Carrier 48TFD008-014, 48TFE008-014, 48TFF008-012 User Manual

4 (1)

48TFD008-014 48TFE008-014 48TFF008,012

Single-Package Rooftop Heating/Cooling Units 50 Hz

Installation, Start-Up and

Service Instructions

CONTENTS

Page

SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1

INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-33

Step 1 — Provide Unit Support . . . . . . . . . . . . . . . . . . . 1

ROOF CURB

SLAB MOUNT

Step 2 — Field Fabricate Ductwork . . . . . . . . . . . . . . . 2

Step 3 — Install External Trap for

Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Step 4 — Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . 2

• POSITIONING

 

Step 5

— Install Flue Hood . . . . . . . . . . . . . . . . . . . . . . .

8

Step 6

— Install Gas Piping . . . . . . . . . . . . . . . . . . . . . .

8

Step 7

— Make Electrical Connection . . . . . . . . . . . .

8

FIELD POWER SUPPLY

FIELD CONTROL WIRING

HEAT ANTICIPATOR SETTINGS

Step 8 — Adjust Factory-Installed Options . . . . . . 11

APOLLO CONTROL

MANUAL OUTDOOR-AIR DAMPER

OPTIONAL DURABLADE ECONOMIZER

OPTIONAL ECONOMI$ER

Step 9 — Adjust Evaporator-Fan Speed . . . . . . . . . 20

START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34-36 SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36-41 TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . 42-46 START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . CL-1

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.

Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.

Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations.

Disconnect gas piping from unit when leak testing at pressure greater than 3.4 kPa (1/2 psig). Pressures greater than 3.4 kPa (1/2 psig) will cause gas valve damage resulting in hazardous condition. If gas valve is ever subjected to pressure greater than 3.4 kPa (1/2 psig), it must be replaced before use. When pressure testing field-supplied gas piping at pressures of 3.4 kPa (1/2 psig) or less, a unit connected to such piping must be isolated by manually closing the gas valve(s).

Before performing service or maintenance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury.

INSTALLATION

Unit is shipped in the vertical discharge configuration. To convert to horizontal configuration, remove screws from side duct opening covers and remove covers. Using the same screws, install covers on vertical duct openings with the insulation side down. Seals around duct openings must be tight. See Fig. 1.

Step 1 — Provide Unit Support

ROOF CURB — Assemble and install accessory roof curb in accordance with instructions shipped with curb. See Fig. 2. Install insulation, cant strips, roofing felt, and counter flashing as shown. Ductwork must be attached to curb. If gas, electric power or control power is to be routed through the curb, attach the accessory thru-the-curb service connection plates to the roof curb in accordance with the accessory installation instructions. Connection plates must be installed before unit is set in roof curb.

IMPORTANT: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket supplied with the roof curb as shown in Fig. 2. Improperly applied gasket can also result in air leaks and poor unit performance.

Curb should be level. Unit leveling tolerances are shown in Fig. 3. This is necessary for unit drain to function properly. Refer to Accessory Roof Curb Installation Instructions for additional information as required.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book

1

4

Catalog No. 004-816

Printed in U.S.A.

Form 48TF-C1SI

Pg 1

1-01

Replaces: New

Tab

1a

6a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SLAB MOUNT (Horizontal Units Only) — Provide a level concrete slab that extends a minimum of 152 mm (6 in.) beyond unit cabinet. Install a gravel apron in front of condenser coil air inlet to prevent grass and foliage from obstructing airflow.

NOTE: Horizontal units may be installed on a roof curb if required.

Step 2 — Field Fabricate Ductwork — Secure all ducts to roof curb and building structure on vertical units. Do not connect ductwork to unit. For horizontal applications, fieldsupplied flanges should be attached to horizontal discharge openings and all ductwork secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.

Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier.

If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes.

A minimum clearance is not required around ductwork. Cabinet return-air static shall not exceed –87 Pa (–.35 in. wg) with Durablade economizer, –26 Pa (–.30 in. wg) with EconoMi$er or –112 Pa (–.45 in. wg) without economizer.

These units are designed for a minimum heating operation continuous return-air temperature of 10 C (50 F) (dry bulb), or an intermittent operation down to 7 C (45 F) (dry bulb), such as when used with a night set-back thermostat.

Step 3 — Install External Trap for Condensate Drain — The unit’s 19-mm (3/4-in.) condensate drain connections are located at the bottom and side of the unit. Unit discharge connections do not determine the use of drain connections; either drain connection can be used with vertical or horizontal applications.

When using the standard side drain connection, make sure the plug (Red) in the alternate bottom connection is tight before installing the unit.

To use the bottom drain connection for a roof curb installation, relocate the factory-installed plug (Red) from the bottom connection to the side connection. See Fig. 4. The piping for the condensate drain and external trap can be completed after the unit is in place.

All units must have an external trap for condensate drainage. Install a trap at least 102-mm (4-in.) deep and protect against freeze-up. If drain line is installed downstream from the external trap, pitch the line away from the unit at 25 mm (1 in.) per 3 m (10 ft) of run. Do not use a pipe size smaller than the 19-mm (3/4-in.) unit connection.

Step 4 — Rig and Place Unit — Inspect unit for transportation damage. File any claim with transportation agency. Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit. Rollers may be used to move unit across a roof. Level by using unit frame as a reference. See Tables 1A and 1B and Fig. 5 for additional information. Operating weight is shown in Tables 1A and 1B and Fig. 5.

Lifting holes are provided in base rails as shown in Fig. 5 and 6. Refer to rigging instructions on unit.

All panels must be in place when rigging.

POSITIONING — Maintain clearance around and above unit to provide minimum distance from combustible materials, proper airflow, and service access. See Fig. 6.

Do not install unit in an indoor location. Do not locate unit air inlets near exhaust vents or other sources of contaminated air.

Be sure that unit is installed so that snow will not block the combustion intake or flue outlet.

Unit may be installed directly on wood flooring or on Class A, B, or C roof-covering material when roof curb is used.

(Copy continued on page 4.)

