-Pressure Water Switch

 

 

 

 

 

Relay/Contactor Coil

 

 

 

Low Pressure Switch

 

 

 

 

 

 

 

 

JW1

Clippable Field Selection Jumper

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOC

Loss of Charge Pressure Switch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High Pressure Switch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LON

Local Operating Network

 

 

 

 

 

Condensate Pan

 

 

 

 

 

MV

Motorized Valve

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Splice Cap

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MVES

Motorized Valve End Switch

 

 

 

 

 

Solenoid Coil

 

 

 

Circuit Breaker

NEC

National Electrical Code

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temperature Switch

 

 

 

*Optional Wiring.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTES:

1.Compressor and blower motor thermally protected internally.

2.All wiring to the unit must comply with NEC and local codes.

3.Transformer is wired to 460 v BLK/RED lead for 460-3-60 units. Transformer is energy limiting or may have circuit breaker.

4.FP1 thermistor provides low temperature protection for water. When using antifreeze solutions, cut JW3 jumper.

5.Refer to microprocessor control, LON, or thermostat installation instructions for wiring to the unit. Wire “N01” from LON to “Y1” Complete C when a motorized valve is not used. Low voltage wiring must be Class 1 and voltage rating equal to or greater than unit supply voltage.

6.Factory cut JW1 jumper. Dry contact will be available between AL1 and AL2.

7.Transformer secondary ground via green wire with yellow strip from “C” terminal to control box.

8.Fan motors are factory wired for medium speed. For high or low speed, remove BLU wire from fan motor speed tap “M” and connect to “H” for high speed or “L” for low speed.

9.For low speed, remove BLK wire from BR “6” and replace with RED. Connect BLK and BRN wires together.

10.Optional LON wires. Only connect if LON connection is desired at the wall sensor.

11.For blower motors with leads. For medium or low speed, disconnect BLK wire from BR “6”. Connect BLK and ORG/PUR wire together. Connect RED for low or BLU for medium to BR “6”.

12.Blower motor factory wired to medium speed. For low speed remove BLU wire from medium tap and connect to low speed tap. For high speed, remove BLU wire from exisiting speed tap and remove BRN jumper wire from high speed tap. Connect BLU wire to high speed tap. Tape off unconnected end of BRN jumper.

13.The 460-v units using an internal secondary pump will require a neutral wire from the supply side in order to feed the accessory with 265-v.

Fig. 16 — 50PCH,PCV Units with Complete C and LON Controller (460 V)

Carrier 50PCH User Manual

15

a50-8440

Deluxe D

 

 

 

LEGEND

 

 

 

 

 

 

AL

Alarm Relay Contacts

P1

Field Wiring Terminal Block

 

 

 

 

 

 

BM

Blower Motor

RVS

Reversing Valve Solenoid

 

 

 

 

 

 

BMC

Blower Motor Capacitor

TRANS

Transformer

 

 

 

 

 

 

 

 

 

 

 

 

BR

Blower Relay

TXV

Thermostatic Expansion Valve

 

 

 

 

 

 

CB

Circuit Breaker

 

 

 

 

 

 

 

 

 

 

 

Field Line Voltage Wiring

 

 

 

 

 

 

CC

Compressor Contactor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Field Low Voltage Wiring

 

 

 

 

 

 

CO

Sensor, Condensate Overflow

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FP1

Sensor, Low Temperature Protection, Water Coil

 

 

 

 

 

 

 

 

 

 

 

Printed Circuit Trace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FP2

Sensor, Low Temperature Protection, Air Coil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Optional Wiring

 

 

 

 

 

 

HP

High-Pressure Switch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HPWS — High-Pressure Water Switch

 

 

 

 

 

 

 

 

 

 

 

Relay/Contactor Coil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

JW1

Clippable Field Selection Jumper

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOC

Loss of Charge Pressure Switch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LON

Local Operating Network

 

 

 

 

 

 

 

 

 

 

 

Condensate Pan

 

 

 

 

 

 

 

MV

Motorized Valve

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MVES

Motorized Valve End Switch

 

 

 

 

 

 

 

 

 

 

 

Solenoid Coil

 

 

 

 

 

 

 

NEC

National Electrical Code

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Optional Wiring.

 

 

 

 

 

 

 

 

 

 

 

Temperature Switch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Thermistor

Ground

Wire Nut

Relay Contacts - N.C.

Relay Contacts - N.O.

Low Pressure Switch

High Pressure Switch

Splice Cap

Circuit Breaker

NOTES:

1.Compressor and blower motor thermally protected internally.

2.All wiring to the unit must comply with NEC and local codes.

3.Transformer is wired to 460-v BLK/RED lead for 460-3-60 units. Transformer is energy limiting or may have circuit breaker.

4.FP1 thermistor provides low temperature protection for water. When using antifreeze solutions, cut JW3 jumper.

5.Refer to microprocessor control, LON, thermostat installation instructions for wiring to the unit. Wire “N01” from LON to “Y1” Deluxe D when motorized valve is not used. Thermostat wiring must be Class 1 and voltage rating equal to or greater than unit supply voltage.

6.Factory cut JW4 jumper. Dry contact will be available between AL1 and AL2.

7.Transformer secondary ground via green wire with yellow stripe from “C” terminal to control box.

8.Blower motor is factory wired for medium and high speeds. For any other combination of speeds, attach black wire to the higher of the two desired speed taps at the motor, and attach the blue wire to the lower of the two desired speed taps.

9.Blower motor is factory wired for high and low speeds. No other combination is available.

10.Optional LON wires. Only connect if LON connection is desired at the wall sensor.

11.The 460-v units using an internal secondary pump will require a neutral wire from the supply side in order to feed the accessory with 265-v.

Fig. 17 — 50PCH,PCV units with Deluxe D and LON Controller (460 V)

WHSP-OPEN

FSD

16

-A50

 

8697

 

LEGEND

BM

Blower Motor

BR

Blower Relay

CO

Condensate Overflow

FSD

Fire Smoke Detector

LWT

Leaving Water Temperature

N.C.

Normally Closed

OAD

Outside Air Damper

OCC

Occupancy Input Contact

RH

Relative Humidity

SAT

Supply Air Temperature

SPT

Space Temperature

Fig. 18 — Units with Complete C and WSHP Open Multiple Protocol Controls

Loading...
+ 36 hidden pages