Carrier’s versatile belted fan coil units satisfy design requirements:

A selection of 8 sizes covers capacities from 600 to 4000 cfm

Choice of motors, from 1/4 to 5 hp, eliminates oversizing

Wide range of coil options for 2-pipe or 4-pipe systems

Optional DX coils with expansion valve and distributor

Single and three-phase electric heat (1.0 to 40 kW)

Features/Benefits

The 42BHC, BVC belt drive fan coil units provide yearround comfort air conditioning with central station operating economy.

A variety of coil options reduces first cost

Four, 6 or 8-row cooling coils combine needed capacities with the most efficient heat transfer surface. For 4-pipe systems, select either of two split-coil options. Coils consist of aluminum fins securely bonded to 1/2-in. OD seamless copper tubes. Each fin’s aluminum collar ensures accurate con-

trol of the fin spacing, while completely covering the tubes to lengthen coil life. All coils also feature manual air vents, with automatic air vent available as an option.

Copyright 2005 Carrier Corporation

Form 42B-1PD

Fan wheels are designed to provide low operating costs

The forward-curved, centrifugal, double-inlet fans are statically and dynamically balanced at the factory to minimize transmission of vibration

to the building structure.

The belt-driven motor (single or three phase) has a variable-pitch pulley which adjusts at the jobsite to accommodate limited ranges of air quantities and pressures.

All motors (single and three phase) are UL listed, factory wired, single speed with thermal overload protection and are continuous duty rated. Motors are supplied with permanently lubricated bearings, class-B insulation and are open drip-proof. The motor mount has an adjustable platform for easy belt adjustment. The motor and its mounting are independently isolated from the cabinet and the blower. An adjustable pitch pulley allows cfm balancing to meet system requirements. Motor drive packages are provided with keyed pulleys.

Complete factory assembly minimizes on-the-jobsite costs and problems

Compact, lightweight units are designed for easy mounting. Knockouts designed to accept 3/8-in. threaded rods are

provided on the top and bottom of each corner of the unit One-in. duct collars on discharge and on return are furnished standard. These integral duct collars cut installation time and labor expense.

Durable construction means easy-to-maintain units

The 42BHC,BVC fan coils casings are fabricated from heavy-gage galvanized G90 steel, reinforced for maximum rigidity and structural strength. Removable side panels with tool-less camlock fasteners allow easy access for servicing interior components.

One-inch matte surface, fiberglass thermal/acoustical insulation lines the fan coil cabinets to prevent sweating and to muffle sound transmission.

The stainless steel, double-sloped condensate drain pan extends under full coil surface to cut maintenance costs.

Slide-in return-duct collar filter makes it possible to remove and replace the filter without disturbing return air ductwork.

Table of contents

Page

Features/Benefits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1,2

Model Number Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Physical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Options and Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4,5

Base Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-13

Accessory Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-18

Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19-21

Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23-33

Typical Wiring Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34-36

Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

Guide Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39,40

INTERNAL FEATURES OF A 42BHC FAN COIL UNIT

2

Model number nomenclature

42BH C 08 L

42BH — Vertical Belt Drive Fan Coil Unit

42BV — Vertical Belt Drive Fan Coil Unit

C — Design

Size — Nominal Cfm

06 — 600

08 — 800

10 — 1000

12 — 1200

16 — 1600

20 — 2000

30 — 3000

40 — 4000

NOTE: Refer to current 42 Series Master Prices for complete model definition, including motor, cfm and total static pressure.

Coil — Rows

B — 4, 2-Pipe

L — 6, 2-Pipe

H — 4/1, Same End Conn.

K — 4/2, Same End Conn.

N — 6/1, Same End Conn.

Q— 6/2, Same End Conn.