Fig. 1 — Horizontal Conversion Panels

2

Carrier 48TFD008-014, 48TFE008-014, 48TFF008-012 User Manual

CONNECTOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D ALT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

 

 

 

 

C

 

DRAIN

 

 

 

 

GAS

POWER

 

CONTROL

PKG. ACCY.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HOLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CRBTMPWR001A00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3/4

3/4″ [19] NPT

 

 

 

 

1/2

CRBTMPWR002A00

 

 

2′-87/16

 

 

1′-1015/16

13/4

 

[19] NPT

11/4″ [31.7]

 

[12.7]

 

 

CRBTMPWR003A00

 

 

 

 

 

 

 

 

1/2

3/4″ [19] NPT

 

 

 

 

1/2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[827]

 

 

 

[583]

 

 

 

 

[44.5]

 

[12.7] NPT

 

 

 

 

 

 

 

 

 

 

 

 

CRBTMPWR004A00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

11/4″ [31.7]

 

[12.7]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

/4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[19] NPT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ROOF CURB

“A”

UNIT SIZE

ACCESSORY

48TF

 

CRRFCURB003A00

1′-2″ [356]

008-014

CRRFCURB004A00

2′-0″ [610]

 

NOTES:

1.Roof curb accessory is shipped disassembled.

2.Insulated panels: 1-in. [25] thick polyurethane

foam, 13/4 lb density.

3. Dimensions in [ ] are in millimeters.

4.Roof curb: 16-gage steel.

5.Attach ductwork to curb (flanges of duct rest on curb).

6.Service clearance 4 ft [1219] on each side.

7. Direction of airflow.

8.Connector packages CRBTMPWR001A00 and 2A00 are for thru-the-curb gas type. Packages CRBTMPWR003A00 and 4A00 are for thru- the-bottom type gas connections.

Fig. 2 — Roof Curb Details

3

Although unit is weatherproof, guard against water from higher level runoff and overhangs.

Position unit on roof curb so that the following clearances are maintained: 7 mm (1/4-in.) clearance between roof curb and base rails on each side and duct end of unit; 84 mm (35/16-in.) clearance between roof curb and condenser coil end of unit. (See Fig. 2, section C-C.)

Locate mechanical draft system flue assembly at least 1219 mm (48 in.) from any opening through which combustion products could enter the building, and at least 1219 mm (48 in.) from an adjacent building or combustible material. When unit is located adjacent to public walkways, flue assembly must be at least 2.13 m (7 ft) above grade.

Flue vent discharge must have a minimum horizontal clearance of 1219 mm (48 in.) from electric and gas meters, gas regulators, and gas relief equipment.

Flue gas can deteriorate building materials. Orient unit so that flue gas will not affect building materials.

Adequate combustion-air space must be provided for proper operation of this equipment. Be sure that installation complies with all local codes and Section 5.3, Air for Combustion and Ventilation, NFGC (National Fuel Gas Code), ANSI (American National Standards Institute), latest revision, U.S.A. Standards.

(Copy continued on page 8.)

MAXIMUM ALLOWABLE

DIFFERENCE mm (in.)

A-B

B-C

A-C

13 (0.5)

25 (1.0)

25 (1.0)

Fig. 3 — Unit Leveling Tolerances

NOTES:

1. Dimension in ( ) is in millimeters.

2.Hook rigging shackles through holes in base rail as shown in detail ‘‘A.’’ Holes in base rails are centered around the unit center of gravity. Use wooden top skid when rigging to prevent rigging straps from damaging unit.

3.Weights include base unit without economizer. See Tables 1A and 1B for economizer weights.

All panels must be in place when rigging.

DRAIN PLUG

NOTE: Drain plug is shown in factory-installed position.

Fig. 4 — Condensate Drain Pan

UNIT

MAX

 

DIMENSIONS

 

 

WEIGHT

‘‘A’’

‘‘B’’

 

‘‘C’’

48TF

 

 

lb

kg

in.

mm

in.

mm

 

in.

mm

D/E/F008

870

395

87.38

2219

40.25

1022

 

41.31

1050

D/E/F012

1035

469

87.38

2219

40.25

1022

 

49.31

1253

D/E014

1050

476

87.38

2219

40.25

1022

 

49.31

1253

Fig. 5 — Rigging Details

4

Table 1A — Physical Data (SI)

UNIT SIZE 48TF

 

 

008

 

 

 

 

012

 

 

 

014

 

Low Heat (D), Medium Heat (E), High Heat (F)

D

 

 

E

 

 

F

D

 

 

E

 

 

F

D

 

 

E

NOMINAL CAPACITY (kW)

 

21.5

 

 

 

 

29.2

 

 

 

35.9

 

OPERATING WEIGHT (kg)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit

 

 

395

 

 

 

 

469

 

 

 

476

 

 

 

 

 

 

 

 

 

Durablade Economizer

 

20

 

 

 

 

20

 

 

 

20

 

EconoMi$er

 

 

28

 

 

 

 

28

 

 

 

28

 

Roof Curb*

 

 

65

 

 

 

 

65

 

 

 

65

 

COMPRESSOR TYPE

 

 

 

Hermetic

 

 

 

 

Hermetic

 

Scroll

 

Quantity

 

 

2

 

 

 

 

2

 

 

 

2

 

Oil (ml)

 

 

 

 

1479 ea

 

 

 

 

1479 ea

 

1597 ea

 

REFRIGERANT TYPE

 

 

 

 

 

 

 

 

R-22

 

 

 

 

 

Operating Charge (kg)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Circuit 1

 

 

2.10

 

 

 

 

3.08

 

 

 

3.49

 

 

 

 

 

 

 

 

 

Circuit 2

 

 

2.22

 

 

 

 

3.22

 

 

 

3.49

 

CONDENSER COIL

 

 

 

 

 

 

Enhanced Copper Tubes, Aluminum Lanced Fins

 

 

 

 

Rows...Fins/m

 

 

1...669

 

 

 

 

2...669

 

 

 

2...669

 

 

 

 

 

 

 

 

 

Total Face Area (sq m)

 

1.90

 

 

 

 

1.92

 

 

 

2.30

 

CONDENSER FAN

 

 

 

 

 

 

 

 

Propeller Type

 

 

 

 

 

Nominal L/s

 

 

2880

 

 

 

 

3050

 

 

 

3050

 

 

 

 

 

 

 

 

 

Quantity...Diameter (mm)

 

2...559

 

 

 

 

2...559

 

 

 

2...559

 

Motor BkW...r/s

 

 

.19...15.5

 

 

 

 

.19...15.5

 

 

 

.19...15.5

EVAPORATOR COIL

 

 

 

 

Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Acutrol™ Feed Device

 

Rows...Fins/m

 

 

3...590

 

 

 

 

3...590

 

 

 

4...590

 

 

 

 

 

 

 

 

 

Total Face Area (sq m)

 

0.74

 

 

 

 

0.93

 

 

 

1.03

 

EVAPORATOR FAN

 

 

 

 

 

 

 

 

Centrifugal Type

 

 

 

 

 

Quantity...Size (mm x mm)

 

 

1...381 x 381

 

 

 

1...381 x 381

 

1...381 x 381

 

 

 

 

 

Type Drive

 

 

 

 

Belt

 

 

 

 

Belt

 

Belt

 

Nominal L/s

 

 

1230

 

 

 

 

1700

 

 

 

1980

 

Motor kW

 

 

1.12

 

 

 

 

1.50

 

 

 

2.24

 

Maximum Continuous BkW

 

1.79

 

 

 

 

1.79

 

 

 

2.76

 

Motor Frame Size

 

 

56

 

 

 

 

56

 

 

 

56

 

Fan r/s Range

 

 

8.2-11.7

 

 

 

 

9.5-13.0

 

 

 

12.0-15.0

Motor Bearing Type

 

 

 

Ball

 

 

 

 

Ball

 

Ball

 

Maximum Allowable r/s

 

26.7

 

 

 

 

26.7

 

 

 

26.7

 

Motor Pulley Pitch Diameter Min/Max (mm)

 

61/86

 

 

 

 

71/97

 

 

 

102/127

 

Nominal Motor Shaft Diameter (mm)

 

16

 

 

 

 

16

 

 

 

22

 

Fan Pulley Pitch Diameter (mm)

 

178

 

 

 

 

178

 

 

 

203

 

Nominal Fan Shaft Diameter (mm)

 

25

 

 

 

 

25

 

 

 

25

 

Belt, Quantity...Type...Length (mm)

 

 

 

1...A...1245

 

 

 

 

1...A...1245

 

1...A...1346

Pulley Center Line Distance (mm)

 

425-489

 

 

 

 

403-445

 

 

 

403-445

 

Speed Change per Full Turn of

 

.70

 

 

 

 

.70

 

 

 

.60

 

Movable Pulley Flange (r/s)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Movable Pulley Maximum Full Turns

 

5

 

 

 

 

5

 

 

 

5

 

From Closed Position

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Setting

 

 

5

 

 

 

 

5

 

 

 

5

 

Factory Speed Setting (r/s)

 

8.2

 

 

 

 

9.5

 

 

 

12.0

 

Fan Shaft Diameter at Pulley (mm)

 

25

 

 

 

 

25

 

 

 

25

 

FURNACE SECTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rollout Switch Cutout Temp (C)

 

90.6

 

 

 

 

90.6

 

 

 

90.6

 

Burner Orifice Diameter (mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Natural Gas

— Std

 

3.05

 

 

 

3.05

 

 

3.05

 

 

3.28

3.05

 

 

3.28

 

 

 

 

 

 

 

Liquid Propane — Alt

 

2.44

 

 

 

2.44

 

 

2.44

 

 

2.59

2.44

 

 

2.59

Thermostat Heat Anticipator Setting (amps)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400 v Stage 1

 

.14

 

 

.14

 

 

.14

 

.14

 

 

 

.14

 

 

 

 

 

 

 

Stage 2

 

.14

 

 

.20

 

 

.20

 

.20

 

 

 

.20

 

Gas Input (kW)

Stage 1

21.1

 

 

31.9

 

 

39.8

31.9

 

 

39.8

 

 

43.9

39.8

 

 

43.9

 

 

 

 

 

 

 

 

Stage 2

31.4

 

 

50.4

 

 

59.8

50.4

 

 

59.8

 

 

65.6

59.8

 

 

65.6

Efficiency (Steady State) (%)

 

 

 

80

 

 

 

 

 

 

80

 

 

 

80

 

Temperature Rise Range (C)

–6-10

 

 

2-18

 

 

7-24

2-18

 

 

7-24

 

 

4-21

7-24

 

 

4-21

 

 

 

 

 

Manifold Pressure (kPa)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Natural Gas

— Std

 

8.3

 

 

 

 

8.3

 

 

 

8.3

 

Liquid Propane

— Alt

 

8.3

 

 

 

 

8.3

 

 

 

8.3

 

Field Gas Connection Size (mm)

13

 

 

19

 

 

19

19

 

 

19

 

 

19

19

 

 

19

 

 

 

 

 

HIGH-PRESSURE SWITCH (kPa)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard Compressor

 

 

 

 

 

 

3103 ± 345

 

 

 

 

 

 

3448 ± 345

 

 

 

 

 

 

 

 

 

 

 

 

Internal Relief (Differential)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cutout

 

 

 

 

 

 

 

 

 

2951

 

 

 

 

 

 

 

Reset (Auto.)

 

 

 

 

 

 

 

 

 

2206

 

 

 

 

 

 

 

LOW-PRESSURE SWITCH (kPa)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cutout

 

 

 

 

 

 

 

 

 

48 ± 21

 

 

 

 

 

 

 

Reset (Auto.)

 

 

 

 

 

 

 

 

152 ± 48

 

 

 

 

 

 

 

FREEZE PROTECTION THERMOSTAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Opens (C)

 

 

 

 

 

 

 

 

 

–1 ± 3

 

 

 

 

 

Closes (C)

 

 

 

 

 

 

 

 

 

7 ± 3

 

 

 

 

 

 

 

OUTDOOR-AIR INLET SCREENS

 

 

 

 

 

 

 

Cleanable

 

 

 

 

 

Quantity...Size (mm)

 

 

 

 

 

 

 

1...508 x 635 x 25

 

 

 

 

 

 

 

 

 

 

 

 

1...406 x 635 x 25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RETURN-AIR FILTERS

 

 

 

 

 

 

 

Throwaway

 

 

 

 

 

Quantity...Size (mm)

 

4...406 x 508 x 51

 

 

4...508 x 508 x 51

 

4...508 x 508 x 51

 

 

 

 

LEGEND

Bhp — Brake Horsepower

BkW — Fan Input Watts x Motor Efficiency

*Weight of 356 mm (14-in.) roof curb.

NOTE: The 48TF units have a loss-of-charge (low pressure) switch located in the liquid line.