R— 8, 2-Pipe

1— 4 With Electric Heat

2— 6 With Electric Heat

3— 8 With Electric Heat

Physical data

UNIT SIZE 42BHC, BVC

06

 

08

 

10

 

12

 

16

 

20

 

30

 

40

NOMINAL CFM

600

 

800

 

1000

 

1200

 

1600

 

2000

 

3000

 

4000

42BHC SHIPPING WT (lb)

203/234

 

205/236

 

253/287

 

256/290

 

312/346

 

344/380

 

437/474

 

553/590

(no heat/ with heat)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

42BVC SHIPPING WT (lb)

200/231

 

202/233

 

243/277

 

247/281

 

289/323

 

351/387

 

436/473

 

522/559

(no heat/ with heat)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FILTERS (2 in. pleated)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Number...Size (in.)

1...161/2 x 24

 

1...161/2 x 24

 

1...181/4 x 33

 

1...181/4 x 33

2...181/4 x 211/2

 

2...203/4 x 22

 

2...29 x 22

 

2...29 x 29

Face Area (sq ft)

2.8

 

2.8

 

4.2

 

4.2

 

5.5

 

6.3

 

8.9

 

11.7

COILS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Size (in.)

15 x 20

 

15 x 20

 

15 x 29

 

15 x 29

 

15 x 39

 

18 x 40

 

27 x 40

 

27 x 54

Face Area (sq ft)

2.1

 

2.1

 

3.0

 

3.0

 

4.1

 

4.9

 

7.7

 

10.3

Fins per inch

 

 

 

 

 

10

 

 

 

 

 

 

 

Coil Water Weight (approx. lb per

0.240

 

0.240

 

0.324

 

0.324

 

0.420

 

0.492

 

0.768

 

1.020

 

 

 

 

 

 

 

row of coil)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FANS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Number...Size (in.)

1...9 x 4

 

1...9 x 6

 

1...10 x 4

 

1...10 x 7

 

1...11 x 10

 

1...12 x 9

 

1...12 x 12

 

1...15 x 12

COPPER COIL CONN. 8 ROW

 

 

 

 

1 OD

 

 

 

 

11/2 OD

(in.) (Cooling)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COPPER COIL CONN. 4 AND 6 ROW

 

3/4

 

OD

 

 

 

1 OD

 

11/2 OD

(in.) (Cooling)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COPPER COIL CONN. 1 AND 2 ROW

 

 

 

 

 

 

1/2 OD

 

 

 

 

 

 

 

(in.) (Heating)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DRAIN CONN. SIZES (in.)

 

 

 

 

 

 

3/4 MPT

 

 

 

 

 

 

 

3

Options and accessories

42BHC, BVC OPTIONS AND ACCESSORIES

ITEM

OPTION*

ACCESSORY†

Automatic Air Vents

X

 

Controls

X

 

Electric Heat

X

 

Filters

X

 

Heating/Cooling Coils

X

 

Insulation

X

 

Mixing Boxes

 

X

Motors

X

 

Thermostats

 

X

Valve Packages

 

X

*Factory-installed option.

 

 

†Field-installed accessory.

 

 

The 42BHC and 42BVC fan coil units are designed to offer maximum flexibility in an application, accessibility for service, quiet operation and durability.

Factory-installed options

Automatic air vents — Automatic air vents have fiberwashers, which allow air in the pipes to pass through, automatically bleeding the system. The fiber washers eliminate the need to manually remove air from the system. When wet, washers swell and seal the system.

Coils — Coils are available in a choice of two-pipe system with 4-row cooling/heating or four-pipe system with 4, 6 or 8-row cooling and 1 or 2 row heating.

Reheat operation is standard. Preheat is available as an option.

Controls

Interlocking disconnect switch

Heater power fusing

24 v Class 2 transformer (40 va)

8-pole control terminal strip

Auto reset temperature limit switch

Airflow safety switch

Motor power fusing

Motor control contactor

24 v condensate overflow switch

Electric heat — Total electric heat eliminates the requirement for a boiler. Heating and/or cooling may be available on an individual basis throughout the year. Resistance electric heat is available from 1.0 kW to 40.0 kW (refer to

electric heater data table for availability per unit) with single-stage or multiple-stage, single power source.

Voltages:

115 v, 208 v, 230 v and 277 v single-phase 60 Hz

208 v, 230 v and 480 v three-phase 60 Hz

Electric heat is available with the following staging options (3-phase staging is balanced).

1 to 12 kW 1 stage only — single phase

3 to 12 kW 1 or 2 stage only — single phase

1 to 40 kW 1 stage only — 3 phase

4 to 40 kW 1 or 2 stage only — 3 phase

12 to 40 kW 1, 2, or 3 stage — 3 phase

Heater coils are constructed of high-grade resistance wire that is supported by ceramic insulators on plated steel brackets. These heat elements are suspended directly in front of the outlet after the blower and the coil. High limit thermal cutouts protect the heater in the event of air failure.

Filters — Two in. pleated filters are standard. One-in. pleated, two 1-in. throwaway, or 2-in. MERV (minimum efficiency reporting value) 11 filters with 2-in. pleated pre-filter are available. The 2-in. MERV 11 filters with 2-in. pleated pre-filter include a filter rack.

Insulation — Tuf-Skin™ II (1-in. thick) insulation is standard. Units are available with ¾-in. closed cell, 1-in. Tuf-Skin Rx™ edge sealed, or 1-in. foil-faced insulation.

Motors — A wide selection of standard motors provides efficient operation in ducted applications with excellent performance with up to 2 inches of total static pressure.

Available motor options:

115 v, 208 v, 230 v and 277 v single-phase 60 Hz

208 v, 230 v and 460 v three-phase 60 Hz

Open drip-proof motors

External junction box

Field-installed accessories

Mixing boxes — Mixing boxes can be used when outside air is required for ventilation. Preassembled at the factory and shipped separately with base rails for field installation, mixing boxes include a linkage kit consisting of two crank arms, 2 swivels and either a 25 in. long (for sizes 06-16) or a 84 in. long (for sizes 20-40) rod for field installation of an actuator.

4

Thermostats — Three thermostats are available for field installation:

Honeywell T834C manual changeover, single-stage heat thermostat features:

off-cool-heat system switch

on-auto fan mode switch

single-stage electric heat

outside air signal

Honeywell T8500 digital, automatic/manual changeover, 2-stage heat thermostat features:

digital display of temperatures and all functions

off-cool-heat-auto system mode buttons

single speed fan operation

on-auto fan mode button

single or two stage electric heat signal

outside air signal

remote temperature sensor available

Sunne T170 single-stage heat, 2-pipe heat/cool auto changeover thermostat features:

digital display of ambient temperature and operating mode

single fan speed operation, power and operating mode buttons

continuous fan operation, cycling water control valve

4-pipe ACO/MCO (automatic changeover/manual changeover) with “on-auto” fan mode button

one or 2 stage electric heat signal available

purge cycle and temperature sensor for 2-pipe cold water/hot water systems

programmable operating range, dead band, digital display, temperature set-back

THERMOSTAT FUNCTIONS

 

 

 

 

THERMOSTATS

 

SYSTEM

FUNCTION

CHANGEOVER

Honeywell

Honeywell

Sunne

 

 

 

 

T834C

T8500

T170

2 Pipe

HW-Heat Only

ACO

X

X

2 Pipe

CW-Cool Only

ACO

X

X

2 Pipe

CW/HW

MCO

X

Heat/Cool

ACO

X

 

 

 

 

CW/HW

MCO

X

2 Pipe

Heat/Cool with

ACO

X

 

 

Aux. Electric Heat

2 Pipe

CW-Cooling with

MCO

X

X

X

Total Electric Heat

ACO

X

X

 

 

4 Pipe

CW/HW

MCO

X

X

X

Heat/Cool

ACO

X

X

 

 

 

LEGEND

 

 

 

 

ACO — Automatic Changeover

 

 

 

Aux

Auxiliary

 

 

 

 

CW

Chilled Water

 

 

 

 

HW — Hot Water

MCO — Manual Changeover

Valve packages — Valve packages are factory assembled for field installation. Motorized valves (24 v) can be operated with power on with spring return or power off/power on.