5

Table 1B — Physical Data (English)

UNIT SIZE 48TF

 

 

008

 

 

 

 

012

 

 

 

014

Low Heat (D), Medium Heat (E), High Heat (F)

D

 

 

E

 

 

F

D

 

 

E

 

 

F

D

 

 

E

NOMINAL CAPACITY (tons)

 

6.1

 

 

 

 

8.3

 

 

 

10.2

OPERATING WEIGHT (lb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit

 

 

870

 

 

 

 

1035

 

 

 

1050

 

 

 

 

 

 

 

Durablade Economizer

 

44

 

 

 

 

44

 

 

 

44

EconoMi$er

 

 

62

 

 

 

 

62

 

 

 

62

Roof Curb*

 

 

143

 

 

 

 

143

 

 

 

143

COMPRESSOR TYPE

 

 

 

Hermetic

 

 

 

 

Hermetic

 

Scroll

Quantity

 

 

2

 

 

 

 

2

 

 

 

2

 

Oil (oz)

 

 

 

 

50 ea

 

 

 

 

50 ea

 

54 ea

REFRIGERANT TYPE

 

 

 

 

 

 

 

R-22

 

 

 

 

 

Operating Charge (lb-oz)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Circuit 1

 

 

4-10

 

 

 

 

6-13

 

 

 

7-11

 

 

 

 

 

 

 

Circuit 2

 

 

4-11

 

 

 

 

7- 2

 

 

 

7-

 

 

8

CONDENSER COIL

 

 

 

 

 

 

 

Enhanced Copper Tubes, Aluminum Lanced Fins

 

 

 

 

Rows...Fins/in.

 

 

1...17

 

 

 

 

2...17

 

 

 

2...17

 

 

 

 

 

 

 

Total Face Area (sq ft)

 

20.50

 

 

 

 

20.50

 

 

 

25.00

CONDENSER FAN

 

 

 

 

 

 

 

 

Propeller Type

 

 

 

 

 

Nominal Cfm

 

 

6100

 

 

 

 

6500

 

 

 

6500

 

 

 

 

 

 

 

Quantity...Diameter (in.)

 

2...22

 

 

 

 

2...22

 

 

 

2...22

Motor BkW...Rpm

 

 

1/4...930

 

 

 

 

1/4...930

 

 

 

1/4...930

EVAPORATOR COIL

 

 

Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Acutrol™ Feed Device

 

Rows...Fins/in.

 

 

3...15

 

 

 

 

3...15

 

 

 

4...15

 

 

 

 

 

 

 

Total Face Area (sq ft)

 

8.0

 

 

 

 

10.0

 

 

 

11.1

EVAPORATOR FAN

 

 

 

 

 

 

 

 

Centrifugal Type

 

 

 

 

 

Quantity...Size (in.)

 

 

 

1...15 x 15

 

 

 

 

1...15 x 15

 

1...15 x 15

 

 

 

 

 

 

Type Drive

 

 

 

 

Belt

 

 

 

 

Belt

 

Belt

Nominal Cfm

 

 

2600

 

 

 

 

3500

 

 

 

4200

Motor Hp

 

 

11/2

 

 

 

 

2

 

 

 

3

 

Maximum Continuous Bhp

 

2.40

 

 

 

 

2.40

 

 

 

3.70

Motor Frame Size

 

 

56

 

 

 

 

56

 

 

 

56

Fan Rpm Range

 

 

492-700

 

 

 

 

571-779

 

 

 

717-900

Motor Bearing Type

 

 

 

Ball

 

 

 

 

Ball

 

Ball

Maximum Allowable Rpm

 

1600

 

 

 

 

1600

 

 

 

1600

Motor Pulley Pitch Diameter Min/Max (in.)

 

2.4/3.4

 

 

 

 

2.8/3.8

 

 

 

4.0/5.0

Nominal Motor Shaft Diameter (in.)

 

5/8

 

 

 

 

5/8

 

 

 

7/8

Fan Pulley Pitch Diameter (in.)

 

7.0

 

 

 

 

7.0

 

 

 

8.0

Nominal Fan Shaft Diameter (in.)

 

 

 

 

 

 

 

 

Belt, Quantity...Type...Length (in.)

 

 

 

1...A...49

 

 

 

 

1...A...49

 

1...A...53

Pulley Center Line Distance (in.)

 

16.75-19.25

 

 

 

 

15.85-17.50

 

 

 

15.85-17.50

Speed Change per Full Turn of

 

41

 

 

 

 

41

 

 

 

36

Movable Pulley Flange (rpm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Movable Pulley Maximum Full Turns

 

5

 

 

 

 

5

 

 

 

5

 

From Closed Position

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Setting

 

 

5

 

 

 

 

5

 

 

 

5

 

Factory Speed Setting (rpm)

 

492

 

 

 

 

571

 

 

 

717

Fan Shaft Diameter at Pulley (in.)

 

1

 

 

 

 

1

 

 

 

1

 

FURNACE SECTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rollout Switch Cutout Temp (F)

 

195

 

 

 

 

195

 

 

 

195

Burner Orifice Diameter (in. ...drill size)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Natural Gas

— Std

 

.120...31

 

 

 

.120...31

 

 

.120...31

 

.129...30

.120...31

 

.129...30

 

 

 

 

 

 

 

Liquid Propane — Alt

 

.096...41

 

 

 

.096...41

 

 

.096...41

 

 

.102...38

.096...41

 

 

.102...38

Thermostat Heat Anticipator Setting (amps)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400 v Stage 1

 

.14

 

 

.14

 

 

.14

 

.14

 

 

 

.14

 

 

 

 

 

Stage 2

 

.14

 

 

.20

 

 

.20

 

.20

 

 

 

.20

Gas Input (Btuh)

Stage 1

72,000

 

 

109,000

 

 

136,000

109,000

 

 

136,000

 

 

150,000

136,000

 

 

150,000

 

 

 

 

 

 

 

 

107,000

 

 

172,000

 

 

204,000

172,000

 

 

204,000

 

 

224,000

204,000

 

 

224,000

Efficiency (Steady State) (%)

 

 

 

80

 

 

 

 

 

 

80

 

 

 

80

Temperature Rise Range (F)

20-50

 

 

35-65

 

 

45-75

35-65

 

 

45-75

 

 

40-70

45-75

 

 

40-70

 

 

 

 

 

Manifold Pressure (in. wg)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Natural Gas

— Std

 

3.5

 

 

 

 

3.5

 

 

 

3.5

Liquid Propane

— Alt

 

3.5

 

 

 

 

3.5

 

 

 

3.5

Field Gas Connection Size (in.)

1/2

 

 

3/4

 

 

3/4

 

3/4

 

 

 

3/4

 

 

 

 

HIGH-PRESSURE SWITCH (psig)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard Compressor

 

 

 

 

 

 

450 ± 50

 

 

 

 

 

 

500 ± 50

 

 

 

 

 

 

 

 

 

 

 

 

Internal Relief (Differential)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cutout

 

 

 

 

 

 

 

 

 

428

 

 

 

 

 

 

 

Reset (Auto.)

 

 

 

 

 

 

 

 

 

320

 

 

 

 

 

 

 

LOW-PRESSURE SWITCH (psig)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cutout

 

 

 

 

 

 

 

 

 

7 ± 3

 

 

 

 

 

 

 

Reset (Auto.)