It is recommended that basic motor controls are ordered when valve packages are ordered.

5

Base unit dimensions

42BHC FAN COIL BASE UNIT (NO CONTROLS)

UNIT

 

 

 

 

 

 

DIMENSIONS (in.)

 

 

 

 

 

 

 

 

 

 

 

 

Supply Duct

 

Return Duct

Mounting Holes

42BHC

Fan Size

Depth

Width

Height

 

 

A

B

C

D

E

F

J

K

 

 

 

 

 

 

 

06

 

9 x

4

363/16

2811/16

181/2

71/8

109/16

137/8

11/8

241/16

167/16

273/16

351/4

08

 

9 x

6

363/16

2811/16

181/2

89/16

109/16

137/8

11/8

241/16

167/16

273/16

351/4

10

 

10 x

4

373/4

371/16

201/4

71/2

1111/16

137/8

11/8

331/16

183/16

363/16

3613/16

12

 

10 x

7

373/4

371/16

201/4

915/16

1111/16

137/8

11/8

331/16

183/16

363/16

3613/16

16

 

11 x 10

3715/16

471/16

201/4

135/16

1211/16

1613/16

11/8

431/16

183/16

463/16

37

20

 

12 x

9

403/8

481/16

223/4

121/2

133/4

173/4

11/8

441/16

2011/16

473/16

397/16

30

 

12 x 12

403/8

481/16

31

157/8

133/4

161/16

61/8

441/16

2815/16

473/16

397/16

40

 

15 x 12

439/16

621/16

31

167/16

161/16

2213/16

51/8

581/16

2815/16

613/16

425/8

NOTES:

1.All dimensions are in inches (±1/4 in.).

2.Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to change without notice.

3.Right hand shown, left hand opposite.

4.Hanger rods, which are field-supplied, are shown for reference only.

6

42BHC FAN COIL WITH MOTOR CONTROL OPTION

UNIT

 

 

 

 

 

DIMENSIONS (in.)

 

 

 

 

 

 

 

 

 

 

 

Supply Duct

 

Return Duct

Mounting Holes

42BHC

Fan Size

Depth

Width

Height

 

 

A

B

C

D

E

F

J

K

 

 

 

 

 

 

06

9 x

4

363/16

2811/16

181/2

71/8

109/16

137/8

11/8

241/16

167/16

273/16

351/4

08

9 x

6

363/16

2811/16

181/2

89/16

109/16

137/8

11/8

241/16

167/16

273/16

351/4

10

10 x

4

373/4

371/16

201/4

71/2

1111/16

137/8

11/8

331/16

183/16

363/16

3613/16

12

10 x

7

373/4

371/16

201/4

915/16

1111/16

137/8

11/8

331/16

183/16

363/16

3613/16

16

11 x 10

3715/16

471/16

201/4

135/16

1211/16

1613/16

11/8

431/16

183/16

463/16

37

20

12 x

9

403/8

481/16

223/4

121/2

133/4

173/4

11/8

441/16

2011/16

473/16

397/16

30

12 x 12

403/8

481/16

31

157/8

133/4

161/16

61/8

441/16

2815/16

473/16

397/16

40

15 x 12

439/16

621/16

31

167/16

161/16

2213/16

51/8

581/16

2815/16

613/16

425/8

NOTES:

1.All dimensions are in inches (±1/4 in.).

2.Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to change without notice.

3.Right hand shown, left hand opposite.

4.Hanger rods, which are field-supplied, are shown for reference only.

7

Base unit dimensions (cont)

42BHC FAN COIL WITH ELECTRIC HEAT OPTION

UNIT

 

 

 

 

 

DIMENSIONS (in.)