 

 

 

 

 

 

 

 

22 ± 7

 

 

 

 

 

 

 

FREEZE PROTECTION THERMOSTAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Opens (F)

 

 

 

 

 

 

 

 

30 ± 5

 

 

 

 

 

 

 

Closes (F)

 

 

 

 

 

 

 

 

45 ± 5

 

 

 

 

 

 

 

OUTDOOR-AIR INLET SCREENS

 

 

 

 

 

 

 

Cleanable

 

 

 

 

 

Quantity...Size (in.)

 

 

 

 

 

 

 

1...20 x 25 x 1

 

 

 

 

 

 

 

 

 

 

 

 

1...16 x 25 x 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RETURN-AIR FILTERS

 

 

 

 

 

 

 

Throwaway

 

 

 

 

 

Quantity...Size (in.)

 

4...16 x 20 x 2

 

 

4...20 x 20 x 2

 

4...20 x 20 x 2

 

 

 

 

LEGEND

Bhp — Brake Horsepower

BkW — Fan Input Watts x Motor Efficiency

*Weight of 356 mm (14-in.) roof curb.

NOTE: The 48TF units have a loss-of-charge (low pressure) switch located in the liquid line.

6

 

STANDARD

DURABLADE

ECONOMI$ER

CORNER

CORNER

CORNER

CORNER

 

 

 

 

 

 

 

 

 

 

 

UNIT

ECONOMIZER

“H”

 

“J”

“K”

 

“L”

 

UNIT WEIGHT

WEIGHT

WEIGHT (A)

WEIGHT (B)

WEIGHT (C)

WEIGHT (D)

 

 

 

48TF

 

 

WEIGHT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Lb

Kg

Lb

Kg

Lb

Kg

Lb

Kg

Lb

Kg

Lb

Kg

Lb

Kg

ft-in.

[mm]

ft-in.

[mm]

ft-in.

 

[mm]

ft-in.

[mm]

D/E/F008

870

395

44

20

62

28

189

86

161

73

239

109

280

127

1-27/8

[

378]

3-55/16

[1050]

2-911/16

 

[856]

2- 27/16

 

[672]

D/E/F012

1035

469

44

20

62

28

225

102

192

87

285

129

333

151

2-57/8

[

759]

4-15/16

[1253]

3-03/8

 

[924]

2-107/16

 

[875]

D/E014

1050

476

44

20

62

28

228

103

195

88

289

131

338

153

1-27/8

[

378]

4-15/16

[1253]

3-03/8

 

[924]

2-107/16

 

[875]

NOTES:

1. Dimensions in [ ] are in millimeters.

2. Center of gravity.

3. Direction of airflow.

4.On vertical discharge units, ductwork to be attached to accessory roof curb only. For horizontal discharge units, field-supplied flanges should be attached to horizontal discharge openings, and all ductwork should be attached to the flanges.

5.Minimum clearance (local codes or jurisdiction may prevail):

a. Between unit, flue side and combustible surfaces, 36 in. [914].

b.Bottom of unit to combustible surfaces (when not using curb), 1 in. [25]. Bottom of base rail to combustible surfaces (when not using curb) 0 inches.

c.Condenser coil, for proper airflow, 36 in. [914] one side, 12 in. [304] the other. The side getting the greater clearance is optional.

d.Overhead, 60 in. [1624] to assure proper condenser fan operation.

e.Between units, control box side, 42 in. [1067] per NEC (National Electrical Code).

f.Between unit and ungrounded surfaces, control box side, 36 in. [914] per NEC.

g.Between unit and block or concrete walls and other grounded surfaces, control box side, 42 in. [1067] per NEC.

h.Horizontal supply and return end, 0 inches.

6.With the exception of the clearance for the condenser coil and combustion side as stated in notes 5a, b and c, a removable fence or barricade requires no clearance.

7.Units may be installed on combustible floors made from wood or Class A, B, or C roof covering material if set on base rail.

8.The vertical center of gravity is 1′-7″ [483] for 008, 1′-11″ [584] for 012 and 014 up from the bottom of the base rail.

CONNECTION SIZES

A13/8Dia [35] Field Power Supply Hole

B21/2Dia [64] Power Supply Knockout

C13/4Dia [44] Charging Port Hole

D7/8Dia [22] Field Control Wiring Hole

E3/4[19] - 14 NPT Condensate Drain

1/2[13] - 14 NPT Gas Connection 48TFD008

F3/4[19] - 14 NPT Gas Connection 48TFE,F008 48TFD,E012 & 014, 48TJF012

G2Dia [51] Power Supply Knockout

BOTTOM POWER CHART, THESE HOLES REQUIRED FOR USE WITH ACCESSORY PACKAGES — CRBTMPWR002A00 (POWER AND CONTROL) AND CRBTMPWR004A00 (POWER, CONTROL, AND GAS)

 

 

 

 

 

 

THREADED

 

WIRE

 

 

 

REQURED

 

 

 

 

 

 

 

 

CONDUIT

 

 

 

HOLE SIZES

 

 

 

 

 

 

 

 

 

 

 

USE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SIZE

 

 

 

 

 

 

 

(MAX.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1/2″ [12.7]

 

 

 

24 V

 

 

 

7/8[22.2]

 

 

 

 

 

 

 

11/4″ [31.7]

 

Power

 

 

13/4[44.4]

 

 

 

 

 

 

3/4″ [19] FPT

 

 

 

Gas

 

 

15/8[41.3]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 6 — Base Unit Dimensions

7

GAS REGULATOR*

Step 5 — Install Flue Hood — Flue hood is shipped screwed to the burner compartment access panel. Remove from shipping location and, using screws provided, install flue hood and screen in location shown in Fig. 7.

Step 6 — Install Gas Piping — Unit is equipped for use with type of gas shown on nameplate. Refer to local building codes.

For natural gas applications, gas pressure at unit gas connection must not be less than 13.5 kPa (4.0 in. wg) (17.0 kPa [5.0 in. wg] in high heat units) or greater than 44.0 kPa (13.0 in. wg) while unit is operating. For liquid propane applications, the gas pressure must not be less than 17.0 kPa (5.0 in. wg) or greater than 44.0 kPa (13.0 in. wg) at the unit connection.

Size gas supply piping for 1.7 kPa (0.5 in. wg) maximum pressure drop. Do not use supply pipe smaller than unit gas connection.

NOTE: When installing gas piping to gas valve inlet, use properly sized back-up wrench on inlet flange flats.

Support gas piping as shown in the table in Fig. 8. For example, a 19 mm (3/4-in.) gas pipe must have one fieldfabricated support beam every 2.4 m (8 ft).