 

 

 

 

 

 

 

 

 

 

 

Supply Duct

 

Return Duct

Mounting Holes

42BHC

Fan Size

Depth

Width

Height

 

 

A

B

C

D

E

F

J

K

 

 

 

 

 

 

06

9 x

4

363/16

2811/16

181/2

71/8

109/16

137/8

11/8

241/16

167/16

273/16

351/4

08

9 x

6

363/16

2811/16

181/2

89/16

109/16

137/8

11/8

241/16

167/16

273/16

351/4

10

10 x

4

373/4

371/16

201/4

71/2

1111/16

137/8

11/8

331/16

183/16

363/16

3613/16

12

10 x

7

373/4

371/16

201/4

915/16

1111/16

137/8

11/8

331/16

183/16

363/16

3613/16

16

11 x 10

3715/16

471/16

201/4

135/16

1211/16

1613/16

11/8

431/16

183/16

463/16

37

20

12 x

9

403/8

481/16

223/4

121/2

133/4

173/4

11/8

441/16

2011/16

473/16

397/16

30

12 x 12

403/8

481/16

31

157/8

133/4

161/16

61/8

441/16

2815/16

473/16

397/16

40

15 x 12

439/16

621/16

31

167/16

161/16

2213/16

51/8

581/16

2815/16

613/16

425/8

NOTES:

1.All dimensions are in inches (±1/4 in.).

2.Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to change without notice.

3.Right hand shown, left hand opposite.

4.Hanger rods, which are field-supplied, are shown for reference only.

8

42BVC FAN COIL BASE UNIT (NO CONTROLS)

UNIT

 

 

 

 

DIMENSIONS (in.)

 

 

 

 

 

 

 

 

 

 

 

Supply Duct

 

Return Duct

42BVC

Fan Size

Depth

Width

Height

 

 

A

B

 

C

E

F

 

 

 

 

 

 

 

06

9 x

4

20

281/16

361/2

71/8

109/16

 

33/4

241/16

167/16

08

9 x

6

20

281/16

361/2

89/16

109/16

 

33/4

241/16

167/16

10

10 x

4

22

371/16

393/8

71/2

1111/16

 

51/2

331/16

183/16

12

10 x

7

22

371/16

393/8

915/16

1111/16

 

51/2

331/16

183/16

16

11 x 10

22

471/16

393/8

135/16

1211/16

 

167/8

431/16

183/16

20

12 x

9

24

481/16

451/8

121/2

133/4

 

1713/16

441/16

2011/16

30

12 x 12

28

481/16

543/16

157/8

133/4

 

161/8

441/16

2815/16

40

15 x 12

28

621/16

575/8

167/16

161/16

 

227/8

581/16

2815/16

NOTES:

1.All dimensions are in inches (±1/4 in.).

2.Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to change without notice.

3.Right hand shown, left hand opposite.

4.Hanger rods, which are field-supplied, are shown for reference only.

9

Base unit dimensions (cont)

42BVC FAN COIL WITH MOTOR CONTROL OPTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT

 

 

 

 

 

 

DIMENSIONS (in.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Supply Duct

 

Return Duct

 

 

 

 

42BVC

Fan Size

 

Depth

Width

 

Height

 

 

 

 

 

 

 

A

B

 

C

E

F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

06

9 x

4

 

20

281/16

 

361/2

71/8

109/16

 

33/4

241/16

167/16

 

 

08

9 x

6

 

20

281/16

 

361/2

89/16

109/16

 

33/4

241/16

167/16

 

 

10

10 x

4

 

22

371/16

 

393/8

71/2

1111/16

 

51/2

331/16

183/16

 

 

12

10 x

7

 

22

371/16

 

393/8

915/16

1111/16

 

51/2

331/16

183/16

 

 

16

11 x 10

 

22

471/16

 

393/8

135/16

1211/16

 

167/8

431/16

183/16

 

 

20

12 x

9

 

24

481/16

 

451/8

121/2

133/4

 

1713/16

441/16

2011/16

 

 

30

12 x 12

 

28

481/16

 

543/16

157/8

133/4

 

161/8

441/16

2815/16

 

40

15 x 12

 

28

621/16

 

575/8

167/16

161/16

 

227/8

581/16

2815/16

 

 

 

 

NOTES:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1. All dimensions are in inches (±1/4 in.).