See Fig. 8 for typical pipe guide and locations of external manual gas shutoff valve.

Step 7 — Make Electrical Connections

Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code), ANSI/NFPA (National Fire Protection Association), latest edition (U.S.A. Standards), and local electrical codes. Do not use gas piping as an electrical ground. Failure to follow this warning could result in the installer being liable for personal injury of others.

FIELD POWER SUPPLY — All units are factory wired for the voltage shown on the nameplate.

Refer to unit label diagram for additional information. Pigtails are provided for field service.

When installing units, provide a disconnect per local codes. Use copper conductors only when splice connectors are used.

All field wiring must comply with local requirements.

Install conduit through side panel openings indicated in Fig. 6. Route power lines through connector to terminal connections as shown in Fig. 9.

Voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in Table 2, Note 2 to determine the percentage of voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Carrier warranty.

NOTE: If field-installed thru-the-bottom connections are used, refer to the accessory installation instructions for power wiring. Refer to Fig. 6 for drilling holes in basepan.

Fig. 7 — Flue Hood Details

BASE UNIT

BASE RAIL

X

228 mm (9") MINIMUM CLEARANCE FOR PANELREMOVAL

MANUAL GAS SHUTOFF VALVE*

1219 mm (48") MINIMUM

DRIP LEG PER NFGC*

ROOF CURB

FIELD-FABRICATED

 

SUPPORT*

FROM GAS METER

LEGEND

NFGC — National Fuel Gas Code (U.S.A. Standard) *Field supplied.

NOTE: Follow all local codes.

SPACING OF SUPPORTS

STEEL PIPE NOMINAL DIAMETER

X DIMENSION

mm (in.)

m (ft)

13 (1/2)

1.8

(6)

19 or 25 (3/4 or 1)

2.4

(8)

32 or larger (11/4 or larger)

3.0 (10)

Fig. 8 — Gas Piping Guide (With Accessory Thru-the-Curb Service Connections)

FIELD CONTROL WIRING — Install a Carrier-approved accessory thermostat assembly according to installation instructions included with the accessory. Locate thermostat assembly on a solid wall in the conditioned space to sense average temperature in accordance with thermostat installation instructions.

NOTE: For wire runs up to 15 m (50 ft), use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 15 to 23 m (51 to 75 ft), use no. 16 AWG insulated wire (35 C minimum). For over 23 m (75 ft), use no. 14 AWG insulated wire (35 C minimum). All wire larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat. Refer to Table 3 for wire conversions.

8

Table 2 — Electrical Data

UNIT

NOMINAL

VOLTAGE

COMPR

OFM

IFM

POWER SUPPLY

MINIMUM UNIT

VOLTAGE

RANGE

 

(ea)

(ea)

DISCONNECT

48TF

 

 

 

 

(50 Hz)

Min

Max

RLA

 

LRA

FLA

FLA

MCA

MOCP*

FLA

LRA

 

 

008

400

360

440

6.4

 

42.0

0.3

2.6

17.6

20

18

108

(3 phase)

 

 

 

 

 

 

 

 

 

 

 

 

 

012

400

360

440

8.9

 

52.0

0.3

2.6

23.2

30

24

128

(3 phase)

 

 

 

 

 

 

 

 

 

 

 

 

 

014

400

360

440

10.4

 

73.0

0.7

5.4

29.4

35

31

192

(3 phase)

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

FLA — Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration

IFM — Indoor (Evaporator) Fan Motor

LRA — Locked Rotor Amps

MCA — Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection

NEC — National Electrical Code (U.S.A.)

OFM — Outdoor (Condenser) Fan Motor

RLA — Rated Load Amps

*Fuse or HACR circuit breaker.

NOTES:

1.In compliance with NEC requirements (U.S.A. Standard) for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker.

2.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance.

% Voltage Imbalance

= 100 x

max voltage deviation from average voltage

average voltage

 

Example: Supply voltage is 400-3-50.

AB = 393 v BC = 403 v AC = 396 v

Average Voltage = 393 + 403 + 396 3

=

1192

3

= 397

Determine maximum deviation from average voltage. (AB) 397 – 393 = 4 v

(BC) 403 – 397 = 6 v (AC) 397 – 396 = 1 v

Maximum deviation is 6 v.

Determine percent of voltage imbalance.

% Voltage Imbalance = 100 x

6

397

= 1.5%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

Route thermostat cable or equivalent single leads of colored wire from thermostat subbase terminals to low-voltage connections on unit (shown in Fig. 10) as described in Steps 1-4 below.

1.If unit is mounted on roof curb and accessory thru-the- curb service plate connection is used, route wire through connection plate.

2.Pass control wires through the hole provided on unit (see connection D in Connection Sizes table in Fig. 6).

3.Feed wires through the raceway built into the corner post to the 24-v barrier located on the left side of the control box. See Fig. 11. The raceway provides the UL-required (Underwriters’ Laboratories) clearance between highand low-voltage wiring.

4.Connect thermostat wires to screw terminals on lowvoltage connection board.

HEAT ANTICIPATOR SETTINGS — Set heat anticipator settings at .14 amp for the first stage and .20 amp for secondstage heating, except for 008 low heat. Set both first and second stage heat anticipator settings for 008 at .14 amp.

Table 3 — American/European Wire Conversions

 

AMERICAN

EUROPEAN

Industry

 

American

Industry

 

Conversion

Standard

Standard Size

Size (mm2)

Size (mm2)

 

 

18 AWG

 

0.82

1.0

16 AWG

 

1.30

1.5

14 AWG

 

2.08

2.5

12 AWG

 

3.30

4.0

10 AWG

 

5.25

6.0

8 AWG

 

6.36

10.0

6 AWG

 

13.29

16.0

4 AWG

 

21.14

25.0

3 AWG

 

26.65

2 AWG

 

33.61

35.0

1 AWG

 

42.39

50.0

1/0 AWG

 

53.49

2/0 AWG

 

67.42

70.0

3/0 AWG

 

85.00

95.0

4/0 AWG

 

107.19

120.0

250 kcmil

 

126.64

150.0

300 kcmil

 

151.97

350 kcmil

 

177.90

185.0

400 kcmil

 

202.63

240.0

500 kcmil

 

253.29

300.0

600 kcmil

 

303.95

LEGEND

AWG — American Wire Gage kcmil — Thousand Circular Mils

9

 

LEGEND

C

Contactor

IFC

Indoor (Evaporator)

 

Fan Contactor

NEC

National Electrical Code

 

(U.S.A. Standard)

 

Splice Connection

 

(Factory Supplied)

 

Equipment Ground

 

Field Wiring

 

Factory Wiring

Fig. 9 — Power Wiring Connections

UNIT LOW VOLTAGE

INTEGRATED

GAS UNIT

CONNECTION

CONTROLLER

BOARD

(IGC)

 

LEGEND

AHA — Adjustable Heat Anticipator

CC — Cooling Compensator

Field Wiring

Factory Wiring

Fig. 10 — Low-Voltage Connections

COMPRESSOR

COMPRESSOR

RACEWAY

 

NO. 2

NO.1

Fig. 11 — Field Control Wiring Raceway

and Compressor Location

10

Step 8 — Adjust Factory-Installed Options

APOLLO CONTROL — The optional Apollo control is used to actively monitor all modes of operation as well as indoor (evaporator) fan status, filter status, and indoor-air quality. The Apollo control is designed to work with Carrier TEMP and VVT® systems.

The thermostat must be wired to the Apollo control before starting the unit. Refer to the Apollo control installation instructions for information on installing the thermostat. See Fig. 12 for Apollo location.

MANUAL OUTDOOR-AIR DAMPER — The outdoor-air hood and screen are attached to the basepan at the bottom of the unit for shipping.

Assembly:

1.Determine quantity of ventilation required for building. Record amount for use in Step 8.

2.Remove and save evaporator coil access panel and screws. See Fig. 13.

3.Separate hood and screen from basepan by removing the screws and brackets securing them. Save all screws and discard brackets.

4.Replace evaporator coil access panel using screws from Step 2.

5.Place hood on front of evaporator coil access panel. See Fig. 14 for hood details. Secure top of hood with the screws removed in Step 3. See Fig. 15.

6.Remove and save 6 screws (3 on each side) from sides of the manual outdoor-air damper. Remove and save 2 manual outdoor-air adjustment screws (one on each side of damper blade).

7.Align screw holes on hood with screw holes on side of manual outdoor-air damper. See Fig. 14 and 15. Secure hood with 6 side screws from Step 6.

8.Adjust minimum position setting of the damper blade by adjusting the 2 manual outdoor-air adjustment screws on the front of the damper blade. See Fig. 13. Slide blade vertically until it is in the appropriate position determined by Fig. 16. Tighten screws.

WIRING TO

APOLLO

CONTROL

THERMOSTAT

CONTROL

WIRING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 12 — Apollo Control Factory-Installed

in Typical Unit

9.Remove and save screws currently on sides of hood. Insert screens. Secure screens to hood using the screws. See Fig. 15.

Fig. 13 — Damper Panel with Manual

Outdoor-Air Damper Installed

Fig. 14 — Outdoor-Air Hood Details

Fig. 15 — Damper with Hood Attached

11

 

250

 

1.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200

(in. wg)

0.8

 

 

 

 

 

 

 

 

 

 

 

 

 

(Pa)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PRESSURE

150

PRESSURE

0.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OPEN

 

 

mm)

 

 

mm)

 

 

 

 

 

 

 

 

 

 

 

(51

 

(76

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

mm)

2"

 

3"

 

 

 

NEGATIVE

100

NEGATIVE

0.4

 

 

 

 

 

 

 

 

 

 

 

 

(25

 

 

 

 

 

 

 

 

mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1"

 

 

 

 

 

 

 

(112

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

.4"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

50

 

0.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

0

2

 

4

 

6

 

 

8

 

 

10

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTDOOR AIRFLOW (cfm x 100)

 

 

 

 

 

 

0

100

 

200

 

300

 

400

 

 

500

 

 

 

 

 

OUTDOOR AIRFLOW (L/s)

 

 

 

 

 

Fig. 16 — Position Setting

OPTIONAL DURABLADE ECONOMIZER — The optional economizer hood assembly is packaged and shipped in the filter section. Damper blades and control boards are installed at the factory and the economizer is shipped in the vertical discharge position.

NOTE: Horizontal discharge block-off plate is shipped with the air hood package. If unit is to be used for vertical discharge application, discard this plate.

Assembly

1.Determine if ventilation air is required in building. If so, determine the minimum amount to be supplied by each unit and record quantity of ventilation air needed for use in Step 8.

2.Remove filter access panel by raising panel and swinging panel outward. Panel is now disengaged from track and can be removed. No tools are required to remove filter access panel. Remove outdoor-air opening panel. Save panels and screws. See Fig. 17. Remove optional economizer and outdoor-air damper hood package from filter section.

3.Assemble outdoor-air hood top and side plates as shown in Fig. 18. Install seal strips on hood top and sides. Put aside screen retainer and retainer screw for later assembly. Do not attach hood to unit at this time.

4.On 012 and 014 units, install vertical discharge block-off plate on right side over return air duct opening. See Fig. 19.

5.a. Slide economizer into unit and secure with screws. See Fig. 20.

NOTE: Be sure to engage rear economizer flange under tabs at rear of vertical return-air opening.

b.Remove screw and discard from barometric relief damper. See Fig. 20.

6.To convert to horizontal discharge application:

a.Rotate the economizer 90 degrees until the economizer motor faces the condenser section (see Fig. 21).

b. Rotate the barometric relief damper hinge 90 degrees. Barometric relief damper should open vertically to operate properly.

c.Install horizontal discharge block-off plate over the opening on the access panel. (Block-off plate MUST be installed before installing hood assembly.) See Fig. 22.

7.Insert economizer plug into economizer harness. Remove tape from barometric relief damper. See Fig. 20.

8.If ventilation air is not required, proceed to Step 9. If ventilation air is required, determine the minimum position setting for required airflow. See Fig. 23. Adjust minimum position setting by loosening the screws on the position setting bracket. See Fig. 24. Slide bracket until the top screw is in the position determined by Fig. 23. Tighten screws.

9.Remove tape from outdoor-air thermostat (OAT). Fasten OAT to inside of hood using screws and speed clips provided. See Fig. 25. Make sure OAT terminals are positioned up.

10.Replace outdoor-air opening panel using screws from Step 2. Replace filter access panel. Ensure the filter access panel slides along the tracks and is securely engaged.

11.Fasten hood top and side plate assembly to outdoor-air opening panel with screws provided.

12.Place knob supplied with economizer on OAT. See Fig. 25. Set OAT for 1.7° C (3° F) below indoor room thermostat setting. If accessory enthalpy control (EC) is used in place of OAT, see instructions shipped with EC for installation and adjustment. See Fig. 25.

13.Connect OAT per Fig. 26.

14.Slide outdoor-air inlet screens into screen track on hood side plate. While holding screens in place, fasten screen retainer to hood using screws provided.