 

 

 

 

 

 

 

 

 

 

 

 

 

2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to

NOTES:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

change without notice.

 

 

 

 

 

 

 

 

 

 

 

 

1. All dimensions are in inches (±1/4 in.).

 

 

 

 

 

 

 

 

 

 

 

 

 

3. Right hand shown, left hand opposite.

 

 

 

 

 

 

 

 

 

 

 

2. Any modifications to product specifications by any person are

 

 

 

 

 

 

 

 

 

 

 

4. Hanger rods, which are field-supplied, are shown for reference only.

 

 

 

 

 

 

 

 

 

 

subject to acceptance of the factory. Product specifications are

 

 

 

 

 

 

 

 

 

 

 

subject to change without notice.

 

 

 

 

 

 

 

 

 

 

 

3.RH shown, LH opposite.

4.Hanger rods, which are field-supplied, are shown for reference only.

10

Carrier 42BHC, 42BVC User Manual

42BVC FAN COIL WITH ELECTRIC HEAT OPTION

UNIT

 

 

 

 

DIMENSIONS (in.)

 

 

 

 

 

 

 

 

 

 

Supply Duct

 

Return Duct

42BVC

Fan Size

Depth

Width

Height

 

 

A

B

C

E

F

 

 

 

 

 

 

06

9 x

4

20

281/16

361/2

71/8

109/16

33/4

241/16

167/16

08

9 x

6

20

281/16

361/2

89/16

109/16

33/4

241/16

167/16

10

10 x

4

22

371/16

393/8

71/2

1111/16

51/2

331/16

183/16

12

10 x

7

22

371/16

393/8

915/16

1111/16

51/2

331/16

183/16

16

11 x 10

22

471/16

393/8

135/16

1211/16

167/8

431/16

183/16

20

12 x

9

24

481/16

451/8

121/2

133/4

1713/16

441/16

2011/16

30

12 x 12

28

481/16

543/16

157/8

133/4

161/8

441/16

2815/16

40

15 x 12

28

621/16

575/8

167/16

161/16

227/8

581/16

2815/16

NOTES:

1.All dimensions are in inches (±1/4 in.).

2.Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to change without notice.

3.Right hand shown, left hand opposite.

4.Hanger rods, which are field-supplied, are shown for reference only.

11

Base unit dimensions (cont)

42BHC UNIT CORNER WEIGHTS (lb)

1

 

2

 

 

2

1

4

3

 

 

 

4

3

 

 

RIGHT HAND UNIT

 

 

 

 

LEFT HAND UNIT

 

 

 

 

 

 

 

 

 

 

 

UNIT

CONFIGURATION

RIGHT-HAND UNITS

LEFT-HAND UNITS

TOTAL

42BHC

1

2

3

4

1

2

3

4

WEIGHT

 

06

No Heat

50

55

47

51

55

50

51

47

203

With Heat

50

58

59

67

58

50

67

59

234

 

08

No Heat

51

55

47

52

55

51

52

47

205

With Heat

50

59

59

68

59

50

68

59

236

 

10

No Heat

63

71

55

63

71

63

63

55

253

With Heat

62

76

68

81

76

62

81

68

287

 

12

No Heat

64

72

56

64

72

64

64

56

256

With Heat

63

76

68

82

76

63

82

68

290

 

16

No Heat

80

87

69

76

87

80

76

69

312

With Heat

79

91

82

95

91

79

95

82

346

 

20

No Heat

90

98

74

82

98

90

82

74

344

With Heat

90

102

88

100

102

90

100

88

380

 

30

No Heat

118

127

92

100

127

118

100

92

437

With Heat

118

131

106

119

131

118

119

106

474

 

40

No Heat

155

162

114

122

162

155

122

114

553

With Heat

155

166

129

140

166

155

140

129

590

 

NOTE: Unit weights (shown in pounds) ±10%, are based on the 8-row coil and 1 Hp motor.