NOTE: Refer to Fig. 27 for Durablade economizer barometric relief damper characteristics.

OUTDOOR-AIR

FILTER ACCESS

OPENING PANEL

PANEL

Fig. 17 — Access Panel Locations

12

ECONOMIZER

ECONOMIZER

ECONOMIZER

TOP

CONTROL BOARD

PLUG

MOTOR

SCREW

SHIPPING

SCREW

Fig. 20 — Durablade Economizer Installed in Unit

ECONOMIZER CONTROL BOARD

ECONOMIZER MOTOR

Fig. 18 — Outdoor-Air Hood Details

POSITION SETTING BRACKET

Fig. 21 — Horizontal Durablade Economizer

Installation (90 Degree Rotation)

Fig. 19 — Vertical Discharge Block-Off Plate

(48TF012, 014 Units Only)

BLOCK-OFF PLATE

Fig. 22 — Horizontal Discharge Block-Off Plate

13

Example:

 

 

OAT

 

TOP

(TERMINALS ARE UP)

Given —

 

 

 

Negative Pressure . . . . . . . . . . . . . . . . . . . . . . . .

. 25

Pa (0.1 in. wg)

 

Outdoor Airflow . . .. . . . . . . . . . . . . . . . . . . . . . . .

520

L/s (1100 cfm)

 

Determine —

 

 

 

Setting = 150 mm (6 in.)

 

 

 

Fig. 23 — Durablade Economizer Damper Minimum

UNIT

Position Setting

 

 

OUTSIDE AIR

 

SCREEN

 

0

1

ENTHALPY

 

CONTROL

2

 

3

 

4

HOOD

5

 

6

 

7

 

8

 

9

 

 

OPEN

 

 

 

POSITIONMINIMUM

 

 

 

 

 

 

 

 

S

 

 

 

 

T

 

3

 

 

1

 

 

 

 

 

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T1

 

4

 

 

2

 

 

5

 

 

 

 

P1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T ID

 

 

 

 

8 S

CONT

OR

CONT

 

 

 

 

 

 

 

 

 

 

%

 

1 R

 

 

 

 

 

 

 

Y

 

 

IMUH

 

9 U

 

UNPOWERED

 

 

 

24

 

 

 

 

 

 

90

 

 

C

 

A

 

 

 

 

 

30

60

70

 

 

8

T

ACT

 

CTS

3

 

 

ENTHALPY

 

60

 

DAMPER

 

 

1

A

5A

TE

 

2

 

 

 

 

 

 

 

 

m

 

 

 

 

10

 

 

 

 

D

CW

A

2

RA

 

SHO

 

TR

 

 

50

 

 

 

 

C

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

TINGS:

 

 

 

 

 

 

OUTDOOR

65

 

 

 

 

 

SETPOINTS

 

M

ST

HIGH

 

 

C

 

 

55

 

OPEN

 

 

B

 

 

3 .

 

WN

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V

 

 

75

 

 

 

 

A

 

 

 

1

A

IN

 

 

 

CONTROL

F

 

 

 

 

 

 

 

A

RUN,

 

 

1

TR1

 

°

 

 

 

 

 

 

 

 

.

 

ENTHALPY

 

 

 

 

 

 

 

 

 

 

 

 

1

IN

 

 

 

 

 

TEMP

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IN

5A

 

 

 

 

 

 

.

70

 

 

 

 

 

CCW

 

1

 

 

 

 

 

 

 

 

 

CLOSED DAMPER

 

 

T

3

 

 

 

 

 

 

 

8

 

 

 

 

 

VDC

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85

REV.

 

97-3672

 

 

 

 

 

 

 

 

 

 

B

C

D S

O

RE V .

B

TR

Fig. 24 — Durablade Economizer Minimum

Fig. 25 — Outdoor-Air Thermostat/

Position Damper Setting

Enthalpy Control Installation

14

Fig. 26 — Wiring Connections for

Outdoor-Air Thermostat

 

175

 

 

0.70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PRESSURE DROP (Pa)

150

 

PRESSURE DROP (in. wg)

0.60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

125

 

0.50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100

 

0.40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75

 

0.30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

 

 

0.20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25

 

 

0.10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.00

 

200

400

600

 

800

 

1000

 

1200

 

 

 

 

 

 

CFM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

100

200

300

400

500

570

 

 

 

 

 

 

L/s

 

 

 

 

 

 

Fig. 27 — Durablade Economizer Barometric Relief

Damper Characteristics

OPTIONAL ECONOMI$ER — See Fig. 28 for EconoMi$er component locations.

1.To remove the existing unit filter access panel, raise the panel and swing the bottom outward. The panel is now disengaged from the track and can be removed. Remove the indoor coil access panel and discard. See Fig. 29.

NOTE: If installing an optional Power Exhaust Assembly, refer to the EconoMi$er Power Exhaust Installation Instructions, then proceed to Step 6. Controller should be mounted in vertical position as shown in Fig. 28.

2.To assemble the hood assembly remove the EconoMi$er hood from its packaging. Locate the outdoor air opening panel. See Fig. 30.

3.Install the 19 mm x 19 mm (3/4 x 3/4-in.) seal strip on the exhaust air hood top panel. Install the 3 mm x 22 mm (1/8 x 7/8-in.) seal strip on the exhaust air hood side panels and bottom brackets. Assemble the exhaust air hood to the outdoor air opening panel as shown in Fig. 30, using the screws provided. Do not attach hood assembly to unit at this time.

4.Install the 3 mm x 22 mm (1/8 x 7/8-in. seal strip on the outdoor air hood top and side panels. Assemble the outdoor air hood to the outdoor air opening panel as shown in Fig. 31, using the screws provided. Do not attach com-

pleted hood (Fig. 32) assembly to the unit at this time.

ECONOMI$ER

CONTROLLER

GEAR-DRIVEN

PLUG

 

DAMPER

ACTUATOR

 

 

OUTDOOR AIR

TEMPERATURE

SENSOR

BAROMETRIC

RELIEF DAMPERS

Fig. 28 — EconoMi$er Component Locations

OUTDOOR-AIR

FILTER ACCESS

OPENING PANEL

PANEL

Fig. 29 — Typical Access Panel Locations

OUTDOOR AIR

OPENING PANEL EXHAUST AIR HOOD TOP

SCREEN

RETAINER

 

EXHAUST AIR

SEAL STRIP

HOOD SIDES

 

EXHAUST AIR SCREEN

EXHAUST AIR BOTTOM BRACKET

Fig. 30 — Exhaust Air Hood Assembly

15

Loading...
+ 33 hidden pages